Spray Nozzle Data Sheet for Tanks

This document provides spray nozzle data for protecting four fuel storage tanks at a refinery in Linares, Chile. It specifies 28 spray nozzles for the kerosene tank, 36 for the gasoline 97 tank, 48 for the diesel tank, and 48 for the gasoline 93 tank. The nozzles will be used to spray water on the exterior of vertical cylindrical tanks from a single ring, with minimum required flow rates between 5.4-6.4 cubic meters per hour. The document provides fluid properties, site conditions, and specifications for the spray nozzles, including manufacturer, model, size, materials and connection type.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
62 views1 page

Spray Nozzle Data Sheet for Tanks

This document provides spray nozzle data for protecting four fuel storage tanks at a refinery in Linares, Chile. It specifies 28 spray nozzles for the kerosene tank, 36 for the gasoline 97 tank, 48 for the diesel tank, and 48 for the gasoline 93 tank. The nozzles will be used to spray water on the exterior of vertical cylindrical tanks from a single ring, with minimum required flow rates between 5.4-6.4 cubic meters per hour. The document provides fluid properties, site conditions, and specifications for the spray nozzles, including manufacturer, model, size, materials and connection type.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

IBD Instalación de Anillo Periférico de

ERSA010-DSM-001 PROJECT
Refrigeración de Manto de Estanques
SPRAY NOZZLE DATA SHEET
CLIENT Enap Refinerías S.A., Planta Linares
REV. DATE BY APPROVED DESCRIPTION
A 30-sep-16 ITG CTM / OFV Se emite para comentarios
0 11-abr-17 ITG CTM / OFV Emisión Final

1. Tag Number
Kerosene Tank Gasoline 97 Tank Diesel Tank Gasoline 93 Tank
2. Service
protection protection protection protection
GENERAL

3. Quantity / Spare / Total 28 / 6 / 34 36 / 6 / 42 48 / 6 / 54 48 / 6 / 54

4. Type Spray Nozzle Spray Nozzle Spray Nozzle Spray Nozzle


For shell of vertical For shell of vertical For shell of vertical For shell of vertical
5. Orientation
tank tank tank tank
6. Rings number 1 1 1 1
7. Fluid Water Water Water Water
8. minimum - - - -
9. Temp. Internal average 15 ºC 15 ºC 15 ºC 15 ºC
FLUID DATA

10. maximun 25 ºC 25 ºC 25 ºC 25 ºC
11. Min. Inlet Pressure 8,7 barg 8,7 barg 8,7 barg 8,7 barg
183 psig 183 psig 183 psig 183 psig
12. Design Pressure
(12 barg) (12 barg) (12 barg) (12 barg)
13. Density @TP 999 kg/m3 999 kg/m3 999 kg/m3 999 kg/m3
14. Viscosity @TP 1,14 cP 1,14 cP 1,14 cP 1,14 cP
15. Location Outdoor Outdoor Outdoor Outdoor
16. Humidity, % 54 - 87% 54 - 87% 54 - 87% 54 - 87%
SITE DATA

17. Wind speed 3-4 m/s 3-4 m/s 3-4 m/s 3-4 m/s
18. minimum -5 ºC -5 ºC -5 ºC -5 ºC
19. Site Temperature average 14 ºC 14 ºC 14 ºC 14 ºC
20. maximun 38 ºC 38 ºC 38 ºC 38 ºC
21. Manufacter Viking or similar Viking or similar Viking or similar Viking or similar
22. Model number VK814 or similar VK814 or similar VK814 or similar VK814 or similar
23. Size (gpm/psi0,5) 3,2 3,2 3,2 3,2
24. Connection 1/2 NPT 1/2 NPT 1/2 NPT 1/2 NPT
25. Material By vendor By vendor By vendor By vendor
SERVICE DATA

Minimum required discharge flow by


26. 5,4 m3/h 5,9 m3/h 6,4 m3/h 6,4 m3/h
each nozzle
27. Distance between nozzle and surface 0,6 m 0,6 m 0,6 m 0,6 m

28. Spray angle 125° 125° 125° 125°


29. Classification temperature - - - -
30. Temperature rating - - - -
31. Maximum ceiling temperature - - - -
32. Code - - - -

Notes:
1. Vendor shall design the water spray nozzles for the correct working
2. Vendor shall consider NFPA 15 recommendations in the system design
3. Spray nozzles shall be listed UL/FM for fire protection in accordance with NFPA 15