Primary Feeder 75 Kva Transformer (Typical) - Feeder, Breaker and Conduit Sizes

This document provides sizing calculations for overcurrent protection devices (OCPDs) for various electrical equipment for a project. It calculates OCPD sizes for: 1) A 75kVA transformer with a selected 200A breaker 2) A 45kVA transformer with a selected 110A breaker 3) A 30kVA transformer with a selected 70A breaker 4) A 465kVA chiller load with a selected 600A breaker The calculations determine load currents, select appropriate OCPD sizes per NEC tables, and size cable based on ambient temperature derating factors.

Uploaded by

Asif Sajwani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
225 views2 pages

Primary Feeder 75 Kva Transformer (Typical) - Feeder, Breaker and Conduit Sizes

This document provides sizing calculations for overcurrent protection devices (OCPDs) for various electrical equipment for a project. It calculates OCPD sizes for: 1) A 75kVA transformer with a selected 200A breaker 2) A 45kVA transformer with a selected 110A breaker 3) A 30kVA transformer with a selected 70A breaker 4) A 465kVA chiller load with a selected 600A breaker The calculations determine load currents, select appropriate OCPD sizes per NEC tables, and size cable based on ambient temperature derating factors.

Uploaded by

Asif Sajwani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 2

Client: CHEVRON Prepared by:

Project Name: Checked by: Date :


Pages:

1. PRIMARY FEEDER 75 KVA TRANSFORMER (TYPICAL).

FEEDER, BREAKER AND CONDUIT SIZES

SOURCE VOLTAGE = 480/277 V, 3 PH., 4W, 60 Hz.

LOAD = 75000 VA

75000 VA
I = = 90.2 AMPS.
3 X 480

I F. = 90.21 X 2.5 = 225.5 NEC TABLE 450.3(B)

SELECTED BREAKER SIZE: 200A, 3P,480V. LESS 10% AT 480 V

CABLE SIZE:
I CONT. = 1.25 X 90.2 = 112.76 AMPS

DERATING FACTOR FOR 50 °C AMBIENT = 0.82 NEC TABLE 310.16

112.8
I =
0.82

= 138 AMPS.

USE 1-3 /C-50 MM² CU, XLPE/PVC

FOR VOLTAGE DROP REFER TO ETAP CALCULATIONS

2.0 OCPD SIZING FOR 45 KVA TRANSFORMER (TYPICAL)

SOURCE VOLTAGE = 480/277 V, 3 PH., 4W, 60 Hz.

LOAD = 45000 VA

45000 VA
I = = 54.1 AMPS.
3 X 480

I F. = 90.21 X 2.5 = 135.3 AMPS. NEC TABLE 450.3(B)

SELECTED BREAKER SIZE: 110A, 3P,480V. LESS 20% AT 480 V


Client: CHEVRON Prepared by:
Project Name: Checked by: Date :
Pages:

3.0 PRIMARY FEEDER 30 KVA TRANSFORMER (TYPICAL).

FEEDER, BREAKER AND CONDUIT SIZES

SOURCE VOLTAGE = 480/277 V, 3 PH., 4W, 60 Hz.

LOAD = 30000 VA

30000 VA
I = = 36.1 AMPS.
3 X 480

I F. = 90.21 X 2.5 = 90.2 NEC TABLE 450.3(B)

SELECTED BREAKER SIZE: 70A, 3P,480V. LESS 20% AT 480 V

4.0 MOTOR/AIR CONDITIONING SSYTEMS

OCPD SIZING

CHILLER LOAD = 465 KVA (TYPICAL)

HP = 465 X 0.85 X 0.746

= 295 HP

I F. = 361 AMPS. NEC TABLE 430.15

OCPD @ 140 % = 361 X 1.4

= 505

SELECTED OCPD : 600AMPS.,3P,480V