FINAL DOCUMENTATION
Air Cooled Air Conditioner Unit / Refrigeration Unit
YARD: ZHEJIANG SHIPYARD
MAKER :DM ALSCOTT MARINE OFFSHORE HVAC LTD.
Page 1 of 9
HULL NO.
GPA696
DMA Project No.:
DMA11259
0 2012/1/4 PRE LJ SX RG
Pages: 9
Rev Date Purpose By Ck’s Appr
Document Title:
INDEX for Air Cooled Air Conditioner Unit / Refrigeration Unit
CLIENT: ZHEJIANG SHIPYARD
SHIP NAME:
CLASSIFICATION: BV
DRAWING TITLE DRAWING NO. REV._DATE
1. Technical Specification and Data.
Design Conditions
Scope of Supply - REV.0_20120104
2. Packaged Air Conditioner
2.1 Packaged air conditioner for HELI RECEPTION ROOM(SCU 01)
Dimensions drawing for packaged air conditioner(indoor) DMA11259-051-001 REV.1_20111229
Dimensions drawing for packaged air conditioner(outdoor) DMA11259-051-002 REV.1_20111228
P&ID of PAC DMA11259-051-003 REV.0_20111226
Electric drawing of Packaged Air conditioner DMA11259-051-010 REV.0_20111226
2.2 Packaged air conditioner for DRY PROVISON ROOM(SCU 02)
Dimensions drawing for packaged air conditioner(outdoor) DMA11259-041-002 REV.1_20111228
DIMENSIONS DRAWING FOR Valve board DMA11259-041-001 REV.0_20111226
P&ID of PAC DMA11259-041-003 REV.0_20111226
Electric drawing of Packaged Air conditioner DMA11259-041-010 REV.0_20111226
2.3 Operation manual Packaged air conditioner
Operation manual for Packaged Air Conditioner(SCU 01)
Operation manual for Packaged Air Conditioner(SCU 02)
Page 2 of 9
HULL NO.
GPA696
DMA Project No.:
DMA11259
0 2012/1/4 PRE LJ SX RG
Pages: 9
Rev Date Purpose By Ck’s Appr
Document Title:
Technical Data, Annex 1
CLIENT: ZHEJIANG SHIPYARD
SHIP NAME:
CLASSIFICATION: BV
Climatic Conditions:
Outside condition: Inside Condition:
Summer 37 °C / 85 % r.h. 25 °C / 50 % r.h.
Air Flow Ratio: 100% return air
Power supply: 480V/3Ph/60Hz
Control power: 220V/1Ph/60Hz
Cooling medium: Direct expansion system
Refrigerant: R407C
Heating medium: Electrical heating
Flag: FRENCH
Regulations: Comply with ISO7547/SOLAS 1974 with the latest amendment.
Flanges: ISO Standard
Page 3 of 9
INSULATION:
U: Total heat transfer
Surface:
coefficient,(W/m2·K)
Weather deck not exposed to sun’s radiation and ship side and external bulkheads 0.9
Deck and bulkhead against engine room, cargo space or other non-air conditioned spaces 0.8
Deck and bulkhead against boiler room or boiler in engine room 0.7
Deck against open air or weather deck exposed to sun’s radiation and deck against hot tanks 0.6
Side scuttles and rectangular windows, single glazing 6.5
Side scuttles and rectangular windows, double glazing 3.5
Bulkhead against alleyway, non-sound reducing 2.5
Bulkhead against alleyway, sound reducing 0.9
Top of wheelhouse 0.5
Page 4 of 9
HULL NO.
GPA696
DMA Project No.:
DMA11259
0 2012/1/4 PRE LJ SX RG
Pages: 9
Rev Date Purpose By Ck’s Appr
Document Title:
Scope Of Supply
CLIENT: ZHEJIANG SHIPYARD
SHIP NAME:
CLASSIFICATION: BV
General :
PAC system description generally
PART A: Air cooled packaged air conditioner for HELI RECEPTION ROOM(SCU 01)
PART B Air cooled packaged air conditioner for DRY PROVISON ROOM(SCU 02)
PART C Engineering Design For HVAC System
PART D Exclusion From Maker’s Supply
Page 5 of 9
SCOPE OF SUPPLY
PART A Air cooled packaged air conditioner for HELI RECEPTION ROOM(SCU
Item No. Marine type packaged air conditioner
A-110 Model: SCU-P1VRA
Service area: HELI RECEPTION ROOM
Return air ratio: 100 %
Qty.: 1
Tag No.:
Model: Plenum supply, vertical deck mount type
Main power source: AC 480 V x 3Ph x 60 Hz
Control power: AC 220 V x 1Ph x 60 Hz
Safety protective device: High pressure
Over load
Lack phase
Lack cooling water
Safety valve
Cooling capacity: 4.0 Kw
Heating capacity: 3.0 Kw
Heating medium: Electric
Refrigerant: R-407C
Outdoor Unit
Casing & coating SUS316
Colour RAL 7032
Compressor type: Hermetic reciprocating compressor
Compressor model: 2JC-07.2Y-40S
power consumption: 1.64 Kw
Condenser type: Air-cooled crossed fin and tube type
Material: Cu/Cu cooper and fins with epoxy coating
Fan type Propeller axial fan
Fan power 2x0.15 Kw
Indoor Unit
Model: Plenum supply type,vertical deck mount type
Casing & coating Steel & Synthetic resin powder coating
Evaporator type: Crossed fin and tube type
Material: Copper Tube/ Alum Fin
Blower type: Double inlet centrifugal blower
Blower model: BDB200C
Air vloume: 800 M3/H
Static pressure 150 Pa
Motor model: M2QA71M4A
Motor power: 0.29 Kw
Drain G3/4
Refrigerant control Thermostatic expansion valve
Air filter material: Nonwoven cotton / synthetic blend media, G4
Page 6 of 9
Outside dimension 800×500×1700 (L x W x H)
Weight 200 Kg
Colour RAL 9010
Switch box (IP44) Default lamp
(CP 1 ) DOL starter fan motor and compressor motor
Control of heating system for PAC
Spare part each unit
Item No. Tag No. Qty. Description Model
A-110.1 1 V-belt for fan and motor unit XPZ 630
PART B Air cooled packaged air conditioner for DRY PROVISON ROOM(SCU
Item No. Marine type packaged air conditioner
A-210 Model: SCU-P1VRA
Service area: DRY PROVISON ROOM
Return air ratio: 100 %
Qty.: 1
Tag No.:
Model: Plenum supply, vertical deck mount type
Main power source: AC 480 V x 3Ph x 60 Hz
Control power: AC 220 V x 1Ph x 60 Hz
Safety protective device: High pressure
Over load
Lack phase
Lack cooling water
Safety valve
Cooling capacity: 3.6 Kw
Refrigerant: R-407C
Outdoor Unit
Casing & coating SUS316
Colour RAL 7032
Compressor type: Hermetic reciprocating compressor
Compressor model: 2KC-05.2Y-40S
power consumption: 1.35 Kw
protection class IP65
Condenser type: Air-cooled crossed fin and tube type
Material: Cu/Cu cooper and fins with epoxy coating
Fan type Propeller axial fan
Fan power 2x0.15 Kw
Indoor Unit(Air cooler)
Model: Air cooler unit EPC 0430
Evaporator type: Crossed fin and tube type
Material: Copper Tube/ Alum Fin
Income air temp ~15℃
Evaporating ~8℃
Air vloume: 1397 M3/H
Motor power: 0.09 Kw
Page 7 of 9
Drain G3/4
Refrigerant control Thermostatic expansion valve
Switch box (IP44) Default lamp
(CP 2 ) DOL starter fan motor and compressor motor
Page 8 of 9
PART C Engineering Design For HVAC System
Maker supply engineering design for HVAC system, including heating/cooling calculation, air duct arrangement
and etc.
Maker’s HVAC&R drawing include dimension drawing, principle drawing, piping drawing,
Maker supplies the test of air flow by testing tool.
PART D Exclusions From Maker’s Supply
Maker’s Scope of Supply includes only what is specified in this Scope of Supply.
The following items are specifically excluded from maker’s Scope of Supply:
1. Installation job of HVAC&R plants, such as air-conditioning refrigeration plant, provision refrigeration plant,
ventilation fan, pump unit etc.
2. Supplying and welding common foundation on board for plants in item 1 which shall installed on the deck
or bulkhead.
3. Supplying and installing the spiral and square ducting including accessories for the HVAC system.
4. Supplying and installing the HVAC ventilation fittings and accessories, such as adjusting damper, grilles,
louvers, nozzles, goosenecks, mushroom heads, which are not mentioned in the scope of supply.
5. Supplying and installing the refrigerant piping including accessories for the HVAC&R system.
6. Supplying and installing the cooling water piping (sea water or fresh water) for the HVAC&R system.
7. Supplying electric installations, cables, starters and any electric fittings not mentioned in maker’s offer.
8. Refrigerant and oil beyond the first filling.
Page 9 of 9