BS7-Touch Screen Panel
BS7-Touch Screen Panel
Table of Contents
1
Conventions
..........................................................................................................................
5
1.1
Maintenance
Contract
.................................................................................................................
6
1.2
Technical
Questions
and
Spare
Parts
Orders
................................................................................
6
1.3
About
This
Operating
Manual
.....................................................................................................
7
1.3.1
Scope
and
Target
Group
...............................................................................................................
7
1.3.2
Symbols
used
in
the
manual
.........................................................................................................
7
2
Safety
...................................................................................................................................
9
2.1
Introduction
...............................................................................................................................
10
2.2
Basic
rules
for
safety-‐conscious
working
.....................................................................................
10
2.2.1
Documentation
...........................................................................................................................
10
2.2.2
Operation
....................................................................................................................................
10
2.2.3
Specifications
..............................................................................................................................
10
2.2.4
Production
stop
..........................................................................................................................
10
2.2.5
Safety
at
work
.............................................................................................................................
10
2.3
System
safety
.............................................................................................................................
11
2.3.1
Technical
personnel
....................................................................................................................
11
2.3.2
Commissioning
...........................................................................................................................
11
2.3.3
System
care
and
maintenance
....................................................................................................
11
2.3.4
Selection
of
the
installation
locations
........................................................................................
11
2.4
Purpose-‐conformant
usage
........................................................................................................
12
3
Description
.........................................................................................................................
13
3.1
Function
BS7
TOUCH
..................................................................................................................
14
3.2
Hardware
...................................................................................................................................
15
3.2.1
Display
........................................................................................................................................
15
3.2.2
Connecting
cable
........................................................................................................................
16
4
Technical
Data
....................................................................................................................
17
4.1
Technical
Data
............................................................................................................................
18
4.1.1
Dimensions
and
weight
..............................................................................................................
18
4.1.2
Ambient
conditions
....................................................................................................................
18
4.1.3
Voltage
supply
............................................................................................................................
18
5
Transport
............................................................................................................................
19
5.1
Unpacking
..................................................................................................................................
20
5.2
Storage
......................................................................................................................................
20
5.3
Return
........................................................................................................................................
20
6
Commissioning
....................................................................................................................
21
7
Operation
...........................................................................................................................
23
7.1
Operating
panel
.........................................................................................................................
24
7.2
Description
of
the
software
........................................................................................................
26
7.2.1
Startup
screen
............................................................................................................................
26
7.2.2
Home
..........................................................................................................................................
29
7.2.3
Alarm
..........................................................................................................................................
32
7.2.4
Fault
............................................................................................................................................
35
7.2.5
Disable
........................................................................................................................................
37
7.2.6
Favorites
.....................................................................................................................................
39
7.2.7
History
........................................................................................................................................
40
600984 02 0 US 3
Table of Contents
4 600984 02 0 US
1 Conventions
600984 02 0 US 5
Conventions
Support contracts
Maintenance contracts
System training
(503) 641-7508
6 600984 02 0 US
Conventions
This instruction manual is valid for Touch Displays BS7 TOUCH on Spark Detection Control
Consoles CC 5000 and CC 7000 series.
This manual replaces the operating section of the earlier Spark Detection Control Consoles CC
5000 and CC 7000 series manuals.
This manual is to be used by those persons who operate, conduct maintenance and repair the
system.
The personnel operating the Spark Detection system must be trained by a GreCon service
technician.
Danger
Death or severe bodily injury could occur if the corresponding safety measures
are not taken.
Warning
Injuries can occur if the corresponding protective measures are not taken.
Caution
There could be damage to the product if the corresponding protective
measures are not taken.
Note
Important information about the product, the handling of the product or the
respective part of the documentation to which special attention must be paid.
600984 02 0 US 7
Conventions
8 600984 02 0 US
2 Safety
600984 02 0 US 9
Safety
2.1 Introduction
The GreCon spark detection extinguishment system is the state of the art systems available and
are manufactured in accordance with the accepted rules of engineering and are safe and reliable.
Nevertheless, during all activities, you have to observe several safety instructions that protect you
from injuries and the product from damages.
Therefore you are asked to carefully read this safety information and these instructions.
2.2.1 Documentation
Keep the documentation ready at hand at all times when working with the system.
2.2.2 Operation
Ensure that the spark detection and extinguishing system is only operated by personnel who
received specific training by GreCon service engineers during startup.
2.2.3 Specifications
Installation, maintenance and replacement of components may only be conducted with the
production plant shutdown and switched offline.
If you have to conduct the required work on ladders or working platforms, protect yourself from
falling. Follow local and plant rules for falling hazard protection.
10 600984 02 0 US
Safety
Assembly, maintenance and repair work may only be conducted by specialized staff trained in the
respective trade.
2.3.2 Commissioning
GreCon spark extinguishing systems are part of safety engineering. Operate the spark
extinguishing system only in good condition.
GreCon advises that the spark detection and extinguishing system must be serviced at least once
a year. If the environment around the system is extremely dirty you may have to service it several
times a year.
Repair failures immediately after their occurrence. Should you be unable to repair any failure on
your own, please contact our customer service or your nearest GreCon representation.
The installation sites must be chosen so that they comply with the technical requirements and are
easily accessible for subsequent maintenance work. Reference OSHA and local regulations for
compliance.
600984 02 0 US 11
Safety
The automatic extinguishers may only be operated in GreCon spark extinguishing systems in
accordance with the technical specifications of this operating manual. Using the device for any
purpose other than that described in the technical data is considered to be not purpose-
conformant.
The manufacturer is not liable for damage that is caused by usage not in conformity with intended
purpose.
Compliance with the operating manual is also a part of usage in conformity with intended purpose.
12 600984 02 0 US
3 Description
600984 02 0 US 13
Description
All the information on these events can be called from the BS7 TOUCH display – both, the current
event data as well as long term history.
Additionally, the entire production system with all the monitoring zones is shown on the BS7
TOUCH, as a process flow diagram. All the events are marked on the process flow diagram
according to their location of occurrence.
The multi-touch function enables the operator to navigate to the area affected by the event. With a
touch of the display, additional information from the current screen content can be called up
directly.
Note
The process flow diagram is generated by GreCon based on the data provided
by the customer. Additions and adjustments must be added with the generating
software. This can only be done at GreCon – not by service technician at the
site.
14 600984 02 0 US
Description
3.2 Hardware
3.2.1 Display
The front of the panel has a display for the process flow diagram and the buttons and menu guides
generated by software. To the right of the display surface are three round hardware buttons.
On its underside, the display unit has various sockets and connection options.
600984 02 0 US 15
Description
The connecting cable for the display is a combination cable for data and electrical energy with two
plugs.
16 600984 02 0 US
4 Technical Data
600984 02 0 US 17
Technical Data
18 600984 02 0 US
5 Transport
600984 02 0 US 19
Transport
5.1 Unpacking
• Check against the delivery note of the freight forwarder whether all the listed items have
been delivered.
• Unpack all the equipment in clean surroundings.
• Preserve the packaging material for future use.
• Remove the documentation that is in the package and preserve it.
• Check the equipment carefully for signs of damage.
• If there are items missing or damaged, inform the freight forwarder, GreCon or your
GreCon representative.
• All the major components have a serial number.
• If there are any deviations, inform GreCon or your GreCon representative.
• If equipment has to be stored until it is installed, ensure suitable storage conditions.
5.2 Storage
Suitable storage conditions:
Storage temperature:........................................ -4°F to 185°F (-20°C to +85°C)
Relative atmospheric humidity: ........................ 5% to 95%, non-condensing
Air pressure: .................................................... 700 hPa to 1200 hPa
Note
If the specifications for storage are not followed, the warranty will be rendered
null and void.
5.3 Return
Packaging should be reused for returns.
20 600984 02 0 US
6 Commissioning
600984 02 0 US 21
Commissioning
Installation of the BS7 TOUCH in the control console and the following start-up
may only be conducted by a GreCon service technician.
22 600984 02 0 US
7 Operation
600984 02 0 US 23
Operation
On the left-hand side of the operating panel are the light displays to , which provide
information on the status of the control console and about the events in the monitoring system.
On the right-hand side of the operating panel, there are three buttons to and indicator lights
. With these buttons, the operator can acknowledge events and test functions.
In the middle of the operating panel is a display with the "Multi-Touch function". The display unit is
protected with a safety glass cover. By lightly touching the pre-defined buttons with a finger, the
operator can click through the operation menu and switch between different views.
24 600984 02 0 US
Operation
Water flowing yellow water flow due to an alarm or a leak has been detected
Status display of green batteries are charged and ready for use
battery yellow batteries are defective and needs service
Status display of, green main power supply connected
main power yellow no power from main power supply
active (horn/flashing light) – by pressing it, the audible alarm
Silence alarm green
is switched off
an event that can be acknowledged has happened – upon
Acknowledge green pressing, all the events that can be acknowledged (alarms,
faults) are acknowledged (collective acknowledgement)
Lamp test green a lamp test – all panel LEDs are tested (illuminated)
Operation
green control console is ready for operation
indication
600984 02 0 US 25
Operation
Upon switching the power supply on, the startup screen appears on the display (after the display
starts up). The startup screen is divided into three areas.
Zone Description
Status bar Provides information about the current status.
Main area Contains all the information on the active menu
Menu bar Contains the buttons of the main menu options
26 600984 02 0 US
Operation
Time
Date
Name of the spark extinguishing system (editable in the
configurator)
User name of the currently logged-in user
Authorization level (1 to 4)
Authorization levels
Level 1
The higher the level, the more rights it encompass. Every higher
authorization level automatically has all the rights of the lower
Level 2 authorization levels.
Level 3 At level 1, you can view all the menu options and data. However, for
certain applications and actions, you need access to a higher
authorization level. In that case, a login screen opens.
Level 4
Login screen
Note
At the end of the chapter, there is a schematic menu overview. It shows what
authorization levels are required for which applications.
600984 02 0 US 27
Operation
The buttons with access to production section (Zones) in the process flow diagram are located in
the main display area.
The menu bar contains the buttons for the main menu options (one button per menu option). From
the main menu, it is possible to go to the first and second sub-menus levels.
Note
At the end of the chapter, there is a pullout page with a schematic view of the
structure of the operating software.
History Opens the lists for the historical events (alarms, faults, disables)
28 600984 02 0 US
Operation
7.2.2 Home
Pressing the "Home" button, you get to the startup screen. The startup screen contains the project-
specific buttons in the main display area. Every button is assigned to a production section.
Pressing the button opens the process flow diagram with the focus on the relevant production
section. For this example we are using three production sections covering 4 zones.
Note
In the larger plants, the buttons are used to focus on the corresponding
production section. With smaller plants, the entire plant could be seen on
pressing any button. In this process flow diagram example, the edging
corresponds to the borders between the projected monitoring area (three
production sections covering 4 zones).
600984 02 0 US 29
Operation
The respective symbol appears both on the buttons in the main display area as well as on the
buttons in the menu bar.
30 600984 02 0 US
Operation
The events are also entered in the process flow diagram with symbols. The symbol is displayed in
the zones in which the event has occurred. The number in the symbol indicates the number of the
events.
600984 02 0 US 31
Operation
7.2.3 Alarm
Pressing the "Alarm" button in the menu bar displays the alarm lists.
• All
• Most recent/oldest
Pressing the "All" button opens the entire active and passive alarms list.
Alarm All
In the middle of the main display area, there is a magnifying glass bar , which enlarges the
selected event, as well as the navigation buttons for following the event in the magnifying glass
bar.
Navigation buttons
returns to the production section in the process flow diagram in
Up arrow which the event has occurred. From the process flow diagram, you
can go back to the alarm list from the menu bar
Acknowledge for acknowledging the alarms in the magnifying glass bar.
button Acknowledged alarms go to the history list of the alarms.
32 600984 02 0 US
Operation
Alarm level
Database ID as running serial number
(alarm 1 or alarm 2)
Symbol for alarm
Alarm in plain text
(red = active, black = passive)
Date of start of alarm Countermeasure activated
Time of start of alarm End time of alarm,
accurate to the millisecond accurate to the millisecond
Abbreviation of the affected component End date of alarm
Zone/location designation
(plain text possible: Filter 1)
If the “Acknowledge” button is not shown on the display after silencing the audible alarm, the event
has not yet ended. The sensors are still sensing the alarming condition or extinguishment is still
activated (typically 5 seconds or a different time interval set in the configuration file).
600984 02 0 US 33
Operation
Pressing the "Information arrow" navigation button, opens an information window. Here, all the
partial results are chronologically listed, which belong to the alarm.
Alarm information
Pressing the "Most recent/Oldest" button opens the entire active and passive alarms list.
In this list, there is a magnifying glass bar at the upper and lower edge of the screen. The most
recent entry is always at the top; the oldest is always at the bottom. All the other entries are
arranged between them in chronological order. In this example there are only two alarms thus no
alarms in the middle section.
34 600984 02 0 US
Operation
7.2.4 Fault
Fault All
All the active and passive faults are entered in the fault list.
Structure of an entry in the fault list:
Fault identification
Database ID as running serial number (for structure, see the table on the following
page)
Symbol for fault
Description of the fault in plain text
(yellow = active, black = passive)
Start date of fault End time of fault, accurate to the millisecond
Start time of fault, accurate to the
End date of fault
millisecond
Number of repetitions of this fault
Abbreviation of the affected component
(e.g. wire rupture/loose contact)
Zone/location designation
plain text possible, example: Filter 1)
600984 02 0 US 35
Operation
Pressing the "Information arrow" navigation button, opens an information window. Here, you
can find detailed information in plain text on the cause of the fault as well as suggestions for fault
rectification.
Upon pressing the button "Close", you return to the fault list.
1)
list see chapter 7.4
36 600984 02 0 US
Operation
7.2.5 Disable
Pressing the "Disable" button causes the system to display the list of disables.
• All
Disables All
All the active disables are entered in this list. Ended disables are written to the history list.
600984 02 0 US 37
Operation
38 600984 02 0 US
Operation
7.2.6 Favorites
600984 02 0 US 39
Operation
7.2.7 History
Pressing the "History" button displays the lists for historical events.
The following are given in these lists:
• all acknowledged alarms
• all acknowledged faults (summation acknowledgement)
• all terminated disables
The entries in this historic list have the same structure as the entries in the current lists for alarm,
fault and disable in the respective menu options.
History Alarm
History Fault
History Disable
40 600984 02 0 US
Operation
7.2.8 Language
Upon pressing the "Country Selection" button there opens a dialog box.
Set language
600984 02 0 US 41
Operation
In the status line, the time display is adjusted by the corresponding number of hours.
42 600984 02 0 US
Operation
Pressing the "Date/Time" button opens a screen for adjusting the systems date and time.
Language Date/Time
1. Use the keys "+" and "-" to set the date and time.
2. Press the "Store" button to save the setting.
600984 02 0 US 43
Operation
7.2.9 Settings
44 600984 02 0 US
Operation
In this menu you can select and individually switch off zones, sensor groups, extinguishment
groups and line modules as well as test sensor groups, extinguishment groups and alarm
measures.
600984 02 0 US 45
Operation
46 600984 02 0 US
Operation
Note
If several status displays are active simultaneously, it means that that zone has
been deactivated in several ways.
Note
The sub-menus "Disable sensor group", "Disable extinguishment group"
and "Disable line module" are structured identically. Therefore, they are not
described repeatedly in this manual.
600984 02 0 US 47
Operation
Pressing the "Test Extinguishment Group" button causes other buttons to appear in the display
area. All the extinguishment zones that can be tested are shown in the display area.
Note
In a function test, the operability of the selected components at the plant is
tested. During the function test, the system can report alarms and faults.
48 600984 02 0 US
Operation
A symbol can now be seen on the button. The symbol remains on the button till the menu is quit.
When the menu is called again, the symbols are cleared.
600984 02 0 US 49
Operation
Note
The sub-menu "Test Sensor Group" is structured identically. Therefore, it is
not described in this manual.
50 600984 02 0 US
Operation
By pressing the button “Test alarm equipment” choice boxes pop up for the connected alarm
measures (horn, strobe light).
600984 02 0 US 51
Operation
52 600984 02 0 US
Operation
Upon pressing the "test state Sensor Group" button other buttons appear in the display area.
Note
In contrast to the component test (self-diagnosis), with the activation of the test
mode, an external examination of the components is prepared.
The testing of the respective component is conducted by the GreCon service
technician with a separate software tool.
600984 02 0 US 53
Operation
If a sensor group is in test mode the following symbol appears on the button:
When pressing the button with the test mode symbol the following display pops up:
Note
The sub-menus "Test state, extinguishment group" and "Test state, line
module" are identical in structure. Therefore, they are not described in the
manual.
54 600984 02 0 US
Operation
Pressing the "Update console" button opens a dialog box with a keyboard.
Note
The pass code is not the same as your password. You will get the pass code
from GreCon service technician.
600984 02 0 US 55
Operation
Upon pressing the button "Switch off" there appear additional buttons.
Upon pressing the button "Start", the control console or the display is switched off.
56 600984 02 0 US
Operation
7.2.9.3 Parameter
Here, you can customize the parameters to the sensor groups and set the time delays for different
system switch-offs.
Settings Parameter
Upon pressing the " Sensor Group Parameters " button other buttons appear in the display area.
600984 02 0 US 57
Operation
Alarm one is within the counter threshold of the number of sparks per unit of
time . As soon as the given number of sparks within the given unit of time is
reached, Alarm 2 is triggered.
Note
The initial parameters are defined in the base configuration by the GreCon
technical department.
58 600984 02 0 US
Operation
600984 02 0 US 59
Operation
Pressing the "System Disable Parameters" button the dialog display opens.
60 600984 02 0 US
Operation
1. By using the "+" and "-" keys, set the desired activation times (delay times) for the system
disable
Note
The activation times for system disable can be customized only in 30-second
steps.
These delay times are used to allow continuing monitoring of production while fan
and conveyors spin down to a stop. Typical setting is 15 minutes is ample time to
allow your pneumatic conveyor fan to spin down. This is dependent on your
production system.
600984 02 0 US 61
Operation
Upon pressing the "Display Settings " button there appears a button for the cleaning mode and
check boxes for activating the internal horn.
You may now clean the screen (see the chapter on "Maintenance").
62 600984 02 0 US
Operation
To end the
cleaning mode,
press the light test
switch next to the
screen for 3
seconds.
In the check box, make a check mark to activate the internal horn.
Note
The internal horn is located in the housing of the operating panel. It has the
same function as the regular alarm devices.
600984 02 0 US 63
Operation
7.2.9.4 Configuration
Settings Configuration
Pressing the "Console configuration" button other buttons appear in the display area.
64 600984 02 0 US
Operation
Button Action
Below the buttons information concerning the actions made are displayed.
600984 02 0 US 65
Operation
• By pressing one of the buttons “All“, ”MM“ or “LMx“ the configuration starts with query Q1
(“Do configuration file and control console match together?“).
• By pressing the “read Module” button the configuration starts with action A4 (transferring
the configuration from module to configuration file).
• Colored indications to on the display show the progress of the configuration.
Query No
Message Yes
Action End
66 600984 02 0 US
Operation
The different queries and actions proceed in the background and are only marked by colored
indications to on the display.
Queries
Do configuration file and control console compare together? (number of modules, software,
Q1
control console, module version)
Q2 Should more modules contain data?
Q3 Are more modules installed in the control console?
Q4 Do all data match together?
The messages are shown as text on the display for the user.
M1 M2 M3
Actions
A1 Send configuration to module x
A2 Send parameter to module x
A3 Wait 5 seconds for data processing in the modules
A4 Read out configuration of module x
A5 Read out parameter of module x
A6 Compare the data of all modules to the data of the configuration file
600984 02 0 US 67
Operation
Upon pressing the “Configuration Files“ button the following display is opened:
When pressing the “Start“ button, you have the following possibilities:
• Copying the configuration files to the USB port
(e.g. for saving the configuration before changes are tested)
• Copying the configuration files from the USB port
(e.g. if a new configuration is to be copied)
Note
The configuration files always refer to both the configuration of the plant as well
as the displays.
68 600984 02 0 US
Operation
7.2.9.5 Administration
Settings Administration
600984 02 0 US 69
Operation
Logging in
Note
Your security-relevant operation steps are stored in an information file.
Logging out
70 600984 02 0 US
Operation
Create user
Note
At the time of commissioning, GreCon service technician will create the users
that you need at the time.
600984 02 0 US 71
Operation
Delete user
72 600984 02 0 US
Operation
Here, the user who is currently logged in can change his password.
Change password
600984 02 0 US 73
Operation
Pressing the "Update Display firmware", button the corresponding button is displayed with a
confirmatory question.
1. Connect one data medium with the new Display firmware at the USB port.
2. Press the button "Start"
74 600984 02 0 US
Operation
Note
The delay time for activating the screen saver can be set in steps of 5 minutes.
600984 02 0 US 75
Operation
Pressing the "Log Files" button other buttons appear on the display.
Logging means recording internal error messages of the software. The logged data can be saved
internally, deleted or exported via the USB port.
• If you wish to save the log files internally, make a check mark in the box after "Save
Information in Log Files"
• If you wish to export the log files, connect a data medium to the USB port and press the
"Start" button after the option "Copy the Log Files to USB Stick"
• If you wish to delete the log files, press the "Start" button after the option "Delete all Log
files"
76 600984 02 0 US
Operation
Pressing the "History Database" button open another button on the display area.
Here, you can copy the complete or part of the lists from the menu option "History".
All lists of the history database are copied completely to the volume
A CSV file with the last 100,000 events is generated and copied to the
volume
Note
The CSV file provides a table structure. The contents of the table can be edited
with Excel.
600984 02 0 US 77
Operation
7.2.10 Info
Info
MAC address of the network connection Size of the current history database
Software versions and their installation
Latest event and oldest event
date
Note
All the data recorded here are stored in the database and can be viewed there.
78 600984 02 0 US
Operation
7.2.11 Help
Here, you can find installation and assembly instructions as well as product documentation.
Help
600984 02 0 US 79
Operation
80 600984 02 0 US
Operation
2. With the on-screen keyboard that is displayed, input the unlocking code from GreCon.
600984 02 0 US 81
Operation
As soon as you have correctly entered the last character of the unlocking code, the
button "OK" becomes active.
82 600984 02 0 US
Operation
Home
Alarm
All
Most
recent/Oldest
Fault
All
Deactivation
All
Favourites
History
Alarm
Authorisation
Fault
Level
Deactivation
Language Country
selection
1
Time
zones
3
Date/Time
3
Info
Help List
of
documents 1
List
of
videos 1
Activate
additional
functions 4
600984 02 0 US 83
Operation
84 600984 02 0 US
Operation
032 Operating voltage < 24V Low operational voltage of valve output. Min. 24V.
033 Short-circuit to ground Short-circuit to ground of valve output.
034 Driver faulty Defective valve output of module-> replace module.
Open circuit Broken wire at the valve output of module. Check wiring and
035
relay.
036 Short-circuit 24V Valve output connected with 24V voltage of system.
037 Collective fault Current of the valve not OK. Check relay and wiring on output.
042 Test line: open circuit Test line: open circuit Check wiring and detector. Replace
detector if necessary.
Test line: short- Test line: short-circuit Check wiring and detector. Replace
043 circuit detector if necessary.
600984 02 0 US 85
Operation
Fault
Display text Trouble information
number
Test line: general Test line: general fault Check wiring and detector. Replace
044 fault detector if necessary.
053 Output faulty Short circuit of relay output or configured and not used.
loose contact Loose contact detected. Please check the wiring of the spark
063
extinguishing system
064 Detector 1 test fault Detector 1 test not OK. Check detector and wiring.
065 Detector 2 test fault Detector 2 test not OK. Check detector and wiring.
066 Detector 3 test fault Detector 3 test not OK. Check detector and wiring.
067 Detector 4 test fault Detector 4 test not OK. Check detector and wiring.
070 Open circuit detector Open circuit of connected detector. Check wiring.
86 600984 02 0 US
Operation
Fault
Display text Trouble information
number
Control signal not Irregular flow switch signal during extinguishing. Irregular flow
084 constant switch signal for other extinguishing systems.
Water flowing Leakage - Water flows. Check pipelines and extinguisher
085
valves for leakage.
086 Inspection flap is open Disable input activated for too long. Check switching-off,
examine wiring.
Position 1 (OPEN) not Initiator ( open) in mechanical extinguishing systems does not
087 OK report open.
Position 2 (CLOSE) not Initiator (closed) in mechanical extinguishing systems does not
088 OK report closed.
Pump supply pressure
089 fault Fault manometric switch, storage tank
090 water pressure too low Fault manometric switch, supply to the pipeline.
091 External fault External fault
Reset pushbutton "Extinguishment" is pressed for a too long
092 Reset button open time >10min. Check the operation and the cable for broken
wire.
093 Bypass not closed The manual bypass valve to release water spray is not closed
No compressed air Low air pressure detected at extinguishment. Check
094
compressed air supply.
Extinguishment excess High temperature detected at extinguishment. Check
095 temperature temperature and reduce below 60°C (140°F).
096 LL-S3-TEXT5 Reserved for EL KK9/1 S3
097 LL-S3-TEXT6 Reserved for EL KK9/1 S3
098 LL-S3-TEXT7 Reserved for EL KK9/1 S3
099 LL-S3-TEXT8 Reserved for EL KK9/1 S3
100 Detector fault The connected detector is defective. Call GreCon service.
Operation fault The connected detector reports an operational fault. Call
101 detector GreCon service.
Detector alarm signal
102 defective Detector alarm signal fault. Check / change detector.
No bus-STW signal within the preadjusted release time.
No control signal BUS
103 (Type 1) Please check the function. Change of configuration may
possibly be required.
The reset time of the STW signal via the bus is too long.
Control signal BUS too
104 long Please check the configuration and the STW at
extinguishment
Control signal BUS not Flow bus signal not constant. Please check the STW and the
105 constant extinguishing medium.
open circuit heater Examination of the heating tape and the wiring including the
106 band return line for the heating tape. Examination of the check-back
relay including the wiring.
Eliminate external supply of the heating tape or replace
Heater band monitor
107 defective defective check-back relay or check internal wiring of control
console.
Water extinguishment: no STW signal within the preadjusted
extinguishing time. Mechanical systems: no check-back signal
No control signal (Type
108 2) from sensor 'Closed' within the preadjusted extinguishing time.
Please check the function. Change of the after-extinguishing
time may possibly be required.
No bus-STW signal within the preadjusted extinguishing time.
No control signal BUS
109 (Type 2) Please check the function. Change of the after-extinguishing
time may possibly be required.
Power supply 1 fault Check the power supply in the control console, and the supply
128
voltage
600984 02 0 US 87
Operation
Fault
Display text Trouble information
number
Power supply 1 batt. The battery in the control console is faulty. Check the battery
129 fault and wiring, replace if required
Power supply 1 batt. The battery in the control console is deep--discharged. Check
130 low the battery and replace it if required
131 Power supply 2 fault Check power supply in the extension unit 1, supply voltage
Power supply 2 batt. The battery in the extension unit is faulty. Check the battery
132 fault and wiring, replace if required
Power supply 2 batt. The battery in the extension unit is deep-discharged. Check
133 low the battery and replace it if required
134 Power supply 3 fault Check power supply in the extension unit 2, supply voltage
Power supply 3 batt. The battery in the extension unit 2 is fault. Check the battery
135 fault and the wiring, if required, replace.
Power supply 3 batt. The battery in the extension unit 2 is deep-discharged. Check
136 low the battery and replace it if required
137 Input 1 S1 fault Input 1 S1 fault
88 600984 02 0 US
Operation
Fault
Display text Trouble information
number
This extinguishment group has not reported any end of
Area disable error type disable for the area disabling. If possible, please check the
156 3 configuration, or get in touch with the responsible customer
service desk.
This unexpected detector group has reported an end of
Area disable error type switching-off for the area disabling. If possible, please check
157 4 the configuration, or get in touch with the responsible
customer service desk.
This unexpected detector group has reported an end of
Area disable error type switching-off for the area disabling. If possible, please check
158 4 the configuration, or get in touch with the responsible
customer service desk.
Collective message indicates that a malfunction was
General memory card determined in the communication with the memory card. Block
163 fault the memory card in the menu and conduct a reset of the
display. Then clear the memory card again.
The maximum number of backup files on the memory card
Max.no. of files
164 exceeded was reached. No more files can be saved. Format the memory
card with card reader or delete files.
Maintenance date The time that was set for carrying out a maintenance was
165 reached reached or has been overshot.
This fault is generated once every morning at 8:00 a.m..
600984 02 0 US 89
Operation
90 600984 02 0 US
8 Maintenance
600984 02 0 US 91
Maintenance
If required, clean the display with a mild commercial household glass cleaning agent and a soft,
lint-free cloth.
Note
To avoid unintentional operation of the display, ensure that the display is in
cleaning mode or has got switched off.
92 600984 02 0 US
9 EC Declaration of
Conformity
600984 02 0 US 93
EC Declaration of Conformity
94 600984 02 0 US
EC Declaration of Conformity
600984 02 0 US 95
GreCon, Inc.
15875 SW 74th Ave
Tigard, Oregon 97224
(503) 641-7731
[email protected]
www.grecon.us