Technician's Installation Guide
Technician's Installation Guide
Original instructions
Thank you very much for purchasing our product.
Before use, please carefully read this manual and keep it for future reference.
1. INTRODUCTION
CONTENTS PAGE
1.1 General information
■ These units are used for both heating and cooling applications.
1. INTRODUCTION................................................................... 1
They can be combined with fan coil units, floor heating
2. ACCESSORIES..................................................................... 1 applications (connect the mixed station), low temperature high
3. SAFETY CONSIDERATIONS............................................... 2 efficiency radiators(field supply).
4. OVERVIEW OF THE UNIT.................................................... 3 ■ The host unit controller is standard supplied with the unit to control
5. UNIT INSTALLATION........................................................... 11 the system.
6 START-UP AND CONFIGURATION.................................... 25 ■ A wired remote controller can also be used to control the system
7. THE HOST UNIT CONTROLLER ELUCIDATION............... 27 (Optional).
8. TROUBLE SHOOTING......................................................... 31
■ Operation range
9. IMPORTANT INFORMATION FOR THE USED
COOLING MODE HEATING MODE
REFRIGERANT..................................................................... 32
t(°C) t(°C)
10. MAIN PARAMETERS......................................................... 33
0
-5
-15
4 7 15 20 t(°C) 35 40 54 t(°C)
DELIVERY WATER TEMPERATURE DELIVERY WATER TEMPERATURE
(*) The unit can not operate in cold weather conditions below -15℃. If
it is necessary to operate, an external auxiliary heat source must
be added as a backup heater. the backup heater also serves as a
backup in case of malfunctioning of the unit and for freeze
ptrotection of the outside water piping during winter time.
Y-shaped filter 1
1
3. SAFETY CONSIDERATIONS manual using a separate circuit.
Insufficient capacity of the power supply circuit or improper electrical
construction may lead to electric shocks or fire.
The precautions listed here are divided into the following types.
They are quite important, so be sure to follow them carefully.
■ Be sure to install a ground fault circuit interrupter according to local
Meanings of DANGER, WARNING, CAUTION and NOTE symbols. laws and regulations.
Failure to install a ground fault circuit interrupter may cause electric
DANGER shocks and fire.
Indicates an imminently hazardous situation which if not
avoided, will result in death or serious injury. ■ Make sure all wiring is secure. Use the specified wires and ensure
that terminal connections or wires are protected from water and
WARNING other adverse external forces.
Indicates a potentially hazardous situation which if not Incomplete connection or affixing may cause a fire.
avoided, could result in death or serious injury.
■ When wiring the power supply, form the wires so that the front panel
CAUTION can be securely fastened.
Indicates a potentially hazardous situation which, if not If the front panel is not in place there could be overheating of the
avoided, may result in minor or moderate injury. It is also terminals, electric shocks or fire.
used to alert against unsafe practices.
■ After completing the installation work, check to make sure that there
NOTE is no refrigerant leakage.
Indicates situations that could only result in accidental
equipment or property damage. ■ Never directly touch any leaking refrigerant as it could cause severe
frostbite.
DANGER ■ Do not touch the refrigerant pipes during and immediately after
operation as the refrigerant pipes may be hot or cold, depending on
the condition of the refrigerant flowing through the refrigerant piping,
■ Before touching electric terminal parts, turn off power switch.
compressor and other refrigerant cycle parts. Burns or frostbite are
■ When service panels are removed, live parts can be easily possible if you touch the refrigerant pipes. To avoid injury, give the
touched by accident. pipes time to return to normal temperature or, if you must
Never leave the unit unattended during installation or servicing touchthembe sure to wear protective gloves.
when the service panel is removed.
■ Do not touch the internal parts (pump, etc.) during and immediately
■ Do not touch water pipes during and immediately after operation
after operation.
as the pipes may be hot and could burn your hand. To avoid injury,
Touching the internal parts can cause burns. To avoid injury, give
give the piping time to return to normal temperature or be sure to
the internal parts time to return to normal temperature or, if you must
wear protective gloves.
touch them, be sure to wear protective gloves.
■ Do not touch any switch with wet fingers. Touching a switch with
wet fingers can cause electrical shock.
■ Before touching electrical parts, turn off all applicable power to
the unit. CAUTION
1 7
8
9
10
2 11
3
12 18
4 13
19
14 1 Water inlet
15 2 Water outlet
5 16
17 3 Auto-watet replenishing orifice
6
4 Water outlet of safety Valve
5 Wire hole
1 Operation panel 11 Plate heat exchanger
2 4-ways valve 12 Condenser
3 Storage tank 13 Axial-flow fan
4 Pump 14 Adapter substitute
5 Electric expansive valve (accessory)
6 Compressor 15 Security discharge
7 Air purge valve 16 Auto-water replenishing
8 Electrical control box valve (accessory)
9 Water manometer 17 Water flow switch
10 Expansion tank 18 High pressure switch
19 Low pressure switch
3
4.3 Refrigerant cycle
19 20 22 23
11
21
17 F
15
24
A
9 10
16
18
7
2 8 5 6 8
25 HP
13
L P 26 4
14
12
C ool ing
1 3 H eating
1 Compressor 10 Differential Pressure Switch (only 10~16kW) 18 Thermistor For Water Inlet
2 4-Way Valve 11 Flow Switch (only 5/7kW) 19 Air purge Valve
3 Gas-liquid Separator 12 Thermistor For Discharge Temperature 20 Expansion Tank
4 Air Side Heat Exchanger (condenser) 13 Thermistor For Outdoor Temperature 21 Circulating Pump
5 Electronic Expansion Valve 14 Thermistor For Evaporation In Heating 22 Water manometer
6 Capillary (only 5/7kW) (Thermistor For Condenser In Cooling) 23 Safety Valve
7 Storage Tank 15 Thermistor For Plate Heat Exchange 1 24 Auto-watet replenishing valve
8 Strainer 16 Thermistor For Plate Heat Exchange 2 25 High Pressure Switch
9 Water Side Heat Exchanger 17 Thermistor For Water Outlet 26 Low Pressure Switch
(Plate Heat Exchange)
4
1. ELECTRICAL PANEL LAYOUT
(The picture below shows the position of the diagram, please participate in the concrete photos)
⑤
④ ③ ② ① ⑦
3 5
4
5
4. Main control board (The picture is for reference only)
30
Remove the inspection panel by unscrewing the five screws. The 1. Use grommet A for the electrical power cable and grommet B
electric control box is located inside the unit at the top of the technical for the other external wires.
components. (The picture below shows the position of the diagram, please
participate in the concrete photos)
6
2. Main control board (The picture is for reference only)
7
3. PFC&IPM module board (The picture is for reference only)
Remove the inspection panel by unscrewing the five screws. 1. Use grommet A for the electrical power cable and grommet B for
The electric control box is located inside the unit at the top of the the other external wires.
technical components. (The picture below shows the position of the diagram, please
participate in the concrete photos)
A
B
1. Input port for switching power supply 14. Remote control port
2. Debugging port 15. Electronic expansion valve port
3. Connection port for operation and display panel 16. AC 220V power supply port
4. Tin/Tb1/Tout/Tb2 temp. sensor port 17. Solenoid valve port (Reserved)
Note: Tin: water inlet temp. Tout: water outlet temp. 18. Exhaust valve electric heater port
Tb1: Temp.1 of plate heat exchanger 19. Electric heater port of Plate heat exchanger
Tb2: Temp. 2 of plate heat exchanger 20. Electric heater port of differential pressure valve
5. Discharged temperature sensor port (Tp) 21. Built-in water pump port
6.1 T3 temperature sensor port 22. Electric heater of the compressor
6.2 T4 ambient temperature sensor port 23. Precharge AC contactor port
7.1. Low pressure switch 24. 4-way valve port
7.2 High pressure switch 25. External water pump/Remote alarm port
8. Checking touch switch 26. Up DC fan port
9. Force-cooling touch switch 27. Down DC fan port
10. Differential pressure valve port 28. Power supply port for switching power supply of PFC board
11. Factory debugging port 29. Drive module port
12. Wired controller port 30. P/N/+15V port
13. AC Current transformer
9
3. IPM module board (The picture is for reference only)
1. Power supply port L3 6. Loaded power supply port for main control board
2. Power supply port L2 7. Power supply port for main control board
3. Power input port L1 8. Power output port L1 after filtering
4. Power input port N 9. Power output port L2 after filtering
5. Ground wire 10.Power output port L3 after filtering
11. Ground wire
10
5. UNIT INSTALLATION
5.1 Before installation
Before installation
Be sure to confirm the model name and the serial number of the unit.
Handling
Due to relatively large dimensions and heavy weight, the unit should
only be handled using lifting tools with slings. The slings can be fitted
A
into foreseen sleeves at the base frame that are made specifically for
this purpose.
Unit A(mm)
5-16kW ≥2000
CAUTION
■ To avoid injury, do not touch the
air inlet or aluminum fins of the unit. Make sure there is enough room to do the installation
■ Do not use the grips in the fan
■ Set the outlet side at a right angle to the direction of the wind.
grills to avoid damage.
■ The unit is top heavy! Prevent the
unit from falling due to improper Strong wind
inclination during handling.
Blown air
■ Turn the air outlet side toward the building's wall, fence or screen.
11
■ To prevent exposure to wind, install the unit with its suction side
facing the wall.
■ Never install the unit at a site where the suction side may be
exposed directly to wind.
■ To prevent exposure to wind, install a baffle plate on the air
discharge side of the unit.
■ In heavy snowfall areas it is very important to select an installation
H
site where the snow will not affect the unit. If lateral snowfall is
possible, make sure that the heat exchanger coil is not affected by
the snow (if necessary construct a lateral canopy).
A
G
B
1 Construct a large canopy.
2 Construct a pedestal.
Install the unit high enough off the ground
E
F
C
D
to prevent it from being buried in snow.
Air outlet
H
A >300
G >600
B
>2000
E
F
D
C
MODEL
(kW) A B C D E F G H
12
5.3.1 Moving and installation 5.3.2 Water Outlet
Since the gravity center of the unit is not at its physical center, The condensed water outlets on the chassis for selection display
so please be careful when lifting it with a sling. as the follow figure:
5/7kW
Never hold the inlet of the outdoor unit to prevent it from
deforming.
Fasten the feet of this unit with bolts firmly to prevent it from 10~16kW
collapsing in case of earthquake or strong wind.
13
5.4 TYPICAL APPLICATION EXAMPLES
The application examples given below are for illustration purposes only.
5.4.1 Application 1
Space cooling and heating application with a standard controller (or optional wired controller) connected to the unit.
10
9.1
11 12
5
9 9.2
2 3 8
6 7 FCU1 FCU2 FCUn
NOTE
If the volume of balance tank(9) larger than 30L, the buffer tank(8) is unnecessary, otherwise the buffer tank(8) should be installed and the
total volume of buffer tank and balance tank should larger than 30L. The drain valve (6) should be installed at the lowest positon of the
system.
An independent backup heater can be selected and installed in the door,which can provide additional heating source and ensure better
performance of the system when the ambient temperature is low.
Unit operation
when there is a cooling or heating request from the standard controller (or optional wired controller), the unit will start operating to achieve
the target water flow temperature as set on standard controller (or optional wired controller). When the room temperature reaches the set point,
the unit will stop operating. The circulation pump (built-in pump 1 and outside pump 2) will also running.
14
5.4.2 Application 2
Space heating only application with a standard controller (or optional wired controller) connected to the unit. Heating is provided through floor
heating loops.
10
9.1
11 12
5
9
9.2 13
2 3 22 8
6 7
FHL1 FHL2 ....... FHLn
NOTE
If the volume of balance tank(9) larger than 30L, the buffer tank(8) is unnecessary, otherwise the buffer tank(8) should be installed and the
total volume of buffer tank and balance tank should larger than 30L.The drain valve (6) should be installed at the lowest positon of the
system.
An independent backup heater can be selected and installed in the door, which can provide additional heating source and ensure better
performance of the system when the ambient temperature is low.
■ Mixing station
As the unit is mainly to provide middle-temperture and high-temperature water, when connecting floor heating, the need to increase the mixing
station (13) before the floor heating.
15
5.4.3 Application 3
Space cooling and heating application with a standard controller (or optional wired controller) connected to the unit. Heating is
provided through floor heating loops and fan coil units. Cooling is provided through the fan coil units only.
T1 T2 Tn
12
15
M1 M2 Mn
9.1
14
11 M 12
5
9 9.2 13
2 3 8
6 7
FHL1 FHL2 FHLn
NOTE
If the volume of balance tank(9) larger than 30L, the buffer tank(8) is unnecessary, otherwise the buffer tank(8) should be installed and the
total volume of buffer tank and balance tank should larger than 30L.The drain valve (6) should be installed at the lowest positon of the
system.
An independent backup heater can be selected and installed in the door, which can provide additional heating source and ensure better
performance of the system when the ambient temperature is low.
■ Mixing station
As the unit is mainly to provide middle-temperture and high-temperature water, when connecting floor heating, the need to increase the mixing
station (13) before the floor heating.
■ Pump operation and space heating and cooling
According to the season, the unit(1) will switch to either heating or cooling mode according to the temperature detected by the standard controller
(or optional wired controller (4)). When space heating/cooling is requested standard controller (or optional wired controller (4)), the pump will
start operating and the unit (1) will switch to heating mode/cooling mode. The unit (1) will operating to achieve the target cold/hot water leaving
temperature.
In the cooling mode. the motorized 2-way valve (14) will be set to closed to prevent cold water running through the floor heating loops (FHL).
CAUTION
When circulation in each fan coil units (FCU 1...3) is controlled by remotely controlled valves (M1...3), it is important to provide a
by-pass valve (15) to avoid the flow switch safety device from being activated. The pass-by valve should be selected as such that at
all time the minimun water flow. It is recommended to select a pressure difference controlled by-pass valve.
16
5.4.4 Application 4
Space cooling and heating application with a standard controller (or optional wired controller) connected to the unit. Heating is provided through
floor heating loops . Cooling is provided through the fan coil units only. The 3-way valve is used to change the direction of water flow when the
operation mode changed.
T1 T2 Tn
12
15
M1 M2 Mn
9.1
11 16 12
5 M
9 9.2 13
2 3 8
6 7
FHL1 FHL2 FHLn
NOTE
B
If the volume of balance tank(9) larger than 30L, the buffer tank(8) is unnecessary, otherwise the buffer tank(8)
should be installed and the total volume of buffer tank and balance tank should larger than 30L.The drain valve (6)
should be installed at the lowest positon of the system. An independent backup heater can be selected and installed
in the door, which can provide additional heating source and ensure better performance of the system when the
ambient temperature is low. inlet M
A
The 3-way valve control requires field control, the unit does not provide control function.
In normal condition, port A should be opened, while signal sent to the 3-way valve (16), port A will be closed and port B will be opened.
When in cool mode, ON signal will sent to the 3-way valve (16), the cold water will flow through port inlet to port B, and port B should
connect to the fan coil units. While in heating mode, the hot water will flow through port inlet to port A, and port A should connect to the
floor heating loops. In this way, all the water from the unit will flow through the floor heating loops and thus ensure better performance of
the floor heating.
17
5.4.5 Application 5
NOTE
If you need to connect an auxiliary bolier (or other additional heating source) and have the ability to control auxiliary bolier,
you need to customize.
CAUTION
Be sure that the boiler and the integration of the boiler in the system is in accordance with relevant local laws and regulations.
Application A
AHS
10
5
9.1
11 12
5
9
9.2
2 3 8
6 7 FCU1 FCU2 FCUn
18
Application B
If application B is selected, the control cable connect to the boiler should also connect to the 3-way valve (16)
AHS
10
5
9.1
11 12
5 16
M
9
9.2
2 3 8
6 7 FCU1 FCU2 FCUn
NOTE
If the volume of balance tank(9) larger than 30L, the buffer tank(8) is unnecessary, otherwise the buffer tank(8) should be installed and the
total volume of buffer tank and balance tank should larger than 30L.The drain valve (6) should be installed at the lowest positon of the system.
An independent backup heater can be selected and installed in the door, which can provide additional heating source and ensure better
performance of the system when the ambient temperature is low.
Operation
When heating is required, either the unit or the boiler starts operating, depending on the outdoor temperature .
■ As the outdoor temperature is measured via the outdoor unit air thermistor, make sure to install the outdoor unit in the shade, so that it is not
influenced by the sun’s heat.
■ Frequent switching can cause corrosion of the boiler at an early stage. Contact the boiler manufacturer.
■ During heating operation of the unit, the unit will operate to achieve the target water flow temperature set on the controller.
■ During heating operation of the boiler, the boiler will operate to achieve the target water flow temperature set on the controller.
19
Before continuing installation of the unit, check the following:
5.5 Water pipe installation ■ The maximum water pressure can not exceed 3 bar.
■ The maximum water temperature is 60°C according to safety
NOTE device setting.
■ Always use materials that are compatible with the water used in the
■ If there is no glycol (anti-freeze) in the system there is a power system and with the materials used in the unit.
supply or pump failure, drain the system (as shown in the figure ■ Ensure that components installed in the field piping can withstand
below). the water pressure and temperature.
■ Drain taps must be provided at all low points of the system to
permit complete drainage of the circuit during maintenance.
WARNING ■ Air vents must be provided at all high points of the system. The
vents should be located at points that are easily accessible for
servicing. An automatic air purge is provided inside the unit. Check
that this air purge valve is not tightened too much so that automatic
release of air in the water circuit remains possible.
Sodium ion No requirement (a) Installation height difference: height difference (m) between the
highest point of the water circuit and the unit. If the unit is located
Calcium ion <50ppm at the highest point of the installation, the installation height is
considered to be 0 m.
Calculating pre-pressure of the expansion vessel
5.5.2 Checking the water circuit The pre-pressure (Pg) to be set depends on the maximum installation
height difference (H) and is calculated as follows:
The units are equipped with a water inlet and outlet for connection
Pg(bar)=(H(m)/10+0.3) bar
to a water circuit. This circuit must be provided by a licensed
technician and must comply with local laws and regulations. Checking the maximum allowed water volume
The unit is only to be used in a closed water system. To determine the maximum allowed water volume in the entire circuit,
Application in an open water circuit can lead to excessive proceed as follows:
corrosion of the water piping. 1. Determine the calculated pre-pressure (Pg) for the corresponding
maximum water volume using the graph below.
20
2. Check that the total water volume in the entire water circuit is ■ Because brass is a soft material, use
lower than this value. appropriate tools for connecting the water
If this is not the case, the expansion vessel inside the unit is too small circuit.
for the installation. Inappropriate tools will cause damage
to the pipes.
NOTE
The unit is only to be used in a closed water system. Application in
A1
an open water circuit can lead to excessive corrosion of the water
piping:
B1 ■ Never use Zn-coated parts in the water circuit. Excessive
A2
corrosion of these parts may occur as copper piping is used in
B2 the unit's internal water circuit.
■ When using a 3-way valve in the water circuit. Preferably
choose a ball type 3-way valve to guarantee full separation
between the domestic hot water and floor heating water circuit.
■ When using a 3-way valve or a 2-way valve in the water circuit.
The recommended maximum changeover time of the valve
pre-pressure = pre-pressure of the expansion vessel
should be less than 60 seconds.
maximum water volume = maximum water volume in the system
A1 System without glycol for the 10~16 kW unit 5.5.6 Protecting the water circuit against freezing
A2 System without glycol for the 5/7 kW unit
Frost can cause damage to the hydraulic system. As this unit is
B1 System with 25% propylene glycol for the 10~16 kW unit
installed outdoors and thus the hydraulic system is exposed to
B2 System with 25% propylene glycol for the 5/7kW unit
freezing temperatures, care must be taken to prevent freezing of the
(Refer to “Caution: Use of glycol” on Page 21.)
system.
Example 1
The 10kW unit is installed 5 m below the highest point in the water All hydraulic parts are insulated to reduce heat loss. Insulation must
circuit. be present on the field piping.
The total water volume in the water circuit is 60 L.
In this example, no action or adjustment is required. The unit is already equipped with several features to prevent
freezing. For example: the software contains special functions using
Example 2 pump and heat pump to protect the entire system against freezing.
The 10kW unit is installed at the highest point in the water circuit. The When the temperature of the water flow in the system drops to a
total water volume in the water circuit is 100 L. certain value, the software will heat the water, either using the heat
Result: pump, the electric heating tap. The freeze protection function will turn
■ Since 100 L is more than 88 L, the pre-pressure must be off only when the temperature increases to a certain value. Refer
decreased (see table above). to “7.3 Operating characteristics” .
■ The required pre-pressure is:
Pg(bar) = (H(m)/10+0.3) bar = (0/10+0.3) bar = 0.3 bar In case of a power failure, the features mentioned above cannot
■ The corresponding maximum water volume can be read from protect the unit from freezing.
the graph: approximately 158 L. Since a power failure could happen when the unit is unattended,
■ Since the total water volume (100 L) is below the maximum water the supplier recommends adding glycol to the water system. Refer
volume (158 L), the expansion vessel suffices for the installation. to “Caution: Use of glycol” .
5.5.4 Setting the pre-pressure of the expansion vessel Depending on the expected lowest outdoor temperature, make sure
When it is required to change the default pre-pressure of the the water system is filled with a concentration of glycol as mentioned
expansion vessel (1.5 bar), keep in mind the following guidelines: in the table below.
■ Use only dry nitrogen to set the expansion vessel pre-pressure.
■ Inappropriate setting of the expansion vessel pre-pressure will When glycol is added to the system, the performance of the unit will
lead to malfunctioning of the system. Pre-pressure should only be be affected. The correction factor of the unit capacity, flow rate and
adjusted by a licensed installer. pressure drop of the system is listed in the table below:
21
5.5.7 Fouling factors
WARNING The performance data given refer to conditions with clean evaporator
plates (fouling factor=1). For different fouling factors, multiply the
ETHYLENE GLYCOL AND PROPYLENE GLYCOL ARE TOXIC figures in the performance tables by the coefficient given in the
following table.
a.The concentrations mentioned in the table above will not
Fouling factors Evaporator
prevent the medium freezing, but will prevent the hydraulics from
bursting. capacity compressor power total power input
b.The maximum allowed water volume is then reduced according (m2 °C/W) correction factor input correction factor correction factor
to the figure “Maxiumum allowed water volume” on Page 21 C.
4.4 x 10-5 - - -
0.86 x 10-4 0.96 0.99 0.99
1.72 x10-4 0.93 0.98 0.98
CAUTION
5.5.8 Filling with water
Use of glycol 1. Connect the water supply to the fill valve and open the valve.
2. Make sure the automatic air purge valve is open (at least 2 turns).
■ For installations with a domestic hot water tank, the use of 3. Fill with water until the manometer indicates a pressure of
propylene glycol, including necessary inhibitors, is only EN1717 approximately 2.0 bar. Remove air in the circuit as much as
or equivalent based on the applicable legislation. possible using the air purge valves. Air present in the water circuit
■ in case of over-pressure when using glycol, be sure to connect the might cause malfunctioning of the backup heater.
safety valve to a drain pan in order to recover the glycol.
Do not fasten plastic cover
Connecting a drain pipe is not required if no glycol is used, the
on the air purge valve at the
discharged water is then drained via the bottom of the unit. topside of the unit when the
system is running. Open air
purge valve, turn
anticlockwise at least 2 full
turns to release air from the
NOTE system.
22
■ Never squeeze bundled cables and make sure they do not 5.6.3 Electrical connection
come in contact with the piping and sharp edges. Make sure no
external pressure is applied to the terminal connections.
The unitary mini chillers leave the factory already wired, and require
■ All field wiring and components must be installed by a
the installation of an omni polar thermal overload switch, a lockable
licensed electrician and must comply with relevant local
mains disconnecting switch for the connection to the mains power
laws and regulations.
supply, and the connection of the flow switch to the corresponding
■ The field wiring must be carried out in accordance with the
terminals. All the above operations must be carried out by qualified
wiring diagram supplied with the unit and the instructions
personnel in compliance with the legislation in force.
given below.
For all electrical work, refer to the electrical wiring diagrams in this
■ Be sure to use a dedicated power supply. Never use a
manual. You are also recommended to check that the characteristics
power supply shared by another appliance.
of the mains electricity supply are adequate for the absorptions
■ Be sure to establish a ground. Do not ground the unit to
indicated in the electrical characteristics table below, also bearing in
a utility pipe, surge protector, or telephone ground.
mind the possible use of other equipment at the same time.
Incomplete grounding may cause electrical shock.
■ Be sure to install a ground fault circuit interrupter (30 mA).
Failure to do so may cause electrical shock.
■ Be sure to install the required fuses or circuit breakers. WARNING
• Power to the unit must be turned on only after installation work
(hydraulic and electrical) has been completed.
• All electrical connections must be carried out by qualified
personnel in accordance with legislation in force in the country
concerned.
5.6.1 Precautions on electrical wiring work • Respect instructions for connecting phase, neutral and earth
conductors.
■ Fix cables so that cables do not make contact with the pipes • The power line should be fitted upstream with a suitable device to
(especially on the high pressure side). protect against short-circuits and leakage to earth, isolating the
■ Secure the electrical wiring with cable ties as shown in figure installation from other equipment.
so that it does not come in contact with the piping, particularly on • Voltage must be within a tolerance of ±10% of the rated power
the high-pressure side. supply voltage for the unit (for three phase units, the unbalance
■ Make sure no external pressure is applied to the terminal between the phases must not exceed 3%).If these parameters are
connectors. not respected, contact the electricity supply company.
■ When installing the ground fault circuit interrupter make sure • For electrical connections, use double insulation cable in
that it is compatible with the inverter (resistant to high frequency conformity with current legislation in the country concerned.
electrical noise) to avoid unnecessary opening of the ground fault • An omnipolar thermal overload switch and a lockable mains
circuit interrupter. disconnecting switch, in compliance with the CEI-EN standards
(contact opening of at least 3mm), with adequate switching and
residual current protection capacity based on the electrical data
NOTE
table shown below, must be installed as near as possible to the
appliance.
The ground fault circuit interrupter must be a high- speed • The devices on the unit must be lockable. An efficient earth
type breaker of 30 mA (<0.1 s). connection is obligatory. Failure to earth the appliance absolves
the manufacturer of all liability for damage.
• Do not use water pipes to earth the unit.
■ This unit is equipped with an inverter. Installing a phase advancing
capacitor not only will reduce the power factor improvement effect,
but also may cause abnormal heating of the capacitor due to high-
frequency waves. Never install a phase advancing capacitor as it
could lead to an accident.
■ Use a round crimp-style terminal for connection to the power 5kW/7kW (1-phase)
supply terminal board. In case it cannot be used due to unavoidable
reasons, be sure to observe the following instructions.
- Do not connect different gauge wires to the same power supply L N GND 1 2 3 4 5 6 7 8 9 10 11
terminal. (Loose connections may cause overheating.)
- When connecting wires of the same gauge, connect them PUMP2 Remote alarm Remote shutdown Remote cooling/heating wire controller
1 2 3 4 5 6 7 8 9 10 11 L N GND
PUMP2 Remote alarm Remote shutdown Remote cooling/heating wire controller
In wiring, make certain that prescribed wires are used, carry out PUMP2 Remote alarm Remote shutdown Remote cooling/heating wire controller
complete connections, and fix the wires so that outside force can
not affect the terminals.
23
2. Electrical Power Connection
Remote cooling/heating
1-phase 3-phase
7 8
L N GND A B C N GND
SWITCH 2
If switch2 is closed, the unit will shift to heating mode forcibly;
If switch2 breaks the unit will shift to cooling mode forcibly.
Residual Current Residual Current
Circuit-breaker Circuit-breaker
L N GND A B C N GND NOTE
AC 220-240V 50Hz AC 380-415V 50Hz
● When the remote control and wire controller used at the same
time, the unit will carry out the last command of arbitrary
terminal.
● Remote shutdown has the highest priority. In the status of
1 2 remote shutdown, other controllers can’t start the unit.
L
220-240V
N Wire controller
L
220-240V
N A1
AC contactor
A2 9 10 11
Additional pump P Q E
Remote alarm
Remote shutdown
5 6
SWITCH
If switch is closed, the unit will be stopped forcibly.
Under this circumstance, anti-frozen protection and other
protection functions are still effective.
If switch breaks, unit can run normally according settings.
24
4. The Specification of Power
WARNING
25
6.2.1 Hydraulic operational area constant speed Ⅰ,Ⅱ,Ⅲ
Constant speed ⅠⅡⅢ Constant speed ⅠⅡⅢ
p/kPa H/m
4300 1/min
RS 15/6 RKC RS25/7.5 RKC
6 1~230V-Rp1 60 1~230V-Rp1 1/4
8
50 4640 1/min p/kPa
5
3400 1/min 40 6
4 M 80
ax
.
3 30
4
60
2390 /min
1 m 2970 1/min
ax 20
2 .
2
1 10 40
800 1/min 1270 1/min
0 0
0 20
0 0.5 1.0 1.5 2.0 2.5 3.0 Q/m3/h 0 1 2 3 4 Q/m3/h
0 0.2 0.4 0.6 0.8 Q/l/s 0 0.2 0.4 0.6 0.8 1.0 1.2 Q/l/s
0 2 4 6 8 10 Q/lgpm 0 4 8 12 16 Q/lgpm
0
P 1/W P 1/W
40 80
20 40
0 0
0 0.5 1.0 1.5 2.0 2.5 3.0 Q/m3/h 0 1 2 3 4 Q/m3/h
10~16kW
5/7 kW
26
6.2.3 Static Pressure Drop Unit 6.2.4 Failure diagnosis at the moment of first installation
5/7kW ■ If nothing is displayed on the user interface, it is necessary to
70.0
check for any of the following abnormalities before diagnosing
60.0 possible error codes.
■ Disconnection or wiring error (between power supply and unit
and between unit and user interface).
External Static Pressure (KPa)
50.0
10kW
70.0
60.0
External Static Pressure (KPa)
50.0
Ⅲ:High Speed 7.1 To access the control panel,open the door
40.0
Ⅰ:Low Speed
10.0
0.0
0.8 1.4 2.0 2.6 3.2 1
2
Flow (m3/h)
80.0
12kW 3
70.0
60.0
External Static Pressure (KPa)
50.0
Ⅲ:High Speed se
t
40.0
3
Ⅱ:Medium Speed
30.0
20.0
Ⅰ:Low Speed
10.0
0.0
0.8 1.4 2.0 2.6 3.2
Flow (m3/h)
14kW
80.0
70.0
60.0
External Static Pressure (KPa)
50.0
Ⅲ:High Speed
40.0
Ⅱ:Medium Speed
30.0
20.0
Ⅰ:Low Speed
10.0
0.0
0.8 1.4 2.0 2.6 3.2
Flow (m3/h)
16kW
80.0
70.0
60.0
External Static Pressure (KPa)
50.0
Ⅲ:High Speed
40.0
Ⅱ:Medium Speed
30.0
20.0
Ⅰ:Low Speed
10.0
0.0
0.8 1.4 2.0 2.6 3.2
Flow (m3/h)
27
7.2 Activating and deactivating the unit
11 ① ② ③ ④ ⑤ ⑥
17
23 22
⑧ 18
19
⑨
24 21
20
⑩
7.1 7.2
12 13 14 15 16
28
NO. Icon Description
29
7.2.3 Functions of combination key
1. Force cooling 3.Auto-lock(unlock) function
Press “ ” and “ ” simultaneously for 3s in the main If don’t operate the controller in 60s, the keyboard will lock
interface to enter into force cooling mode. The force cooling mode automatically. Press “ ”and “ ” simultaneously for 3s
icon will be constantly light. to unlock.
Press “ ” button and “ ” button simultaneously for 3s to
quit force cooling mode. The unit will enter power off mode 4.Factory Reset:
automatically when quitting force cooling mode. In main interface, long press “ENTER” for 3s, the unit will close and
recovers to factory default mode.
2. Parameter query function Display panel will display“OFF”。
①To enter parameter query function.
Press “ ” and “ ” simultaneously for 3s to enter into the
interface of parameter query function. At this moment, first 2 digits 7.2.4 Shutting down for long periods
of the nixie tube will display sequence number and the
last 2 digits is specific parameters. If it is previewed not to use the machine for long periods After
Press “ ” or “ ” to query the relative parameters. deactivating the chiller:
See query orders in Table 11-1. -Make sure the model is in the Power off model " ", or
alternatively disconnect the unit from the power supply.
②Quit parameter query function If there’s no operation in 20s -Make sure the remote control switch is closed (if present) .
when enter the parameter query, it will quit automatically and -Close the water valves.
return to the main interface.
Press “ ” and “ ” simultaneously to quit parameter query
manually.
1 Frequency Display operating frequency when the unit is in cooling mode and heating mode.
30
7.3 Operating characteristics 5. Fan speed control
1. Set temperature in cooling For correct operation of the unit with different ambient
Range:10~20℃ (default:12℃) temperatures, the microprocessor controls the fan speed based
If the set temperature is between 10~13℃, the compressor start and on the ambient temperature and the condensing or evaporation
shut down according to the difference between the inlet temperature temperature as well as compressor frequency, thus enabling heat
and the set temperature as follows: exchange to be increased and/or decreased, maintaining the
condensing or evaporation temperature practically constant.
Tin-Ts
on 6. Frost prevention protection
2 To prevent the water freezing and damaging the plate heat
exchanger, the microprocessor will perform antifreeze protection
-1
off program if the heat exchanger temperature or the water
temperature below a certain temperature.
a. In the cooling mode or water pump mode: if the heat exchanger
If the set temperature is between 14~20℃,the compressor start and temperature or the outlet temperature sensor is less than 3℃, the
shut down according to the difference between the inlet temperature compressor will shut down and the controller display Pb code, the
and the set temperature as follows: water pump will continue to run until the heat exchanger
Tin-Ts temperature or the outlet temperature sensor is above 8℃ and the
unit will resume normal operation.
on b. In the heating mode or standby mode: if the heat exchanger
2 temperature or the inlet temperature sensor is less than 8℃, the
controller display Pb code, the water pump will continue to run until
-2
off the heat exchanger temperature or the inlet temperature sensor is
above 15℃. If the heat exchanger temperature or the inlet
temperature sensor continues to fall below 5℃, the unit will be
2. Set temperature in heating forced heating operation, the compressor and the water pump will
Range:35~50℃ (default:40℃) be running until the heat exchanger temperature or the inlet
If the set temperature is between 35~44℃,the compressor start and temperature sensor is above 15℃.
shut down according to the difference between the inlet temperature c. If the ambient temperature is less than 8℃and the heat
and the set temperature as follows: exchanger temperature or the inlet temperature sensor is less
Tin-Ts than 2℃, the electric exchanger temperature heating will turn on
until the heat exchanger temperature or the inlet temperature
sensor is above 7℃.
2 off
If the unit is likely to operate below 0℃, it is advisable to add
-2
on antifreeze to the water system to prevent the unit from freezing the
system in the event of a power cut off or failure.
If the set temperature is between 45~50℃,the compressor start and 7. Fin heat exchanger high temperature protection
shut down according to the difference between the inlet temperature When the fin heat exchanger temperature over than 62°C, system
and the set temperature as follows: will shut down, but not returns to normal operation until the
Tin-Ts temperature decreased less than 52°C.
CAUTION
NOTE
If there is a possibility that the outside temperature may drop
The set temperature refers to the set return water temperature or below zero,there is the risk of freezing.
inlet temperature; The water circuit MUST BE EMPTIED AND SHUT OFF
In the event of a temporary power failure, when power returns, the POWER (when draining after heat pump operation take care
mode set previously will be retained in the memory. as the water may be hot) or antifreeze must be added in the
proportion recommended by the manufacturer.
3. Comperssor start up delay
In order to prevent the compressor frequent start and stop, the
compressor must ensure that each start since the last stop since the
minimum time of 300 seconds.
T3&T4 temperature sensor malfunction 5) Only certificated person is allowed to do installation, operation
Voltage protection and maintenance.
32
10. MAIN PARAMETERS
Model 5 7 10 12 12 14 16
Power supply V-Ph-Hz 220-240, 1, 50 220-240, 1, 50 220-240, 1, 50 220-240, 1, 50 380-415, 3, 50 380-415, 3, 50 380-415, 3, 50
Max. input consumption W 2800 3000 4800 5200 5200 5600 5900
Max. input current A 14.6 15.6 25.0 26.0 8.9 9.6 10.1
33
Product fiche 1
Outdoor MGC-V5W/D2N1 MGC-V7W/D2N1 MGC-V10W/D2N1 MGC-V12W/D2N1
Heat pump space heater
Indoor - - - -
Indoor unit sound power (*) [dB(A)] - - - -
Outdoor unit sound power (*) [dB(A)] 63.0 66.0 68.0 68.0
Space heating Energy efficiency class 35°C (Low temp. app.) - A+ A+ A+ A+
Average climate (Design temperature = –10°C)
Prated (declared heating capacity) @ –10°C [kW] 6.2 8.0 11.0 12.3
Space heating 35°C Seasonal space heating efficiency (ηs) [%] 139 135 131 135
Annual energy consumption ion [kWh] 3,600 4,750 6,900 7,400
Warmer climate (Design temperature =2°C)
Prated (declared heating capacity) @ 2°C [kW] 5.1 6.8 9.0 9.3
Space heating 35°C Seasonal space heating efficiency (ηs) [%] 169 165 161 164
Annual energy consumption [kWh] 1,125 1,484 2,155 2,312
Ecodesign technical data
Air-to-water heat pump Y/N Yes Yes Yes Yes
Water-to-water heat pump Y/N No No No No
Brine-to-water heat pump Y/N No No No No
Product description
Low-temperature heat pump Y/N Yes Yes Yes Yes
Equipped with a supplementary heater Y/N Yes Yes Yes Yes
Heat pump combination heater Y/N No No No No
Air to water unit Rated airflow (outdoor) [m3/h] 3200 3750 4800 4800
Brine/water to water unit Rated water/brine flow (outdoor H/E)
Capacity control -
Poff (Power consumption Off mode) [kW] 0.011 0.011 0.018 0.018
Pto (Power consumption Thermostat off mode) [kW] 0.005 0.005 0.023 0.023
Other Psb (Power consumption Standby mode) [kW] 0.011 0.011 0.019 0.019
PCK (Power crankcase heater model) [kW] 0.032 0.032 0.060 0.060
Qelec (Daily electricity consumption) [kWh]
Qfuel (Daily fuel consumption) [kWh]
Part load conditions space heating average climate
Pdh (declared heating capacity) [kW] 5.51 5.70 10.20 10.50
(A) condition (-7°C) COPd (declared COP) - 2.50 2.30 2.30 2.25
Cdh(degradation coefficient) - 0.90 0.90 0.90 0.90
Pdh (declared heating capacity) [kW] 3.59 4.40 6.10 3.80
(B) condition (2°C) COPd (declared COP) - 3.88 3.48 3.20 3.35
Cdh(degradation coefficient) - 0.90 0.90 0.90 0.90
Pdh (declared heating capacity) [kW] 2.20 2.90 3.80 4.40
(C) condition (7°C) COPd (declared COP) - 4.56 5.60 4.75 5.00
Cdh(degradation coefficient) - 0.90 0.90 0.90 0.90
Pdh (declared heating capacity) [kW] 1.06 1.29 2.10 2.10
(D) condition (12°C) COPd (declared COP) - 4.15 4.30 4.70 5.15
Cdh(degradation coefficient) - 0.90 0.90 0.90 0.90
Tol (temperature operating limit) [°C] -10.00 -10.00 -10.00 -10.00
(E) Tol (temperature operating limit) Pdh (declared heating capacity) [kW] 5.10 5.45 9.50 10.00
COPd (declared COP) - 2.45 2.30 2.25 2.15
WTOL (Heating water Operation Limit) [°C] 52.00 52.00 52.00 52.00
Tblv [°C] -7.00 -4.00 -7.00 -6.00
(F) Tbivalent temperature Pdh (declared heating capacity) [kW] 5.51 6.26 10.20 10.90
COPd (declared COP) - 2.50 2.54 2.30 2.35
Capacity of the back-up heater integrated in the unit Psup back-up heater (@Tdesignh: –10°C) [kW] 3.00 3.00 4.50 4.50
Supplementary capacity at P_design Psup (@Tdesignh: –10°C) [kW] 1.10 2.55 1.50 2.30
34
Product fiche 2
Outdoor MGC-V12W/D2RN1 MGC-V14W/D2RN1 MGC-V16W/D2RN1
Heat pump space heater
Indoor - - -
Indoor unit sound power (*) [dB(A)] - - -
Outdoor unit sound power (*) [dB(A)] 68.0 70.0 72.0
Space heating Energy efficiency class 35°C (Low temp. app.) - A+ A+ A+
Average climate (Design temperature = –10°C)
Prated (declared heating capacity) @ –10°C [kW] 12.3 13.8 16.0
Space heating 35°C Seasonal space heating efficiency (ηs) [%] 143 148 133
Annual energy consumption [kWh] 7,050 7,600 9,878
Warmer climate (Design temperature =2°C)
Prated (declared heating capacity) @ 2°C [kW] 9.3 9.5 9.8
Space heating 35°C Seasonal space heating efficiency (ηs) [%] 172 176 163
Annual energy consumption [kWh] 2,202 2,374 3,086
Ecodesign technical data
Air-to-water heat pump Y/N Yes Yes Yes
Water-to-water heat pump Y/N No No No
Brine-to-water heat pump Y/N No No No
Product description
Low-temperature heat pump Y/N Yes Yes Yes
Equipped with a supplementary heater Y/N Yes Yes Yes
Heat pump combination heater Y/N No No No
Air to water unit Rated airflow (outdoor) [m3/h] 4800 4800 6200
Brine/water to water unit Rated water/brine flow (outdoor H/E)
Capacity control -
Poff (Power consumption Off mode) [kW] 0.018 0.020 0.020
Pto (Power consumption Thermostat off mode) [kW] 0.023 0.026 0.026
Other Psb (Power consumption Standby mode) [kW] 0.019 0.020 0.020
PCK (Power crankcase heater model) [kW] 0.060 0.062 0.062
Qelec (Daily electricity consumption) [kWh]
Qfuel (Daily fuel consumption) [kWh]
Part load conditions space heating average climate
Pdh (declared heating capacity) [kW] 11.10 12.30 11.40
(A) condition (-7°C) COPd (declared COP) - 2.50 2.45 2.10
Cdh(degradation coefficient) - 0.90 0.90 0.90
Pdh (declared heating capacity) [kW] 7.00 7.60 8.50
(B) condition (2°C) COPd (declared COP) - 3.60 3.80 3.40
Cdh(degradation coefficient) - 0.90 0.90 0.90
Pdh (declared heating capacity) [kW] 4.30 4.90 5.83
(C) condition (7°C) COPd (declared COP) - 5.20 5.30 5.24
Cdh(degradation coefficient) - 0.90 0.90 0.90
Pdh (declared heating capacity) [kW] 2.00 2.40 2.82
(D) condition (12°C) COPd (declared COP) - 4.90 5.55 5.75
Cdh(degradation coefficient) - 0.90 0.90 0.90
Tol (temperature operating limit) [°C] -10.00 -10.00 -10.00
Pdh (declared heating capacity) [kW] 10.40 10.90 11.50
(E) Tol (temperature operating limit)
COPd (declared COP) - 2.35 2.20 2.10
WTOL (Heating water Operation Limit) [°C] 52.00 52.00 52.00
Tblv [°C] -7.00 -5.00 -4.00
(F) Tbivalent temperature Pdh (declared heating capacity) [kW] 11.10 11.20 12.61
COPd (declared COP) - 2.50 2.80 2.35
Capacity of the back-up heater integrated in the unit Psup back-up heater (@Tdesignh: –10°C) [kW] 4.50 4.50 4.50
Supplementary capacity at P_design Psup (@Tdesignh: –10°C) [kW] 1.90 2.90 4.50
35
Technical parameters
Model(s): MGC-V5W/D2N1
Air-to-water heat pump: YES
Water-to-water heat pump: NO
Brine-to-water heat pump: NO
Low-temperature heat pump: YES
Equipped with a supplementary heater: NO
Heat pump combination heater: NO
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat
pumps, parameters shall be declared for low-temperature application.
Parameters shall be declared for average, colder and warmer climate conditions.
Other items
Capacity control variable For air-to-water heat pumps: Rated air
- 3200 m³/h
flow rate, outdoors
Sound power level, indoors/ outdoors LWA -/63 dB
For water-/or brine-to-water heat pumps: Rated - - m³/h
Annual energy consumption QHE 3600 kWh brine or water flow rate, outdoor heat exchanger
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating
Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).
(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
36
Technical parameters
Model(s): MGC-V7W/D2N1
Air-to-water heat pump: YES
Water-to-water heat pump: NO
Brine-to-water heat pump: NO
Low-temperature heat pump: YES
Equipped with a supplementary heater: NO
Heat pump combination heater: NO
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat
pumps, parameters shall be declared for low-temperature application.
Parameters shall be declared for average, colder and warmer climate conditions.
Other items
Capacity control variable For air-to-water heat pumps: Rated air
- 3750 m³/h
flow rate, outdoors
Sound power level, indoors/ outdoors LWA -/66 dB
For water-/or brine-to-water heat pumps: Rated - - m³/h
Annual energy consumption QHE 4750 kWh brine or water flow rate, outdoor heat exchanger
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating
Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).
(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
37
Technical parameters
Model(s): MGC-V10W/D2N1
Air-to-water heat pump: YES
Water-to-water heat pump: NO
Brine-to-water heat pump: NO
Low-temperature heat pump: YES
Equipped with a supplementary heater: NO
Heat pump combination heater: NO
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat
pumps, parameters shall be declared for low-temperature application.
Parameters shall be declared for average, colder and warmer climate conditions.
Other items
Capacity control variable For air-to-water heat pumps: Rated air
- 4800 m³/h
flow rate, outdoors
Sound power level, indoors/ outdoors LWA -/68 dB
For water-/or brine-to-water heat pumps: Rated - - m³/h
Annual energy consumption QHE 6900 kWh brine or water flow rate, outdoor heat exchanger
GD Midea Heating & Ventilating Equipment Co. , Ltd.Penglai industry Road, Beijiao, Shunde,
Contact details
Foshan, Guangdong, 528311 P.R. China
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating
Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).
(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
38
Technical parameters
Model(s): MGC-V12W/D2N1
Air-to-water heat pump: YES
Water-to-water heat pump: NO
Brine-to-water heat pump: NO
Low-temperature heat pump: YES
Equipped with a supplementary heater: NO
Heat pump combination heater: NO
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat
pumps, parameters shall be declared for low-temperature application.
Parameters shall be declared for average, colder and warmer climate conditions.
Other items
Capacity control variable For air-to-water heat pumps: Rated air
- 4800 m³/h
flow rate, outdoors
Sound power level, indoors/ outdoors LWA -/68 dB
For water-/or brine-to-water heat pumps: Rated - - m³/h
Annual energy consumption QHE 7400 kWh brine or water flow rate, outdoor heat exchanger
GD Midea Heating & Ventilating Equipment Co. , Ltd.Penglai industry Road, Beijiao, Shunde,
Contact details
Foshan, Guangdong, 528311 P.R. China
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating
Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).
(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
39
Technical parameters
Model(s): MGC-V12W/D2RN1
Air-to-water heat pump: YES
Water-to-water heat pump: NO
Brine-to-water heat pump: NO
Low-temperature heat pump: YES
Equipped with a supplementary heater: NO
Heat pump combination heater: NO
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat
pumps, parameters shall be declared for low-temperature application.
Parameters shall be declared for average, colder and warmer climate conditions.
Other items
Capacity control variable For air-to-water heat pumps: Rated air
- 4800 m³/h
flow rate, outdoors
Sound power level, indoors/ outdoors LWA -/68 dB
For water-/or brine-to-water heat pumps: Rated - - m³/h
Annual energy consumption QHE 7050 kWh brine or water flow rate, outdoor heat exchanger
GD Midea Heating & Ventilating Equipment Co. , Ltd.Penglai industry Road, Beijiao, Shunde,
Contact details
Foshan, Guangdong, 528311 P.R. China
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating
Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).
(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
40
Technical parameters
Model(s): MGC-V14W/D2RN1
Air-to-water heat pump: YES
Water-to-water heat pump: NO
Brine-to-water heat pump: NO
Low-temperature heat pump: YES
Equipped with a supplementary heater: NO
Heat pump combination heater: NO
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat
pumps, parameters shall be declared for low-temperature application.
Parameters shall be declared for average, colder and warmer climate conditions.
Other items
Capacity control variable For air-to-water heat pumps: Rated air
- 4800 m³/h
flow rate, outdoors
Sound power level, indoors/ outdoors LWA -/70 dB
For water-/or brine-to-water heat pumps: Rated - - m³/h
Annual energy consumption QHE 7600 kWh brine or water flow rate, outdoor heat exchanger
GD Midea Heating & Ventilating Equipment Co. , Ltd.Penglai industry Road, Beijiao, Shunde,
Contact details
Foshan, Guangdong, 528311 P.R. China
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating
Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).
(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
41
Technical parameters
Model(s): MGC-V16W/D2RN1
Air-to-water heat pump: YES
Water-to-water heat pump: NO
Brine-to-water heat pump: NO
Low-temperature heat pump: YES
Equipped with a supplementary heater: NO
Heat pump combination heater: NO
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat
pumps, parameters shall be declared for low-temperature application.
Parameters shall be declared for average, colder and warmer climate conditions.
Other items
Capacity control variable For air-to-water heat pumps: Rated air
- 6200 m³/h
flow rate, outdoors
Sound power level, indoors/ outdoors LWA -/72 dB
For water-/or brine-to-water heat pumps: Rated - - m³/h
Annual energy consumption QHE 9878 kWh brine or water flow rate, outdoor heat exchanger
GD Midea Heating & Ventilating Equipment Co. , Ltd.Penglai industry Road, Beijiao, Shunde,
Contact details
Foshan, Guangdong, 528311 P.R. China
(*) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating
Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).
(**) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
42
Information requirements for comfort chillers
Model(s): MGC-V5W/D2N1
Degradation co-efficient
for chillers (*) Cdc 0.9 -
Crankcase heater
Off mode POFF 0.010 kW PCK 0.000 kW
mode
Thermosat-off
PTO 0.001 kW Standby mode PSB 0.011 kW
mode
Other items
(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9.
(**) From 26 September 2018.
43
Information requirements for comfort chillers
Model(s): MGC-V7W/D2N1
Degradation co-efficient
for chillers (*) Cdc 0.9 -
Crankcase heater
Off mode POFF 0.010 kW PCK 0.000 kW
mode
Thermosat-off
PTO 0.001 kW Standby mode PSB 0.011 kW
mode
Other items
(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9.
(**) From 26 September 2018.
44
Information requirements for comfort chillers
Model(s): MGC-V10W/D2N1
Degradation co-efficient
for chillers (*) Cdc 0.9 -
Crankcase heater
Off mode POFF 0.019 kW PCK 0.000 kW
mode
Thermosat-off
PTO 0.000 kW Standby mode PSB 0.019 kW
mode
Other items
(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9.
(**) From 26 September 2018.
45
Information requirements for comfort chillers
Model(s): MGC-V12W/D2N1
Degradation co-efficient
for chillers (*) Cdc 0.9 -
Crankcase heater
Off mode POFF 0.019 kW PCK 0.000 kW
mode
Thermosat-off
PTO 0.000 kW Standby mode PSB 0.019 kW
mode
Other items
(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9.
(**) From 26 September 2018.
46
Information requirements for comfort chillers
Model(s): MGC-V12W/D2RN1
Degradation co-efficient
for chillers (*) Cdc 0.9 -
Crankcase heater
Off mode POFF 0.019 kW PCK 0.000 kW
mode
Thermosat-off
PTO 0.000 kW Standby mode PSB 0.019 kW
mode
Other items
(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9.
(**) From 26 September 2018.
47
Information requirements for comfort chillers
Model(s): MGC-V14W/D2RN1
Degradation co-efficient
for chillers (*) Cdc 0.9 -
Crankcase heater
Off mode POFF 0.021 kW PCK 0.000 kW
mode
Thermosat-off
PTO 0.000 kW Standby mode PSB 0.021 kW
mode
Other items
(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9.
(**) From 26 September 2018.
48
Information requirements for comfort chillers
Model(s): MGC-V16W/D2RN1
Degradation co-efficient
for chillers (*) Cdc 0.9 -
Crankcase heater
Off mode POFF 0.021 kW PCK 0.000 kW
mode
Thermosat-off
PTO 0.000 kW Standby mode PSB 0.021 kW
mode
Other items
(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9.
(**) From 26 September 2018.
49
16127400000001 V3.0
此页不做菲林
说明书尺寸为A4,黑白印刷,双胶纸
I-J
P42-49增加 lot21参数、封底页版本号升级
J-K
P43-49,GWP to the Refrigerant 参数全部更改为2088
封底页版本号升级