Voltage Transformer Test Set M210 - M211 PDF
Voltage Transformer Test Set M210 - M211 PDF
Voltage Transformer Test Set M210/M211 measures voltage transformer (VT) errors with the method based on high
voltage capacitance bridge. This method provides accurate measurement of the VT errors in continuous ranges
of primary and secondary voltages. The method allows to decrease dimensions and weight of the equipment
significantly
M210/M211 can also be used as a capacitive high voltage bridge for measuring capacitance and dissipation
factor (tanδ) during testing of high voltage equipment *
Easy handling
VERSIONS
Voltage Transformer Test Set M210/M211 is available in six versions, which differ in accuracy class and maximum
primary voltage.
M210/M211 Primary voltage Secondary voltage range Rated voltage of High Voltage
version range (U1), kV (U2), V Capacitors (UCH), kV
M210.1
0,01…45 45
M211.1
M210.2
0,01…100 0,6…1000 100
M211.2
M210.3
0,01…230 230
M211.3
The version of M210/M211 for higher voltage can be supplied upon customer’s request
TEST ARRANGEMENT
Step-up HV zone
Voltage
Regulator Transformer VT under test
а Electronic
Voltage Burden
х S1 M410/M411 PE ~50/60 Hz 230 V
Х Mains
HV Measuring
Capacitor VoltageTransformer
U1 Test Set M210/M211
CH
I2 U2
I1* Measuring
I1 Unit
INTERFACE I1
UNIT
FOC
Fig.1 VT testing
CX tanδx
~50/60 Hz 230 V
Voltage Transformer
Test Set M210/M211
I2 U2
I1* Measuring
INTERFACE Unit
I1
UNIT
FOC
TECHNICAL SPECIFICATIONS
Measurement ranges and error limits of VT Test Set M210 – VT testing
Limits of
absolute
Value Measurement range Additional conditions
measurement
error
300 V ≤ U1 ≤ UСH,
± 0,015 % |∆φ| ≤ 100 min 6 V ≤ U2 ≤ 1000 V
Ratio error, ε -100 % ≤ ε ≤ 100 % ± 0,05 % |∆φ| ≤ 100 min 100 V ≤ U1 < 300 V,
± 0,1 % |∆φ| > 100 min 6 V ≤ U2 ≤ 1000 V
Measurement ranges and error limits of VT Test Set M210 – С&tanδ testing
Limits of relative Limits of absolute
СХ/С0 Test current, А
measurement error of δC, % measurement error of dissipation factor Δtanδ
0,01…0,1 ±[1∙10-2 +2∙10-4∙(C0/CX-10) + |tanδX-tanδ0|] ±[1∙10-4 + 2∙10-6∙(C0/CX -10) + 0,005∙|tanδX - tanδ0|]
up to 0,2
0,1…103 ±1∙10-2 + |tanδX - tanδ0|] ±[1∙10-4 + 0.005∙|tanδX - tanδ0|]
Measurement ranges and error limits of VT Test Set M211 – С&tanδ testing
Measurement ranges and error limits of VT Test Set M210/M211 – voltage parameters testing
Power mains
Measuring Unit built-in rechargeable battery
Charging and Calibration Power Supply Units 220/230 V, 50 Hz
Operating Temperature - 10...40 °C
Relative Humidity up to 80 % non-condensing
Measuring HV capacitor
Size, mm Unit 45 kV 100 kV 230 kV
250×350×185 170 × 425 260 × 610 390 × 995
Weight, kg 10 7 17 55
Standards
Safety EN 61010-1:2010
EMC EN 61326-1:2013
ORDERING INFORMATION
Scope of supply
The following items are supplied with the standard VTTS modification: