Development and production of measurement devices

М210/M211 Voltage Transformer Test Set

Voltage Transformer Test Set M210/M211 measures voltage transformer (VT) errors with the method based on high
voltage capacitance bridge. This method provides accurate measurement of the VT errors in continuous ranges
of primary and secondary voltages. The method allows to decrease dimensions and weight of the equipment
significantly

M210/M211 can also be used as a capacitive high voltage bridge for measuring capacitance and dissipation
factor (tanδ) during testing of high voltage equipment *

FEATURES AND BENEFITS APPLICATIONS

Measurement of VT errors in continuous ranges of M210/M211 is used by:


primary and secondary voltages
Manufacturer of Voltage Transformers
High measurement accuracy (VT testing): up to Calibration Laboratories
± 0,005 % and ± 0,3 minutes
On-site testing of Voltage Transformers
High measurement accuracy (С&tanδ testing): up to Metrology Institutes
± 0,005 % (Cx) and ± 0,00005 (tanδ)*

Measurement of true RMS values of primary and


secondary voltages, THD and n-th harmonic ratios
(up to 40-th) measurement

A more cost-effective solution than combination


of standard voltage transformers or voltage divider
and comparator

Easy handling

Small size and low weight

* Additional function. Can be supplied upon customer's request


M210/M211
Voltage Transformer Test Set

VERSIONS
Voltage Transformer Test Set M210/M211 is available in six versions, which differ in accuracy class and maximum
primary voltage.

M210/M211 Primary voltage Secondary voltage range Rated voltage of High Voltage
version range (U1), kV (U2), V Capacitors (UCH), kV
M210.1
0,01…45 45
M211.1
M210.2
0,01…100 0,6…1000 100
M211.2
M210.3
0,01…230 230
M211.3

The version of M210/M211 for higher voltage can be supplied upon customer’s request

TEST ARRANGEMENT

Step-up HV zone
Voltage
Regulator Transformer VT under test

а Electronic
Voltage Burden
х S1 M410/M411 PE ~50/60 Hz 230 V
Х Mains

HV Measuring
Capacitor VoltageTransformer
U1 Test Set M210/M211
CH
I2 U2

I1* Measuring
I1 Unit
INTERFACE I1
UNIT
FOC

Fiber optic cable

Fig.1 VT testing

Step-up HV Standard Device under HV zone


Voltage Capacitor (C0) test
Regulator Transformer

CX tanδx
~50/60 Hz 230 V

Voltage Transformer
Test Set M210/M211

I2 U2

I1* Measuring
INTERFACE Unit
I1
UNIT
FOC

Fiber optic cable

Fig. 2 С&tanδ testing*

* Additional function. Can be supplied upon customer's request


M210/M211
Voltage Transformer Test Set

TECHNICAL SPECIFICATIONS
Measurement ranges and error limits of VT Test Set M210 – VT testing
Limits of
absolute
Value Measurement range Additional conditions
measurement
error
300 V ≤ U1 ≤ UСH,
± 0,015 % |∆φ| ≤ 100 min 6 V ≤ U2 ≤ 1000 V

100 V ≤ U1 < 300 V,


± 0,05 % |∆φ| ≤ 100 min
Ratio error, ε - 100 % ≤ ε ≤ 100 % 6 V ≤ U2 ≤ 1000 V
100 V ≤ U1≤ UСH,
± 0,1 % |∆φ| > 100 min
6 V ≤ U2 ≤ 1000 V

± 0,5 % 10 V ≤ U1 < 100 V and/or 0,6 V≤ U2< 6 V


300 V ≤ U1 ≤ UСH,
± 1 min |∆φ| ≤ 100 min 6 V ≤ U2 ≤ 1000 V

100 V ≤ U1 < 300 V,


Phase displacement, ± 3 min |∆φ| ≤ 100 min
6 V ≤ U2 ≤ 1000 V
- 300 min ≤ ∆φ ≤ 300 min
∆φ
100 V ≤ U1 ≤ UСH,
± 5 min |∆φ| > 100 min
6 V ≤ U2 ≤ 1000 V

± 10 min 10 V ≤ U1< 100 V and/or 0,6 V ≤ U2< 6 V


Relative value of
secondary voltage, 2...190 % ± 1 %* 0,6 V ≤ U2≤ 1000 V
US/ USr
Test voltage
49...51 Hz** ± 0,02 Hz −
frequency, f

Measurement ranges and error limits of VT Test Set M211 – VT testing


Limits of
absolute
Value Measurement range Additional conditions
measurement
error
± 0,005 % |∆φ| ≤ 30 min 300 V ≤ U1 ≤ UСH,
± 0,01 % 30 min< |∆φ| ≤100 min 6 V ≤ U2 ≤ 1000 V

Ratio error, ε -100 % ≤ ε ≤ 100 % ± 0,05 % |∆φ| ≤ 100 min 100 V ≤ U1 < 300 V,
± 0,1 % |∆φ| > 100 min 6 V ≤ U2 ≤ 1000 V

± 0,5 % 10 V ≤ U1< 100 V and/or 0,6 V≤ U2< 6 V


± 0,3 min |∆φ| ≤ 30 min 300 V ≤ U1 ≤ UСH,
± 1 min 30 min < |∆φ| ≤ 100 min 6 V ≤ U2 ≤ 1000 V

100 V ≤ U1 < 300 V,


Phase ± 3 min |∆φ| ≤ 100 min
6 V ≤ U2 ≤ 1000 V
-300 min ≤ ∆φ ≤ 300 min
displacement, ∆φ
100 V ≤ U1 ≤ UСH,
± 5 min |∆φ| > 100 min
6 V ≤ U2 ≤ 1000 V

± 10 min 10 V ≤ U1< 100 V and/or 0,6 V ≤ U2 < 6 V


Relative value of
secondary voltage, 2...190 % ± 1 %* 0,6 V ≤ U2 ≤ 1000 V
US/ USr
Test voltage
49...51 Hz** ± 0,02 Hz −
frequency, f
*relative error
** measuring at the frequency of 60 Hz can be agreed with the customer
M210/M211
Voltage Transformer Test Set

Measurement ranges and error limits of VT Test Set M210 – С&tanδ testing
Limits of relative Limits of absolute
СХ/С0 Test current, А
measurement error of δC, % measurement error of dissipation factor Δtanδ
0,01…0,1 ±[1∙10-2 +2∙10-4∙(C0/CX-10) + |tanδX-tanδ0|] ±[1∙10-4 + 2∙10-6∙(C0/CX -10) + 0,005∙|tanδX - tanδ0|]
up to 0,2
0,1…103 ±1∙10-2 + |tanδX - tanδ0|] ±[1∙10-4 + 0.005∙|tanδX - tanδ0|]

Measurement ranges and error limits of VT Test Set M211 – С&tanδ testing

Limits of relative Limits of absolute


СХ/С0 Test current, А
measurement error of δC, % measurement error of dissipation factor Δtanδ
0,01…0,1 ±[5∙10-3+2∙10-4∙(C0/CX-10) + |tanδX- tanδ0|] ±[5∙10-5 + 2∙10-6∙(C0/CX-10) + 0,005∙| tanδX- tanδ0|]
up to 0,2
0,1…103 ±5∙10-3 + |tanδX - tanδ0|] ±[5∙10-5 + 0,005∙|tanδX- tanδ0|]

Measurement ranges and error limits of VT Test Set M210/M211 – voltage parameters testing

Value Range Error limits Additional conditions


U1 300…UСH Сн using
True RMS voltage, V δU = ± 0,5 %
U2 10…1000 −

First harmonic true RMS U11 300…UСH Сн using


voltage, V δU = ± 0,5 %
U21 10…1000 −

ΔKu1 = ± 0,2 % Сн using at KU1<2


Primary voltage THD (KU1), % 0...20
δKu1 = ± 10 % Сн using at KU1≥2
ΔKu2 = ± 0,05 % at KU2<2
Secondary voltage THD (KU2), % 0...20
δKu2 = ± 5 % at KU2≥2

ΔKu1(n) = ± 0,05 % Сн using at KU1(n)<1


Primary voltage n-th harmonic ratio (KU1(n)), % 0...15
δKu1(n) = ± 5 % Сн using at KU1(n)≥1

Secondary voltage n-th harmonic ratio ΔKu2(n) = ± 0,05 % at KU2(n)<1


0...15
(KU2(n)), % δKu2(n) = ±5 % at KU2(n)≥1

Frequency (f), Hz 49...51 ±0,02 −

Power mains
Measuring Unit built-in rechargeable battery
Charging and Calibration Power Supply Units 220/230 V, 50 Hz
Operating Temperature - 10...40 °C
Relative Humidity up to 80 % non-condensing

Measuring HV capacitor
Size, mm Unit 45 kV 100 kV 230 kV
250×350×185 170 × 425 260 × 610 390 × 995
Weight, kg 10 7 17 55
Standards
Safety EN 61010-1:2010
EMC EN 61326-1:2013

Calibration Interval 3 years recommended


M210/M211
Voltage Transformer Test Set

ORDERING INFORMATION
Scope of supply
The following items are supplied with the standard VTTS modification:

No Item Name Part no.

1* Measuring Unit M210.1 411722.006-01


M210.2 411722.006-02
M210.3 411722.006-03
M211.1 411722.017-01
M211.2 411722.017-02
M211.3 411722.017-03

2* High-voltage Measuring Capacitor 45 411634.032


(in kit with M21x.1)

3* High-voltage Measuring Capacitor 100 411634.033


(in kit with M21x.2)

4* High-voltage Measuring Capacitor 230 411634.034


(in kit with M21x.3)

5 Extension 35 (in kit with M21x.3) 715531.037

6 Extension 50 (in kit with M21x.3) 301568.057


6

7 Extender (in kit with M21x.3) 301568.056


7

8 End terminal 35 (in kit with M21x.3) 301127.008-01

9 End terminal 50 (in kit with M21x.3) 301127.008

10 Charging Unit 436112.016

11 Interface Unit 411619.019

12 Calibration Power Supply Unit 436112.027

* Please specify modification when ordering


M210/M211
Voltage Transformer Test Set

No Item Name Part no.

13* FOC Fiber-optic cable, 5 m 468615.014-03


FOC Fiber-optic cable, 10 m 468615.014-04
FOC Fiber-optic cable, 30 m 468615.014-05

* Please specify modification when ordering

14 IC(U2) Secondary voltage instrument cable; 2,5 m 685612.061

15 IC1(U2) Secondary voltage instrument cable; 5 m 685612.112

16 SPIC Serial port interface cable 685614.087

17 PC(C) Power cord for calibration 685611.143

18 Package bag for Measuring Unit 323382.050

19 Package bag for accessories 323382.051

20 Package bag (in kit with M21x.1) 323382.054

21 Package bag (in kit with M21x.2) 323382.055

22 Case (in kit with M21x.3) 323362.043

23 M210/M211 Software (installation disk) 411210.002 К

24 Operating manual 411210.002 ОМ

25 Passport 411210.002 P

Additional order

26 Fully installed Laptop

27 Optional software for С&tanδ testing M201.900.000.000