0% found this document useful (0 votes)
32 views2 pages

Three Conductor in Air: Ampacity Tables

This document provides ampacity tables for three conductor cables in air. It specifies ampacity ratings for copper and aluminum conductors of different American Wire Gauge (AWG) and kcmil sizes operating at voltages between 600-5000V and 2001-35,000V. The ampacities are given for cables in still air at ambient temperatures of 40°C and 90°C for non-shielded cables and 90°C and 105°C for shielded cables. It notes the ratings apply to a single loaded cable and corrections may be needed for bundled cables.

Uploaded by

alberto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
32 views2 pages

Three Conductor in Air: Ampacity Tables

This document provides ampacity tables for three conductor cables in air. It specifies ampacity ratings for copper and aluminum conductors of different American Wire Gauge (AWG) and kcmil sizes operating at voltages between 600-5000V and 2001-35,000V. The ampacities are given for cables in still air at ambient temperatures of 40°C and 90°C for non-shielded cables and 90°C and 105°C for shielded cables. It notes the ratings apply to a single loaded cable and corrections may be needed for bundled cables.

Uploaded by

alberto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Ampacity Tables

Three Conductor In Air

Three conductor
cable in air
Any load factor from 30 to 100%.

The ampacities are for a single loaded cable


in still air. In a group of loaded cables in close
proximity in air, exposed or enclosed, follow
the correction method shown on the ampacity
correction factors page.

Air ambient temperature 40°C.

One cable in air per support or messenger


Copper
Non-Shielded Shielded
Conductor 600-5000 2001-5000 5001-35,000
Size Volts Ampacity Volts Ampacity Volts Ampacity
AWG-kcmil 90° C 90° C 105°C 90° C 105°C
(194°F) (194°F) (221°F) (194°F) (221°F)
8......... 59......... 59... 66... —... —...
.6......... 79......... 79... 88... 93... 105...
4......... 104......... 105... 115... 120... 135...
2......... 138......... 140... 154... 165... 185...
1......... 161......... 160... 180... 185... 210...
1/0......... 186......... 185... 205... 215... 240...
2/0......... 215......... 215... 240... 245... 275...
3/0......... 249......... 250... 280... 285... 315...
4/0......... 287......... 285... 320... 325... 360...
250......... 320......... 320... 355... 360... 400...
350......... 394......... 395... 440... 435... 490...
500......... 487......... 485... 545... 535... 600...
750......... 615......... 615... 685... 670... 745...
1000........\ 707......... 705... 790... 770... 860...

PROPIEDAD DEL ING. RAUL HERRERA


Aluminum
Non-Shielded Shielded
Conductor 600-5000 2001-5000 5001-35,000
Size Volts Ampacity Volts Ampacity Volts Ampacity
AWG-kcmil 90° C 90° C 105°C 90° C 105°C
(194°F) (194°F) (221°F) (194°F) (221°F)
8......... 46......... 46... 51... —... —...
.6......... 61......... 61... 68... 72... 80...
4......... 81......... 81... 90... 95... 105...
2......... 108......... 110... 120... 125... 145...
1......... 126......... 125... 140... 145... 165...
1/0......... 145......... 145... 160... 170... 185...
2/0......... 168......... 170... 185... 190... 215...
3/0......... 194......... 195... 215... 220... 245...
4/0......... 224......... 225... 250... 255... 285...
250......... 250......... 250... 280... 280... 315...
350......... 309......... 310... 345... 345... 385...
500......... 385......... 385... 430... 425... 475...
750......... 495......... 495... 550... 540... 600...
1000........\ 584......... 585... 650... 635... 705...

ENGINEERING TECHNICAL CENTER

PROPIEDAD DEL ING. RAUL HERRERA

You might also like