0% found this document useful (0 votes)
62 views2 pages

Ampacity Charts for Conductors

This document provides ampacity tables for single conductor cables in air. It lists the ampacity ratings in amps for both copper and aluminum conductors of various American Wire Gauge (AWG) sizes and kcmil operating at voltages between 600-35,000 volts. The ampacities are given for both non-shielded and shielded cables in still air at temperatures of 90°C and 105°C. It notes the ratings apply to a single cable and that correction factors must be applied for cables installed in close proximity.

Uploaded by

alberto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
62 views2 pages

Ampacity Charts for Conductors

This document provides ampacity tables for single conductor cables in air. It lists the ampacity ratings in amps for both copper and aluminum conductors of various American Wire Gauge (AWG) sizes and kcmil operating at voltages between 600-35,000 volts. The ampacities are given for both non-shielded and shielded cables in still air at temperatures of 90°C and 105°C. It notes the ratings apply to a single cable and that correction factors must be applied for cables installed in close proximity.

Uploaded by

alberto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Ampacity Tables

Single Conductor In Air

Single conductor cable


in air
Open circuited shield operation, i.e. shields
bonded and grounded at one point only.

Any load factor from 30 to 100%. The


ampacities are for a single, loaded cable in
still air. In a group of loaded cables in close
proximity in air, exposed or enclosed, follow
the correction method shown on the
ampacity correction factors page.

One cable per support or messenger


Copper
Non-Shielded Shielded
Conductor 600-5000 2001-5000 5001-15,000 15,001-35,000
Size Volts Ampacity Volts Ampacity Volts Ampacity Volts Ampacity
AWG-kcmil 90° C 90° C 105°C 90° C 105°C 90° C 105°C
(194°F) (194°F) (221°F) (194°F) (221°F) (194°F) (221°F)
8......... 83......... 83... 93... —... —... —... —...
6......... 109......... 110... 120... 110... 125... —... —...
4......... 145......... 145... 160... 150... 165... —... —...
2......... 192......... 190... 215... 195... 215... —... —...
1......... 223......... 225... 250... 225... 250... 225... 250...
1/0......... 258......... 260... 290... 260... 290... 260... 290...
2/0......... 298......... 300... 330... 300... 335... 300... 330...
3/0......... 345......... 345... 385... 345... 385... 345... 380...
4/0......... 400......... 400... 445... 400... 445... 395... 445...
250......... 445......... 445... 495... 445... 495... 440... 490...
350......... 552......... 550... 615... 550... 610... 545... 605...
500......... 695......... 695... 775... 685... 765... 680... 755...
750......... 898......... 900... 1000... 885... 990... 870... 970...
1000......... 1076......... 1075... 1200... 1060... 1185... 1040... 1160...
1250......... 1228......... 1230... 1370... 1210... 1350... 1185... 1320...
1500......... 1367......... 1365... 1525... 1345... 1500... 1315... 1465...
1750......... 1493......... 1495... 1665... 1470... 1640... 1430... 1595...
2000......... 1606......... 1605... 1790... 1575... 1755... 1535... 1710...

PROPIEDAD DEL ING. RAUL HERRERA


Aluminum
Non-Shielded Shielded
Conductor 600-5000 2001-5000 5001-15,000 15,001-35,000
Size Volts Ampacity Volts Ampacity Volts Ampacity Volts Ampacity
AWG-kcmil 90° C 90° C 105°C 90° C 105°C 90° C 105°C
(194°F) (194°F) (221°F) (194°F) (221°F) (194°F) (221°F)
8......... 64......... 64... 71... —... —... —... —...
6......... 85......... 85... 95... 87... 97... —... —...
4......... 113......... 115... 125... 115... 130... —... —...
2......... 150......... 150... 165... 150... 170... —... —...
1......... 174......... 175... 195... 175... 195... 175... 195...
1/0......... 201......... 200... 225... 200... 225... 200... 225...
2/0......... 232......... 230... 260... 235... 260... 230... 260...
3/0......... 269......... 270... 300... 270... 300... 270... 300...
4/0......... 312......... 310... 350... 310... 350... 310... 345...
250......... 347......... 345... 385... 345... 385... 345... 380...
350......... 431......... 430... 480... 430... 480... 430... 475...
500......... 544......... 545... 605... 535... 600... 530... 590...
750......... 707......... 710... 790... 700... 780... 685... 765...
1000......... 853......... 855... 950... 840... 940... 825... 920...
1250......... 982......... 980... 1095... 970... 1080... 950... 1055...
1500......... 1103......... 1105... 1230... 1085... 1215... 1060... 1180...
1750......... 1216......... 1215... 1355... 1195... 1335... 1165... 1300...
2000......... 1321......... 1320... 1475... 1295... 1445... 1265... 1410...