0% found this document useful (0 votes)
127 views2 pages

Three Conductor Underground Ducts: Ampacity Tables

This document provides ampacity tables for underground ducts with three conductor cables. It gives ampacity ratings in amps for copper and aluminum cables with various conductor sizes operating at different voltage levels. The tables provide ratings for configurations with 1, 3, or 6 cables installed in underground duct banks, accounting for factors like cable insulation, ambient earth temperature, and burial depth.

Uploaded by

alberto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
127 views2 pages

Three Conductor Underground Ducts: Ampacity Tables

This document provides ampacity tables for underground ducts with three conductor cables. It gives ampacity ratings in amps for copper and aluminum cables with various conductor sizes operating at different voltage levels. The tables provide ratings for configurations with 1, 3, or 6 cables installed in underground duct banks, accounting for factors like cable insulation, ambient earth temperature, and burial depth.

Uploaded by

alberto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Ampacity Tables

Three Conductor
Underground Ducts

Three conductor cable


underground ducts
One cable per duct, all cables equally loaded
and in outside ducts only.

Earth ambient temperature 20°C


Earth thermal resistivity RHO 90.
100% load factor

Depth of burial - 30” to top of duct bank with


duct on 7 1/2 centers.

One circuit — one cable in duct bank


Three conductor Three conductor
Copper - underground ducts Aluminum - underground ducts
Non- Non-
Shielded Shielded
Shielded Shielded
Conductor 600- 600-
Size 2001-5000 5001-35000 2001-5000 5001-35000
2000 2000
AWG- Volts Volts Volts Volts
Volts Volts
kcmil Ampacity Ampacity Ampacity Ampacity Ampacity
Ampacity
90° C 90° C 105°C 90° C 105°C 90° C 90° C 105°C 90° C 105°C
(194°F) (194°F) (221°F) (194°F) (221°F) (194°F) (194°F) (221°F) (194°F) (221°F)
8......... 59......... 59... 64... —... —... 46......... 46... 50... —... —...
.6......... 78......... 78... 84... 88... 95... 61......... 61... 66... 69... 74...
4......... 102......... 100... 110... 115... 125... 80......... 80... 86... 89... 96...
2......... 133......... 135... 145... 150... 160... 104......... 105... 110... 115... 125...
1......... 154......... 155... 165... 170... 185... 120......... 120... 130... 135... 145...
1/0......... 177......... 175... 190... 195... 210... 138......... 140... 150... 150... 165...
2/0......... 202......... 200... 220... 220... 235... 158......... 160... 170... 170... 185...
3/0......... 231......... 230... 250... 250... 270... 180......... 180... 195... 195... 210...
4/0......... 264......... 265... 285... 285... 305... 206......... 205... 220... 220... 240...
250......... 292......... 290... 315... 310... 335... 228......... 230... 245... 245... 265...
350......... 354......... 355... 380... 375... 400... 278......... 280... 310... 295... 315...
500......... 429......... 430... 460... 450... 485... 340......... 340... 365... 355... 385...
750......... 529......... 530... 570... 545... 585... 426......... 425... 460... 440... 475...
1000........\ 599......... 600... 645... 615... 660... 495......... 495... 535... 510... 545...

PROPIEDAD DEL ING. RAUL HERRERA


Three circuits — three cables in duct bank
Three conductor Three conductor
Copper - underground ducts Aluminum - underground ducts
Non- Non-
Shielded Shielded
Shielded Shielded
Conductor 600- 600-
Size 2001-5000 5001-35000 2001-5000 5001-35000
2000 2000
AWG- Volts Volts Volts Volts
Volts Volts
kcmil Ampacity Ampacity Ampacity Ampacity Ampacity
Ampacity
90° C 90° C 105°C 90° C 105°C 90° C 90° C 105°C 90° C 105°C
(194°F) (194°F) (221°F) (194°F) (221°F) (194°F) (194°F) (221°F) (194°F) (221°F)
8......... 53......... 53... 57... —... —... 41......... 41... 44... —... —...
.6......... 69......... 69... 74... 75... 81... 54......... 54... 58... 59... 64...
4......... 89......... 89... 96... 97... 105... 70......... 70... 75... 75... 81...
2......... 116......... 115... 125... 125... 135... 90......... 90... 97... 100... 105...
1......... 133......... 135... 145... 140... 155... 103......... 105... 110... 110... 120...
1/0......... 151......... 150... 165... 160... 175... 118......... 120... 125... 125... 135...
2/0......... 172......... 170... 185... 185... 195... 135......... 135... 145... 140... 155...
3/0......... 196......... 195... 210... 205... 220... 153......... 155... 165... 160... 175...
4/0......... 223......... 225... 240... 230... 250... 174......... 175... 185... 180... 195...
250......... 245......... 245... 265... 255... 270... 191......... 190... 205... 200... 215...
350......... 294......... 295... 315... 305... 325... 231......... 230... 250... 240... 255...
500......... 354......... 355... 380... 360... 385... 280......... 280... 300... 285... 305...
750......... 430......... 430... 465... 430... 465... 347......... 345... 375... 350... 375...
1000......... 484......... 485... 520... 485... 515... 399......... 400... 430... 400... 430...

Six circuits — six cables in duct bank


Three conductor Three conductor
Copper - underground ducts Aluminum - underground ducts
Non- Non-
Shielded Shielded
Shielded Shielded
Conductor 600- 600-
Size 2001-5000 5001-35000 2001-5000 5001-35000
2000 2000
AWG- Volts Volts Volts Volts
Volts Volts
kcmil Ampacity Ampacity Ampacity Ampacity Ampacity
Ampacity
90° C 90° C 105°C 90° C 105°C 90° C 90° C 105°C 90° C 105°C
(194°F) (194°F) (221°F) (194°F) (221°F) (194°F) (194°F) (221°F) (194°F) (221°F)
8......... 46......... 46... 50... —... —... 36......... 36... 39... —... —...
.6......... 70......... 60... 65... 63... 68... 46......... 46... 50... 49... 53...
4......... 77......... 77... 83... 81... 87... 60......... 60... 65... 63... 68...
2......... 98......... 98... 105... 105... 110... 77......... 77... 83... 80... 86...
1......... 112......... 110... 120... 115... 125... 87......... 87... 94... 90... 98...
1/0......... 127......... 125... 135... 130... 145... 99......... 99... 105... 105... 110...
2/0......... 144......... 145... 155... 150... 160... 112......... 110... 120... 115... 125...
3/0......... 163......... 165... 175... 170... 180... 128......... 130... 140... 130... 140...
4/0......... 185......... 185... 200... 190... 200... 144......... 145... 155... 150... 160...
250......... 202......... 200... 220... 205... 220... 158......... 160... 170... 160... 170...
350......... 242......... 240... 270... 245... 275... 190......... 190... 205... 190... 205...
500......... 289......... 290... 310... 290... 305... 228......... 230... 245... 230... 245...
750......... 348......... 350... 375... 340... 365... 281......... 280... 305... 275... 295...
1000......... 390......... 390... 420... 380... 405... 322......... 320... 345... 315... 335...