The document provides ampacity tables for single conductor cables for direct burial applications. It gives ampacity ratings in amps for copper and aluminum conductors ranging from 8 AWG to 2000 kcmil buried underground at depths of 36 inches. The tables provide ratings for cables with both shielded and non-shielded insulation, as well as for single cable circuits and multiple cable circuits with cables spaced 7.5 inches apart. The ratings are based on an ambient earth temperature of 20°C and earth thermal resistivity of 90.

Uploaded by

alberto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
113 views2 pages

Underground Cable Ampacity Tables

The document provides ampacity tables for single conductor cables for direct burial applications. It gives ampacity ratings in amps for copper and aluminum conductors ranging from 8 AWG to 2000 kcmil buried underground at depths of 36 inches. The tables provide ratings for cables with both shielded and non-shielded insulation, as well as for single cable circuits and multiple cable circuits with cables spaced 7.5 inches apart. The ratings are based on an ambient earth temperature of 20°C and earth thermal resistivity of 90.

Uploaded by

alberto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Ampacity Tables

Single Conductor
Underground Direct Burial

Single conductor cable


direct burial
1/C group buried 36” deep with cables laid on
7-1/2” centers, open circuited shield
operation, i.e. shields bonded and grounded
at one point only.

Earth ambient temperature 20°C


Earth thermal resistivity RHO 90
100% load factor

One circuit — three cables


one conductor Copper - direct burial one conductor Aluminum - direct burial
Non- Non-
Shielded Shielded
Shielded Shielded
Conductor
Size 600-2000 2001-5000 5001-35000 600-2000 2001-5000 5001-35000
AWG- Volts Volts Volts Volts Volts Volts
kcmil Ampacity Ampacity Ampacity Ampacity Ampacity Ampacity
90° C 90° C 105°C 90° C 105°C 90° C 90° C 105°C 90° C 105°C
(194°F) (194°F) (221°F) (194°F) (221°F) (194°F) (194°F) (221°F) (194°F) (221°F)
8......... 108......... 110... .115... —... —... 84......... 85... 90... ....—... —...
6......... 139......... 140... 150... 130... 140... 108......... 110... 115... 110... 110...
4......... 180......... 180... 195... 170... 180... 140......... 140... 150... 130... 140...
2......... 231......... 230... 250... 210... 225... 180......... 180... 195... 165... 175...
1......... 261......... 260... 280... 240... 260... 203......... 205... 220... 185... 200...
1/0......... 297......... 295... 320... 275... 295... 231......... 230... 250... 215... 230...
2/0......... 337......... 335... 365... 310... 335... 263......... 265... 285... 245... 260...
3/0......... 384......... 385... 415... 355... 380... 299......... 300... 320... 275... 295...
4/0......... 434......... 435... 465... 405... 435... 338......... 340... 365... 315... 340...
250......... 472......... 470... 510... 440... 475... 368......... 370... 395... 345... 370...
350......... 569......... 570... 615... 535... 575... 444......... 445... 480... 415... 450...
500......... 690......... 690... 745... 650... 700... 540......... 540... 580... 510... 545...
750......... 847......... 845... 910... 805... 865... 667......... 665... 720... 635... 680...
1000......... 980......... 980... 1055... 930... 1005... 778......... 780... 840... 740... 795...
1250......... 1083......... 1085... 1165... 1035... 1115... 868......... 870... 935... 830... 895...
1500......... 1176......... 1175... 1265... 1125... 1210... 952......... 950... 1025... 910... 980...
1750......... 1257......... 1255... 1355... 1200... 1295... 1027......... 1025... 1105... 980... 1060...
2000......... 1325......... 1325... 1430... 1265... 1365... 1094......... 1095... 1180... 1045... 1130...

PROPIEDAD DEL ING. RAUL HERRERA


Single conductor cable
direct burial
1/C group buried 36” deep with cables laid on
7-1/2” centers, second circuit similarly
spaced. Groups separated 24", open circuited
shield operation, i.e. shields bonded and
grounded at one point only.

Earth ambient temperature 20°C


Earth thermal resistivity RHO 90
100% load factor

Two circuits — six cables


one conductor Copper - direct burial one conductor Aluminum - direct burial
Non-
Non- Shielded
Shielded Shielded
Shielded
Conductor 600-
Size 600-2000 2001-5000 5001-35000 2001-5000 5001-35000
2000
AWG- Volts Volts Volts Volts Volts
Volts
kcmil Ampacity Ampacity Ampacity Ampacity Ampacity
Ampacity
90° C 90° C 105°C 90° C 105°C
90° C 90° C 105°C 90° C 105°C
(194°F) (194°F) (221°F) (194°F) (221°F)
(194°F) (194°F) (221°F) (194°F) (221°F)
8......... 101......... 100... .110... —... —...
79......... 80... 85... —... —...
6......... 130......... 130... 140... 120... 130...
101......... 100... 110... 95... 100...
4......... 167......... 165... 180... 160... 170...
130......... 130... 140... 125... 130...
2......... 214......... 215... 230... 195... 210...
167......... 165... 180... 155... 165...
1......... 241......... 240... 260... 225... 240...
188......... 190... 200... 175... 190...
1/0......... 275......... 275... 295... 255... 275...
214......... 215... 230... 200... 215...
2/0......... 311......... 310... 335... 290... 315...
243......... 245... 260... 225... 245...
3/0......... 354......... 355... 380... 330... 355...
276......... 275... 295... 255... 275...
4/0......... 399......... 400... 430... 375... 405...
311......... 310... 335... 290... 315...
250......... 435......... 435... 470... 410... 440...
339......... 340... 365... 320... 345...
350......... 522......... 520... 560... 495... 530...
408......... 410... 440... 385... 415...
500......... 631......... 630... 680... 600... 645...
494......... 495... 530... 470... 505...
750......... 773......... 775... 835... 740... 795...
609......... 610... 655... 580... 625...
1000......... 892......... 890... 960... 855... 920...
708......... 710... 765... 680... 730...
1250......... 985......... 985... 1060... 945... 1020...
790......... 790... 851... 760... 820...
1500......... 1068......... 1070... 1150... 1025... 1105...
865......... 865... 930... 830... 895...
1750......... 1140......... 1140... 1230... 1095... 1180...
932......... 930... 1005... 895... 965...
2000......... 1200......... 1200... 1295... 1150... 1240...
991......... 990... 1070... 950... 1025...