Ampacity Tables
Triplexed Conductor
Underground Direct Burial
Triplexed cable
direct burial
Triplexed cables or three single conductors
buried 36” deep and separated by 24”.
Shields bonded and grounded at multiple
points.
Earth ambient temperature 20°C
Earth thermal resistivity RHO 90
100% load factor
One circuit
Three single or triplexed conductors Three single or triplexed conductors
Copper - direct burial Aluminum - direct burial
Non- Non-
Shielded Shielded
Shielded Shielded
Conductor 600- 600-
Size 2001-5000 5001-35000 2001-5000 5001-35000
2000 2000
AWG- Volts Volts Volts Volts
Volts Volts
kcmil Ampacity Ampacity Ampacity Ampacity Ampacity
Ampacity
90° C 90° C 105°C 90° C 105°C 90° C 90° C 105°C 90° C 105°C
(194°F) (194°F) (221°F) (194°F) (221°F) (194°F) (194°F) (221°F) (194°F) (221°F)
8......... 92......... 90... 100... —... —... 72......... 70... 80... —... —...
.6......... 118......... 120... 125... 115... 125... 92......... 90... 100... 90... 100...
4......... 153......... 150... 165... 150... 160... 119......... 120... 130... 115... 125...
2......... 197......... 195... 210... 190... 200... 153......... 155... 165... 145... 160...
1......... 223......... 225... 240... 215... 230... 174......... 175... 185... 165... 180...
1/0......... 255......... 255... 275... 245... 265... 198......... 200... 215... 190... 205...
2/0......... 289......... 290... 310... 275... 300... 226......... 225... 245... 215... 235...
3/0......... 329......... 330... 355... 315... 340... 257......... 255... 275... 245... 265...
4/0......... 373......... 375... 400... 360... 385... 291......... 290... 315... 280... 300...
250......... 408......... 410... 440... 390... 420... 319......... 320... 345... 305... 330...
350......... 490......... 490... 530... 470... 505... 385......... 385... 415... 370... 400...
500......... 592......... 590... 640... 565... 605... 467......... 465... 505... 445... 480...
750......... 724......... 725... 780... 685... 735... 579......... 580... 625... 550... 595...
1000........\ 825......... 825... 890... 770... 830... 672......... 670... 725... 635... 685...
PROPIEDAD DEL ING. RAUL HERRERA
Two circuits
Three single or triplexed conductors Three single or triplexed conductors
Copper - direct burial Aluminum - direct burial
Non- Non-
Shielded Shielded
Shielded Shielded
Conductor 600- 600-
Size 2001-5000 5001-35000 2001-5000 5001-35000
2000 2000
AWG- Volts Volts Volts Volts
Volts Volts
kcmil Ampacity Ampacity Ampacity Ampacity Ampacity
Ampacity
90° C 90° C 105°C 90° C 105°C 90° C 90° C 105°C 90° C 105°C
(194°F) (194°F) (221°F) (194°F) (221°F) (194°F) (194°F) (221°F) (194°F) (221°F)
8......... 85......... 85... 90... —... —... 67......... 65... 70... —... —...
.6......... 109......... 110... 115... 105... 115... 85......... 85... 90... 85... 90...
4......... 141......... 140... 150... 140... 150... 110......... 110... 120... 105... 115...
2......... 181......... 180... 195... 175... 185... 141......... 140... 150... 135... 145...
1......... 205......... 205... 220... 200... 215... 160......... 160... 170... 155... 165...
1/0......... 233......... 235... 250... 225... 240... 182......... 180... 195... 175... 190...
2/0......... 264......... 265... 285... 255... 275... 206......... 205... 220... 200... 215...
3/0......... 300......... 300... 325... 290... 310... 234......... 235... 250... 225... 240...
4/0......... 339......... 340... 365... 325... 350... 265......... 265... 285... 255... 275...
250......... 370......... 370... 400... 355... 385... 289......... 290... 310... 280... 300...
350......... 444......... 445... 480... 425... 460... 348......... 350... 375... 335... 360...
500......... 534......... 535... 575... 510... 550... 421......... 420... 455... 405... 435...
750......... 649......... 650... 700... 615... 660... 520......... 520... 560... 485... 535...
1000........\ 738......... 740... 795... 690... 740... 601......... 600... 645... 565... 610...