CONTACTORS & OCR (HiMC, HiTH) PDF

The HiMC Magnetic Contactor series from Hyundai employs a modular design allowing for quick mounting of accessories. It provides convenience, economic benefits, and high reliability. The HiMC contactor has a superior design for industrial applications requiring high reliability and performance, such as in motor control centers, shipyards, and power plants. It is suitable for various control systems.

Uploaded by

FILIN VLADIMIR
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views79 pages

CONTACTORS & OCR (HiMC, HiTH) PDF

The HiMC Magnetic Contactor series from Hyundai employs a modular design allowing for quick mounting of accessories. It provides convenience, economic benefits, and high reliability. The HiMC contactor has a superior design for industrial applications requiring high reliability and performance, such as in motor control centers, shipyards, and power plants. It is suitable for various control systems.

Uploaded by

FILIN VLADIMIR
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 79

Reliability

The HiMC Magnetic Contactor series employs a modular design which


allows quick and simple mounting of auxiliary contact blocks, timers,
mechanical latching blocks, etc.
HiMC provides convenience, economic benefit and high reliability.

Solution
Superior design for industrial applications such as motor control centers,
the HiMC contactor is appropriate to various control systems, and favored
by shipyard and power plant; where high reliability and performance are
the criteria.
We build a better future!

Significantly Extended Life Strong

Noise Free Silence

Compact Design Small

CONTENTS
Ordering Information •06 HLB2 & HOKZE •29 HiMP •48
HiMC •10 Accessory •31 HME •73
HiTH •22 HiMS Diagram •34
HMX & HMT •27 HiMS Drawing •36
Hi Series

HiMC 9 ~ HiMC 50 Small Frame Size Contactor

■ The electrical and mechanical life of HiMC has been significantly


extended.
■ New materials prevent any generation of corroded substances,
Quick and Easy Disassembly
and the core enables noise-free status with the help of special
anti-rust oil treatment.
■ Various accessories can be attached easily.
■ Terminal wiring is designed to meet IEC 60529 and protection
degree of IP 20.
■ By using clips, HiMC’s coil can be replaced easily and its
frequency is available in both 50 Hz and 60 Hz.

Fast and Easy Coil Change

HiMC 65 ~ HiMC 800 Large Frame Size Contactor

■ The electrical and mechanical life of HiMC has been


significantly extended. The optimized design of the arc chamber
minimizes contact erosion.
■ HiMC contactor maintains noise-free operation through the
DC-control method.
■ HiMC contactor is available in both AC/DC and 50 Hz / 60 Hz
with an electronic circuit which enables operation through
Variety of Installation
severe voltage drop.
■ HiMC contactors can be used in various environments by
adopting special plastic(CTI/600 V) which has heat & waterproof
charateristics.
■ By adopting a cassette unit, the coil assembly can be replaced
conveniently.
■ As the cover of HiMC contactor can be easily opened,
maintenance is very convenient.
■ Two auxiliary contact blocks of 1NO+1NC can be attached to
each side of HiMC, allowing auxiliary contacts to be added up to
4NO+4NC.

Easy Coil Change Easy Contacts Inspection


Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMC

HMX & HMT

HiTH

HiMP & HME

HiTH 40H
HiTH 130K80

HMT HME

HMX

HiMP

UL UL
Qualified Standards & Approvals TYPE CE CSA KR LR ABS BV NK TYPE CE CSA KR LR ABS BV NK
HiMC 9 ● ● ● ● ● ● ● HMX ● ● ● ● ● ● ●
◆Standards HiMC 12 ● ● ● ● ● ● ● HMT ● ● ● ● ● ● ●
HiMC 18 ● ● ● ● ● ● ● HiTH 22K(H) ● ◉ ● ○ ● ● ○
- KS C4504 HiMC 22 ● ● ● ● ● ● ● HiTH 40K(H) ● ◉ ● ○ ● ● ○
- IEC 60947 HiMC 32 ● ● ● ● ● ● ● HiTH 50K(H) ● ◉ ● ○ ● ● ○
HiMC 40 ● ● ● ● ● ● ● HiTH 90K(H) ● ◉ ● ○ ● ● ○
- EN 60947 ●
HiMC 50 ● ● ● ● ● ● ● HiTH 130K(H) ◉ ● ○ ● ● ○
- UL 508 HiMC 65 ● ● ● ● ● ● ● HiTH 220K(H) ● ◉ ● ○ ● ● ○
HiMC 80 ● ● ● ● ● ● ● HiTH 300K(H) ● ◉ ● ○ ● ● ○
- BS 47794, BS 5424, BS 4941
HiMC 90 ● ● ● ● ● ● ● HiTH 500K(H) ● ◉ ● ○ ● ● ○
- VDE 0660 HiMC 110 ● ● ● ● ● ● ● HiTH 800K(H) ● ◉ ● ○ ● ● ○
HiMC 130 ● ● ● ● ● ● ● HiAB ● ◉ ○ ◉ ○ ◉ ○
- Det Norske Veritas
HiMC 150 ● ● ● ● ● ● ● HiAC ● ◉ ○ ◉ ○ ◉ ○
- JISC 8328, JEM 1038 HiMC 180 ● ● ● ● ● ● ● HiAL ● ● ○ ● ○ ● ○
HiMC 220 ● ● ● ● ● ● ● HiAR ● ● ○ ● ○ ● ○
◆Approvals
HiMC 260 ● ● ● ● ● ● ●
- UL / HiMC 300 ● ● ● ● ● ● ●
.. HiMC 400 ● ● ● ● ● ● ●
- CE (Community European / TUV Rheinland)
HiMC 500 ● ● ● ● ● ● ●
- ISO 18001, 14001, 9001 HiMC 630 ● ◉ ● ● ● ● ●
HiMC 800 ● ◉ ● ● ● ● ● ●available ◉testing ○N/A
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

Ordering Information

Magnetic Contactor

HiMC 22 W 22 S / 220 X
Rated Current(440VAC) W AC Control 2 Number of NO Safety Cover Operational Blank X
Blank S Voltage
Type Current Type Current G DC Control 2 Number of NC
60 Hz 50 Hz
Without With W AC 24~600 V
9 9A 110 110 A F Free Voltage Cover Cover
G DC 24~250 V
12 12 A 130 130 A Free voltage type
is available from F AC/DC 220, 440 V
18 18 A 150 150 A HiMC 65 to 800
Please refer to the
22 22 A 180 180 A Technical Data,
page 14 & 15
32 32 A 220 220 A

40 40 A 260 260 A

50 50 A 300 300 A

65 65 A 400 400 A

80 80 A 500 500 A

90 90 A 630 630 A

800 800 A

Thermal Overload Relay

HiTH 22 K 22 S
Type Rated Current Safety Cover
Hyundai Type Applied MC
Name
H K Blank S
innovative
22 HiMC 9~22 2 Element 3 Element Please refer to the Without With
THermal (Option) (Standard) Technical Data Cover Cover
overload 40 HiMC 32~40 page 24 & 25
relay 50 HiMC 50

90 HiMC 65~90

130 HiMC 110~130

220 HiMC 150~220

300 HiMC 260~300

500 HiMC 400~500

800 HiMC 630~800


Control Relay Separate Mounting Unit for HiTH

HMX 22 / 220 X HiTHMB 22 S


Control Relay Number of Contacts Operational Blank X Applied Safety Cover
Type
22 31 40
Voltage TOR Blank S
AC: HMX
60 Hz 50 Hz Without With
DC: HMT AC 24~600 V 22 HiTH22
2a 2b 3a 1b 4a Cover Cover
DC 24~250 V 40 HiTH40

50 HiTH50

90 HiTH90

Mechanical Interlock Unit Aux. Contact Block

HiTL 50 HAB 22
Type Application M.C Mounting Application
Type 2 2
Mechanical 40 HiMC 9~40 Side M/C
Interlock Unit 50 HiMC 50 HiAB Top HiMC 9~50
Number Number
130 HiMC 65~130 HiAL 11 Left HiMC 9~22 of of
NO NC
200 HiMC 150~200 HiAC Top HMX, HMT

300 HiMC 260~300 HiAL 5S Left


HiMC 65~130
800 HiMC 400~800 HiAR 6S Right

HiAL 7S Left
Hi Series

HiMC 150~800
HiAR 8S Right
07
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

Ordering Information

Digital Motor Protection Relay / Deluxe Type

HiMP-D 06 S Z / 220
Rated Current Connecting Control
Option
Hyundai innovative Setting Range Method Voltage
Motor Protection 06 0.5~6 A T Tunnel Type - Standard 220 AC 220 V
Deluxe type
60 5~60 A S Screw Type Z Earth Leakage Protection 110 AC 110 V

I Short Circuit Protection ★★★ ETC

•Separate Connection Cable •Display Bracket •ZCT

Inner Ratio of zero


Specification Length(m) Order No. Specification
Diameter(mm) phase current
HiMP - CBL 1 1.0 HiMP - Bracket HiMP - ZCT 30 30

HiMP - CBL 1.5 1.5 HiMP - ZCT 50 50

HiMP - CBL 2 2.0 HiMP - ZCT 65 65


200 mA/100 mV
HiMP - CBL 4 4.0 HiMP - ZCT 80 80

HiMP - ZCT 100 100

HiMP - ZCT 120 120

Electronic Motor Protection Relay

HME H 06 / 220
Tunnel Rated Current Setting Range Control Voltage
S
(DefiniteTime Delay) 05 0.5~6.5 220 AC 220 V
E Screw or Tunnel 30 3~30 110 AC 110 V
H Pin 60 5.0~60 ★★★ ETC
Digital Motor Protection Relay / Standard Type

HiMP 22 H - P D 03 S / 220
Number of CT Wiring Method Characteristics Safety Cover
Hyundai Control Voltage
Blank S
innovative H 2CT T Tunnel Type D Definite
Motor Without With 110 110VAC
K 3CT S Screw Type I Inverse Cover Cover
Protection Inverse+ 220 220VAC
P Pin Type N
Relay Reverse Phase
★★★ ETC

Wiring Method Frame Applied MC Current Rated Current


Characteristics
22 HiMC 9~22 Name Setting Range
Tunnel Type
40 HiMC 32~40 03 0.3~3 A
Screw Type
50 HiMC 32~50
22 HiMC 9~22 22 2.2~22 A
Definite
Pin Type 40 HiMC 32~40 40 4~40 A
50 HiMC 50
50 5~50 A

01 0.3~1.5 A

05 1~5 A
Inverse 22 4.4~22 A

40 8~40 A

50 10~50 A

Accessories for Digital Motor Protection Relay

•35mm Din-Rail Bracket •Terminal Block

HiMP Rail HiMP TB 22


35mm Din-Rail Bracket Terminal Block Application

Standard 22 22AF
Type 50 40/50AF
Deluxe
•Outer CT 60 06/60AF
Type
Hi Series

HiMP CT 300 H
09

Current Transformer CT Ratio CT Number of CT


080 80 : 5 Standard H 2CT
130 130 : 5 Type K 3CT
180 180 : 5 Deluxe
D 3CT
Type
220 220 : 5

300 300 : 5

400 400 : 5

500 500 : 5

630 630 : 5

800 800 : 5
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMC

Technical Data of Contactors


TYPE HiMC 9 HiMC 12 HiMC 18 HiMC 22 HiMC 32 HiMC 40 HiMC 50 HiMC 65 HiMC 80
Rated Insulation Voltage V 750 750 750 750 750 750 750 750 750
Rated Operational Voltage V 690 690 690 690 690 690 690 690 690
AC1(Ith) A 20 20 25 32 50 50 70 100 110
200~240 V 2.2/10 3.7/13 4.5/18 5.5/22 7.5/32 11/40 15/50 18.5/70 22/80
380~440 V 4/9 5.5/12 7.5/18 11/22 15/32 18.5/40 22/50 30/65 37/80
500~550 V kW/A 4/7 7.5/12 8.5/15 15/22 18.5/28 22/32 30/45 37/60 45/64
660~690 V 5.5/7 7.5/9 7.5/9 15/18 18.5/22 22/26 25/31 37/44 45/52
AC3 1000 V - - - - - - - - -
200 V 2 3 5 5 10 10 15 20 25
230 V 2 3 5 7.5 10 10 15 20 30
HP
IEC 60947

460 V 5 7.5 10 15 20 30 40 50 60
575 V 7.5 10 15 20 25 30 40 50 60
200~240 V 8 11 15 18 22 25 35 50 55
AC4 A
380~440 V 6 9 9 13 17 24 32 47 52
Electrical(AC3) x1,000 2,500 2,500 2,500 2,500 2,000 2,000 2,000 2,000 2,000
Lifetime
Mechanical x1,000 25,000 25,000 25,000 25,000 15,000 15,000 15,000 10,000 10,000

Operating Times Closing ms 15~25 15~25 14~25 50~65


AC/DC Opening ms 4~15 4~15 4~15 25~90
Operating Frequency per hour(AC3) times 1000 1000 1000 1000 750 750 750 450 450

AC ★★ 220 VAC 100 130 180 220 320 400 500 700 800
A
Making Capacity 480 VAC 90 120 180 220 320 400 500 650 800

AC ★★ 220 VAC 80 104 144 176 256 320 400 560 640
A
Breaking Capacity 480 VAC 72 96 144 176 256 320 400 520 640
Continuous Current A 20 20 25 32 45 50 65 80 90
100~120 V 1-Ph 0.5/9.8 0.5/9.8 1/16 1.5/20 2/24 2/24 3/34 - -
UL508

220~240 V HP/A 1/8 1/8 3/17 3/17 5/28 5/28 7.5/40 - -


Max. HP
220~240 V 3-Ph 2/6.8 3/9.6 5/15.2 5/15.2 10/28 10/28 15/42 20/54 25/68
440~480 V HP/A 5/7.6 5/7.6 10/14 10/14 20/27 20/27 30/40 50/52 60/65
Size 00 0 1 2
115 V 1-Ph 0.33 1 2 3
NEMA

230 V HP 1 3 3 7.5
Max. HP 200 V 1.5 3 7.5 10
3-Ph
230 V 1.5 3 7.5 15
HP
460/575 V 2 5 10 25
Mounting Method Screw & DIN-Rail Screw
Auxiliary Contact 1a1b 1a1b 1a1b 1a1b 2a2b 2a2b 2a2b★ 2a2b★ 2a2b★
W(AC) 0.37 0.37 0.37 0.37 0.47 0.47 0.74 2.1 2.1
Weight G(DC) Kg 0.68 0.68 0.68 0.68 0.77 0.77 0.77 2.15 2.15
F(A/DC) 2.23 2.23

The auxiliary contact for DC above HiMC 50 is 2a1b.
★★
AC making and AC breaking capacity are 50 operations.
HiMC 90 HiMC 110 HiMC 130 HiMC 150 HiMC 180 HiMC 220 HiMC 260 HiMC 300 HiMC 400 HiMC 500 HiMC 630 HiMC 800
750 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
690 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
135 150 160 200 230 260 300 350 450 550 750 900
25/90 30/110 37/130 45/150 55/180 63/220 75/260 90/300 125/400 140/500 190/630 220/800
45/90 55/110 65/130 75/150 90/180 110/220 132/260 160/300 220/400 250/500 330/630 440/800
50/80 60/110 70/120 90/140 110/180 132/200 150/220 160/273 220/350 300/426 330/500 500/720
50/60 55/65 60/70 90/100 110/120 132/150 160/173 200/220 250/300 335/360 400/412 500/630
- 65/50 75/54 90/66 110/78 132/96 160/113 200/141 250/178 275/192 300/213 400/284
30 30 40 40 50 60 75 100 125 150 200 250
30 40 40 50 60 75 75 100 150 200 250 300
60 75 100 100 125 150 200 200 300 400 500 600
75 100 100 125 150 200 200 250 350 400 500 600
65 80 90 125 150 180 200 220 300 350 400 630
62 75 90 110 150 180 200 220 300 350 400 630
2,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 500 500 500 500
10,000 5,000 5,000 5,000 5,000 5,000 5,000 5,000 5,000 5,000 5,000 5,000
50~65 55~65 50~55 55~65 55~65 55~65
25~90 55~65 42~55 45~65 45~65 45~65
450 450 450 300 300 300 300 300 300 300 300 300
900 1100 1300 1500 1800 2200 2600 3000 4000 5000 6300 8000
900 1100 1300 1500 1800 2200 2600 3000 4000 5000 6300 8000
720 880 1040 1200 1440 1760 2080 2400 3200 4000 5040 6400
720 880 1040 1200 1440 1760 2080 2400 3200 4000 5040 6400
100 150 160 200 230 260 300 350 450 550 750 900
- - - - - - - - - - - -
- - - - - - - - - - - -
30/80 30/80 40/104 50/130 60/154 75/192 75/192 100/248 125/312 150/360 250/480 300/720
60/65 60/77 75/96 100/124 125/156 150/180 150/180 200/240 250/302 250/302 500/477 600/708
3 4 5 6 7
7.5 - - - -
15 - - - -
Hi Series

25 40 75 150 -
30 50 100 200 300
50 100 200 400 600
11

Screw
2a2b★ 2a2b★ 2a2b★ 2a2b★ 2a2b★ 2a2b★ 2a2b★ 2a2b★ 2a2b★ 2a2b★ 2a2b★ 2a2b★
2.1 2.95 2.95 5.45 5.45 5.45 7.05 7.05 14.50 14.50 26.55 26.55
2.15 3.0 3.0 5.60 5.60 5.60 7.20 7.20 14.50 14.50 26.55 26.55
2.23 3.23 3.23 5.67 5.67 5.67 7.40 7.40 14.60 14.60 27.55 27.55
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMC

Technical Data of Contactors


Inching & Plugging Duty (AC-4 Duty)

Operational Ratio of Electrical lifetime


Voltage Inching (million) HiMC 9 HiMC 12 HiMC 18 HiMC 22 HiMC 32 HiMC 40 HiMC 50 HiMC 65 HiMC 80
1 1.5 2.7 3.7 4 5.5 7.5 11 15 18.5
10%
5 1 1.5 2.7 3.7 4.5 5.5 7.5 11 15
1 1 1.5 2.7 3.7 4.5 5.5 7.5 11 15
220 V 50%
5 0.5 0.75 1.1 1.5 2.2 3.7 3.7 5.5 7.5
1 0.75 1.1 1.5 2.5 4.5 4.5 5.5 7.5 9
100%
Inching

5 0.3 0.5 0.75 1.1 1.8 2.7 3.7 4 4


1 2.2 4 4 7.5 11 15 22 30 37
10%
5 1.5 2.2 3.7 7.5 9 11 15 22 30
kW
1 1.5 3.7 4 7.5 9 11 15 22 30
440 V 50%
5 0.75 1.5 2.2 3.7 4.5 5.5 7.5 11 15
1 1.1 2.2 3.7 5.5 7.5 11 15 15 15
100%
5 0.5 1.1 1.5 2.2 3.7 3.7 5.5 7.5 7.5
1 0.75 0.75 1.5 2.2 2.5 3.7 5.5 7.5 9
Plugging

220 V
5 0.2 0.4 0.5 0.75 1.1 1.5 2.2 3 3.7
100%
1 0.75 1 2.2 3.7 4.5 4.5 7.5 11 15
440 V
5 0.2 0.4 0.75 1.5 2.2 2.2 3.7 5.5 5.5
Inching Operations
※ - Ratio of Inching(%) = × 100
Standard Operations + Inching Operations
- The inching limit of making & breaking frequency is below the continuous 10 operations based on 1 operation per 1 second.

Rated Operational Current for DC-loads.

Con- Operational
nection Application Voltage HiMC 9 HiMC 12 HiMC 18 HiMC 22 HiMC 32 HiMC 40 HiMC 50 HiMC 65 HiMC 80
24 V 10 12 18 20 25 35 50 65 75
DC-1 duty 48 V 10 12 18 20 25 35 40 65 65
(L/R≤1ms) 110 V 6 10 13 15 25 25 35 65 50
220 V 3 7 8 10 12 12 15 50 20
2 Poles Series

24 V 8 12 12 20 25 35 45 45 65
DC-3, DC-5 duty 48 V 4 6 6 15 20 20 25 25 40
(L/R≤15ms) 110 V 2.5 4 4 8 10 10 15 15 20
220 V 0.8 1.2 1.2 2 3 3 3.5 3.5 5
24 V 8 12 12 20 25 35 - - -
DC-13 duty 48 V 4 6 6 12 15 15 - - -
(L/R≤40ms) 110 V 2 3 3 3 4 4 - - -
220 V 0.3 0.5 0.5 1.2 1.2 1.2 - - -
24 V 10 12 18 20 25 35 50 65 75
DC-1 duty 48 V 10 12 18 20 25 35 50 65 75
(L/R≤1ms) 110 V 8 12 18 20 25 35 50 65 75
220 V 8 12 18 20 22 30 40 50 55
3 Poles Series

24 V 8 12 12 20 25 35 50 50 80
DC-3, DC-5 duty 48 V 6 10 10 20 25 30 35 35 60
(L/R≤15ms) 110 V 4 8 8 15 20 20 30 30 50
220 V 2 4 4 8 10 10 12 12 20
24 V 8 12 12 20 25 35 - - -
DC-13 duty 48 V 6 10 10 15 25 25 - - -
(L/R≤40ms) 110 V 3 5 5 10 12 12 - - -
220 V 0.8 2 2 4 4 4 - - -
※ - DC-1 duty is applied to resistance load and DC-13 duty is applied to inductive coil load (IEC 60947).
- DC-3 duty is applied to starting or inching of shunt motors and DC-5 duty is applied to starting or inching of series motors (IEC 60947).
- DC-3 and DC-5 duty of making & breaking capacity is 4 times to above table and its operation is fifty times.
- Electrical lifetime is up to 500 thousand when the frequency is below than 100 operations per a hour.
HiMC 90 HiMC 110 HiMC 130 HiMC 150 HiMC 180 HiMC 220 HiMC 260 HiMC 300 HiMC 400 HiMC 500 HiMC 630 HiMC 800
19 25 30 37 45 55 65 75 110 132 160 200
15 15 22 25 30 37 45 50 65 70 75 132
15 19 22 30 37 45 50 55 75 80 90 150
7.5 9 9 11 15 19 22 25 30 32 37 45
11 11 15 19 25 30 32 37 45 50 55 75
5.5 5.5 7.5 9 11 15 17 22 25 30 37 45
37 50 60 75 90 110 132 150 200 250 300 400
30 37 45 55 75 90 110 125 132 140 150 190
30 37 45 55 75 90 110 132 150 167 190 220
15 18.5 22 30 37 37 42 50 75 80 90 110
22 25 30 45 55 60 65 75 110 120 132 160
11 13 15 22 25 30 32 37 55 63 75 90
9 11 15 19 22 25 30 37 45 50 55 75
3.7 4.5 5.5 7.5 11 13 15 18.5 22 25 30 37
18.5 22 30 37 45 45 49 55 75 90 110 150
7.5 11 15 19 22 25 26 30 37 40 45 75

HiMC 90 HiMC 110 HiMC 130 HiMC 150 HiMC 180 HiMC 220 HiMC 260 HiMC 300 HiMC 400 HiMC 500 HiMC 630 HiMC 800
80 100 120 150 180 220 260 300 400 500 630 800
65 100 100 120 180 180 220 240 240 300 630 800
50 80 80 100 150 150 180 200 200 220 630 800
20 50 50 100 150 150 180 200 200 220 630 800
65 100 120 150 180 220 260 300 400 500 630 800
40 60 60 100 150 150 180 200 200 260 630 630
20 40 40 80 120 120 130 150 150 180 630 630
5 30 30 60 80 80 80 90 90 130 630 630
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
Hi Series

- - - - - - - - - - - -
80 100 120 150 180 220 260 300 400 500 630 800
80 100 120 150 180 220 260 300 400 500 630 800
13

80 100 100 150 180 220 260 300 400 500 630 800
60 80 80 150 180 220 260 300 300 400 630 800
80 100 120 150 180 220 260 300 400 500 630 800
60 90 90 130 180 220 260 280 280 400 630 630
50 80 80 120 150 150 180 200 200 260 630 630
20 50 50 80 100 100 130 150 150 180 630 630
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
- - - - - - - - - - - -
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMC

Technical Data of Contactors


Characteristics of Coil

HiMC 9 HiMC 12 HiMC 18 HiMC 22 HiMC 32 HiMC 40 HiMC 50 HiMC 65 HiMC 80


Operation Time Electrical Power Consumption

AC Inrush VA 60 60 60 60 60 60 140 180 180


(220V/60Hz) Sealed VA/W 14/2.9 14/2.9 14/2.9 14/2.9 14/2.9 14/2.9 16/5 6.7/3.3 6.7/3.3
AC Inrush VA 60 60 60 60 60 60 140 100 100
(110V/60Hz) Sealed VA/W 14/2.9 14/2.9 14/2.9 14/2.9 14/2.9 14/2.9 16/5 2.7/1.6 2.7/1.6
Inrush W 6.5 6.5 6.5 6.5 6.5 6.5 100 91 91
DC
Sealed W 6.5 6.5 6.5 6.5 6.5 6.5 14 1.7 1.7
Making Coil ON AC 15~25 15~25 15~25 15~25 15~25 15~25 14~25 50~65 50~65

Main Contact ON DC - - - - - - - 50~65 50~65
ms
Making Coil OFF AC 4~15 4~15 4~15 4~15 4~15 4~15 5~15 25~90 25~90
→ Main Contact
OFF DC - - - - - - - 25~90 25~90
Min. Control Transformer Capacity VA 50 50 50 50 50 50 100 100 100

AC Operational AC Operational DC Operational


Application Voltage (60 Hz)
Note
Voltage (50 Hz) Voltage
24 22 12
1) The rated voltage shall be applied to the contactor
48 42 24
coll.
110 48 48
2) The coil can operate correctly during short period
120 100 60 even at 85~110% of the rated voltage, when it is
Coil Ratings

208 110 80 saturated at 40℃ on the rated voltage and


frequency.
220 220 100
HiMC 3) If none-rated voltage is applied to the coil
240 240 110
9 ~ 50 continuously, it is apt to be deteriorated in electrical
380 380 125 insulation and mechanical operation.

440 400 200


4) Different voltage range shall be informed in
460 415 220 advance.

480 440 250


575 500
600 550
※If none-rated voltage is applied to the coil for long time, the lifetime of the contactor can be reduced.
HiMC 90 HiMC 110 HiMC 130 HiMC 150 HiMC 180 HiMC 220 HiMC 260 HiMC 300 HiMC 400 HiMC 500 HiMC 630 HiMC 800
180 290 290 360 360 360 380 380 1700 1700 1700 1700
6.7/3.3 7.4/3.8 7.4/3.8 9.3/5.8 9.3/5.8 9.3/5.8 9.3/5.8 9.3/5.8 14.7/7.2 14.7/7.2 17.1/10.6 17.1/10.6
100 180 180 240 240 240 250 250 800 800 850 850
2.7/1.6 3.3/2.1 3.3/2.1 6.4/4.4 6.4/4.4 6.4/4.4 6.4/4.4 6.4/4.4 10/5.2 10/5.2 10.5/8 10.5/8
91 193 193 234 234 234 234 234 850 850 850 850
1.7 2.3 2.3 3.4 3.4 3.4 3.4 3.4 5.9 5.9 9.5 9.5
50~65 55~65 55~65 50~55 50~55 50~55 55~65 55~65 55~65 55~65 55~65 55~65
50~65 55~65 55~65 50~55 50~55 50~55 55~65 55~65 55~65 55~65 55~65 55~65
25~90 40~90 40~90 42~55 42~55 42~55 45~65 45~65 45~65 45~65 45~65 45~65
25~90 40~90 40~90 42~55 42~55 42~55 45~65 45~65 45~65 45~65 45~65 45~65
100 150 150 200 200 200 200 200 1000 1000 1000 1000

AC Operational AC Operational DC Operational AC/DC Operational


Application Voltage (60 Hz)
Note
Voltage (50 Hz) Voltage Voltage
24 22 24
48 42 48 HiMC 65~500 1) The rated voltage shall be
applied to the contactor coil.
220
110 48 60
AC: 100~240 2) The coil can operate correctly
120 100 80 during short period even at
DC: 110~220
208 110 100 85~110% of the rated
440 voltage, when it is saturated
220 220 110 at 40℃ on the rated voltage
AC: 380~450
HiMC and frequency.
240 240 125
65 ~ 220
380 380 200 3) If none-rated voltage is
applied to the coil
440 400 220
continuously, it is apt to be
460 415 250 deteriorated in electrical
Coil Ratings

insulation and mechanical


480 440 operation.
575 500
4) Different voltage range shall
600 550 be informed in advance.
110 100 48
120 110 60 HiMC 630~800
Hi Series

110
208 220 80
AC: 100~127
220 240 100
DC: 100~110
380 110
15

240
HiMC 220
380 400 125
300 ~ 800 AC: 200~240
440 415 200 DC: 200~220
460 440 220 440
480 500 250 AC: 380~450
575 550 DC: -

600
※If none-rated voltage is applied to the coil for long time, the lifetime of the contactor can be reduced.
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMC

Auxiliary Contacts and Contact Blocks

Based on IEC 60947 Standard

Auxiliary Contacts Auxiliary Contact Blocks


Type HiMC HAB, HAC, HAS
HiAL, HiAR
9 ~ 50 65 ~ 800 Fixed Contacts Convertible Contacts
Rated Insulation Voltage V 750 750 750 750 750
Rated Thermal Current Ith A 16 16 16 16 16
110 V 10 10 10 10 10
Rated Current
AC-12 duty 220 V 8 8 8 8 8
A
(Resistive 440 V 6 6 6 6 6
heating loads)
690 V 2 2 2 2 2
110 V 6 6 6 6 6
Rated Current
220 V 6 6 6 6 6
AC-15 duty A
(Coil loads) 440 V 3 3 3 3 3
690 V 2 2 2 2 2
24 V 5 5 5 5 5
Rated Current
DC-12 duty 48 V 3 3 3 3 3
A
(Resistive 110 V 2.5 2.5 2.5 2.5 2.5
heating loads)
220 V 1 1 1 1 1
24 V 3 3 3 3 3
Rated Current
48 V 2 2 2 2 2
DC-13 duty A
(Coil loads) 110 V 1 1 1 1 1
220 V 0.6 0.6 0.6 0.6 0.6

UL & CSA Standard

Auxiliary Contacts 1) Auxiliary Contact blocks


Type HiMC HAB, HAC, HAS 2)
HiAL, HiAR 1)
9 ~ 50 65 ~ 800 Fixed Contacts Convertible Contacts
Rated Thermal Current Ith V 16 16 16 16 16
120 V 6 6 3 3 6
AC 240 V 3 3 1.5 1.5 3
A
Rated Current 480 V 1.5 1.5 0.75 0.75 1.5
600 V 1.2 1.2 0.6 0.6 1.2
DC 125 V 1.1 1.1 1.1 1.1 1.1
A
Rated Current 250 V 0.55 0.55 0.55 0.55 0.55
※ Contact rating code: 1) A600-P600 (Aux. contact & HiAL, HiAR)
2) B300-P300 (Aux. contact block)
Star-delta Starting Contactors

Voltage, Current & Torque of Star-delta Starting Contactors

Starting (Star-use Contactor) Operating (Delta-use Contactor/C2)


Starting Method
Starting Current Torque Full Load Current Contact Voltage Full Load Current Contact Current Contact Voltage
Direct 6 Im 1.5T 6 Im Em /√3 Im Im Em /√3
Star-delta 2 Im 0.5T 2 Im Em /√3 Im Im / √3 Em
※Im: Delta wiring load current Em: line-to-line voltage T: Rated torque (assumed torque fluctuations)

Contactors for Normal Star-delta Starters

200 ~ 240 V AC, 3 , 60 Hz 380 ~ 440 V AC, 3 , 60 Hz


Motor Capacity Main Circuit △ Circuit Y Circuit Motor Capacity Main circuit △ Circuit Y Circuit
TOR TOR
kW HP FLC (C1) (C2) (C3) kW HP FLC (C1) (C2) (C3)

5.5 7.5 22 HiMC 22 HiMC 22 HiMC 22 HiTH 22K 5.5 7.5 12 HiMC 22 HiMC 22 HiMC 22 HiTH 22K
7.5 10 32 HiMC 32 HiMC 32 HiMC 22 HiTH 40K 7.5 10 18 HiMC 22 HiMC 22 HiMC 22 HiTH 22K
11 15 40 HiMC 40 HiMC 40 HiMC 32 HiTH 40K 11 15 22 HiMC 22 HiMC 22 HiMC 22 HiTH 22K
15 20 50 HiMC 50 HiMC 50 HiMC 32 HiTH 50K 15 20 32 HiMC 32 HiMC 32 HiMC 22 HiTH 40K
18.5 25 70 HiMC 50 HiMC 50 HiMC 40 HiTH 50K 18.5 25 40 HiMC 40 HiMC 40 HiMC 22 HiTH 40K
22 30 80 HiMC 65 HiMC 65 HiMC 40 HiTH 90K 22 30 50 HiMC 40 HiMC 40 HiMC 32 HiTH 40K
30 40 110 HiMC 90 HiMC 90 HiMC 50 HiTH 90K 30 40 65 HiMC 50 HiMC 50 HiMC 40 HiTH 50K
37 50 130 HiMC 110 HiMC 110 HiMC 65 HiTH 130K 37 50 80 HiMC 65 HiMC 65 HiMC 40 HiTH 90K
45 60 150 HiMC 130 HiMC 130 HiMC 65 HiTH 130K 45 60 90 HiMC 65 HiMC 65 HiMC 40 HiTH 90K
55 75 180 HiMC 150 HiMC 150 HiMC 90 HiTH 220K 55 75 110 HiMC 90 HiMC 90 HiMC 50 HiTH 90K
75 100 260 HiMC 180 HiMC 180 HiMC 110 HiTH 220K 75 100 150 HiMC 110 HiMC 110 HiMC 65 HiTH 130K
90 125 300 HiMC 220 HiMC 220 HiMC 130 HiTH 220K 90 125 180 HiMC 130 HiMC 130 HiMC 90 HiTH 130K
110 150 367 HiMC 300 HiMC 300 HiMC 150 HiTH 300K 110 150 220 HiMC 150 HiMC 150 HiMC 110 HiTH 220K
132 180 434 HiMC 400 HiMC 400 HiMC 220 HiTH 500K 132 180 260 HiMC 180 HiMC 180 HiMC 110 HiTH 220K
160 220 519 HiMC 400 HiMC 400 HiMC 220 HiTH 500K 160 220 300 HiMC 220 HiMC 220 HiMC 130 HiTH 220K
250 350 810 HiMC 630 HiMC 630 HiMC 400 HiTH 800K 250 350 500 HiMC 400 HiMC 400 HiMC 220 HiTH 500K
300 - - - - - - 300 402 560 HiMC 400 HiMC 400 HiMC 300 HiTH 500K
※ - Above data are based on squirrel cage motor(AC-3) and slip-ring motor(AC-2). Those data are subject to change according to motor classes and motor manufacturers.
- Above data are based on less than 10 seconds motor starting time. Motor starting time must be considered when over 10 seconds motor starting time shall be applied.
- Inrush current shall be considered when a capacitor is used.
Hi Series

- Recommendable change-over time from Y to △ is between 30 ms and 80 ms.


- 58% of motor full load current is recommended for HiOR setting current.
17

Main Circuit Control Circuit


Diagram Diagram

For HiMC 9 ~ 50 For HiMC 65 ~ 800


Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMC

Transformer and Condensor Load


Transformer Load ★ Condenser Load ★★
Single phase Three phase Three phase
Type
220 V 440 V 220 V 440 V 220 V 440 V
(kVA) (kVAR)
HiMC 9 1 1.5 2 2.5 2 3
HiMC 12 1.5 2 3 4 3 4
HiMC 18 2 3 3.5 5 4 6
HiMC 22 2.5 4 4 7.5 5 10
HiMC 32 3 5 5 10 9 16
HiMC 40 4 7.5 6.5 12 11 20
HiMC 50 5 10 10 18 13 24
HiMC 65 7 15 12 25 17 34
HiMC 80 8 17 13 27 20 40
HiMC 90 9 18 15 30 22 45
HiMC 110 10 20 18 35 24 48
HiMC 130 15 25 25 42 29 58
HiMC 150 17 33 30 60 35 70
HiMC 180 20 40 35 70 42 84
HiMC 220 25 50 42 85 58 115
HiMC 260 30 57 48 95 63 125
HiMC 300 33 66 57 100 69 139
HiMC 400 44 90 75 150 92 185
HiMC 500 55 110 90 180 115 230
HiMC 630 65 130 110 220 145 291
HiMC 800 90 175 150 300 185 369
※ Electrical endurance: 100,000 (IEC 60947-4-1, AC-6a, 6b)

The inrush shall be less than 30 times of the full load current of the transformer.
★★
The condenser must be discharged before being re-energized. Maximum residual voltage at terminals shall be under than 50 V.
Wire and Tightening Torque
Main Circuit

Type Terminal Screw Wire Size (mm2) Compressing Terminal Size (mm2) Tightening Torque (kgf.cm)
HiMC 9 M4 1.25 ~ 5.5 1.25/M4 ~ 5.5/M4 23
HiMC 12 M4 1.25 ~ 5.5 1.25/M4 ~ 5.5/M4 23
HiMC 18 M4 1.25 ~ 5.5 1.25/M4 ~ 5.5/M4 23
HiMC 22 M4 1.25 ~ 5.5 1.25/M4 ~ 5.5/M4 23
HiMC 32 M5 2 ~ 14 1.25/M5 ~ 14/M5 26.5
HiMC 40 M5 2 ~ 14 1.25/M5 ~ 14/M5 26.5
HiMC 50 M5 2 ~ 22 2/M5 ~ 22/M5 28.8
HiMC 65 M8 2 ~ 38 2/M8 ~ 38/M8 60
HiMC 80 M8 2 ~ 38 2/M8 ~ 38/M8 60
HiMC 90 M8 2 ~ 38 2/M8 ~ 38/M8 60
HiMC 110 M8 2 ~ 60 2/M8 ~ 60/M8 60
HiMC 130 M8 2 ~ 60 2/M8 ~ 60/M8 60
HiMC 150 M10 2 ~ 150 2/M10 ~ 150/M10 100
HiMC 180 M10 2 ~ 150 2/M10 ~ 150/M10 100
HiMC 220 M10 2 ~ 150 2/M10 ~ 150/M10 100
HiMC 260 M10 2 ~ 200 2/M10 ~ 200/M10 100
HiMC 300 M10 2 ~ 200 2/M10 ~ 200/M10 100
HiMC 400 M10 2 ~ 240 2/M10 ~ 240/M10 100
HiMC 500 M10 2 ~ 240 2/M10 ~ 240/M10 100
HiMC 630 M12 80 ~ 325 80/M12 ~ 325/M12 140
HiMC 800 M12 80 ~ 325 80/M12 ~ 325/M12 140

Control Circuit

Type Terminal Screw Wire Size (mm2) Compressing Terminal (mm2) Tightening Torque (kgf.cm)
HiMC 9 ~ 50
M3.5 1.25 ~ 2 1.25/M3.5 ~ 2/M3.5 12
HiMC 65 ~ 800

Installation and Surroundings


Hi Series

◆Perpendicular &
1. Install in a dry & vibration-free location. Slant Installation
Installation
19

2. Perpendicular installation is recommended, but


±30° slant is acceptable.
3. Over 30° slant and horizonal installation may
shorten life-time, and may effect on the other
characteristics.

Surroundings 1. Ambient temperature: 20° C (standard), -25 ~ 40°C ◆Horizontal Installation


Average temperature (24 hours): below 35° C
2. Relative humidity: 45 ~ 85% RH
Altitude: below 2000 m
Vibration-proof: 10~55 Hz 2g
Impact-proof: 5g
3. Storage temperature: -30 ~ 65° C, Non freezing site.
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMC

Rating The contactors can be operated according to rated thermal current (Ith), rated operating current (Ie),
making & breaking capacities, electrical & mechanical endurance and utilization category.

Utilization Categories ◆AC - 1: Non-inductive or slightly inductive loads, ◆DC - 1: Non-inductive or slightly inductive
resistance furnaces. loads, resistance furnaces.
◆AC - 2: Slip-ring motors: starting, plugging ◆DC - 3: Shunt motors: plugging, inching
◆AC - 3: Squirrel cage motors: starting, switching off ◆DC - 5: Series motors: plugging, inching
motors during running. ◆DC - 12: Resistive heating loads
◆AC - 4: Squirrel cage motors: plugging, inching ◆DC - 13: Coil loads
◆AC - 12: Resistive heating loads
◆AC - 15: Coil loads

Making and Breaking Capacities According to Utilization Category

Duty Make Make and Break


Type Current Voltage Cos Number of operation Current Voltage Cos Number of Operation
AC-1 - - - - 1.5Ie 1.05Ue 0.8 50
AC-2 - - - - 4.0Ie 1.05Ue 0.65 50
AC-3 10Ie Ue 0.45(≤100 A) 50 8.0Ie 1.05Ue 0.45(≤100 A) 50
AC-4 12Ie Ue 0.35(≻100 A) 50 10.0Ie 1.05Ue 0.35(≻100 A) 50
DC-1 - - - - 1.5Ie 1.05Ue 1.0 50
DC-3 - - - - 4.0Ie 1.05Ue 2.5 50
DC-5 - - - - 4.0Ie 1.05Ue 15 50
AC-15 - - - - 10Ie 1.1Ue 0.3 10
DC-13 - - - - 1.1Ie 1.1Ue 6P 10

Operating Cycles According to Utilization Category

Duty Make and Break


Type Current Voltage Cos On-time Number of Operation
AC-1 1.0Ie 1.05Ue 0.8 0.05 sec 6000
AC-2 2.0Ie 1.05Ue 0.65 0.05 sec 6000
AC-3 2.0Ie 1.05Ue 0.45(Ie≤100 A) 0.05 sec 6000
AC-4 6.0Ie 1.05Ue 0.35(Ie≻100 A) 0.05 sec 6000
DC-1 1.0Ie 1.05Ue 1.0 0.05 sec 6000
DC-3 2.5Ie 1.05Ue 2.0 0.05 sec 6000
DC-5 2.5Ie 1.05Ue 7.5 0.05 sec 6000
AC-15 10Ie 1.1Ue 0.3 0.05 sec 6000
DC-13 1.1Ie 1.1Ue 6P 0.05 sec 6000

Electrical Endurance According to Utilization Category

Duty Make Break


Type Current Voltage Cos Current Voltage Cos
AC-1 1Ie 1Ue 0.95 1Ie 1Ue 0.95
AC-2 2.5Ie 1Ue 0.65 2.5Ie 1Ue 0.65
AC-3 6Ie 1Ue 0.65(Ie≤17 A) 1Ie 0.17Ue 0.65(Ie≤17 A)
AC-4 6Ie 1Ue 0.35(Ie≻17 A) 6Ie 1Ue 0.35(Ie≻17 A)
DC-1 1Ie 1Ue 1 1Ie 1Ue 1
DC-3 2.5Ie 1Ue 2 2.5Ie 1Ue 2
Ie: Rated Current
DC-5 2.5Ie 1Ue 7.5 2.5Ie 1Ue 7.5 Ue: Rated Voltage
Electrical Endurance Curve of Main Contacts

Electrical Endurance in AC-3 Duty (380~440VAC) Selection of AC3 & AC4 Contactors
◆When the frequency of operation is lower than the
recommendation, motor output can be increased, but should not
exceed the making and breaking capacities of the contactor.
If thermal overload relay is used, the short-circuit protection
should be carefully considered and the recommended fuse ratings
should not be exceeded.
◆The contactors can be chosen considering the electrical
endurance by means of the diagrams.
◆The electrical endurance of the contactor for AC-3, AC-4 duty can
be calculated using this formula.

1
L=
P1/L1 + P2/L2 + … + Pn/Ln

•L: electrical endurance of the contactor.


Electrical Endurance in AC-3 Duty (380~440VAC) •L1: electrical endurance in AC-3 duty
•L2: electrical endurance in AC-4 duty
•P1: part of use in AC-3 duty
•P2: part of use in AC-4 duty
•P1 + P2 + … + Pn = 1
◆Ex
In=80 A, Is=480 A, 95% non-plugging duty Ia=60 A and 5%
plugging duty Is=360 A. What is the electrical endurance of
contactor HiMC 90.
106
L = = 0.57×106
(Operation) 0.95/3.0 + 0.05/0.35

•On AC-3 duty endurance curve, lifetime of HiMC 90 is


3.0x106 at 60 A
•On AC-4 duty, lifetime of HiMC 90 is 0.035x106 at 360 A

Electrical Endurance in AC-4 Duty (380~440VAC) Electrical Endurance in AC-4 Duty (380~440VAC)
Hi Series
21

※Starting current shall be under 6 times of rated current.


Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiTH

Thermal overload relay

Features

◆ The HiTH series thermal overload relay compensates the ambient temperature
automatically. The compensation range is between -25℃ and +55℃.
◆ The HiTH series has the phase unbalance protection device, which increases the
reliability of the motor protection.
◆ These relays are provided with built-in free tripping mechanism, which can be trip
regardless of the position of Reset Button position. Control
Terminal
◆ These relays have 1NO and 1NC aux. contacts with galvanic isolation.
◆ HiTH 130 ~ 800 are Current Transformer(CT) type relays. HiTH 800 is able to
Main
transmit Max. 800 ampere. Terminal

◆ Protection cover for the main and control terminal meet IP 20.(HiTH 22, 40, 50 & 90)
◆ The HiTH series is pin type, so it can be connected to the
magnetic contactor directly. (HiTH 22, 40, 50 & 90)
◆ Both screw and 35mm Din rail mounting are available through the separate
mounting units.

The HiTH series has three function modes as below,

1) A position : Auto. Reset 2) H position : Manual Reset 3) Test position : Manual Reset & Test
Function

In this position, the relay resets “H” position is the normal delivery Test position is to perform the manual
automatically around one minute after position. The relay can be reset test since this mode works like an extra
the relay is tripped. When the reset manually about one minute after the stop button of the operating circuit.
button is inserted into the relay body at relay is tripped. The reset button can When the reset button is pushed at
“H” position, the button can be turn to be turn to the “H” from “A” or “TEST” “TEST” position, the “NO” contact is
the “A” position. position. closed and the “NC” contact is opened.

※Caution : please make it sure that the reset button is at “TEST” position to carry out the manual test.

Adjusting the Rated Current Tripping Indicator

Three Steps of the Rated ◆ The indication bar is to


Operation Current can be be projected 5~7mm
adjusted by “+” or “-” driver.
when the relay is tripped,
so the relay status can
be recognized easily.
◆ Caution : Do not press
the indication bar when
you reset.
Selection of Thermal Overload Relay Protection of Phase Loss

>> Motors of short starting time >> Discordant Tripping Unit


◆ For motors of normal starting time within a few seconds, the relays can be
When R phase becomes phase loss, the
selected by the table of page 22 & 23.
bimetal of R phase remains and the other
◆ The full load current(FLC) of the motor must be within the setting range of the
bimetals of S & T phase are bended.
thermal overload relay.
The bottom slide of the Discordant Tripping
◆ The starting time of high-inertia motor is an important factor at selecting
Unit keeps the original position due to the
thermal overload relays. bimetal of R phase; whereas, the top slide
◆ The tripping time of the motors, whose starting current is 6~7 times of the rated moves because of the bending bimetals of
current, can be obtained from the HiOR tripping curves, page 24 & 25. This S & T phase.
time should be longer than around 25% of the motor starting time. The difference moving ratio of top and
bottom slides make the Discordant Tripping
>> Motors of long starting time time to be shorter than normal tripping time;
◆ If the starting time of the motor is longer than the tripping time of HiTH 22~90, please refer to the figure.
the current transformer type shall be used.
◆ The current transformer type relays include the Non-Tripping features during ◆Tripping Function
the motor starting time.
◆ The rated current can be decreased by looping the primary cable several times
on the transformer according to the following table.
Normal Position
(Untripped Position)
Current Range(Example: 130 A)
Number of Primary Loops Current Range (A) Current Ratio
1 78 ~ 130 130 / 5
2 39 ~ 65 65 / 5 Overload of
3 26 ~ 26.7 26.7 / 5 3 Phase
(Normal Tripping)
4 19.5 ~ 43.3 43.3 / 5
5 15.6 ~ 26 26 / 5
6 13 ~ 21.7 21.7 / 5
Discordant
7 11.14 ~ 18.5 18.5 / 5
Tripping
8 9.75 ~ 16.25 16.25 / 5 (R Phase Loss)

◆ The second rated current of current transformer is 5 A, the overload relay is


able to control the current between 3 A and 5 A.
◆ The corresponding setting value for the relay can be calculated by using the
following formula.
Hi Series

Rated current of motor


Setting current(A) =
Current ratio
23

>> Making and breaking capacities of auxiliary contacts


Grade AC15 1) Grade DC13 2)
Aux.Contact 95-96 Alarm.Contact 97-98 Aux.Contact 95-96 Alarm.Contact 97-98
U/V U/V
Ie(A) Ie(A) Ie(A) Ie(A)
110 2.0 1.2 24 1.0 1.0
220 1.5 1.0 110 0.4 0.4
500 1.0 0.6 220 0.15 0.15
660 0.5 0.3 440 0.07 0.07
※ 1) AC15 duty - Making/Breaking Current = Ie×10 2) DC13 duty - Making/Breaking Current = Ie×1.1
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiTH

Technical Data / Specification

HiTH 22K(H) HiTH 40K(H) HiTH 50K(H) HiTH 90K(H)


Applied Contactor HiMC 9 ~ 22 HiMC 32 ~ 40 HiMC 50 HiMC 65 ~ 90
Rated Current Name Allowable Scope of Current
0.18 0.12 ~ 0.18
0.26 0.18 ~ 0.26
0.35 0.25 ~ 0.35
0.5 0.34 ~ 0.5
0.7 0.5 ~ 0.7
0.9 0.6 ~ 0.9
1.2 0.8 ~ 1.2
1.6 1.1 ~ 1.6
2.1 1.5 ~ 2.1
3 2~3
4.2 2.8 ~ 4.2
5 3~5
6 4~6
8 5.6 ~ 8
10 7 ~ 10 7 ~ 10
13 9 ~ 13 9 ~ 13
18 12 ~ 18 12 ~ 18
22 16 ~ 22 16 ~ 22
26 18 ~ 26 18 ~ 26
32 24 ~ 32 24 ~ 32
40 28 ~ 40 28 ~ 40 28 ~ 40
50 36 ~ 50 36 ~ 50
65 45 ~ 65
80 60 ~ 80
90 70 ~ 90
Element 2 Heaters H type(Option)
Number 3 Heaters K type(Standard)
Aux. Contact 1a1b
Reset Type Man. / Auto Unit
Phase Fault Protection K type Only(Standard)
Suitable Wire Main Circuit 1~6 2 ~ 14 2 ~ 22 2 ~ 35
(mm2) Control Circuit 2 × 0.75 ~ 2.5
Net Weight(Kg)
0.17 / 0.16 0.23 / 0.22 0.28 / 0.27 0.53 / 0.51
K type / H type

Saparate Mounting Unit(HiTHMB)


HiTH 130K(H) HiTH 220K(H) HiTH 300K(H) HiTH 500K(H) HiTH 800K(H)

Applied Contactor HiMC 110 ~ 130 HiMC 150 ~ 220 HiMC 260 ~ 300 HiMC 400 ~ 500 HiMC 630 ~ 800

Rated Current Name Allowable Scope of Current

80(CT Ratio 80:5) 48 ~ 80

130(CT Ratio 130:5) 78 ~ 130 78 ~ 130

180(CT Ratio 180:5) 108 ~ 180

220(CT Ratio 220:5) 132 ~ 220 132 ~ 220

300(CT Ratio 300:5) 180 ~ 300 180 ~ 300

400(CT Ratio 400:5) 240 ~ 400

500(CT Ratio 500:5) 300 ~ 500

630(CT Ratio 630:5) 378 ~ 630

800(CT Ratio 800:5) 480 ~ 800

Features CT Assembly

2 Element H type(Option)
Element
Number
3 Element K type(Standard)

Aux. Contact 1a1b

Reset Type Man. / Auto Unit

Phase Fault Protection K type Only(Standard)

Main Circuit - - - - -
Suitable Wire
(mm2)
Controll Circuit 2 × 0.75 ~ 2.5
Hi Series

Net Weight (Kg)


1.65 / 1.3 1.85 / 1.49 1.94 / 1.59 2.25 / 1.88 5.74 / 4.62
K type / H type
25

HiTH 40K(H) HiTH 50K(H) HiTH 90K(H) HiTH 130K80


Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiTH

HiTH Tripping Curve

Three-phase Overload

◆Tripping Curve of 3 phase shows the average tripping time of cold starting condition at +20℃ ambient temperature.
(Tripping time of Hot Start: 20~40% of Cold Start)

Single-phase Overload

◆Average tripping time of single phase is 40~60% of three phase tripping time based on cold start.

HiTH 22, 0.18-3.0 HiTH 22, 4.2-6.0 HiTH 22/40, 8.0-22 HiTH 40/50/90, 26-40
h 2 h 2 h 2 h 2

min. 60 min. 60 min. 60 min. 60


40 40 40 40

20 20 20 20

10 10 10 10
6 6 6 6
4 4 4 4

2 2 2 2

sec. 60 sec. 60 sec. 60 sec. 60


40 40 40 40

20 20 20 20

10 10 10 10
6 6 6 6
4 4 4 4

2 2 2 2

1 1 1 1
1 1.2 1.5 2 3 4 5 6 8 10 12 1 1.2 1.5 2 3 4 5 6 8 10 12 1 1.2 1.5 2 3 4 5 6 8 10 12 1 1.2 1.5 2 3 4 5 6 8 10 12
Times Current Setting Times Current Setting Times Current Setting Times Current Setting

HiTH 50/90, 50 HiTH 90, 65-90 HiTH 130 - 300 HiTH 500 - 800
h 2 h 2 h 2 h 2

min. 60 min. 60 min. 60 min. 60


40 40 40 40

20 20 20 20

10 10 10 10
6 6 6 6
4 4 4 4

2 2 2 2

sec. 60 sec. 60 sec. 60 sec. 60


40 40 40 40

20 20 20 20

10 10 10 10
6 6 6 6
4 4 4 4

2 2 2 2

1 1 1 1
1 1.2 1.5 2 3 4 5 6 8 10 12 1 1.2 1.5 2 3 4 5 6 8 10 12 1 1.2 1.5 2 3 4 5 6 8 10 12 1 1.2 1.5 2 3 4 5 6 8 10 12
Times Current Setting Times Current Setting Times Current Setting Times Current Setting
HMX & HMT

Control Relays

Features

◆HMX is for AC, and HMT is for DC


◆The protection degree is IP20.
◆Screw and 35 mm DIN-Rail mounting is available.
◆Both HMX and HMT have three types of contact (2NO+2NC, 3NO+1NC, & 4NO).
◆These are proper for control circuit and factory automation.
◆The following auxiliary blocks can be attached by one-touch method.
•Aux. contact block •Timer •Latching Block •Surge absorber(RC-Unit)

Applicable Standard ◆ IEC 60947–5–1 ◆UL 508 ◆VDE 0660 ◆CENELEC–EN 50011

Technical Data

Contact
IEC 60947 750
Rated Insulation Voltage V
VDE0660 1000
Thermal Current Ith (AC-1) A 20
220 V 10
380 V 4
AC-15 440 V 3.5
500 V 3
690 V 2
24 V 5
Rated DC-12
48 V A 3
Operational (Resistance
110 V 2.5
Current Ie Load)
220 V 1
24 V 3
DC-13 48 V 2
(Coil Load) 110 V 1
220 V 0.6
AC Operated 10 … 25
Closing Time
DC Operated 20 … 50
ms
AC Operated 5 … 20
Opening Time
DC Operated 15 … 35
Mechanical Lifetime 10000 Times 1500
Wire Size mm2 2×0.75 … 2.5
Hi Series

Operation Frequency Times/Hours 3000


Plug-Fuse (Fast/Slow) 35/25
Applicable Max. Fuse MCB-C Features A 16
27

HRC Fuse (DIN/BS88) 25


Coil
Making VA/W 60/44
AC (60 Hz)
Consumption Power Normal VA/W 7.5/1.9
DC Making/Normal W 6.5
AC Operated kg 0.34
Weight
DC Operated kg 0.61

UL Standard
Rated Thermal Current A 20
120 VAC 6 120 VDC 1.1
Rated Current A Rated Current A
240 VAC 3 240 VDC -
※ Contact Rating Code: A300 ~ P150
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HMX & HMT

Mechanical Interlock Unit

◆The mechanical interlocking of two contactors for reversing contactors is


available with interlock unit.
A simultaneous closing of two contactors is prevented.

Type Contactors
HiTL 40 HiMC 9 ~ 40
HiTL 50 HiMC 50
HiTL 130 HiMC 65 ~ 130
HiTL 220 HiMC 150~220
HiTL 300 HiMC 260 ~ 300
HiTL 800 HiMC 400 ~ 800

◆Handling
•The electrical interlock should be applied via the“b”contact when
mechanical interlock is used.
•Horizontal installation is not allowed.
•Mechanical interlock shall be installed on HiMC 150-800 after removing
auxiliary contact blocks between two magnetic contactors.

◆Dimensions

Type A B C D E F G H Ф
HiMC 9, 12, 15, 18, 22 98 83 50~66 32~35 10 86.2 - 7.5 4.8
HiMC 32, 40 136 83 50~66 33.5~53.5 10 86.7 - 8 4.8
HiMC 50 149.2 85.8 57.6~70 53.8~60.8 10 99.2 - 8 4.8
HiMC 65, 80, 90 201.6 130 110~116 80 14 135.7 7.5 12 5.5
HiMC 110, 130 220 142 120~130 90 14 150.3 3.5 12 6.2
HiMC 150, 180, 220 316 189 161~171 120 40 168 3 15 9
HiMC 260, 300 340 202 180 120~130 40 187.4 3 15 11
HiMC 400, 500 398 251 196~225 154 40 235.5 3 20 11
HiMC 630, 800 592 280 230~250 226~250 40 272.3 3 24 12
HLB2 & HOKZE

Mechanical Latching Block

HLB2 Characteristics

◆Fast & Easy mounting to contactors and control relays.

◆HLB2 keeps the contactor mechanically latched.

Operation

◆How to OFF contactors or control relays


•Manually: Push the lever to the “O” position.
•Electrically: Put power to the coil.

◆Caution
•Do not excite the contactors (or control relays) and mechanical latching
blocks simultaneously.
•Refer to the right diagram for the control circuit.

Ratings and Characteristics

VA 25
Power Consumption
W 30
Pick-up Voltage V (0.85 - 1.1) x UC
Operating Cydes Cycle/h 1,200
24 V Fixed
AC and DC Controlled
AC / DC 110 V 110 ~ 125 V
Voltage
220 V 200 ~ 240 V
Mechanical Endurance 1,000 times 500
ex) HLB 2 / 220 (AC/DC)
※ Different voltage range shall be informed in advance.
Hi Series
29
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HLB2 & HOKZE

Electronic Timer Block

HOKZE Characteristics
◆Fast & Easy mounting.

◆Accurate and multi function through electronic method.

◆Wide voltage range is realized, and both AC & DC are applicable


on the block.

◆On-delay and Interval functions are furnished on the timer block at once.

Ratings & Characteristics

Mode HOKZE 1 HOKZE 2


Rated Voltage AC/DC V 90 ~ 240 24 ~ 60
Operating Voltage V (0.85 ~ 1.1) X Rated Voltage
Making Capacity VA 90
Maximum Load VA 15
Position A 10 ~ 220
Delay Time
Position B 0.15 ~ 15
Precision % ±5
% 0.1
Repeat Accuracy
sec 50ms

Function Charts
※ The timer needs a recovery time of at least 150ms between
operations to be reset for the next operation.

Position 1: ON-DELAY / t: adjustable delay time 0.15...220S Position 2: Interval Timer


Accessory

Auxiliary Contact Blocks

Type Consist Characteristics Application


HiAB 22 2NO + 2NC -
HiAB 13 1NO + 3NC -
HiAB 31 3NO + 1NC -
HiAB 04 0NO + 4NC -
HiMC 9 ~ 50
HiAB 40 4NO + 0NC -
HiAB 11 1NO + 1NC -
HiAB 02 0NO + 2NC -
HiAB 20 2NO + 0NC -
HiAL 11 ★
1NO + 1NC Left Hand Side HiMC 9 ~ 22
HiAC 13 1NO + 3NC -
HiAC 22 2NO + 2NC -
HiAC 40 4NO + 0NC -
HMX
HiAC 11 1NO + 1NC -
HMT
HiAC 02 0NO + 2NC -
HiAC 20 2NO + 0NC -
HiAL 5S 1NO + 1NC Left Hand Side
HiMC 65 ~ 130
HiAR 6S 1NO + 1NC Right Hand Side
HiAL 7S 1NO + 1NC Left Hand Side
HiMC 150 ~ 800
HiAR 8S 1NO + 1NC Right Hand Side

The side mounting Aux. contact block shall not be used with the top mounting Aux. contact block at the same time.

HiAC 22 HiAC 20 HiAL 11 HiAL 5S HiAR 6S


Hi Series
31
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

Accessory

Surge Absorber

◆Surge Absorber drops surge voltage, which is 10~20 times of the rated voltage occurred at the
operation of the contactor or auxiliary switch, to below 3 times of rated voltage.

◆It is suitable for PLC control circuit.

◆Damage to electronic parts from high surge voltage is prevented by the use of surge absorber.

◆Applicable to 50 Hz and 60 Hz.

Item Type Voltage Application


HRC 40/48 28 ~ 48 V
HMX
HRC 40/220 110 ~ 220 V
HiMC 9W ~ 40W
HRC 40/380 240 ~ 380 V
HRC 90/48 28 ~ 48 V
HiMC 50W
RC - Unit HRC 90/220 110 ~ 220 V
HiMC 65W ~ 90W
HRC 90/380 240 ~ 380 V
HRC 300/48 28 ~ 48 V
HRC 300/220 110 ~ 220 V HiMC 110W ~ 300W
HRC 300/380 240 ~ 380 V
Clamping Diode HOKYZX 38 HMT, HiMC 9G ~ 300G

◆Diagram

RC-Unit
Spare Parts

Control Coil Main Contact


Type Applicable MC Type Contactors
HMCOL 22X HMX HiMCTIP 9 ★
HiMC 9
HMCOL 22T HMT HiMCTIP 12★ HiMC 12
HiMCOL 40W/G HiMC 9 ~ 40 HiMCTIP 18 ★
HiMC 18
HiMCOL 50W/G HiMC 50 HiMCTIP 22★ HiMC 22
HiMCOL 90W/G/F HiMC 65 ~ 90 HiMCTIP 32 ★
HiMC 32
HiMCOL 130W/G/F HiMC 110 ~ 130 HiMCTIP 40★ HiMC 40
HiMCOL 220W/G/F HiMC 150 ~ 220 HiMCTIP 50 ★
HiMC 50
HiMCOL 300W/G/F HiMC 260 ~ 300 HiMCTIP 65 ★
HiMC 65
HiMCOL 500W/G/F HiMC 400 ~ 500 HiMCTIP 80 ★
HiMC 80
HiMCOL 800W/G/F HiMC 630 ~ 800 HiMCTIP 90 ★
HiMC 90
※ Ordering method: ex) HiMCOL 40W / 220X (Blank: 60 Hz, X: 50 Hz) HiMCTIP 110★ HiMC 110
HiMCTIP 130 ★
HiMC 130

Arc Chute HiMCTIP 150★ HiMC 150


HiMCTIP 180 ★
HiMC 180
Type Contactors
HiMCTIP 220★ HiMC 220
HiMCHT 90 HiMC 65 ~ 90
HiMCTIP 260 ★
HiMC 260
HiMCHT 130 HiMC 110 ~ 130
HiMCTIP 300 ★
HiMC 300
HiMCHT 220 HiMC 150 ~ 220
HiMCTIP 400 ★
HiMC 400
HiMCHT 300 HiMC 260 ~ 300
HiMCTIP 500 ★
HiMC 500
HiMCHT 500 HiMC 400 ~ 500
HiMCTIP 630★★ HiMC 630
HiMCHT 800 HiMC 630 ~ 800
HiMCTIP 800 ★★
HiMC 800

One set consists of 3 moving contacts and 6 fixed contacts.
★★
One set consists of 6 moving contacts and 12 fixed contacts.
(Two contact elements make one contact set.)
Insulation Barrier Unit
Type Contactors
HiMCIB 130 HiMC 65 ~ 130
HiMCIB 300 HiMC 150 ~ 300
HiMCIB 500 HiMC 400 ~ 500
HiMCIB 800 HiMC 630 ~ 800
Hi Series
33

Coil Main Contact Arc Chute


Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMS Diagram

Location of Contacts

Contactor Aux. Contact Block

HiMC 9W11 HiMC 9G11


HiMC 12W11 HiMC 12G11
HiMC 18W11 HiMC 18G11
HiMC 22W11 HiMC 22G11 HiAB 22 HiAB 11
2NO+2NC 1NO+1NC

HiAB 31 HiAB 02
HiMC 32W22 HiMC 32G22 3NO+1NC 0NO+2NC

HiMC 40W22 HiMC 40G22


HiMC 50W22

HiAB 13 HiAB 20
1NO+3NC 2NO+0NC

HiMC 50G21

HiAB 04 HiAL 5S
0NO+4NC HiAL 7S
1NO+1NC

HiMC 65W22 HiMC 220W22


HiMC 80W22 HiMC 260W22 HiAB 40 HiAR 6S
4NO+0NC HiAR 8S
HiMC 90W22 HiMC 300W22
1NO+1NC
HiMC 110W22 HiMC 400W22
HiMC 130W22 HiMC 500W22
HiMC 150W22 HiMC 630W22
HiMC 180W22 HiMC 800W22
Control Relay Aux. Contact Block

◆AC Operation Type

HiAC 13
HMX 22 1NO+3NC

HiAC 22
HMX 31 2NO+2NC

HiAC 31
HMX 40 3NO+0NC

HiAC 40
4NO+0NC

◆DC Operation Type

HiAC 11
HMT 22
1NO+1NC

HiAC 02
HMT 31
0NO+2NC
Hi Series
35

HMT 40 HiAC 20
2NO+0NC
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMS Drawing

Dimensional Drawings
M3.5 (Main Terminal)
59.6 35
M3.5 (Coil Terminal) M3.5 (Aux. Terminal)

32
HMX
73.5

45

60

50
HMT Accessories A(mm)
HiAC 35
4.8 HLB2 42.5
31 8
44 A 79.8 HOKZE 39
(11.5)
※( ): HMT(DC)

26.2
15.5 M3.5 (Coil Terminal) 62.1 35
(84.9)
M4 (Main Terminal)
M3.5 (Aux. Terminal)
9

HiMC 9
HiMC 12
30
74

51

66

50
HiMC 18 Accessories A(mm)

HiMC 22 HiAB 35

HLB2 42.5
22.6 8 4.8 HOKZE 39
44 A 86.2 ※( ): G type(DC)
(121.4)

26.2
15.5 M3.5 (Coil Terminal) 61.5 53.5
M4 (Main Terminal)
M3.5 (Aux. Terminal)
9

HiMC 32W
52.2

30
50
74

66

HiMC 40W
Accessories A(mm)
HiAB 35

HLB2 42.5
28.8 8 4.8
63 A 86.7 HOKZE 39

26.2
15.5 M3.5 (Coil Terminal) 96.7 35
M4 (Main Terminal)
M3.5 (Aux. Terminal)
9

HiMC 32G
30
66

50
52.2

HiMC 40G
74

Accessories A(mm)
HiAB 35

HLB2 42.5
28.8 8 4.8
HOKZE 39
63 A 121.9
36.8 M3.5 (Coil Terminal) 73.8
M5 (Main Terminal) 60.8
M3.5 (Aux. Terminal)
80.6

HiMC 50
86

57

71.3
57.6
35

Accessories A(mm)
HiAB 35

HLB2 42.5
32.4 8 4.8
69.6 A 99.2 HOKZE 39

35 M3.5 (Coil Terminal)


15 M8 (Main Terminal) 101.7

80 5.5 (Mounting Hole)

M3.5 (Aux. Terminal)

HiMC 65
HiMC 80
138
130

123

HiMC 90

110
116
56 12
93.8 10 143.2

35 M3.5 (Coil Terminal)


15 M8 (Main Terminal) 111.3

90 6.2 (Mounting Hole)

M3.5 (Aux. Terminal)

HiMC 110
155
142

139

HiMC 130
120
130

64 12
Hi Series

103 10 153.8

46
M3.5 (Coil Terminal)
37

25 118.5
M10 (Main Terminal)
120 9.0 (Mounting Hole)

M3.5 (Aux. Terminal)

HiMC 150
189

164

HiMC 180
161
171

HiMC 220

90 15
138 10 171
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMS Drawing

Dimensional Drawings

M3.5 (Coil Terminal)


47
M10 (Main Terminal) 11.0 (Mounting Hole)
25 131.9

M3.5 (Aux. Terminal)

HiMC 260
210
202

180
185

HiMC 300

94 15 120
150 10 189.9 130

72 M3.5 (Coil Terminal)


30 170 11.0 (Mounting Hole)
M10 (Main Terminal)

M3.5 (Aux. Terminal)

HiMC 400
251
225

196
225
HiMC 500

115 20 145
179 10 237.5 154

80 M3.5 (Coil Terminal)


40 199.8 12.0 (Mounting Hole)
M12 (Main Terminal)

M3.5 (Aux. Terminal)


HiMC 630
300
280
270

230
250

HiMC 800

160 24 226
276 10 274.5 250
M3.5 (Aux. Terminal) M4 (Main Terminal)

1.3
HiTH 22

86.5
44.2
26.8
30

74.5
62.6

34.1
13 51.8

M3.5 (Aux. Terminal) M5 (Main Terminal)


2.0
87.7

75.7
28.8

HiTH 40
32.4

61.3
52.8
12

30

34.1

17.3 52.3

Hi Series

M3.5 (Aux. Terminal) M5 (Main Terminal)


2.5

39
96.5
32.8

32.8
12

30

53

84.5

HiTH 50
74.1

43.5

20 53.1
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMS Drawing

Dimensional Drawings

M3.5 (Aux. Terminal) M5 (Main Terminal)

2.5
116.5
54.4

HiTH 90

50
15

104.5
78.5
30

101.5

60.3
22.6 61.4

64 187.1

15 8.5 160.1

111.3
M5 (Main Terminal)
116.5

134.5
37

HiTH 130 49
72

15 48.5
M3.5 (Aux. Terminal) 8.5 131.6

116 172

180

90 187.1

25 160.1
11.0
120

M5 (Main Terminal)
144.5
122.5
37

49

HiTH 220
72

25 48.5
M3.5 (Aux. Terminal) 11.0 131.6

116 172

180
94
187.1
30 11.0
131.9

M5 (Main Terminal)

135

158.5
HiTH 300
37

49
72

30 48.9
131.6
M3.5 (Aux. Terminal) 11.0
160.1
116
180 172

115

30 11.0 187.1

170

M5 (Main Terminal)
145
170

HiTH 500
37

49
72

50
M3.5 (Aux. Terminal)
11.0 131.6
115
160.1
180
172

160 219.1

M5 (Main Terminal) 40 16.0 199.8


Hi Series
41
146.5

146.5
187

HiTH 800
100

80

13.0 51.8
M3.5 (Aux. Terminal) 163.6
160 192.1
245 204
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMS Drawing

Dimensional Drawings

M3.5 (Coil Terminal) 86.2


44 M5 (Main Terminal) 62.1 35
M3.5 (Aux. Terminal)

HiMC 9
HiMC 12 30

50
66
101

HiMC 18
134.8

HiMC 22
+
4.8
HiTH 22

44.2 34.1
86.5

M3.5 (Coil Terminal) 86.7


63 M5 (Main Terminal) 61.5 53.5
M3.5 (Aux. Terminal)

HiMC 32 30

66
49
100.2

HiMC 40
126.5

+
HiTH 40
4.8

52.8 34.1
87.7

M3.5 (Coil Terminal) 99.2


69.6 M5 (Main Terminal) 73.8 60.8
M3.5 (Aux. Terminal)

35
57.6

71.3

HiMC 50
99.5

+
139.1

HiTH 50
4.8

53 43.5
96.5
93.8 101.7
M3.5 (Coil Terminal)
M8 (Main Terminal) 80

M3.5 (Aux. Terminal)

HiMC 65
155.1

HiMC 80

110
116
203

HiMC 90 5.5 (Mounting Hole)

+
HiTH 90

78.5 60.5
104.7
143.2

103 167.8
64 M3.5 (Coil Terminal) 125.3
15 M8 (Main Terminal)

90

M3.5 (Aux. Terminal)


128
142

HiMC 110
273.5

7
300
280

7
HiMC 130
M5 (Main Terminal)
40

+ 76

HiTH 130
134.5

49

15 62.5
8.5 132
M3.5 (Aux. Terminal) 145.6 148
116.0 174.1 184
186
180.0 201.1

138 191.3
90 M3.5 (Coil Terminal) 138.8 120
11.0 25
Hi Series

11.0 (Main Terminal)

M3.5 (Aux. Terminal)


43

HiMC 150
171

HiMC 180
345
322
309.0

HiMC 220 22 22

+ M5 (Main Terminal)
76
37

HiTH 220
49

11

25.0 68.8
M3.5 (Aux. Terminal) 11.0 151.9 128
180.4 152
141.0 184
192.3
180.0 207.4
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMS Drawing

Dimensional Drawings
150 210.2
94
M3.5 (Coil Terminal) 152.2 130
25
M10 (Main Terminal)

M3.5 (Aux. Terminal)

180
HiMC 260
HiMC 300
342.5

375
352
27 27
+
M5 (Main Terminal)

55.5
HiTH 300 76

49

11
30.0
11.0 69.2 128
M3.5 (Aux. Terminal) 151.9 152
146.0 180.4 184
192.3
180.0 207.4

179 257.8
115 190.3 154
M3.5 (Coil Terminal)
30
M10 (Main Terminal)

M3.5 (Aux. Terminal)

225
HiMC 400
HiMC 500
445
421
391.8

39 39
+ 61.75

HiTH 500 M5 (Main Terminal) 76


170

49
12

30.0 11.0
70.3 108
M3.5 (Aux. Terminal) 151.9 132
145.0 180.4 184
192.3
180.0 207.4

276 294.8
160 M3.5 (Coil Terminal)
220.1
40 M12 (Main Terminal)
M3.5 (Aux. Terminal)
250
250

HiMC 630
416.5
451.5

HiMC 800
520
496

84 84
+
55

82
HiTH 800 M5 (Main Terminal)
80

40
12

M3.5 (Aux. Terminal) 13.0 72.1


160 183.9 108
245 212.4 132
224.3 280
239.4
26.2 15.5 M3.5 (Coil Terminal) 62.1 35
M4 (Main Terminal) (84.9) 4.8
M3.5 (Aux. Terminal)

HiMR 9
HiMR 12
83

66
30
51

50
HiMR 18
HiMR 22

22.6 44 8 18
98 86.2 89
(121.4)

※( ): G type(DC)

26.2 15.5 M3.5 (Coil Terminal) 61.5 53.5 18


M4 (Main Terminal)
M3.5 (Aux. Terminal)

HiMR 32
83

30
52.2

66
49

HiMR 40

28.8 63 8 4.8
136 86.7

Hi Series

M3.5 (Coil Terminal)


29.4 36.8 73.8 60.8 18.8
M5 (Main Terminal) 4.8
45

M3.5 (Aux. Terminal)

35
HiMR 50
80.6
86

57

57.6

32.4 69.6 8 140.4


149.2 99.2
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMS Drawing

Dimensional Drawings

M3.5 (Coil Terminal) 115.7 205


35 15 M8 (Main Terminal)

6
M3.5 (Aux. Termianl)
HiMR 65 80 27.8 80

HiMR 80
138
130
123

180
160

113
HiMR 90

56 93.8
201.6 10 26 125
157.2 141

M3.5 (Coil Terminal) 125.3 225


35 15

7
M8 (Main Terminal)

M3.5 (Aux. Termianl)


90 27 90

HiMR 110
155
142
139

197
177

125

HiMR 130

64 103
220 10 26 145
167.8 159

M3.5 (Coil Terminal) 138.8 305


11

46 25 M10 (Main Terminal)

120 30 120
M3.5 (Aux. Termianl)
HiMR 150
189
164

250
225

HiMR 180
166

HiMR 220

90 138
288 10 35.3 183
191.3 205
M3.5 (Coil Terminal) 152.2 325

11
47 25
M10 (Main Terminal)

125 35 125
M3.5 (Aux. Terminal)
HiMR 260
210
202

180
260
235
185

HiMR 300

94 150
310 10 35.3 192
210.2 214

378
M3.5 (Coil Terminal) 185.3
11
72 30
M10 (Main Terminal)

154 31 154

M3.5 (Aux. Terminal)


HiMR 400
210.5
251
225

300
275

HiMR 500

115 179
364 10 40.3 224
257.8 246

Hi Series

M3.5 (Coil Terminal) 220.1 580


80 40
14

M12 (Main Terminal)


47

244 30 244

M3.5 (Aux. Terminal)

HiMR 630
250
300
280
270

360
330

HiMR 800

160 276
556 10 44.3 317
294.8 337
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMP

Digital Motor Protection Relay [Deluxe Type]

High-trust Realization
◆ The Micro Controller Unit of HiMP series provides superior reliability.
◆ Real time processing and high precision.

Various Protective Features


◆ Basic functions
•Over-current •Under-current •Stall •Lock
•Phase loss •Phase unbalance •Reverse phase

◆ Optional functions
•Electric leakage current •Instantaneous short current

Preliminary Alert Function


◆ HiMP series can prevent the sudden over-current trip through the preliminary alert function.
◆ HiMP series can be inspected easily due to displaying load ratio by bar-graph during operation.

Operating Time Function


◆Accumulated motor operation time can be displayed.
◆Certain operating time can be set to alert, so oil exchange point can be checked conveniently.

Digital Ampere Meter Function


◆ HiMP series are able to check the three phase ampere without additional ampere meter.

▲ R Phase Current ▲ S Phase Current ▲ T Phase Current

Display the Cause of Fault


◆ Easy maintenance and repair

▲ Over-Current ▲ Under-Current ▲ Phase Failure


Separable Display Part
◆ The display part can be installed separately from the
body ; therefore, the values and cause of the fault
can be checked without opening the panel door.

Various Wiring Methods


◆ Both terminal screw type and tunnel type are
available.

Ring-Terminal
◆ Ring-terminal type can be applied to the main
and control circuit.

Selectable Inverse and Definite

Hi Series
49

Inverse(t30) Definite

Applicable to the Inverter Control Circuit


◆ HiMP series have high performance under the harmonic noise, so they can be used for the
inverter control circuit under 20-240 Hz range.
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMP

Rating and Specification


HiMP-D Series
Type
HiMP-D S HiMP-D T
Panel Mount Unit or Extension3)
Wiring of Main Circuit Screw Tunnel Type
Allowable Current Partition •06: 0.5 ~ 6 A •60: 5 ~ 60 A
Current Setting Range •Min. current ~ Max. current X 105%
Operating Voltage (50 Hz/60 Hz) •110 V: 75 ~ 120% •220 V: 75 ~ 120% •Special order
Over-current •Over 112.5%±5% - Inverse(cold/hot curve), Definite
Under-current •User setting (30% ~ 70% of operating current/ Min. setting value shall be over 70% of Min. rated current.)
Phase Failure •Over 70% of unbalance rate
Phase Unbalance •Over 50% of unbalance rate
Features Stall •Over 180% of setting current - Definite only
& Restriction
Setting Range Lock •User setting (200% ~ 1000%) - Definite only
Reverse Phase •Reverse phase perception at the beginning.
Leakage Current 1) •User setting (100 ~ 2500 mA)
Short Circuit 2) •User setting (200% ~ 1000% of rated current)
Inverse •Delay time: OFF/1 ~ 30 sec, Operation time: 1 ~ 30 sec (600% basis)
Over-Current
Definite •Delay time: OFF/1 ~ 30 sec, Operation time: 1 ~ 30 sec
Under-current •1 ~ 30 sec
Phase Failure •2 sec
Time Phase Unbalance •5 sec
Setting Range Stall •5 sec
Restriction
Lock •Within 2 msec
Reverse Phase •Within 500 msec
Leakage Current 1) •0.1~ 10 sec
Short Circuit 2) •Within 50 msec
Preliminary Alert Function •60% ~ 110% of rated current
Operating time Function •OFF / 0 ~ 9990 hour
Manual •By RESET button manually (Not working during operation)
Reset Method Electrical •By control power off.
Automatic •After setting time.
Test Method •Tripping by the TEST button (Not working during operation)
Current •± 5%
Tolerance
Time •Motor protection according to IEC 60947 5)
Number •Trip contact: 1a1b •Alert contact: 1a 4)
Aux. Contact
Capacity •3A/250 VAC (Resistance load)
Over-Current Capacity •Over 20 times/2 sec of Max. operating current
Insulation Resistance •Over 100MΩ/500VDC
Fast Between Circuit and Frame •2000 VAC/1 min.
Transient Between Circuits •2000 VAC/1 min.
Burst Between Contacts •1000 VAC/1 min.
Operation •-25 ~ 70 ℃
Temperature
Environment Storage •-30 ~ 80 ℃
Humidity •45 ~ 85% RH
1) 2) Leakage and Short Circuit function can not be selected at the same time.
3) Connecting cable and display breaket should be ordered when extension type is required.
4) When the leakage function is selected, alert contact is used as ZCT input terminal
5) Class 5 (Time 1, 2, 3), Class 10 (Time 4, 5, 6, 7, 8),
Class 15 (Time 9, 10, 11, 12, 13), ...

HiMP-D S HiMP-D T
Function
Function Description Remark
•Prevent the motor from over-current. •Standard
Over-current
•Trip it over 112.5% of setting current and time. •Ref. cold/hot curve

•Prevent the vain rotation from power fault.


Under-current •Selective function
•Trip it by setting rate of under-current and time.

•Prevent the phase failure from line fault and touch.


Phase Failure •Selective function
•Trip 2sec when deviation is over 70% among three phases.

•Prevent the phase unbalance from fault of insulation/wring.


Phase Unbalance •Selective function
•Trip 5sec when deviation is over 50% among three phases.
Protective
Function •Prevent drop-voltage or restriction from rising load.
Stall •Selective function
•Current is over 180% of setting current, trip it 5sec on definite condition

•Prevent damage of motor from rapid load increase.


Lock •Selective function
•Current is over setting current, trip it within 2sec on definite condition

•Prevent the reverse rotation from wiring fault.


Reverse Phase •Selective function
•Trip within 500 msec at the starting time.

•Prevent the leakage current from insulation fault.


Leakage Current •Optional function
•Current is over setting leakage current, trip at the setting time

•Prevent the short circuit from insulation fault of motor and wiring failure.
Short Circuit •Optional function
•Current is over setting rate of operating current, trip within 50 msec.

•Prevent trip from sudden over-currents.


Preliminary Alert 4) •Current is over setting rate of operating current, operate the alarm and alert •Selective function
contact until trip.

•Display accumulated time over 50% of rated current. •RESET is NOT


Accumulated Operating Time
•Display unit: day allowed.

•Certain operating time can be set for motor oil exchange.


Operating Time Alert 4) •Optional function
•At set time, display and alert contact operate.

•Compensate the tolerance of current between motor and relay. Increase the
number of tunnel on the low-current and use the outer CT on the high-current.
CT Ratio
•Compensate the setting current and indication value by CT ratio.
ex) CT ratio should be 20 when 100:5 CT is used.

Delay Time •Immovable time of over-current protection. •Selective function


Hi Series

•Check of relay and sequence without suppling power.


TEST
•On the same condition of 600% current.
51

•Decide the reset method after trip


•Manual reset is
•Manual(non)/Electrical(Pr)/Automatic(0 ~ 20 min) reset can be selected
basic on the reset
RESET - Manual reset is by button
condition of electric
- Electrical reset is by power off
and auto.
- Automatic reset is by setting time

•Curve of over-current protection on the Inverse


- Cold: First operating condition after enough rest
Cold/Hot
- Hot: Consecutive operating condition •On the Inverse only
Curve
•Delay time is over 1: operate for hot curve after delay time
•Delay time off: operate according to hot curve after setting time
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMP

Control & Setting Method

Function of Display Part


MODE button RESET/TEST button SET button
◆ Information indicator shows Current Value, Cause of Trip and
Setting Value
◆ Bar-graph: Displays the load rate
◆ TEST / RESET button Display window
1) Check the trip condition of relay before operating the motor
2) Reset the relay after trip operation
SELECT button
◆ MODE button: Change the mode of function set, current
display and operating time.
Bar-graph
◆ SET button: Records the setting condition
◆ SELECT button
1) Mode of current indication: Displays the current of each phase
and rated setting current.
2) Mode of function setting: Changes the function/setting values
3) Trip condition shows the trip cause and displays the failure
current value.

Before Operating Motor, Set the Function


◆ Check the relay and circuit through TEST & RESET button
1) Check the wiring condition carefully before testing.
2) After pressing the TEST & RESET button, test is displayed on the indicator.
If the current is over 600% of set current, the tripping operation is executed.
3) Press the TEST & RESET button again to reset to the normal condition.
◆ Change the function through the MODE button before setting the function.
※ Set the function by using SELECT and SET button.

No Key Function Default Operating Scope


1 Operating Current 06 Type: 0.5 ~ 6.3 A 60 Type: 5.0 ~63 A
2 Over-current Operating Feature : Inverse, : Definite
3 Over-current Operating Time 1 ~ 30 sec
4 Delay Time / 1 ~ 30 sec
5 Under-current Proportion / 30% ~ 70%
6 Under-current Operating Time 1 ~ 30 sec
7 Stall /
8 Lock / 200% ~ 1000%
9 Negative Phase /
10 Phase Fault /
3)
Electric Leakage Current (optional function) 100 ~ 2500 mA
111) Electric Leakage Operating Time (optional function) 0.1 ~ 10 sec
Short Current Operating Proportion (optional function) / 300% ~ 1800%
2)
12 Pre-alarm Function / 60% ~ 110%
4)
13 CT Ratio 0.2 ~ 240
14 Operating Time Alarm / 10 ~ 9990 hour
15 Reset / / 0 ~ 1200 sec (Manual/Electric/Auto)
1) Leakage and Short Circuit function can not be selected at the same time.
2) Pre-alarm function does not work when Leakage or Short Circuit function is selected.
3) Dip switch setting.
4) The CT ratio of 60 type shall not be changed.(06 type default is 1, and 60 type default is 10.)
CT ratio step: 0.2, 0.5, 1, 2, 5, 10, 15, 16, 20, 24, 26, 30, 32, 36, 40, 44, 48, 50, 60, 80, 100, 120, 126, 150, 160, 200 and 240
1) Display the by pressing the MODE button 4) Setting value is recorded by pressing the ‘SET’ button, and
◆ User can be change the function by pressing the SELECT then the selected function is displayed.
button. ◆ When value of rated current is set-up, is displayed
◆ To return to the current mode, press the MODE button. after setting values recoding.
◆ If users do not need to store the setting value, do not press
the SET button.
Push the MODE button without recording.

Current Indication MODE

2) To change the setting value, display the set value by Current Indication MODE
pressing the SET button.
◆ Setting value is displayed for the rated current( ). 5) If you want to set another function, repeat the above
sequence from 2) to 4) section.
◆ Finish the setting by pressing the MODE button 2 times.

Current Indication MODE

Current Indication MODE


3) Setting value is changed by pressing the SELECT button

Current Indication MODE

Indication on the Current MODE

◆ The max. current is displayed among the


Hi Series

three phases in the normal condition.


R. Current
◆ When the SELECT button is pressed, the
53

value is displayed according to the order


of the diagram. Delay Time S. Current

◆ If any button is not pressed for 5 seconds,


Max. Current
it returns to the normal condition.

Operation Time T. Current

Operating Current
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMP

Control & Setting Method

Information Indication under the Trip Condition


◆ The cause of trip is displayed on the LED.
◆ By pressing the button, user can see the fault current as the sequence below indicates.

Over-Current

Under Current Negative Phase

Stall Earth Leakage


Over-Current Trip

Lock Short Current

Phase Fall

Contact Operation Condition


◆ Alert and trip contact operate simultaneously under the off condition.
If electric leakage current function is included, alert contact is used as the input terminal for ZCT.
Characteristic Curves

Inverse Condition Inverse Condition Inverse Condition

Inverse Condition Inverse Condition Definite Condition

Hi Series
55
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMP

Dimension Drawings

HiMP-D S / HiMP-D SZ / HiMP-D SI Units

58
84 1.6

41
M3.5

111.3
5
73.6

M5
81

M4

43.3
23.3

78.5 9 101

95.6

HiMP-D S / HiMP-D SZ / HiMP-D SI Separation Type

84 1.6 58
M3.5
41

8.9 7.4
90

M5
81
5
73.6

43.3

M4
23.3

78.5 101
95.6

Panel Mounting
< Cutting Size of Panel >
12.5
1.8

20
54

19 55
38

74 1 21.3
HiMP-D T / HiMP-D TZ / HiMP-D TI Units

58

M3.5

84 1.6

8.9 7.4

111.3
5

12
81

M4
22.2

41

78.5

95.6

HiMP-D T / HiMP-D TZ / HiMP-D TI Separation Type

M3.5 58

84 1.6

8.9 7.4
90

12
81
5

M4
22.2

41
78.5

95.6
Hi Series

Panel Mountion
57

< Cutting Size of Panel >


12.5
1.8

20
54

19 55
38

74 1 21.3
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMP

Wiring Diagram

Three Phase Wiring Single Phase Wiring★★

★★★

★★

Inclusing Outer CT


It is recommended to install capacitor near the motor side rather than the line side.
★★
Please turn off the reverse phase function when it is used for single phase motor
★★★
When the electrical leakage current function is included, the AL(07 - 08) contact
shall be used as the input terminal for ZCT.
Zero Current Transformer

L K
k

A
B

G
C
2.5

Type A B C D E F G
E
–ZCT 30
HiMP– 30 75 100 40 80 30 40
–ZCT 50
HiMP– 50 91 130 40 80 30 48
–ZCT 65
HiMP– 65 108 130 40 80 30 56.5
F
6

–ZCT 80
HiMP– 80 123 150 40 130 30 64
12 –ZCT 100
HiMP– 100 140 180 50 160 40 72.5
–ZCT 120
HiMP– 120 160 180 50 160 40 82.5

◆Usage of Ring–Terminal
Use the ring terminal after taking off the protective cover in
main terminal and removing display part on the body.

Hi Series
59

◆Be careful not to mixed with main units and display parts during combining.
Caution

◆When repetitive operation is required, trip operation can be made earlier than setting time.
◆When the electrical leakage current function is included, the AL(07 - 08) contact shall be used as the
input terminal for ZCT.
◆If display parts are seperated, take caution of electrical shock as the protective cover is removed.
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMP

Digital Motor Protection Relay [Standard Type]

Enviromental Influences High Reliability


◆ Ambient Temperature ◆ HiMP standard series provides superior reliability
•Operation : -25~70℃ •Storage : -30~80℃ by the Micro Controller Unit (MCU)

◆ Relative Humidity : 45~85%

Various Protective Features

Protection Function
Model Over Current Phase Reverse Remarks
Unbalance Restriction
Definite Inverse Failure Phase
HiMP22H-PD/SD/TD
HiMP40H-PD/SD/TD ● - ● ● ● -
HiMP50H-PD/SD/TD
2CT
HiMP22H-PI/SI/TI
HiMP40H-PI/SI/TI - ● ● ● ● -
HiMP50H-PI/SI/TI
HiMP22K-PI/SI/TI
HiMP40K-PI/SI/TI - ● ● ● ● -
HiMP50K-PI/SI/TI
3CT
HiMP22K-PN/SN/TN
HiMP40K-PN/SN/TN - ● ● ● ● ●
HiMP50K-PN/SN/TN

- Over Current Protection : Operate according to the inverse or definit characteristic curve
- Phase Failure Protection : Trip 2 seconds when the phase failure rate is over 70%
(If 2CT, just R and T protection is applicable)
- Phase Unbalance Protection : Trip 5 seconds when the phase failure rate is over 50%
(If 2CT, just R and T protection is applicable)
- Restriction Protection : Inverse type is operated according to inverse characteristics
Definit type is operated according to definit characteristics
- Reverse Phase Protection : Trip 0.1 second when the reverse phase

Applicable to the Inverter Control Circuit


◆HiMP standard series have high performance under the harmonic noise, so they can be used for the inverter
control circuit under 20~200 Hz range.

Electron Wave and Noise Tolerance


◆ Completed to EMS test.
◆ Secured from the magnetic field as using troidal CT.
Various Wiring Methods
◆ HiMP standard series can applied to various methods and influences.
◆ Pin Type : Complete combination with HiMC series Magnetic Contactors

HiMP Magnetic Contactor


HiMP22H(K)-P HiMC 9 / HiMC 12 / HiMC 18 / HiMC 22
HiMP40H(K)-P HiMC 32 / HiMC 40
HiMP50H(K)-P HiMC 50

◆ Screw Type

HiMP Max. Rated Current Applied Bolt


HiMP22H(K)-S 22A M4
HiMP40H(K)-S 40A M5
HiMP50H(K)-S 50A M5

◆ Tunnel Type : Using 12mm cable holl

Non Flame Material Various Installation Method


◆ V-0 Class flame material provides maximum ◆ 35mm Din rail mounting is available with
safety against electrical flame. additional mounting bracket (Optional)

Hi Series
61
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMP

Rating and Specification

Definite Inverse Inverse/Reverse Phase


Type HiMP22H/40H/50H HiMP22H/40H/50H HiMP22K/40K/50K HiMP22K/40K/50K
- D- - I- - I- - N-
Number of CT 2CT 2CT 3CT 3CT
Over Current
Phase Failure1)
Function Phase Unbalance1)
Restriction 2)
Reverse Phase 3) - - -
Wiring of Main Circuit P : Pin Type S : Screw Type T : Tunnel Type
03 : 0.3~3 A 01 : 0.3~1.5 A
Allowable HiMP 22 22 : 2.2~22 A 05 : 1.0~5.0 A
Current 22 : 4.4~22 A
Partition HiMP 40 40 : 4.0~40 A 40 : 8~40 A
HiMP 50 50 : 5.0~50 A 50 : 10~50 A
Operation Voltage(50/60 Hz) •110 V : 75~120 % •220 V : 75~120 % •Other Voltage
Over Current Over 112.5 %±5 % - Inverse(cold / hot curve), Definite
Phase Failure Over 70 % of Unbalance Rate
Phase Unbalance Over 50 % of Unbalance Rate
Features
Over 300 % After
Restriction Characteristic Curve
Starting
Reverse Phase - Perception of Reverse Phase
and Sychronous Phase

Over Delay Time Delay Time Setting -


Current
Operating Time 0.2~30 sec 0.2~30 sec(Based on 600 %)
Time Phase Failure 2 sec
Setting
Range Phase Unbalance 5 sec
Restriction After Starting Time Characteristic Curve
Reverse Phase - Within 150 msec
Reset Manual By RESET Button Manually(Not Working During Operation)
Method Electrical By Control Power Off
Test Method By TEST Button(Not Working During Operation)
Current ±5 %
Tolerance
Time ±5 %(or 0.5 sec)
Number 2SPST(1a1b at power on)
Aux. Contact
Capacity 3 A / 250 VAC(Resistance load)
Over Current Capacity Over 20 Times / 2 sec of Max. Operating Current
Insulation Resistance Over 100 MΩ/ 500 VDC
Fast Between Circuit and Frame 2000 VAC / 1 min.
Transient Between Circuits 2000 VAC / 1 min.
Burst Between Contacts 1000 VAC / 1 min.
※ 1) R & T phase can be detected in case of H type(2CT).
2) The restriction follows the characteristic curve.
3) Reverse phase type shall not be applied to single phase
load or inverter load.

Pin Type Screw Type Tunnel Type Combined with Contactor


Functions

Function Description Remark

•Prevent the motor from over current.


Over Current Ref. Cold/Hot curve
•Trip it over 112.5% of setting current and time.

•Prevent the phase failure from line fault and touch.


Phase Failure •Trip 2sec when deviation is over 70% among three phase.
(2CT model is perceived only R and T phase)

•Prevent the phase unbalance from fault of insulation/wring.


Phase
Protection •Trip 5sec when deviation is over 50% among three phase.
Unbalance
(2CT model is perceived only R and T phase)

•Prevent damage of motor from rapid load increase of restriction.


Restriction •The definite is tripped by the rated current over 300% after delay time
at the starting time.

Reverse •Prevent the reverse rotation from wiring fault. Only for
Phase •Trip within 150 sec at the starting time. three phase circuit

•Immovable time of over current protection


•The definite, delayed over current operation at the motor starting time.
Ex) Trip time of the 150% over current Only for
Delay Time
definite characteristics
- Starting : over current operating time X 2
- Normal : trip after over current operating time

•Check of relay and sequence without supplying power. Non trip for load
TEST
•Change to the trip state when you press the test button. operation

•Decide the reset method after trip.


Non trip for load
RESET - Manual reset is by button.
operation
Hi Series

- Electrical reset is by power off.

•Curve of over current protection on the inverse.


63

Cold/Hot - Cold : First operating condition after enough rest.


On the lnverse only
Curve - Hot : Consecutive operating condition.
•Operate according to hot curve after setting time.
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMP

Control and Setting Method(Inverse Characteristics)

Function
◆ LOAD(A) knob : Setting the rated current
◆ O-Time(s) knob : Setting the operaing time for over current
◆ TEST/RESET button
1) Test the trip state of HiMP before motor operation
2) Reset after that the HiMP is tripped
◆ O.C/FAULT LED : Indication operation state for over current,
phase failure and reverse phase

Setting Method
1. Cut the up stream power supply for safety 5. Set the operating current
Set the current by considering the rated current of a motor
2. Check the rated voltage and apply the control power to
to protect from the over current.
A1 and A2 terminal
1) Check if the rated current of a motor is within the current
3. Check the TEST/RESET button operation setting range of an HiMP
1) Check of the wiring is correct (Refer to the wiring diaram) 2) Set the LOAD (Rated current) knob to the maximum
2) When you press the TEST/RESET button, the O.C LED value and then start a motor.
is turned on and the HiMP is tripped. 3) Under normal motor operation, rotate the LOAD knob to
3) When you press the TEST/RESET button under HiMP is the counterclockwise until the O.C LED turned on and off.
tripped, the O.C LED is turned off and HiMP is reset. The current at this point is over 105% rated current.
4) At this point, rotate the LOAD knob to the clockwise until
Caution) For safety, when the motor is operating the TEST/RESET
the O.C LED turned off. The current at this point is rated
button do not work.
current of motor.
4. Set the operating time
The operating time is set on the based on 600% of the rated
current in the characteristic curve by O-time (Operating time) Inverse (t5)
knob.
1) Set the operating time by considering the operating time
and start current according to the types of the load.
(EX: If the start current is 600% of the normal operation
current and the starting is 10 sec, set the time knob
around 11~12sec. with 10~20% margin)
Operating Time (sec)

2) Operate by cold curve at the first operating condition after


that operate by hot curve.
Caution) The HiMP can be tripped to protect the motor when the motor is
started a few times continuously. When a motor is frequently
changing the rotating direction (foward and reverse), set the
operating time longer.

Operating Current Proportion


6. Check the LED operation
- Inverse 2CT : Protection for over current, phase failure, phase unbalance and restriction
- Inverse 3CT : Protection for over current, phase failure, phase unbalance and restriction
- Inverse 3CT/Reverse phase : Protection for over current, phase failure, phase unbalance, restriction and reverse phase

LED Signal
Condition Remark
Red Green

Normal OFF ON

Over Current ON
0.3sec
Preliminary Alert
1) and OFF
interval
OFF
Operation
Phase Failure/ ON
0.3sec
Progress of Phase OFF and
interval
Unbalance. OFF

ON
Progress of 0.6sec
and OFF
Over Current interval
OFF

Over Current Trip ON OFF

Irregular
R-phase ON and 2sec cycle
OFF

Phase
Irregular
Failure/ S-phase
Trip ON and 2sec cycle
Phase (Except 2CT)
OFF
Unbalance

Irregular
T-phase ON and 2sec cycle
OFF
Hi Series

Irregular
Reverse Phase
ON and 1sec cycle
(Only N-Type)
OFF
65

※1) When the current reaches the setting value (105%) over current preliminary alert operate; giving a signal without trip.
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMP

Control and Setting Method(Definite Characteristics)

Function
◆ LOAD(A) knob : Setting the rated current
◆ O-Time(s) knob : Setting the operaing time for over current
◆ TEST/RESET button
1) Test the trip state of HiMP before motor operation
2) Reset after that the HiMP is tripped
◆ O.C/FAULT LED : Indication operation state for over current,
phase failure and restriction

Setting Method
1. Cut the up stream power supply for safety 5. Set the operating current
Set the current by considering the rated current of a motor
2. Check the rated voltage and apply the control power to
to protect from the over current.
A1 and A2 terminal
1) Check if the rated current of a motor is within the current
3. Check the TEST/RESET button operation setting range of an HiMP
1) Check if the wiring is correct (Refer to the wiring diaram) 2) Set the LOAD (Rated current) knob to the maximum
2) When you press the TEST/RESET button, the O.C LED value and then start a motor.
is turned on and the HiMP is tripped. 3) Under normal motor operation, rotate the LOAD knob to
3) When you press the TEST/RESET button under HiMP is the counterclockwise until the O.C LED turned on and off.
tripped, the O.C LED is turned off and the HiMP is reset. The current at this point is over 105% rated current.
4) At this point, rotate the LOAD knob to the clockwise until
Caution) For safety, when the motor is operating the TEST/RESET
the O.C LED turned off. The current at this point is rated
button do not work.
current of motor.
4. Set the operating time
The operating time is operated to the starting time and
Definite Condition
normal operation.
1) Starting : After the operation is automatically delayed by
over current setting time, start operating the over current
portection
2) Normal : The HiMP is tripped after the selected operation
time.
Operating Time (sec)

3) Set the operation time by considering starting current and


starting time according to the load.
EX.) Set the operation time between 6sec and 8sec
Caution) The restriction operates, if the motor starting time comes to
exceed the setting time at over 300% of full load current.
Therefore excessive setting time could result in the failure of
the motor.

Operating Current Proportion


6. Check the LED operation
- Definite 2CT : Protection for over current, phase failure, phase unbalance and restriction

LED Signal
Condition Remark
Red Green

Normal OFF ON

Over Current 0.3sec


Preliminary Alert
1)
ON OFF
interval

Operation
Phase Failure/ ON
0.3sec
Progress of Phase OFF and
interval
Unbalance. OFF

ON
Progress of 0.6sec
and OFF
Over Current interval
OFF

Over Current ON ON

ON
Restriction and ON 3sec cycle
OFF

Irregular
Trip R-phase ON and 2sec cycle
OFF

Phase Irregular
Failure/ S-phase
ON and 2sec cycle
Phase (Except 2CT)
OFF
Unbalance
Irregular
T-phase ON and 2sec cycle
Hi Series

OFF

※1) When the current reaches the setting value (105%) over current preliminary alert operate; giving a signal without trip.
67
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMP

Characteristic Curves

Inverse Condition (t1) Inverse Condition (t5) Inverse Condition (t10)

Inverse Condition (t20) Inverse Condition (t30) Definite Condition


Dimension Drawings

HiMP22K(H)-T/HiMP40K(H)-T/HiMP50K(H)-T

1 60
55 92 44

4.5
30.4
40.8

11.1
4.5

55.8
6-M3.5

70
The bottom dimension of installation braket for
8.2

DIN-RAIL (Addition 5mm height of product)


3- 12.7
26.8
7.2

15.8
29.6
75.4
Fig.1

HiMP22K(H)-S

6-M4
72.4
55

13.4 9.8 16.7


Installation braket for DIN-RAIL
30.4

Fig.2 (Refer to Fig.1 about the dimension not included)


Hi Series

HiMP40K(H)-S/HiMP50K(H)-S

6-M5
69
72.4
52.7

14 12.5 16.7 Installation braket for DIN-RAIL


30.4

Fig.3 (Refer to Fig.1 about the dimension not included)


Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMP

Dimension Drawings

HiMP22K(H)-P

11.3 62.3

20.8
4.6

35

82
52.5

13.4 9.8 16.7


3-M4
30.4
Fig.4 (Refer to Fig.1 about the dimension not included)

HiMP40K(H)-P
14.4 61.6
21.1
4.6

35

82.3
51.5

3-M5 14 12.5 16.7


30.4
Fig.5 (Refer to Fig.1 about the dimension not included)

HiMP50K(H)-P
16.2 24.2 74.1
23.1
4.6

35

84.3
51.5

3-M5 14 12.5 16.7


30.4
Fig.6 (Refer to Fig.1 about the dimension not included)
HiMP-CT80 ~ CT500

180

58 58

75.7
28.4

22.5
15 21 6 49

76 60

Fig.7

HiMP-CT630 ~ CT800

244
82 82 60
111
22

42
4- 7
44

82 2 80
245 100
Hi Series

Fig.8
71
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMP

Wiring Diagram

Three Phase Wiring Single Phase Wiring1)

Inclusing Outer CT

※ 1) 3CT Type (Reverse phase) HiMP can not be used to the single phase motor.
HME

Electronic Motor Protector

EMP(Hyundai electronic motor protector) is a high tech device, which protects motors from damages by
detecting overload and phase loss.

Features

◆Various wiring methods are available for the main line, such as
Pin type, Screw type, and Tunnel type.

◆An EMP can be used as an ampere meter to measure the


actual load current, and can be adjusted up to 103% of actual
load current.

HME-E Series
◆Test function enables the EMP to perform self-operating test
and circuit test.

◆Both 110VAC and 220VAC are applicable on an EMP and


power consumption is optimized by adopting condenser drop
circuit.

◆Control circuit achieves high reliability under the inching and


pulsatory load.

◆Temperature compensating circuit prevents the EMP from


being influenced by ambient temperature.
HME-S Series
◆Large load protection is available through the external current
transformer type.

◆HME-H is the Pin type EMP, so it can be connected to a


magnetic contactor directly. Hi Series
73

HME-H Series
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HME

Electronic Motor Protector

Technical Specification

HME-H Series HME-E Series HME-S Series


Type
05 30 05 30 60 05 30 60
220 V 80 ~ 260 VAC
Control Voltage
440 V 220 ~ 440 VAC
Current Setting Range 05 ~ 6.5 3 ~ 30 0.5 ~ 6.5 3 ~ 30 5 ~ 60 0.5 ~ 6.5 3 ~ 30 5 ~ 60
Time Setting Range Time Delay Not Applicable 0.2 sec ~ 30 sec
(Definite) Operating Time 0.2 sec ~ 15 sec 0.2 sec ~ 10 sec
Manual By pushing RESET button
Reset
Electrical By cut-off control power
TEST By pushing TEST button during setting time
Rated Insulation Voltage 600 VAC
Operation -15℃ ~ 60℃ -10℃ ~ 60℃
Temperature
Ambient Storage -25℃ ~ 75℃ -55℃ ~ 85℃
Humidity 40 ~ 85% RH
1C Contact
Auxiliary Contact
220 VA/5 A(Resistive Load)
Minimum Operating Current 103% of the setting current
Overload 15 times of setting current / Over 8 sec
Power Consumption Less than 1 W
Current ±15% ±10%
Tolerance
Time ±15%
Wiring PIN Screw or Tunnel Tunnel

◆External current transformer type is available for over 60A, and the other specifications are the same with above table.
HME-H 80 HME-E 80 HME-S 80
HME-H 125 HME-E 125 HME-S 125
HME-H 200 HME-E 200 HME-S 200
HME-H 315 HME-E 315 HME-S 315
HME-H 400 HME-E 400 HME-S 400
HME-H 630 HME-E 630 HME-S 630
HME-H 750 HME-E 750 HME-S 750

HME S200
Time and Current Setting

1) Delay time setting (D-Time knob)


This setting applies in HME-S only.
The D-time knob is to be at the expected start time.
If the setting (D-Time) is shorter than appropriate starting time, the relay will be tripped through the
overload indicator and the operation will be delayed during the setting time.

2) Operating time setting (O-Time knob)


The O-Time knob is to be at the expected start time.

3) Current setting (Load knob)


After motor starting the load knob is to be turned in the counter-clockwise direction slowly until the
LED flickers.
This flickering point indicates 100% value of the actual load current. By the load knob, the actual load
current can be measured without an ammeter.

4) The load knob is to be turned in the clockwise direction until the LED light goes out. This point
indicates 103% of the actual load current.

Tripping Curves

Hi Series
75

05 Type: 3 A set 05 Type: 3 A set


60 Type: 30 A set 60 Type: 30 A set
Time setting: 2 sec Time setting: 2 sec

<Fig 1.> <Fig 2.>

<Fig 1.> Example of the tripping. Curves for HME-H05, HME-E60


<Fig 2.> Example of the tripping. Curves for HME-S05, HME-S60
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HME

Relay Wiring Diagram

<Fig 3.> HME-H.E Type <Fig 4.> HME-S Type


In case of HME-H, Tc(95) and L2 are connected.

CT Wiring Diagram

<Fig 5.> <Fig 6.> <Fig 7.>

<Fig 5.> The current range of the CT type EMP is based on one-turn of the main line on the CT.
<Fig 6.> When small load range is required, it is recommened to turn the main line more on the CT.
<Fig 7.> It is recommended to use secondary or additional CT when large load range is requested.
Electronic Motor Protector

HME-H Type

HME-E Type

HME-S Type Hi Series


77
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HME

WARNING

Notice of installation, operation, and maintenance


◆ The product shall be handled with care during all procedures.
◆ Only qualified persons shall carry out all works, and standardized tools shall be used.
◆ Before and during wiring work, the up-steam breaker shall be cut off, and the line shall be
electrically isolated.
◆ The appropriate torque shall be applied during wiring work, and the wiring tightness shall be
checked periodically.
◆ Missed or damaged parts and / or products shall be replaced immediately.
◆ Appropriate frequency, current, and voltage shall be applied to the product.
◆ The product shall be operated after appropriate adjustment work.
◆ The installation condition shall be checked periodically.
◆ Lubricating, vibration, humidity, corrosive gas, and any abnormal condition are prohibited.
◆ Excessively repeating operations shall be avoided.
◆ Dust and external materials shall not get into the product at any time.
If not, electric shock, fire, and / or injury can be resulted.

NOTICE

Notice of transport and storage


◆ The product shall be kept in a packaged condition.
◆ Hand carry is prohibited on the heavy-weighted product.
If not, injury can be resulted.

Safety Notice
◆ This catalog is subject to be up-dated without notice.
◆ Please contact the representative of Hyundai Heavy Industries for further information.
HHIS-WC-LE-B31-02, 2005. 8 Designed by Design Korea
www.hyundai-elec.com

Head Office 1 Jeonha-dong, Dong-gu, Ulsan, Korea


Tel. 82-52-230-8101~8 Fax. 82-52-230-8100
Seoul HYUNDAI B/D, 140-2, Gye-dong, Jongno-gu, Seoul, Korea
(Sales & Marketing) Tel. 82-2-746-7589, 7510, 8474 Fax. 82-2-746-7648
Orlando 3452 Lake Lynda Drive, Suite 110, Orlando, Florida U.S.A. 32817
Tel. 1-407-249-7350 Fax.1-407-275-4940
London 2nd Floor, The Triangle, 5-17 Hammersmith Grove London, W6 0LG, UK
Tel. 44-20-8741-0501 Fax. 44-20-8741-5620
Tokyo 8th Fl., Yurakucho Denki Bldg.1-7-1, Yuraku-cho, Chiyoda-gu, Tokyo, Japan 100-0006
Tel. 81-3-3212-2076, 3215-7159 Fax. 81-3-3211-2093
Cairo Apartment No. 503, 5th Fl., Bldg. No. 7 Block 2, 9th Division, El-nasr Road, New Maadi, Cairo, Egypt
Tel. 20-2-520-0148~9 Fax. 20-2-754-7528
Sofia 41, Rojen Blvd. 1271, Sofia Bulgaria
Tel. 359-2-938-1068, 936-0300 Fax. 359-2-936-0742
Yangzhong Lianzhong Avenue, Xinba Scientific and Technologic Zone, Yangzhong City, Jiangsu Province, China(212-212)
(Jiangsu Hyundai Nanzi Electric Co., Ltd.)
Tel. 86-511-842-0666, 0212 Fax. 86-511-842-0668