model proTECTO 700 1000 1000 1500 2200 2200 3000 3000
ER ER ER
rating
rating in VA 700 1000 1000 1500 2200 2200 3000 3000
rating in W 560 800 800 1200 1760 1760 2400 2400
input
nominal voltage 220 / 230 / 240 V AC
input voltage range at 50% load 140 – 276 V
input voltage range at 100% load 184 – 276 V
input frequency range 50 Hz ± 5% / 60 Hz ± 5%
nominal frequency standard 50 Hz, adjustable by software, 50 Hz, 60 Hz or
auto select
tolerance of frequency ±5%
nominal current in A 3,3 4,5 6 6,5 9,5 13,5 12,5 16
(nominal load and charged capacitors, input
voltage 230 Volt)
maximum input current in A 3,7 5,2 10 7,8 11,2 16 15,5 20
(nominal load, minimum input voltage and
capacitor charging)
inrush current < nominal current
power factor (cos ϕ) > 0,98
harmonical distortion (THDI) 7%
„Hold-Up Zeit“ < 40 ms
(back-up time which can be ralized without
switching on capacitor – no interruption of
the output voltage occures)
model proTECTO 700 1000 1000 1500 2200 2200 3000 3000
ER ER ER
output
output voltage 230 V (adjustable to 220 or 240 V)
tolerance of output voltage - static ± 1,5 %
tolerance of output voltage – dynamic (load 5%
impact 0 to 100%)
voltage reset after dynamic variation < 20 ms
waveform of output voltage sinus
output frequency in normal operation 50 or 60 Hz ± 5 %
rate of frequency adjustment 1 Hz / s
output frequency in capacitor operation 50 or 60 Hz ± 0,2 %
voltage distortion / linear load <2%
voltage distortion / non-linear load <4%
power factor output 0,8
crest factor according to EN 50091-1 til 3:1
(peak current to RMS-current)
efficiency 98 %
(ECO Mode and Smart Active)
overload
overload in normal operation 100 - < 110% about 2 minutes
(afterwards switch over bypass) 110 - < 150% about 4 seconds
> 150% about 1 second
overload in battery operation 100 - < 110 % about 1 minute
(afterwards switch off) 110 - < 150 % about 4 seconds
> 150 % about 0,5 seconds
short-circuit current 3 x I Nenn about 0,5 seconds
bypass
voltage tolerance for switch over 180 – 264 Volt
tolerance of frequency from ± 0,5 Hz til ± 5Hz adjutable
time to switch over 2 ms
battery
nominal voltage 24 V 36 V 36 V 36 V 72 V 72 V 72 V 72 V
number of modules 2 3 * 3 6 * 6 *
nominal capacity per module 7 Ah 7 Ah * 9 Ah 7 Ah * 9 Ah *
type closed and maintenance-free
life duration 3 - 6 years (depending on environmental conditions)
recharge time appr..4 hours
charge current 0,8 A 0,8 A 7 A 0,8 A 0,8 A 8 A 0,8 A 8 A
battery test automatical each 40 hours
* external batteries
model proTECTO 700 1000 1000 1500 2200 2200 3000 3000
ER ER ER
displays
normal operation icon at LCD-display illuminate
battery operation icon at LCD-display illuminate, UPS beeps all 4 seconds
battery discharged icon at LCD-display blinking, UPS beeps 1 time per
second
bypass active icon at LCD-display illuminate
stand by icon at LCD-display illuminate
maintenance necessary icon at display illuminate
load LCD-display
capacitor charge LCD-display
interfaces
Sub-D 9 Pin socket RS 232 interface
USB-Port USB-interface
slot slot for communication plug-in card
connections
input IEC 10 A IEC 16 A
output 4 x IEC 10 A 8 x IEC 10 A 8 x IEC 10 A
+ 1 IEC 16 A
Input fuse (thermal fuse) in A 7 (10 ER-version) 10 12 (16 ER 16 (20 ER
version) version)
DC-connection for battery module no standard no standard
protection
protections over current – short circuit – over voltage - low voltage
heat – deep discharge protection of the batteries
Impuls withstand voltage IEC 801-5 6 KV 1.2 / 50 µsec; 3 KA 8/20 µsec; 300 Joule
environmental conditions
environmental temperature 0 up to 40°C
relative air humidity < 95% non-condensing
noise level in 1 m distance < 40 dB(A)
model proTECTO 700 1000 1000 1500 2200 2200 3000 3000
ER ER ER
cabinet
material sheet steel / front plastics
colour black
protection class IP 20
dimensions
dimensions (H x W x D) in mm 235 x 158 x 422 333 x 190 x 446
weight
weight in kg 11 13,5 7* 15 26 10,6* 28 14*
delivery
manual in german (on CD-ROM) yes
schuko/IEC mains cable 1
IEC/IEC connection cable 2
plug for battery-increase - 1 - 1 - 1
RS232 connection cable 1
USB-cable 1
shutdown-software for Windows 7 / 2008 / yes
Vista / 2003 / XP, Novell and Linux system
on CD-ROM.
options
external service by-pass
manual by-pass switches the load from the
inverter to the mains power supply without
interrupting the output power supply in case
of maintenance
dimensions (H x W x D) in mm 180x300x115
weight in kg 3
SNMP card
NetMan 102 Plus SNMP interface-card X
software
network version of PowerShield³ shutdown-
software for Windows 7 / 2008 / Vista /
2003 / XP, Novell, UNIX and Linux system. X
*external batteries
FRONT VIEW
REAR SIDE
display fan
rear side
model 2200VA
model 3000VA
mains ok timer
communication-ports
On the rear side of the ups you can find the following communication ports:
• RS232-plug
• USB-plug
RS232-interface
RS232-interface
communication-slot