EDS3000 UL User Manual
EDS3000 UL User Manual
Druckschalter
Electronic
Pressure Switch
Manocontacteur
électronique
EDS 3000
D/E/F 18.060.H.4/04.14
Contents 10. Technical specifications
10.1. EDS 3000 with ceramic sensor cell;
1. Functions of the EDS 3000 absolute and relative pressure
1.1. Exclusion of liability ≤ 16 bar
E 2. Mounting 10.2. EDS 3000 with thin film DMS sensor cell;
relative pressure ≥ 40 bar
E
3. Operating keys of the EDS 3000
11. Ordering details
4. Digital display 11.1. EDS 3000 with ceramic sensor cell;
5. Output function absolute and relative pressure
5.1. Switching outputs ≤ 16 bar
.1.1. Switching point setting
5 11.2. EDS 3000 with ceramic sensor cell;
5.1.2. Window function setting absolute and relative pressure
5.2. Analogue output ≤ 16 bar
5.3. Setting the switching points according to DESINA® standard
and hystereses and/or switching 11.3. EDS 3000 with thin film DMS sensor cell;
values for the window function relative pressure ≥ 40 bar
5.4. Setting ranges for 11.4. EDS 3000 with thin film DMS sensor cell;
the switching outputs relative pressure ≥ 40 bar
6. Basic settings according to DESINA® standard
6.1. Altering the basic settings 12. Accessories
6.2. Summary of basic settings 12.1. For electrical connection
7. Programming enable 12.2. for mechanical connection
7.1. Altering the operating 13. Dimensions
programming enable
7.2. Altering the main
programming enable
8. Error messages
9. Wiring diagrams
D/E/F 18.060.H.4/04.14
D/E/F 18.060.H.4/04.14
30 31
1. Functions of the EDS 3000
Depending on the model, the unit offers the following functions:
Measuring value indication of the actual pressure in PSI, MPa, bar or in a
scale defined by the user. Warning:
Display of the maximum value or of a pre-set switching point. The EDS 3000 must be screwed in using a suitable spanner via the pressure
E Switching of the switching outputs according to the pressure and the pre-set
switching parameters.
connection.
If the EDS 3000 is not fitted correctly, e.g. if the housing is turned manually, the E
Analogue output. housing could be damaged, or made completely inoperable, due to the swivel
Menu for basic settings (adapting the EDS 3000 to the particular application). function of the EDS 3000.
Programming enable.
Additional assembly notes which, from experience, reduce the effect of
1.1. Exclusion of liability electromagnetic interference:
This operating manual was made to the best of our knowledge. Nevertheless Make screened connections as short as possible.
and despite the greatest care, it cannot be excluded that mistakes could have Use screened lines (e.g. LIYCY 4 x 0.5 mm²).
crept in. Therefore please understand that in the absence of any provisions The cable screening must be fitted by qualified personnel subject to the
to the contrary hereinafter our warranty and liability – for any legal reasons ambient conditions and with the aim of suppressing interference.
whatsoever – are excluded in respect of the information in this operating Direct proximity to connecting lines of user units or electrical or electronic
manual. In particular, we shall not be liable for lost profit or other financial units causing interference must be avoided as far as possible.
loss. This exclusion of liability does not apply in cases of intent and gross
negligence. Moreover, it does not apply to defects which have been deceitfully
concealed or whose absence has been guaranteed, nor in cases of culpable 3. Operating keys of the EDS 3000
harm to life, physical injury and damage to health. If we negligently breach
any material contractual obligation, our liability shall be limited to foreseeable
damage. Claims due to the Product Liability shall remain unaffected.
Display of the
In the event of translation, only the original version of the operating manual in
pressure unit
German is legally valid.
2. Mounting
The EDS 3000 can be mounted directly onto a hydraulic block via the pressure 4-digit
connection, or indirectly using a hose or Minimess line (for torque values, digital display
see Point 10 - Technical specifications). The unit can be turned through 340°
around its longitudinal axis for optimum alignment. The display and key-pad
can also be turned through 270°.
The electrical connection must be carried out by a qualified electrician
according to the relevant regulations of the country concerned. (VDE 0100 in LED display for
Germany). The pressure switch housing must be earthed correctly at the same active switching
time. When fitting the switch into a hydraulic block it is sufficient if the block is point
earthed via the hydraulic system. In the case of a Minimess hose-mounting, the
D/E/F 18.060.H.4/04.14
D/E/F 18.060.H.4/04.14
housing must be earthed separately (e.g. screened line).
On
If the actual pressure exceeds the nominal pressure of the unit, it can no Lo.1
Lo.1 minus 1% FS Safety zone
Switching value
Switch-back value
longer be displayed and the display begins to flash. Off
Off
Abbreviations:
"hi.1", "hi.2" = High level 1 or 2 = upper switching value 1 or 2
"Lo.1", "Lo.2" = Low level 1 or 2 = lower switching value 1 or 2
FS (Full Scale) = relative to the full measuring range
D/E/F 18.060.H.4/04.14
D/E/F 18.060.H.4/04.14
Note: The window function only operates correctly (switching on and off),
when all switching values (including the safety zone) are greater
than 0 bar and lower than the nominal pressure range.
34 35
5.2. Analogue output 5.4. Setting ranges for switching outputs
Analogue output signal: 4 .. 20 mA or 0 .. 10 V Measuring range Switching point Hysteresis Increment*
(can be set in the menu "basic settings"). in bar in bar in bar in bar
-1 .. 1 - 0.97 .. 1.00 -0.99 .. 0.98 0.01
5.3. Setting the switching points, hystereses and/or 0 .. 1 0.016 .. 1.000 0.006 .. 0.990 0.002
E switching values for the window function
Press "mode" key.
0 .. 2.5 0.040 .. 2.500
0 .. 6 0.09 .. 6.00
0.015 .. 2.475
0.03 .. 5.94
0.005
0.01
E
"S.P.1" or "hi.1" is displayed. 0 .. 10 0.16 .. 10.00 0.06 .. 9.90 0.02
Keep pressing the "mode" key until the required parameter is displayed (for 0 .. 16 0.25 .. 16.00 0.10 .. 15.80 0.05
pre-set switching point function: "S.P.1", "hYS.1", "S.P.2", "hYS.2" appears; 0 .. 40 0.6 .. 40.0 0.2 .. 39.6 0.1
for pre-set window function (WIN) "Hi.1", "Lo.1", "Hi.2" or "Lo.2" is shown). 0 .. 100 1.6 .. 100.0 0.6 .. 99.0 0.2
After 2 seconds the actual setting flashes. 0 .. 250 4.0 .. 250.0 1.5 .. 247.5 0.5
Use the or the keys to alter the setting. 0 .. 400 6 .. 400 2 .. 396 1
Use the "mode" key to call up other parameters, if required, and alter the 0 .. 600 9 .. 600 3 .. 594 1
setting using the and the keys.
If no keys are pressed for 3 seconds, the display changes back and the
settings are saved.
Measuring range Lower switching value Upper switching value Increment*
in bar in bar in bar in bar
-1 .. 1 - 0.97 .. 0.96 -0.95 .. 0.98 0.01
0 .. 1 0.016 .. 0.982 0.024 .. 0.990 0.002
0 .. 2.5 0.040 .. 2.455 0.060 .. 2.475 0.005
0 .. 6 0.09 .. 5.89 0.14 .. 5.94 0.01
0 .. 10 0.16 .. 9.82 0.24 .. 9.90 0.02
display actual
switching
0 .. 16 0.25 .. 15.70 0.40 .. 15.80 0.05
Keep pressing "mode" point 1 setting the switching point 0 .. 40 0.6 .. 39.2 0.9 .. 39.6 0.1
key until the required = Value decreases 0 .. 100 1.6 .. 98.2 2.4 .. 99.0 0.2
parameter is displayed. = Value increases 0 .. 250 4.0 .. 245.5 6.0 .. 247.5 0.5
0 .. 400 6 .. 392 9 .. 396 1
0 .. 600 9 .. 589 14 .. 594 1
* All ranges given in the table are adjustable by the increments shown.
Notes:
If "LOC" appears in the display when trying to alter the settings,
programming is disabled.
Corrective action: set programming enable(s) to "FREE" .
(see point 7 "Programming enables")
If the or the key is held down during alteration, the value automatically
advances.
If a setting has been altered, "PROG" appears briefly in the display when the
D/E/F 18.060.H.4/04.14
D/E/F 18.060.H.4/04.14
display is switched over. The new setting is then saved in the unit.
36 37
6. Basic settings 6.2. Summary of the basic settings
In order to adapt the unit to a particular application, the function of the
EDS 3000 can be altered via several basic settings. These are combined Setting Display Setting Pre-
in a menu. range setting
Switching mode switching output 1 (Sm 1) SP/ Win SP
E 6.1. Altering the basic settings Switching output 1 operates in E
switching point / hysteresis function
Switching output 1 operates in
Important note: window function
when the menu is activated no switching operations are carried out. Switching direction switching output 1 (S 1) ON/OFF ON
N/O function
Switch off supply voltage or disconnect the unit from the supply voltage.
N/C function
Switch-on delay switching output 1 0.00..99.99s 0
(Ton 1)
Time in seconds which must elapse, once
the particular switching point has been
reached or exceeded, before switching will occur.
Switch-off delay switching output 1 0.00..99.99s 0
press "mode" key display press "mode" key
and hold down. (release until required
change setting with or , (Toff 1)
then choose next point in
Switch on supply "mode" menu point appears.
the menu Time in seconds which must elapse, once
voltage (hold key key) Then release the key
down for 3s) (see summary 6.2.) the pressure has fallen below the particular
switch-back point, before switching will occur.
To close the basic setting menu: Switching output 2 is set
Call up the menu point "END", set to "YES", the EDS 3000 returns to the as described above
normal display mode after 2 seconds. Primary display (Primary) ACT/ ACT
Display value which should remain Top/
permanently in the display: S.P.1/
S.P.2/
Note:
If after about 25 seconds no keys have been pressed, the menu actual pressure OFF
automatically closes down. Any changes which may have been made will not pressure peak value
be saved. switching point 1 or 2
or
display off
(for function, see point 4 " digital display")
D/E/F 18.060.H.4/04.14
D/E/F 18.060.H.4/04.14
Reset time (RTIM) 0 .. 300s 0
Indicates how long
the last peak pressure is
shown on the display .
38 39
Setting Display Setting Pre- Setting Display Setting Pre-
range setting range setting
Display filter (Display) SLOW/ MEDI Upper display range (Range High) -899 .. 9899 1000
Display reacts slowly MEDI/ (only in "RANG"="FREE" setting)
to pressure variations FAST Upper display range limit
E Analogue output (Output) MAMP/ MAMP E
Display reacts at standard The analogue output provides VOLT
to pressure variations a 4..20 mA signal
D/E/F 18.060.H.4/04.14
that the EDS 3000 displays.
Lower display range (Range Low) -999 .. 9899 0.0
(only in "RANG" = "FREE" setting)
Lower display range limit
40 41
Setting Display Setting Pre- 7. Programming enable
range setting The unit has 2 types of programming enable which must both be set to "ON"
Version number (Version) to change the settings. The operating programming enable can be set or
Display of the current software version removed during operation. It provides protection from unintentional alteration.
Disabling the programming via the main programming enable means that the
(for reference only).
E To close basic settings (End) YES/NO NO
settings cannot be changed during operation. This serves, for example, as a
safety function or as protection against unauthorised alterations.
E
This closes the basic settings
menu. 7.1. Altering the operating programming enable
Basic settings can still be altered.
If the basic settings have been altered, "ProG" appears briefly when quitting
the basic settings menu, and then the selected display value is shown in the
primary display.
D/E/F 18.060.H.4/04.14
Note:
If a setting has been changed, "PROG" is displayed briefly when the display is
switched over. The new setting is then saved in the unit.
42 43
8. Error messages
If an error is detected, then a corresponding error message appears which 9. Wiring diagrams
must be acknowledged by pressing any key. Possible error messages are as Model with 1 switching output Model with 1 switching output
follows: and 1 analogue output
4-pole plug, M12x1 4-pole plug, M12x1
E E.01 The switching points and hystereses have been set in such a
way that the resulting switch-back point is no longer within the
E
permissible setting range.
EDS 3X46-1 EDS 3X46-3
Example: Analogue
Switching point is set to 180 bar, the hysteresis to 200 bar. Signal
Action: Check all the settings (programming enable, switching points, 4-pole plug, M12x1 5-pole plug, M12x1
switch-back points and basic settings) and correct these if
necessary. If the errors occur frequently, please contact Hydac
Service.
EDS 3X46-2 EDS 3X48-5
E.12 An error has been detected in the stored calibration data.
Analogue
Possible causes are strong electromagnetic interference or
Signal
a component fault.
Action: Disconnect the unit and re-connect. If the error message is still
displayed, the unit must be returned to the manufacturer for
re-calibration or repair. Model to DESINA® standard Model to DESINA® standard
with self monitoring with self monitoring,
E.21 A communication error occurring within the unit has been detected. and 1 switching output 1 switching output
Possible causes are strong electromagnetic interference or a and 1 analogue output
defective component. 5-pole plug, M12x1 5-pole plug, M12x1
Action: Disconnect the unit and re-connect. If the error message continues
to be displayed, please contact our service department.
Analogue
EDS 3X48-1
D/E/F 18.060.H.4/04.14
D/E/F 18.060.H.4/04.14
EDS 3X48-3
Signal
Diagnostic
Signal Diagnostic
Signal
44 45
10. Technical specifications
10.1. EDS 3000 with ceramic sensor cell;
absolute and relative pressure ≤ 16 bar
Input data: DESINA® diagnostic signal (Pin 2)
E Measuring ranges
ceramic sensors absolute pressure 1; 2,5 bar
Function I.O.: HIGH-Pegel / N.I.O: LOW-Pegel
Level HIGH: approx. +UB / LOW: < +0.3 V
E
Overload pressures 3; 8 bar Ambient conditions
Burst pressure 5; 12 bar Compensated temperature range -10 .. +70 °C
Measuring ranges
Operating temperature range -25 .. +80 °C (-25 .. + 60 °C acc. to UL)
ceramic sensors relative pressure -1 .. 1; 1; 2,5; 6; 10; 16 bar
Overload pressures 3; 3; 8; 18; 30; 48 bar Storage temperature range -40 .. +80 °C
Burst pressure 5; 5; 12; 30; 50; 80 bar Fluid temperature range -25 .. +80 °C
Mechanical connection G1/4 A DIN 3852 mark EN 61000-6-1 / 2 / 3 / 4
G1/2 B DIN-EN 837 mark* certificate No. E318391
Threaded port DIN 3852-G1/4 Vibration resistance to ≤ 10 g
Torque value 20 Nm (G1/4); DIN EN 60068-2-6 at 10 .. 500 Hz
45 Nm (G1/2)
Shock resistance to ≤ 50 g
Parts in contact with medium Mech. connection: Stainless steel
DIN EN 60068-2-29 (11 ms)
Sensor cell: Ceramic
Protection class to IEC 60529 IP 67
Seal: copper (G1/2) / FPM / EPDM
(as per model code) Other data
Output data Supply voltage 9 .. 35 V DC without analogue output
Accuracy to DIN 16086, ≤ ± 0.5 % FS typ. 18 .. 35 V DC with analogue output
Max. setting ≤ ± 1 % FS max. when using acc. to UL-specification - limited energy -
(display, analogue output) 9.3 UL 61010; Class 2;
Repeatability ≤ ± 0.25 % FS max. UL 1310/1585; LPS UL 60950
Temperature drift ≤ ± 0.025 % FS / °C max. zero point Current consumption max. 2,455 A total
≤ ± 0.025 % FS / °C max. range max. 35 mA with inaktive switching outputs
max. 55 mA with inaktive switching outputs
Analogue output (optional)
and analogue output
Signal selectable: Display 4-digit, LED, 7 segment, red,
4 .. 20 mA ohmic resistance max. 500 W height of digits 7 mm
0 .. 10 V ohmic resistance min. 1 kW Weight approx. 120g
Switching outputs Note: Reverse polarity protection of the supply voltage, excess voltage,
Type PNP transistor output override, short circuit protection are provided.
D/E/F 18.060.H.4/04.14
D/E/F 18.060.H.4/04.14
Switching current max. 1.2 A FS (Full Scale) = relative to the complete measuring range
* Envir. conditions to 1.4.2 UL 61010-1; C22.2 No 61010-1
Switching cycles > 100 million
Reaction time < 10 ms
Long-term drift ≤ ± 0.3 % FS typ. / year
46 47
10.2. EDS 3000 with thin film DMS sensor cell;
relative pressure ≥ 40 bar
Input data Ambient conditions
E Measuring ranges
Overload pressures
40; 100; 250; 400; 600 bar
80; 200; 500; 800; 1000; bar
Compensated temperature range
Operating temperature range
-10 .. +70 °C
-25 .. +80 °C (-25 .. + 60 °C acc. to UL)
E
Burst pressure 200; 500; 1000; 2000; 2000 bar Storage temperature range -40 .. +80 °C
Mechanical connection G1/4 A DIN 3852 Fluid temperature range -25 .. +80 °C
Threaded port DIN 3852-G1/4 mark EN 61000-6-1 / 2 / 3 / 4
Torque value 20 Nm mark* Certificate No. E318391
Parts in contact with medium Mech. connection: Stainless steel Vibration resistance to ≤ 10 g
Seal: FPM (G 1/4 A DIN 3852) DIN EN 60068-2-6 at 10 .. 500 Hz
Output data Shock resistance to ≤ 50 g
Accuracy to DIN 16086, ≤ ± 0.5 % FS typ. DIN EN 60068-2-29 (11 ms)
Max. setting ≤ ± 1 % FS max. Protection class to IEC 60529 IP 67
(display, analogue output) Other data
Repeatability ≤ ± 0.25 % FS max. Supply voltage 9 .. 35 V DC without analogue output
Temperature drift ≤ ± 0.025 % FS / °C max. zero point 18 .. 35 V DC with analogue output
≤ ± 0.025 % FS / °C max. range when using acc. to UL-specification - limited energy -
9.3 UL 61010; Class 2;
Analogue output (optional)
UL 1310/1585; LPS UL 60950
Signal selectable: Current consumption max. 2,455 A total
4 .. 20 mA ohmic resistance max. 500 W max. 35 mA with inaktive switching outputs
0 .. 10 V ohmic resistance min. 1 kW max. 55 mA with inaktive switching outputs
Switching outputs and analogue output
Type PNP transistor output Display 4-digit, LED, 7 segment, red,
Switching current max. 1.2 A height of digits 7 mm
Switching cycles > 100 million Weight approx. 120g
Reaction time < 10 ms Note: Reverse polarity protection of the supply voltage, excess voltage,
override, short circuit protection are provided.
Long-term drift ≤ ± 0.3 % FS typ. / year
FS (Full Scale) = relative to the complete measuring range
DESINA® diagnostic signal (Pin 2) * Envir. conditions to 1.4.2 UL 61010-1; C22.2 No 61010-1
Function I.O.: HIGH-Pegel / N.I.O: LOW-Pegel
Level HIGH: approx. +UB / LOW: < +0.3 V
D/E/F 18.060.H.4/04.14
D/E/F 18.060.H.4/04.14
48 49
11. Model codes (also order codes)
11.1. EDS 3000 with ceramic sensor cell; 11.2. EDS 3000 with ceramic sensor cell;
absolute and relative pressure ≤ 16 bar absolute and relative pressure ≤ 16 bar
according to DESINA® standard
E EDS 3 X X X - X - XXXX - XXX - X X
EDS 3 X X 8 - X - XXXX - D00 - X X
E
Model (technology)
1 = ceramic absolute Model (technology)
3 = ceramic relative 1 = ceramic absolute
Type of connection, mechanical 3 = ceramic relative
1 = G 1/2 B DIN-EN 837 male thread
4 = G 1/4 A male thread Type of connection, mechanical
9 = G 1/4 female thread to DIN 3852 1 = G 1/2 B DIN-EN 837 male thread
4 = G 1/4 A male thread
Type of connection, electrical 9 = G 1/4 female thread to DIN 3852
6 = 4-pole plug M12x1
only possible on output models Type of connection, electrical
"1", "2" and "3" 8 = 5-pole plug M12x1
(connector not included) (connector not included)
8 = 5-pole plug M12x1
Output
only possible on output model "5" 1 = 1 switching output
(connector not included) 3 = 1 switching output and 1 analogue output
Output
1 = 1 switching output (only in conjunction Pressure ranges in bar
with electrical connection type "6") Type 1 (ceramic absolute)
2 = 2 switching outputs (only in conjunction 0001; 02.5
with electrical connection type "6") Type 3 (ceramic relative)
3 = 1 switching output and 1 analogue output (only in 0001 (-1 .. 1 bar); 01.0; 02.5; 06.0; 0010; 0016
conjunction with electrical connection type "6")
5 = 2 switching outputs and 1 analogue output (only Modification number
in conjunction with electrical connection type "8") D00 = pin configuration conforms to DESINA® standard
with self-monitoring
Pressure ranges in bar
Type 1 (ceramic absolute) Material of seal (in contact with medium)
0001; 02.5 F = FPM seal (e.g. for hydraulic oils)
Type 3 (ceramic relative) E = EPDM seal (e.g. for water, refrigerants)
0001 (-1 .. 1 bar); 01.0; 02.5; 06.0; 0010; 0016
Connection material (in contact with medium)
Modification number 1 = stainless steel
000 = standard (determined by manufacturer)
Material of seal (in contact with medium)
D/E/F 18.060.H.4/04.14
D/E/F 18.060.H.4/04.14
F = FPM seal (e.g. for hydraulic oils)
E = EPDM seal (e.g. for water, refrigerants)
Connection material (in contact with medium)
1 = stainless steel
50 51
11.3. EDS 3000 with Thin film dms sensor cell; 11.4. EDS 3000 with thin-film DMS sensor cell;
relative pressure ≥ 40 bar relative pressure ≥ 40 bar
according to DESINA® standard
E EDS 3 4 X X - X - XXXX - XXX
EDS 3 4 X 8 - X - XXXX - D00
E
Model (technology)
4 = thin-film DMS, relative Model (technology)
Type of connection, mechanical 4 = thin-film DMS, relative
4 = G 1/4 A male thread Type of connection, mechanical
9 = G 1/4 female thread to DIN 3852 4 = G 1/4 A male thread
9 = G 1/4 female thread to DIN 3852
Type of connection, electrical
6 = 4-pole plug M12x1 Type of connection, electrical
only possible on output models 8 = 5-pole plug M12x1
"1", "2" and "3" (connector not included)
(connector not included)
8 = 5-pole plug M12x1 Output
only possible on output model "5" 1 = 1 switching output
(connector not included) 3 = 1 switching output and 1 analogue output
Output Pressure ranges in bar
1 = 1 switching output 016, 040, 100, 250, 400, 600
(only in conjunction with electrical connection type "6")
2 = 2 switching outputs (only in conjunction Modification number
with electrical connection type "6") D00 = pin configuration conforms to DESINA® standard
3 = 1 switching output and 1 analogue output with self-monitoring
(only in conjunction with electrical connection type "6")
5 = 2 switching outputs and 1 analogue output
(only in conjunction with electrical connection type "8")
Pressure ranges in bar
016, 040, 100, 250, 400, 600
Modification number
000 = standard (determined by manufacturer)
D/E/F 18.060.H.4/04.14
D/E/F 18.060.H.4/04.14
52 53
12. Accessories
12.1. Electrical connection 12.2. mechanical Connection
12.1.1. For output models "1", "2" and "3"
Colour coding:
Pin 1: brown
Pin 2: white
Pin 3: blue
Pin 4: black
ZBM 3100
Screw clamp for wall-mounting the EDS 3000, including rear weld plate
order no.: 3184632
12.1.2. For all output models and DESINA® model with self-monitoring
D/E/F 18.060.H.4/04.14
Pin 3: blue
Pin 4: black
Pin 5: grey
54 55
13. Dimensions
E E
6hex-SW27
Copper seal
FPM-/EPDM seal
Diameter
NOTE:
D/E/F 18.060.H.4/04.14
D/E/F 18.060.H.4/04.14
The information in this brochure relates to the operating conditions
and applications described.
For applications or operating conditions not described, please
contact the relevant technical department.
Subject to technical modifications.