RTU560

Remote Terminal Unit

Subdevice Communication Interface


IEC 60870-5-104

Contents: This manual gives an overview of the RTU560


Subdevice Communication Interface IEC 60870-5-104
protocol
RTU560 Subdevice Communication Interface IEC 60870-5-104 Revision

Revision

Document identity: 1KGT 150 519 V001 1

Revision: 0 Date: 2002-03-26


Basic document

Revision: 1 Date: 2002-12-10


- Chapter `Filetransfer´ updated
- Chapter `Transparent Data´ added
- (Available with firmware Release 6)

We reserve all rights in this document and in the information contained therein.
Reproduction, use or disclosure to third parties without express authority is strictly
forbidden.

© Copyright 2002 ABB Utilities GmbH.

ABB Utilities GmbH 1KGT 150 519 V001 1 iii


RTU560 Subdevice Communication Interface IEC 60870-5-104 Contents

Contents

SUBDEVICE COMMUNICATION INTERFACE IEC 60870-5-104

REVISION.................................................................................................. III

CONTENTS............................................................................................... V

ABBREVIATIONS ....................................................................................VII

INTRODUCTION ...................................................................................... IX
Preface ...................................................................................................................ix
References .............................................................................................................ix
Conventions............................................................................................................ix

1 PHYSICAL LAYER...........................................................................1-1

2 LINK LAYER ....................................................................................2-1


2.1 General ................................................................................................... 2-1

3 APPLICATION LAYER.....................................................................3-1

4 ADDRESSING ..................................................................................4-1

5 DATA TYPES – MONITORING DIRECTION ...................................5-1


5.1 SPI – Single Point Information................................................................. 5-1
5.2 DPI – Double Point Information ............................................................... 5-2
5.3 STI – Step Position Information ............................................................... 5-3
5.4 BSI – Bit String Information ..................................................................... 5-4
5.5 ITI – Integrated Total Information............................................................. 5-5
5.6 DMI – Digital Measured Information......................................................... 5-6
5.7 AMI – Analog Measured Information........................................................ 5-7
5.8 MFI – Measured Float Information ........................................................... 5-9

6 DATA TYPES – CONTROL DIRECTION.........................................6-1


6.1 SCO – Single Command Output .............................................................. 6-1
6.2 DCO – Double Command Output............................................................. 6-2
6.3 RCO – Regulation Command Output ....................................................... 6-3
6.4 ASO – Analog Setpoint Output ................................................................ 6-4
6.5 DSO – Digital Setpoint Output ................................................................. 6-5
6.6 BSO – Bit String Output........................................................................... 6-6
6.7 Read Command ...................................................................................... 6-7

ABB Utilities GmbH 1KGT 150 519 V001 1 v


Contents RTU560 Subdevice Communication Interface IEC 60870-5-104

7 FILE TRANSFER............................................................................. 7-1


7.1 Download ................................................................................................ 7-2
7.2 Upload..................................................................................................... 7-2

8 TRANSPARENT DATA ................................................................... 7-1


8.1 Transparent Data Channel....................................................................... 7-1
8.2 Command Direction................................................................................. 7-1
8.2.1 Monitoring Direction .................................................................... 7-3
8.2.2 Request procedure ...................................................................... 7-4
8.3 Encapsulated SPABUS messages........................................................... 7-5
8.3.1 General ....................................................................................... 7-5
8.3.2 Request procedure ...................................................................... 7-6

9 TIME SYNCHRONIZATION ............................................................. 9-1

10 GENERAL INTERROGATION....................................................... 10-1

11 SYSTEM EVENTS ......................................................................... 11-1

12 STATUS CHANGE ........................................................................ 12-1


12.1 Offline to Online .....................................................................................12-1
12.2 Online to Offline .....................................................................................12-1

13 INTEROPERABILITY LIST............................................................ 13-1


13.1 Network configuration .............................................................................13-2
13.2 Physical layer .........................................................................................13-2
13.3 Link layer................................................................................................13-3
13.4 Application Layer....................................................................................13-3
13.5 Basic application functions .....................................................................13-6

vi 1KGT 150 519 V001 1 ABB Utilities GmbH


RTU560 Subdevice Communication Interface IEC 60870-5-104 Abbreviations

Abbreviations

CMU Communication and Data Processing Unit

AMI Analog Measured value Input

ASO Analog Setpoint command Output

BCU Bus Connection Unit

BSI Bit String Input (8, 16 bit)

CS Control System

CSC Command Supervision Channel

CS-Command Clock Synch Command

DCO Double Command Output

DMI Digital Measured value Input (8, 16 bit)

DPI Double Point Input

DSO Digital Setpoint command Output (8, 16 bit)

EPI Event of Protection equipment Input (1bit)

GCD General Configuration Data

HCI Host Communication Interface

IED Intelligent Electronic Device

IOC I/O Controller (Controller on I/O Board)

IOD Input Output Data

IOM I/O Bus Master (Function of SLC)

ITI Integrated Totals Input

MFI Analog Measured value Floating Input

MPU Main Processing Unit

NCC Network Control Center

PB Peripheral Bus

PBP Peripheral Bus Processor

ABB Utilities GmbH 1KGT 150 519 V001 1 vii


Abbreviations RTU560 Subdevice Communication Interface IEC 60870-5-104

PDP Process Data Processing

PLC Programmable Logic Control

PPP Point to Point Protocol

PSU Power Supply Unit

RCO Regulation step Command Output

RTC Real Time Clock

SBO Select before Operate

SCADA Supervision, Control and Data Acquisition

SCI Sub-Device Communication Interface

SCO Single Command Output

SEV System Events

SLC Serial Line Controller

SOC Strobe Output Channel

SPI Single Point Input

STI Step position Input (8 bit)

TSI Time Synch Input

TSO Time Synch Output

viii 1KGT 150 519 V001 1 ABB Utilities GmbH


RTU560 Subdevice Communication Interface IEC 60870-5-104 Introduction

Introduction

Preface
This document describes the functions of the subdevice interface in RTU560 according
to IEC 60870-5-104

References
[1] Telecontrol equipment and systems - Part 5-104
Transmission protocols -
Network access for IEC60870-5-101
using standard transport profiles First edition 12-2000

Conventions
In this document function codes of data types according to IEC 60870-5-104 are marked
with angel brackets:

<Function code>

Italic fonts with the heading Parameter are references to configuration parameter in
RTUtil NT. The parameter is followed by definitions in round brackets where to find this
parameter in RTUtil NT.

Example:

Parameter: Link address (RTU560 – Line parameter)

In this document references to elements of the standard will be printed bold and in
brackets: [1]

The tables in the next chapters include lists of functions, options and message types
supported according to the protocol structure given in IEC 60870-5 (EPA three layer
model) for
• the physical layer
• the link layer
• the application layer
This layered model is valid for the protocol [1].

ABB Utilities GmbH 1KGT 150 519 V001 1 ix


1 Physical Layer

The transmission speeds in control and in monitor direction is fixed 10 MBit/sec.

Possible communication interfaces are:

• Ethernet Interface on 560ETH02/03


• Ethernet Interface on RTU560E (560CMU80)

ABB Utilities GmbH 1KGT 150 519 V001 1 1-1


2 Link Layer

2.1 General

For each Ethernet connection an slave IP-Address is necessary for the 560ETH02/03.

Parameter: Slave IP-Address (RTU560 – Interface parameter)

Protection against loss and duplication of message is handled like defined in


[1]

The selectable parameter have to be calculated regarding the real communication


technology. All parameter preset to the default values from [1].
Option / Parameter Range of Values / Explanations Default
Send or test APDUs (t1) 1 to 255 seconds 15s
Acknowledge no data 1 to 255 seconds 10s
message (t2)
Sending test frames (t3) 1 to 255 seconds 30s
Timeout of 1 to 255 seconds 30s
connection establishment (t0)
Maximum difference receive 1-32767 12
sequence number (k)
Latest acknowledge after 1-32767 8
number of I format (w) w must not exceed 2/3 of k
ASDU address structure Structure of the ASDU address field 16
Information object address Structure of the information object address field 24
structure
Time internal of clock 60 ... 65000 s 300 s
synchronization commands

Table 2-1: Line Parameter - IEC 60870-5-104

ABB Utilities GmbH 1KGT 150 519 V001 1 2-1


3 Application Layer

Overview on type identifications for data elements of the application layer defined in [1].

The column RTU560 Type shows the type of data with must be configured in RTUtil NT.
ASDUs Description Functio RTU560
n Code Types
M_SP_NA_1 Single-point information 1 SPI
M_SP_TB_1 Single-point information with time tag CP56Time2a 30 SPI
M_PS_NA_1 Packed single-point information with status change 20 SPI
detection
M_DP_NA_1 Double-Point information 3 DPI
M_DP_TB_1 Double-Point information with time tag CP56Time2a 31 DPI
M_ST_NA_1 Step position information 5 STI
M_ST_TB_1 Step position information with time tag CP56Time2a 32 STI
M_BO_NA_1 Bitstring of 32 bit 7 BSI8/16/32
M_BO_TB_1 Bitstring of 32 bit with time tag CP56Time2a 33 BSI8/16/32
M_ME_NA_1 Measured value, normalized value 9 AMI
DMI8/16
M_ME_TD_1 Measured value, normalized value with time tag 34 AMI
CP56Time2a DMI8/16
M_ME_NB_1 Measured value, scaled value 11 AMI
M_ME_TE_1 Measured value, scaled value with time tag 35 AMI
CP56Time2a
M_ME_NC_1 Measured value, short floating point 13 MFI
M_ME_TF_1 Measured value, short floating point value with time 36 MFI
tag CP56Time2a
M_IT_NA_1 Integrated totals 15 ITI
M_IT_TB_1 Integrated totals with time tag CP56Time2a 37 ITI

Table 3-1: Table of ASDU in monitoring direction

ABB Utilities GmbH 1KGT 150 519 V001 1 3-1


Application Layer RTU560 Subdevice Communication Interface IEC 60870-5-104

ASDUs Description Function RTU560 Types


Code
C_SC_NA_1 Single command 45 SCO
C_DC_NA_1 Double command 46 DCO
C_RC_NA_1 Regulation step command 47 RCO
C_SE_NA_1 Set point command, normalized value 48 ASO
DSO8/16
C_SE_NB_1 Set point command, scaled value 49 ASO
C_BO_NA_1 Bitstring of 32 bit 51 BSO1/2/8/16/32

Table 3-2: Table of ASDU in control direction

3-2 1KGT 150 519 V001 1 ABB Utilities GmbH


4 Addressing

Selection according to [1]. The sizes of the addressing fields has following size:
Option / Parameter Set value of IEC 60870-5-104
Common address ASDU 2 octets
length
Information object address 3 octets
length
Cause of transmission length 2 octet

Table 4-1: Address elements

ABB Utilities GmbH 1KGT 150 519 V001 1 4-1


5 Data Types – Monitoring Direction

5.1 SPI – Single Point Information

Binary process information indicated by one bit:


Supported M_SP_NA_1 <1> without timestamp
Data Types Parameter:
Transmit with timestamp (SPI- Protocol Address and Parameter)

M_SP_TB_1 <30> with timestamp CP56Time2a


Parameter:
Transmit with full timestamp (Line- IEC 60870-5-104)
Additional
Readable by a read command (see 6.7)
Parameter:
Sub parameter – Read Command (Line- IEC 60870-5-104)

Packed Single Format <20>


It is possible to configure packed single format <20>. With the parameter
Position the bit position within an packed single format could be configured.
This value is extracted from the telegram and send as normal SPI to the
internal communication. The numbering of the bit position starts with 1.
For a normal SPI the parameter Position has no effect.
Parameter:
Sub parameter – Position (Line- IEC 60870-5-104)

Conversion of value

RTU560 internal communication Protocol specific


off 0
on 1

Conversion of quality descriptors

RTU560 internal communication Protocol specific


BL Blocked Blocked
SB Substituted Substituted
NT Not Topical Not Topical
IV Invalid Invalid

Conversion of cause of transmission

RTU560 internal communication Protocol specific


T Test Test
P/N Positive/negative confirmation - Irrelevant -
Cause Spontaneous 3 - spontaneous
Requested 5 - requested
Interrogated 20 - interrogated

ABB Utilities GmbH 1KGT 150 519 V001 1 5-1


Data Types – Monitoring Direction RTU560 Subdevice Communication Interface IEC 60870-5-104

5.2 DPI – Double Point Information

Binary process information indicated by two bits.


Supported M_DP_NA_1 <3> without timestamp
Data Types Parameter:
Transmit with timestamp (DPI- Protocol Address and Parameter)

M_DP_TB_1 <31> with timestamp CP56Time2a


Parameter:
Transmit with full timestamp (Line- IEC 60870-5-104)
Additional Readable by a read command (see 6.7)
Parameter:
Sub parameter – Read Command (Line- IEC 60870-5-104)

Conversion of value

RTU560 internal communication Protocol specific


intermediate 0
off 1
on 2
indeterminate 3

Conversion of quality descriptors

RTU560 internal communication Protocol specific


BL Blocked Blocked
SB Substituted Substituted
NT Not Topical Not Topical
IV Invalid Invalid

Conversion of cause of transmission

RTU560 internal communication Protocol specific


T Test Test
P/N Positive/negative confirmation - Irrelevant -
Cause Spontaneous 3 - spontaneous
Requested 5 - requested
Interrogated 20 - interrogated

5-2 1KGT 150 519 V001 1 ABB Utilities GmbH


RTU560 Subdevice Communication Interface IEC 60870-5-104 Data Types – Monitoring Direction

5.3 STI – Step Position Information

Binary process information indicated by 8 bit.


Supported M_ST_NA_1 <5> without timestamp
Data Types Parameter:
Transmit with timestamp (STI- Protocol Address and Parameter)

M_ST_TB_1 <32> with timestamp CP56Time2a


Parameter:
Transmit with full timestamp (Line- IEC 60870-5-104)
Additional Readable by a read command (see 6.7)
Parameter:
Sub parameter – Read Command (Line- IEC 60870-5-104)

Conversion of value

RTU560 internal communication Protocol specific


Range min. -64 -64
... ...
Range max. +63 +63

Conversion of quality descriptors

RTU560 internal communication Protocol specific


OV Overflow Overflow
BL Blocked Blocked
SB Substituted Substituted
NT Not Topical Not Topical
IV Invalid Invalid
T Transient Bit Transient Bit

Conversion of cause of transmission

RTU560 internal communication Protocol specific


T Test Test
P/N Positive/negative confirmation - Irrelevant -
Cause Spontaneous 3 - spontaneous
Requested 5 - requested
Interrogated 20 - interrogated

ABB Utilities GmbH 1KGT 150 519 V001 1 5-3


Data Types – Monitoring Direction RTU560 Subdevice Communication Interface IEC 60870-5-104

5.4 BSI – Bit String Information

Binary process information indicated by 8, 16 or 32 bit.


Supported M_BO_NA_1 <7> without timestamp
Data Types Parameter:
Transmit with timestamp (BSI- Protocol Address and Parameter)

M_BO_TB_1 <33> with timestamp CP56Time2a


Parameter:
Transmit with full timestamp (Line- IEC 60870-5-104)
Additional Readable by a read command (see 6.7)
Parameter:
Sub parameter – Read Command (Line- IEC 60870-5-104)

Conversion of value

RTU560 internal communication Protocol specific


Range min. 0 0
... ...
Range max. BSI8: Bit mask of 8 bit; 255
range ... 255
BSI16: Bit mask of 16 bit; 65535
range ... 65535
BSI32: Bit mask of 32 bit; 4294967295
range ... 4294967295

Conversion of quality descriptors

RTU560 internal communication Protocol specific


OV Overflow Overflow
BL Blocked Blocked
SB Substituted Substituted
NT Not Topical Not Topical
IV Invalid Invalid

Conversion of cause of transmission

RTU560 internal communication Protocol specific


T Test Test
P/N Positive/negative confirmation - Irrelevant -
Cause Spontaneous 3 - spontaneous
Requested 5 - requested
Interrogated 20 - interrogated

5-4 1KGT 150 519 V001 1 ABB Utilities GmbH


RTU560 Subdevice Communication Interface IEC 60870-5-104 Data Types – Monitoring Direction

5.5 ITI – Integrated Total Information

Binary process information indicated by 32 bit as a countered value.


Supported M_IT_NA_1 <15> without timestamp
Data Types Parameter:
Transmit with timestamp (ITI- Protocol Address and Parameter)

M_IT_TB_1 <37> with timestamp CP56Time2a


Parameter:
Transmit with full timestamp (Line- IEC 60870-5-104)
Additional Readable by a read command (see 6.7)
Parameter:
Sub parameter – Read Command (Line- IEC 60870-5-104)

Conversion of value

RTU560 internal communication Protocol specific


Range min. 0 0
... ...
Range max. 4294967295 4294967295

Conversion of quality descriptors

RTU560 internal communication Protocol specific


SEQ Sequence number Sequence number
CY Carry Carry
CA Adjusted Adjusted
IV Invalid Invalid

Conversion of cause of transmission

RTU560 internal communication Protocol specific


T Test Test
P/N Positive/negative confirmation - Irrelevant -
Cause Spontaneous 3 - spontaneous
Requested 5 - requested
Interrogated 20 - interrogated

ABB Utilities GmbH 1KGT 150 519 V001 1 5-5


Data Types – Monitoring Direction RTU560 Subdevice Communication Interface IEC 60870-5-104

5.6 DMI – Digital Measured Information

Binary process information indicated by 8 or 16 bit used as a measured value from


digital inputs in normalized format.
Supported M_ME_NA_1 <9> without timestamp
Data Types Parameter:
Transmit with timestamp (DMI- Protocol Address and Parameter)

M_ME_TD_1 <34> with timestamp CP56Time2a


Parameter:
Transmit with full timestamp (Line- IEC 60870-5-104)
Additional Readable by a read command (see 6.7)
Parameter:
Sub parameter – Read Command (Line- IEC 60870-5-104)

Conversion of value

RTU560 internal communication Protocol specific


Range min. -100% -1
... ...
Range max. +100% +1-2-15

Conversion of quality descriptors

RTU560 internal communication Protocol specific


OV Overflow Overflow
BL Blocked Blocked
SB Substituted Substituted
NT Not Topical Not Topical
IV Invalid Invalid

Conversion of cause of transmission

RTU560 internal communication Protocol specific


T Test Test
P/N Positive/negative confirmation - Irrelevant -
Cause Spontaneous 3 - spontaneous
Requested 5 - requested
Interrogated 20 - interrogated

5-6 1KGT 150 519 V001 1 ABB Utilities GmbH


RTU560 Subdevice Communication Interface IEC 60870-5-104 Data Types – Monitoring Direction

5.7 AMI – Analog Measured Information

Analog process information used as a measured value from analog inputs in normalized
or scaled format.
Supported M_ME_NA_1 <9> normalized without timestamp
Data Types Parameter:
Transmit with timestamp
Transmission format
(AMI- Protocol Address and Parameter)

M_ME_NB_1 <11> scaled without timestamp


Parameter:
Transmit with timestamp
Transmission format
(AMI- Protocol Address and Parameter)

M_ME_TD_1 <34> normalized with timestamp CP56Time2a


Parameter:
Transmission format
(AMI- Protocol Address and Parameter)
Transmit with full timestamp
(Line- IEC 60870-5-104)

M_ME_TE_1 <35> scaled with timestamp CP56Time2a


Parameter:
Transmission format
(AMI- Protocol Address and Parameter)
Transmit with full timestamp
(Line- IEC 60870-5-104)
Additional Maximum Value
Maximum Value in the external protocol to be converted to +100 % on
RTU560 internal communication.
Parameter:
Maximum Value (AMI – Protocol Address and Parameter)

Minimum Value
Minimum Value in the external protocol to be converted to -100 % on
RTU560 internal communication.
Parameter:
Minimum Value (AMI- Protocol Address and Parameter)

Decimal Factor
<Not supported yet>

Engineering Unit
<Not supported yet>

Readable by a read command (see 6.7)


Parameter:
Sub parameter – Read Command (Line- IEC 60870-5-104)

ABB Utilities GmbH 1KGT 150 519 V001 1 5-7


Data Types – Monitoring Direction RTU560 Subdevice Communication Interface IEC 60870-5-104

Conversion of value

RTU560 internal communication Protocol specific


Range min. -100% Normalized : -1
Scaled : -32768
... ...
Range max. +100% Normalized : +1-2-15
Scaled : +32767

Conversion of quality descriptors

RTU560 internal communication Protocol specific


OV Overflow Overflow
BL Blocked Blocked
SB Substituted Substituted
NT Not Topical Not Topical
IV Invalid Invalid

Conversion of cause of transmission

RTU560 internal communication Protocol specific


T Test Test
P/N Positive/negative confirmation - Irrelevant -
Cause Periodic / Cyclic 1 - Periodic / Cyclic
Spontaneous 3 - spontaneous
Requested 5 - requested
Interrogated 20 - interrogated

Scaling of Measurands, Subdevice Communication Interface

100 % Overflow
Value on internal
communication

Example:
Maximum Value = 1000
Minimum Value = -1000
Measured Value,
External Protocol

- Range - 1000 1000 + Range


(Minimum Value) (Maximum Value)

Overflow - 100 %

5-8 1KGT 150 519 V001 1 ABB Utilities GmbH


RTU560 Subdevice Communication Interface IEC 60870-5-104 Data Types – Monitoring Direction

5.8 MFI – Measured Float Information

Analog process information indicated by 32 bit used as a measured value from analog
inputs in float format.
Supported M_ME_NC_1 <13> without timestamp
Data Types Parameter:
Transmit with timestamp (MFI- Protocol Address and Parameter)

M_ME_TF_1 <36> with timestamp CP56Time2a


Parameter:
Transmit with full timestamp (Line- IEC 60870-5-104)
Values R32-IEEE STD 754
Additional Readable by a read command (see 6.7)
Parameter:
Sub parameter – Read Command (Line- IEC 60870-5-104)

Conversion of value

RTU560 internal communication Protocol specific


Range min. -3.4s1038 -3.4s1038
...
Range max. + 3.4s1038 + 3.4s1038

Conversion of quality descriptors

RTU560 internal communication Protocol specific


OV Overflow Overflow
BL Blocked Blocked
SB Substituted Substituted
NT Not Topical Not Topical
IV Invalid Invalid

Conversion of cause of transmission

RTU560 internal communication Protocol specific


T Test Test
P/N Positive/negative confirmation - Irrelevant -
Cause Periodic / Cyclic 1 - Periodic / Cyclic
Spontaneous 3 - spontaneous
Requested 5 - requested
Interrogated 20 - interrogated

ABB Utilities GmbH 1KGT 150 519 V001 1 5-9


6 Data Types – Control Direction

6.1 SCO – Single Command Output

Binary process command (one bit)


Supported C_CS_NA_1 <45>
Data Types
Command None
Authority
Additional None

Conversion of value

RTU560 internal communication Protocol specific


off 0
on 1

Conversion of quality descriptors

RTU560 internal communication Protocol specific


SE Select / Execute Select / Execute
(1 select, 0 execute)

Conversion of cause of transmission

RTU560 internal communication Protocol specific


T Test Ignored
P/N Positive/negative confirmation Relevant in monitor direction only
Cause Activation 6 - Activation
Activation Confirmation 7 - Activation Confirmation
Deactivation 8 - Deactivation
Deactivation Confirmation 9 - Deactivation Confirmation
Activation Termination 10 - Activation Termination

ABB Utilities GmbH 1KGT 150 519 V001 1 6-1


Data Types – Control Direction RTU560 Host Communication Interface with IEC 60870-5-104

6.2 DCO – Double Command Output

Binary process command (two bits)


Supported C_DC_NA_1 <46>
Data Types
Command None
Authority
Additional None

Conversion of value

RTU560 internal communication Protocol specific


off 1
on 2

Conversion of quality descriptors

RTU560 internal communication Protocol specific


SE Select / Execute Select / Execute
(1 select, 0 execute)

Conversion of cause of transmission

RTU560 internal communication Protocol specific


T Test Ignored
P/N Positive/negative confirmation Relevant in monitor direction only
Cause Activation 6 - Activation
Activation Confirmation 7 - Activation Confirmation
Deactivation 8 - Deactivation
Deactivation Confirmation 9 - Deactivation Confirmation
Activation Termination 10 - Activation Termination

6-2 1KGT 150 519 V001 1 ABB Utilities GmbH


RTU560 Host Communication Interface with IEC 60870-5-104 Data Types – Control Direction

6.3 RCO – Regulation Command Output

Regulation process command (two bits)


Supported C_RC_NA_1 <47>
Data Types
Command None
Authority
Additional regulating step command are in principle retriggerable commands

Conversion of value

RTU560 internal communication Protocol specific


Lower 1
Higher 2

Conversion of quality descriptors

RTU560 internal communication Protocol specific


SE Select / Execute Only S/E = 0 (execute) supported

Conversion of cause of transmission

RTU560 internal communication Protocol specific


T Test Ignored
P/N Positive/negative confirmation Relevant in monitor direction only
Cause Activation 6 - Activation
Activation Confirmation 7 - Activation Confirmation
Deactivation 8 - Deactivation
Deactivation Confirmation 9 - Deactivation Confirmation
Activation Termination 10 - Activation Termination

ABB Utilities GmbH 1KGT 150 519 V001 1 6-3


Data Types – Control Direction RTU560 Host Communication Interface with IEC 60870-5-104

6.4 ASO – Analog Setpoint Output

Analog process command (16 bit signed number)


Supported C_SE_NA_1 <48> normalized
Data Types Transmission format
(ASO- Protocol Address and Parameter

C_SE_NB_1 <49> scaled


Transmission format
(ASO- Protocol Address and Parameter)
Command None
Authority
Additional Analog set-point output is a persistent output

Conversion of value

RTU560 internal communication Protocol specific


Range min. -100% Normalized : -1
Scaled : -32768
... ...
Range max. +100% Normalized : +1-2-15
Scaled : +32767

Conversion of quality descriptors

RTU560 internal communication Protocol specific


SE Select / Execute Only S/E = 0 (execute) supported

Conversion of cause of transmission

RTU560 internal communication Protocol specific


T Test Ignored
P/N Positive/negative confirmation Relevant in monitor direction only
Cause Activation 6 - Activation
Activation Confirmation 7 - Activation Confirmation
Deactivation 8 - Deactivation
Deactivation Confirmation 9 - Deactivation Confirmation
Activation Termination 10 - Activation Termination

6-4 1KGT 150 519 V001 1 ABB Utilities GmbH


RTU560 Host Communication Interface with IEC 60870-5-104 Data Types – Control Direction

6.5 DSO – Digital Setpoint Output

Binary process command (8 or 16 bit signed number)


Supported C_SE_NA_1 <48> normalized
Data Types
Command None
Authority
Additional Digital set-point output is a persistent output

Conversion of value

RTU560 internal communication Protocol specific


Range min. -100% -1
... ...
Range max. +100% +1-2-15

Conversion of quality descriptors

RTU560 internal communication Protocol specific


SE Select / Execute Only S/E = 0 (execute) supported

Conversion of cause of transmission

RTU560 internal communication Protocol specific


T Test Ignored
P/N Positive/negative confirmation Relevant in monitor direction only
Cause Activation 6 - Activation
Activation Confirmation 7 - Activation Confirmation
Deactivation 8 - Deactivation
Deactivation Confirmation 9 - Deactivation Confirmation
Activation Termination 10 - Activation Termination

ABB Utilities GmbH 1KGT 150 519 V001 1 6-5


Data Types – Control Direction RTU560 Host Communication Interface with IEC 60870-5-104

6.6 BSO – Bit String Output

Binary process command (1, 2, 8, 16, 32 bit unsigned number)


Supported C_BO_NA_1 <51>
Data Types
Command None
Authority
Additional Always persistent output; instead of command deactivation (cause of
transmission 8) a new command with the data value ‘0’ has to be
generated.
Process output is supported for the two least significant octets of the 32
bit value.

Conversion of value

RTU560 internal communication Protocol specific


Range min. 0 0
... ...
Range max. 4294967295 4294967295

Conversion of quality descriptors

RTU560 internal communication Protocol specific


SE Select / Execute Only S/E = 0 (execute) supported

Conversion of cause of transmission

RTU560 internal communication Protocol specific


T Test Ignored
P/N Positive/negative confirmation Relevant in monitor direction only
Cause Activation 6 - Activation
Activation Confirmation 7 - Activation Confirmation
Deactivation 8 - Deactivation
Deactivation Confirmation 9 - Deactivation Confirmation
Activation Termination 10 - Activation Termination

6-6 1KGT 150 519 V001 1 ABB Utilities GmbH


RTU560 Host Communication Interface with IEC 60870-5-104 Data Types – Control Direction

6.7 Read Command

Process command to read a specific datapoint

Supported C_RD_NA_1 <102>


Data Types

Values None

Command None
Authority

Additional A read command can be configured for every datapoint of the


monitoring direction.

The read command can be configured in two modes:

Absolute time
The read command for the specific datapoint is send at the configured
time within a day. It is send only once per day.

Cyclic time
The read command for the specific datapoint is send cyclicly. The time
period must be configured. The time period is configured in minutes.
Possible values are 1 to 1440 minutes.

Conversion of quality descriptors

RTU560 SCI internal Protocol specific


SE Select / Execute Only S/E = 0 (execute) supported

Conversion of cause of transmission

RTU560 SCI internal Protocol specific


T Test Ignored
P/N Positive/negative confirmation Relevant in monitor direction only
Cause Request 5 - Request

ABB Utilities GmbH 1KGT 150 519 V001 1 6-7


7 File transfer

The file transfer is used for exchanging files between a control center and a subordinated
device connected to a RTU560.

Before starting file transfer to a subordinated RTU, the control center must deactivate the
RTU (stop data acquisition and processing). This increases performance for file transfer,
as the periodic measurand telegrams of this station will disappear from the line until the
RTU restarts.

The file name in the protocol is fixed for all supported file types to 1 (transparent file).
Supported file types
GCD-configuration file
IOD-configuration file
OAD-configuration file
PTX-configuration file
PRO-configuration file
UNDEF- file not specified in greater detail

Supported Data F_FR_NA_1 <120>


Types F_SR_NA_1 <121>
F_SC_NA_1 <122>
F_LS_NA_1 <123>
F_AF_NA_1 <124>
F_SG_NA_1 <125>
F_DR_TA_1 <126>
Values -
Command None
Authority
Additional

Conversion of cause of transmission

RTU560 host internal Protocol specific


T Test Ignored
P/N Positive/negative confirmation Relevant in monitor direction only
Cause Spontaneous 3 – spontaneous
Requested 5 – requested
File transfer 13 - file transfer

ABB Utilities GmbH 1KGT 150 519 V001 1 7-1


File transfer RTU560 Host Communication Interface with IEC 60870-5-104

7.1 Download

The download of configuration files does not trigger any restarting mechanism in the
subordinated device. For activating the new configuration file, the control center has to
issue a Reset Process Command (C_RP_NA_1, TI 105) after writing the files to the
device.

The file transfer will only be routed to the subordinated device it belongs to. The
distribution is done between the message F_LS_NA_1 and the message F_AF_NA_1
and may last a couple of seconds. The message F_AF_NA_1 is only acknowledged
positively when file distribution were successful.

7.2 Upload

All supported file types can also be uploaded from a RTU560 or subordinated devices.

7-2 1KGT 150 519 V001 1 ABB Utilities GmbH


8 Transparent Data

In automation systems may be required information that is not mapped to the


IEC 60870-5-104 protocol. This information includes several device specific parameter
etc.

Several type identifications of the private range have been selected to enable
transparent data transfer through the RTU560 to subordinate devices.

8.1 Transparent Data Channel

8.2 Command Direction

With the “Transparent Data Message C_TD_NA_1” the Controlling Station is able to
request data from subordinate devices through the RTU560.

The Type Ident is 145, the link address, ASDU address and the Information object
address must be configured by RTUtil NT.

The “Transparent Data Message C_TD_NA_1” will be answered from RTU560 by


sending the message back to Controlling Station with Cause of Transmission 7
(Activation confirmation).

When the message is accepted by the RTU (message can be processed by the RTU and
device answers to the request message), the RTU sends a “positive confirmation”
ACTCON, otherwise (message cannot be processed by the RTU) the RTU sends a
“negative confirmation” ACTCON.

Every transparent data command is checked on link address, ASDU address,


informationation object address and “No of Data Bytes in Current Segment“.

If the link address, ASDU address or information object address doesn’t match to the
configuration in RTUtil NT or the “No of Data Bytes in Current Segment” is higher than
200, the command is confirmed negative.

ABB Utilities GmbH 1KGT 150 519 V001 1 7-1


Transparent Data RTU560 Host Communication Interface with IEC 60870-5-104

ASDU Type 145: C_TD_NA_1


D7 D6 D5 D4 D3 D2 D1 D0
Type Identification = 145
1 0 0 1 0 0 0 1
Variable Structure Qualifier
0 0 0 0 0 0 0 1
Cause of Transmission
0 X 0 0 0 1 1 X
Common Address of ASDU
X X X X X X X X
Information Object Address
X X X X X X X X
Total Number of Segments (1 .. 255)
7 6 5 4 3 2 1 0
2 2 2 2 2 2 2 2
Current Segment Number (1 .. 255)
7 6 5 4 3 2 1 0
2 2 2 2 2 2 2 2
Protocol Type: (1.. 255) Protocol Type Value in Protocol
2
7
2
6
2 2
5
2
4
2
3
2
2
2
1 0
Type field
No of Data Bytes, Current Segment (max. SPAbus 7
200) RP570/571 8*
7 6 5 4 3 2 1 0
2 2 2 2 2 2 2 2 Modbus 9*
First Data Byte of Segment IEC 60870-5-101 101*
IEC 60870-5-102 102
IEC 60870-5-103 103*
IEC 60870-5-104 104*
User data IEC 1107 107
: :
Last Data Byte of Segment * : reserved for future use

7-2 1KGT 150 519 V001 1 ABB Utilities GmbH


RTU560 Host Communication Interface with IEC 60870-5-104 Transparent Data

8.2.1 Monitoring Direction

With the “Transparent Data Response M_TD_NA_1”, the RTU is able to receive any data
as transparent data from subordinate devices.

The Type Ident is 146, the link address, ASDU address and the Information object
address must be configured by RTUtil NT. They are equal to the one used in command
direction.

The maximum amount of segments is 255, each of them contains up to 200 data bytes.

If all data can be sent in one message (data segmentation not necessary), the contents
of both segmentation control fields are set to 1.

ASDU Type 146: M_TD_NA_1


D7 D6 D5 D4 D3 D2 D1 D0
Type Identification = 146
1 0 0 1 0 0 1 0
Variable Structure Qualifier
0 0 0 0 0 0 0 1
Cause of Transmission
0 0 0 0 0 1 1 0
Common Address of ASDU
X X X X X X X X
Information Object Address
X X X X X X X X
Total Number of Segments (1 .. 255)
7 6 5 4 3 2 1 0
2 2 2 2 2 2 2 2
Current Segment Number (1 .. 255)
7 6 5 4 3 2 1 0
2 2 2 2 2 2 2 2
Protocol Type: (1 .. 255) Protocol Type Value in Protocol
2
7
2
6
2
5
2
4
2
3
2 2
2
2
1 0 Type field
No of Data Bytes, Current Segment (max. SPAbus 7
200) RP570/571 8*
2
7
2
6
2
5 4
2
3
2 2
2
2
1
2
0 Modbus 9*
First Data Byte of Segment IEC 60870-5-101 101*
IEC 60870-5-102 102
IEC 60870-5-103 103*
IEC 60870-5-104 104*
User data IEC 1107 107
: :
* : reserved for future use
Last Data Byte of Segment

ABB Utilities GmbH 1KGT 150 519 V001 1 7-3


Transparent Data RTU560 Host Communication Interface with IEC 60870-5-104

8.2.2 Request procedure

Subordinate
RTU560 Device
Transparent data C_TD_NA_1.act
channel command - Device checks, if
activation corresponding
command is possible
Transparent data to transmit.
C_TD_NA_1.act_con P/N
channel command -
activation
User data will be send
confirmation
to target, reply(s) will
be send as answer
with
COF = REQUESTED
Transparent data
M_TD_NA_1.requested (segment 1)
channel information –
Requested
. If reply is larger than
. max. User data size
in M_TD_NA_1, user
. data will be
Transparent data segmented in
M_TD_NA_1.requested (segment n)
channel information – several telegrams.
Requested

7-4 1KGT 150 519 V001 1 ABB Utilities GmbH


RTU560 Host Communication Interface with IEC 60870-5-104 Transparent Data

8.3 Encapsulated SPABUS messages

8.3.1 General

With the “Transparent Data Message C_SB_NA_1” the Controlling Station is able to
request data and execute commands of a SPAbus device connected to a subordinate
device through the RTU560.

The Type Ident is 133, the link address, ASDU address and the Information object
address must be configured by RTUtil NT.

The “Transparent Data Message C_SB_NA_1” will be answered from RTU by sending
the message back to Central System with Cause of Transmission 7 (Activation
confirmation).

When the message is accepted by the subordinate device (Device answers to the
request message), the RTU sends a “positive confirmation” ACTCON with the reply data
included, otherwise (message cannot be processed) the RTU sends a “negative
confirmation” ACTCON.

Every transparent data command is checked on link address, ASDU address, information
object address and “No of Data Bytes in Current Segment“.

If the link address, ASDU address, information object address or “No of Data Bytes”
doesn’t match to the configuration in RTUtil NT, the command is confirmed negative.

ASDU Type 133: C_SB_NA_1


D7 D6 D5 D4 D3 D2 D1 D0
Type Identification = 133
1 0 0 0 0 1 0 1
Variable Structure Qualifier *N defines, the number of
1 *N information elements
Cause of Transmission (characters) in the ASDU
0 X 0 0 0 1 1 X
(0 .. 127)
Common Address of ASDU
X X X X X X X X
Information Object Address
X X X X X X X X
First Data Byte of Segment

SPAbus command message


(in control direction)
or
: : SPAbus reply message
(in monitoring direction)
Last Data Byte of Segment

ABB Utilities GmbH 1KGT 150 519 V001 1 7-5


Transparent Data RTU560 Host Communication Interface with IEC 60870-5-104

8.3.2 Request procedure

Subordinate
RTU560 Divice
Encapsulated SPAbus C_SB_NA_1.act
command -activation Device checks, if
corresponding
command is possible
to transmit.
User data will be
send to target, reply
will be send as
Encapsulated
activation
SPAbus command – C_SB_NA_1.act_con P/N
confirmation
activation
confirmation

7-6 1KGT 150 519 V001 1 ABB Utilities GmbH


9 Time Synchronization

If the RTU560 should synchronize subordinated devices it must be configured. The


configuration parameter are described in chapter 2.1.

Important note:

The time synchronization command is only send to subordinated devices which are in
state ONLINE and only if the time tag of the own RTU is valid (synchronized).

Supported C_CS_NA_1 <103>


Data Types

Values Complete time and date information in CP56Time2a format

Command None
Authority

Additional None

Conversion of cause of transmission

RTU560 SCI internal Protocol specific


T Test Ignored
P/N Positive/negative confirmation Relevant in monitor direction only
Cause Activation 6 - Activation
Activation Confirmation 7 - Activation Confirmation

ABB Utilities GmbH 1KGT 150 519 V001 1 9-1


10 General Interrogation

The general interrogation to the subordinated devices is send directly after the
initialization of the RTU and on every change of the subordinated link from state
OFFLINE to state ONLINE.

Supported Data C_IC_NA_1 <100>


Types

Values 0

Command None
Authority

Additional None

Conversion of quality descriptors

RTU560 SCI internal Protocol specific


QOI Qualifier of Interrogation 20 - Qualifier of Interrogation

Conversion of cause of transmission

RTU560 SCI internal Protocol specific


T Test Ignored
P/N Positive/negative confirmation Relevant in monitor direction only
Cause Activation 6 - Activation
Activation Confirmation 7 - Activation Confirmation
Activation Termination 10 - Activation Termination

ABB Utilities GmbH 1KGT 150 519 V001 1 10-1


11 System Events

The subdevice interface manages internal status messages for every device connected
to these line. These status messages are created from the subdevice interface itself for
every connected device.

The subdevice interface supports 2 system events only


Description of system event Address offset
RTU is active 24
RTU inoperable 48

While initialization the system events RTU_IS_ACTIVE (24) as SPI with value 1 is send
to the internal communication. On a running system this system event doesn´t change.

The system event RTU_INOPERABLE (48) is send as SPI to the internal communication
in dependency of the state of the subordinated device:
State of the subordinated device Value of system event 48
OFFLINE 1
ONLINE 0

ABB Utilities GmbH 1KGT 150 519 V001 1 11-1


12 Status Change

12.1 Offline to Online

If the status of a subordinated device or line changes from OFFLINE to ONLINE a


general interrogation command is send to the concerning device(s)

The system event RTU_INOPERABLE (48) with value 0 is send as SPI to the internal
communication for every device that changed the state.

12.2 Online to Offline

If the status of a subordinated device or line changes from ONLINE to OFFLINE all
configured data points connected to this devices are send to the internal communication
with the actual state, marked as INVALID and with the timestamp of the own RTU.

The system event RTU_INOPERABLE (48) with value 1 is send as SPI to the internal
communication for every device that changed the state.

ABB Utilities GmbH 1KGT 150 519 V001 1 12-1


13 Interoperability List

Interoperability definitions

Following interoperability definitions are copied from IEC 60870-5-104, clause 8; the
original numbering and layout is maintained.

Supported and selectable parameter

This document defines by mark squares þ parameter settings and selections from the
standard IEC 60870-5-104 that are supported by RTU560.

Functions and parameter with filled (black) squares n are not supported by RTU560 !

ABB Utilities GmbH 1KGT 150 519 V001 1 13-1


Interoperability List RTU560 Subdevice Communication Interface IEC 60870-5-104

13.1 Network configuration

(network-specific parameter)

n Point-to-point n Multipoint-party line


n Multiple point-to-point n Multipoint-star

13.2 Physical layer

(network-specific parameter)

Transmission speed (control direction)


Unbalanced interchange Unbalanced interchange Balanced interchange
circuit V.24/V.28 circuit V.24/V.28 circuit X.24/X.27
Standard Recommended if >1200 bit/s
n 100 bit/s n 2400 bit/s n 2400 bit/s n 56000 bit/s
n 200 bit/s n 4800 bit/s n 4800 bit/s n 64000 bit/s
n 300 bit/s n 9600 bit/s n 9600 bit/s
n 600 bit/s n 19200 bit/s n 19200 bit/s
n 1200 bit/s n 38400 bit/s

Transmission speed (monitor direction)


Unbalanced interchange Unbalanced interchange Balanced interchange
circuit V.24/V.28 circuit V.24/V.28 circuit X.24/X.27
Standard Recommended if >1200 bit/s
n 100 bit/s n 2400 bit/s n 2400 bit/s n 56000 bit/s
n 200 bit/s n 4800 bit/s n 4800 bit/s n 64000 bit/s
n 300 bit/s n 9600 bit/s n 9600 bit/s
n 600 bit/s n 19200 bit/s n 19200 bit/s
n 1200 bit/s n 38400 bit/s

13-2 1KGT 150 519 V001 1 ABB Utilities GmbH


RTU560 Subdevice Communication Interface IEC 60870-5-104 Interoperability List

13.3 Link layer

(network-specific parameter)
Frame format FT 1.2, single character 1 and the fixed time out interval are used exclusively in this
companion standard.

Link transmission procedure Address field of link

n Balanced transmission n Not present (balanced transmission only)


n Unbalanced transmission n One octet
n Two octets
Frame length n Structured
≤ 255 Maximum length L (number of octets) n Unstructured
(selectable)

13.4 Application Layer

Transmission mode for application data


Mode 1 (Least significant octet first), as defined in clause 4.10 of IEC 870-5-4, is used exclusively in this
companion standard.

Common address of ASDU

(system-specific parameter)
n One octet þ Two octets
Information object address

(system-specific parameter)
n One octet þ structured
n Two octets þ unstructured
þ Three octets
Cause of transmission

(system-specific parameter)
n One octet þ Two octets (with originator address)

ABB Utilities GmbH 1KGT 150 519 V001 1 13-3


Interoperability List RTU560 Subdevice Communication Interface IEC 60870-5-104

Selection of standard ASDUs

Process information in monitor direction


(station-specific parameter)

þ <1> := Single-point information M_SP_NA_1


n <2> := Single-point information with time tag M_SP_TA_1
þ <3> := Double-point information M_DP_NA_1
n <4> := Double-point information with time tag M_DP_TA_1
þ <5> := Step position information M_ST_NA_1
n <6> := Step position information with time tag M_ST_TA_1
þ <7> := Bitstring of 32 bit M_BO_NA_1
n <8> := Bitstring of 32 bit with time tag M_BO_TA_1
þ <9> := Measured value, normalized value M_ME_NA_1
n<10> := Measured value, normalized value with time tag M_ME_TA_1
þ<11> := Measured value, scaled value M_ME_NB_1

n<12> := Measured value, scaled value with time tag M_ME_TB_1


þ<13> := Measured value, short floating point value M_ME_NC_I

n<14> := Measured value, short floating point value with time tag M_ME_TC_1
þ<15> := Integrated totals M_IT_NA_1

n<16> := Integrated totals with time tag M_IT_TA_1

n<17> := Event of protection equipment with time tag M_EP_TA_1

n<18> := Packed start events of protection equipment with time tag M_EP_TB_1

n<19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1

n<20> := Packed single-point information with status change detection M_PS_NA_1

n<21> := Measured value, normalized value without quality descriptor M_ME_ND_1

þ<30> := Single-point information with time tag CP56Time2a M_SP_TB_1


þ<31> := Double-point information with time tag CP56Time2a M_DP_TB_1
þ<32> := Step position information with time tag CP56Time2a M_ST_TB_1
þ<33> := Bitstring of 32 bit with time tag CP56Time2a M_BO_TB_1
þ<34> := Measured value, normalized value with time tag CP56Time2a M_ME_TD_1
þ<35> := Measured value, scaled value with time tag CP56Time2a M_ME_TE_1
þ<36> := Measured value, short floating point value with time tag CP56Time2a M_ME_TF_1
þ<37> := Integrated totals with time tag CP56Time2a M_IT_TB_1
þ<38> := Event of protection equipment with time tag CP56Time2a M_EP_TD_1

n<39> := Packed start events of protection equipment with time tag CP56Time2a M_EP_TE_1

n<40> := Packed output circuit information of protection equipment with time tag M_EP_TF_1
CP56Time2a

13-4 1KGT 150 519 V001 1 ABB Utilities GmbH


RTU560 Subdevice Communication Interface IEC 60870-5-104 Interoperability List

Process information in control direction


(station-specific parameter)
þ <45> := Single command C_SC_NA_1
þ <46> := Double command C_DC_NA_1

þ <47> := Regulating step command C_RC_NA_1


þ <48> := Set point command, normalized value C_SE_NA_1
n <49> := Set point command, scaled value C_SE_NB_1
n <50> := Set point command, short floating point value C_SE_NC_1
þ <51> := Bitstring of 32 bit C_BO_NA_1

System information in monitor direction


(station-specific parameter)

þ <70> := End of initialization M_EI_NA_1

System information in control direction


(station-specific parameter)

þ <100> := Interrogation command C_IC_NA_1


þ <101> := Counter interrogation command C_CI_NA_1
þ <102> := Read command C_RD_NA_1
þ <103> := Clock synchronization command C_CS_NA_1

n <104> := Test command C_TS_NA_1

n <105> := Reset process command C_RP_NA_1

n <106> := Delay acquisition command C_CD_NA_1

Parameter in control direction


(station-specific parameter)

n <110> := Parameter of measured value, normalized value P_ME_NA_1

n <111> := Parameter of measured value, scaled value P_ME_NB_1


n <112> := Parameter of measured value, short floating point value P_ME_NC_1
n <113> := Parameter activation P_AC_NA_1

File transfer
(station-specific parameter)

þ <120> := File ready F_FR_NA_1


þ <121> := Section ready F_SR_NA_1
þ <122> := Call directory, select file, call file, call section F_SC_NA_1
þ <123> := Last section, last segment F_LS_NA_1
þ <124> := Ack file, ack section F_AF_NA_1
þ <125> := Segment F_SG_NA_1
þ <126> := Directory F_DR_TA_1

ABB Utilities GmbH 1KGT 150 519 V001 1 13-5


Interoperability List RTU560 Subdevice Communication Interface IEC 60870-5-104

13.5 Basic application functions


Station initialization
(station-specific parameter)

þ Remote initialization
General Interrogation
(system- or station-specific parameter)

þ global

n group 1 n group 7 n group 13

n group 2 n group 8 n group l4

n group 3 n group 9 n group 15

n group 4 n group 10 n group 16

n group 5 n group 11

n group 6 n group 12 Addresses per group have to be defined

Clock synchronization
(station-specific parameter)

n Clock synchronization

Command transmission
(object-specific parameter)

þ Direct command transmission þ Select and execute command

þ Direct set point command transmission n Select and execute set point command

n C_SE_ACTTERM used

þ No additional definition (pulse duration is defined within RTU 560 individually per command object)

n Short pulse duration

n Long pulse duration

þ Persistent output

Transmission of Integrated totals


(station- or object-specific parameter)

n Counter request n General request counter

n Counter freeze without reset n Request counter group 1

n Counter freeze with reset n Request counter group 2

n Counter reset n Request counter group 3

n Request counter group 4

13-6 1KGT 150 519 V001 1 ABB Utilities GmbH


RTU560 Subdevice Communication Interface IEC 60870-5-104 Interoperability List

Parameter loading
(object-specific parameter)

n Threshold value

n Smoothing factor

n Low limit for transmission of measured value

n High limit for transmission of measured value

Parameter activation
(object-specific parameter)

n Act/deact of persistent cyclic or periodic transmission of the addressed object

File transfer
(station-specific parameter)

þ File transfer in monitor direction


þ File transfer in control direction

ABB Utilities GmbH 1KGT 150 519 V001 1 13-7


Interoperability List RTU560 Subdevice Communication Interface IEC 60870-5-104

13-8 1KGT 150 519 V001 1 ABB Utilities GmbH