0% found this document useful (0 votes)
80 views7 pages

HVDC Control Multitask PDF

1) The document presents a robust control strategy for a VSC-HVDC transmission system between two AC networks. 2) The control strategy equips the VSC converters with a multi-task controller to facilitate power management between the AC systems, independent reactive power control at the connection points, and frequency regulation at the sending end network. 3) The control strategies for the VSCs are detailed and their performance is tested under large disturbances in simulations, substantiating the dynamic performance of the VSC-HVDC system with the proposed control approach.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
80 views7 pages

HVDC Control Multitask PDF

1) The document presents a robust control strategy for a VSC-HVDC transmission system between two AC networks. 2) The control strategy equips the VSC converters with a multi-task controller to facilitate power management between the AC systems, independent reactive power control at the connection points, and frequency regulation at the sending end network. 3) The control strategies for the VSCs are detailed and their performance is tested under large disturbances in simulations, substantiating the dynamic performance of the VSC-HVDC system with the proposed control approach.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

Electrical Power and Energy Systems 53 (2013) 684–690

Contents lists available at SciVerse ScienceDirect

Electrical Power and Energy Systems


journal homepage: www.elsevier.com/locate/ijepes

Multi-task control for VSC–HVDC power and frequency control


O.A. Giddani a,⇑, Abdelaziz Y.M. Abbas a, Grain P. Adam b, Olimpo Anaya-Lara b, K.L. Lo b
a
School of Electrical and Nuclear Engineering, Sudan University of Science and Technology, Khartoum, Sudan
b
Electronic and Electrical Engineering Department, University of Strathclyde, Glasgow, UK

a r t i c l e i n f o a b s t r a c t

Article history: A robust control strategy for a VSC–HVDC transmission scheme between two ac networks is presented.
Received 27 July 2011 The VSC converters at both ends of the dc line are equipped with a multi-task controller that facilitates:
Accepted 2 May 2013 power management between the two ac systems, provision of independent reactive power control at the
point of common couplings (PCCs) and frequency regulation at the sending-end side. The paper investi-
gate the utilization of VSC–HVDC system to provide frequency regulation to an ac network; this is useful
Keywords: for networks with high penetration of renewables (e.g. wind), and nuclear generation. The proposed con-
Fault-Ride Through capability
trol strategies for the VSCs are presented in detail, investigating further the tuning method for the proper
Power management
Frequency control
operation of the inner controllers. The robustness of the control system is tested under large distur-
Pulse width modulation bances. The study is conducted in Matlab/Simulink and results that substantiate the dynamic perfor-
Reactive power compensation mance of the VSC–HVDC with the proposed control are thoroughly discussed.
Ó 2013 Published by Elsevier Ltd.

1. Introduction In this paper, a robust controller is developed to equip a


VSC–HVDC transmission with multi-task functionality providing
High-voltage dc transmission systems based on voltage source power management, frequency regulation and dynamic voltage
converters (VSC–HVDC) use switching devices such IGBTs or GTOs control at the point of connection. Transient system stability and
which can be turned ON and OFF at any time (using pulse width the improvement in Fault Ride-Through capability is investigated
modulation, PWM), increasing control flexibility and capabilities, during both ac faults at the receiving end and dc faults at the mid-
such independent active and reactive power flow control. Also, dle of the dc link.
with PWM the converter harmonics are those associated with the
PWM switching frequency, typically between 1 and 2 kHz [1,2].
2. Modeling of the VSC–HVDC test system
In addition, the VSC can provide four-quadrant power controllabil-
ity. The reactive power exchange between the VSC converter and
The VSC–HVDC transmission test system is shown in Fig. 1 with
the ac system can be controlled to provide greater flexibility for
parameters given in Appendix A. The VSCs have been modeled as
the AC system, such as stabilizing a particular bus voltage and
three-level NPC converters. Generation in the ac networks has been
operating at unity power factor to minimize the transmission cur-
modeled by synchronous generators with AVR and turbine-gover-
rent and reduce the transmission losses [3,4]. All these features
nor control. The coupling transformers condition the ac network
have made of VSC–HVDC systems an attractive solution for various
voltage to a suitable level for the converter, and provide a reac-
applications in power systems (not previously considered due to
tance between the converter and the ac busbar to limit and control
technical and economical limitations) such as the following [5,6]:
the ac current. Three-phase reactors are used to facilitate active
and reactive power flow control.
 Integration of large offshore wind farms located far away from
Applying Kirchhoff Voltage Law to the system in Fig. 1, with
shore.
time t in seconds and all other quantities in per unit, the dynamic
 Connection of weak and isolated areas.
equations for VSC1 converter are [8,9]:
 Development of multi-terminal DC networks.
 Provision of independent reactive power control. disabc1 R1 1
¼  isabc1 þ ðv sabc1  v cabc1 Þ ð1Þ
dt L1 L1

⇑ Corresponding author. Address: School of Electrical and Nuclear Engineering, where R1 = RT1 + RF1 and L1 = LT1 + LF1.
University of Science and Technology, 61th Avenue, Eastern Diems, PO Box 72, To simplify the design of the control system, the three-phase
Khartoum, Sudan. Tel.: +00249 121 077 716. quantities are expressed in the dq reference frame using the Park
E-mail address: [email protected] (O.A. Giddani). transformation matrix given in Eq. (2) as:

0142-0615/$ - see front matter Ó 2013 Published by Elsevier Ltd.


http://dx.doi.org/10.1016/j.ijepes.2013.05.002
O.A. Giddani et al. / Electrical Power and Energy Systems 53 (2013) 684–690 685

dc link
ac network1
ac network2

C C
B1 B2
T3 T1 SR1 SR2 T2
TL

SG1 SG2
C C

1990+j185 MVA 2390+j285MVA


dc link
VSC1 VSC2

Fig. 1. VSC–HVDC transmission test system.


2 3 2   32 3
fd cos h cos h  23p cosðh  43pÞ fb By substituting Eqs. (6) in (1), then
6 7 26     76 7 2 3 2 3 2 3
4 fq 5 ¼ 4 sin h sin h  23p sin h  43p 54 fb 5 ð2Þ isd1   isd1   ud1
3 d6 R1 =L1 0 1=L1 0
fo 1=2 1=2 1=2 fc 7 6 7 6 7
4 isq1 5 ¼ 4 isq1 5 þ 4 uq1 5
dt 0 R1 =L1 0 1=L1
Applying Park’s transformation to Eq. (1) the differential equations
for VSC1 in dq coordinates are [10,11]: ð7Þ
disdq1 R1 ½V sdq1  V cdq1  jxLisdq1  where udq1 = ud1 + juq1, idq1 = id1 + jiq1, vsdq1 = vsd1 + jvsq1 and
¼  isdq1 þ ð3aÞ
dt L1 L1 vcdq1 = vcd1 + jvcq1.
The power balance equation between the dc and ac sides in VSC1 is: The variables udq1 are new control variables obtained from PI
controllers which regulate the dq-axis currents. The values of udq
dV dc1 32 ðv cd1  isd1 þ v cq1  isq1 Þ Idc are defined as:
¼  ð3bÞ
dt C  V dc1 C Z
 
udq1 ¼ kpi ðisdq1  isdq1 Þ þ kii ðisdq1  isdq1 Þdt ð8Þ
Similarly, the dynamic equations of the inverter-side converter
(VSC2) are:
where kpi and kii are the proportional and integral gains of the cur-
disdq2 R2 ½V cdq2  V sdq2 þ jxLisdq2  rent controller, and the superscript  refers to the reference value.
¼  isdq2 þ ð4aÞ
dt L2 L2 Replacing the integral part of Eq. (8) by new auxiliary control
variables zdq1 (where zdq1 = zd1 + jzq1), the following set of equations
dV dc2  32 ðv cd2  isd2 þ v cq2  isq2 Þ Idc is obtained:
¼ þ ð4bÞ
dt C  V dc2 C 
udq1 ¼ kpi ðisdq1  isdq1 Þ þ kii zdq1 ð9Þ
In a converter with sinusoidal PWM, the relationship between the dzdq1 
modulation index M, dc link voltage and the dq components of ¼ idq1 þ idq1 ð10Þ
dt
the ac voltage at the converter terminals is given by [12,13]:
Substituting Eqs. (9) in (7) then
1 2 3
v cd þ jv cq ¼ MVdc ½cosd þ jsind ð5Þ 2 3 2 3 isd1
2 isd1 ðR1 þ kpi Þ=L1 K ii =L1 0 0 6 7
76 zd1 7
d6 7 6
6 zd1 7 6 1 0 0 0 76 7
6 7¼6 76 isq1 7
3. Control system strategy dt 4 isq1 5 4 0 0 ðR1 þ kpi Þ=L1 K ii =L1 56
6
7
7
4 zq1 5
zq1 0 0 1 0
The main function of the VSC is to generate a fundamental-
2 3
frequency ac voltage from a dc voltage, and to control the gener- kpi =L1 0
ated voltage in phase and magnitude. Vector control, typically used 6 7"
61 0 7  #
to control the VSC–HVDC, consists of inner and outer controllers. 6 7 isd1
þ6
60 kpi =L1 7
7 i ð11Þ
The function of the inner controller is to regulate the current such 6 7 sq1
that it follows the references provided by the outer controllers, and 40 1 5
to ensure that the converter is not overloaded during major distur-
bances. The outer controller is responsible for supplying references
From Eq. (11), the dq-currents are defined in the Laplace domain as
values to the inner controller. There are four possible control
follow:
modes to choose from for the outer controller: constant dc voltage, 2 3
constant dc power, constant ac voltage, and variable frequency 2 3 s K ii =L1 0 0
isd1 ðsÞ 6 72  3
control modes. The choice of the outer controller mode depends 6 z ðsÞ 7 6 1 s þ ðR1 þ K pi Þ=L1 0 0 7 isd1
6 d1 7 1 6 76  7
on the application of the VSC–HVDC. The dc voltage controller reg- 6 7¼ 60 0 s K ii =L1 74 i 5
4 isq1 ðsÞ 5 s2 þ ðR1 þK pi Þ s þ K ii 6
6
7 sq1
7
ulates the dc link voltages to ensure the power balance between L1 L1 4 0 0 1 s þ ðR1 þ K pi Þ=L1 5
zq1 ðsÞ
the sending- and receiving-end converters. In order to design an
inner current controller, the cross-coupling terms in Eq. (3) need ð12Þ
to be decoupled as follow [10,11]:
Therefore, the Laplace transfer function of the inner (current)
udq1 ¼ v sdq1  v cdq1 þ jxLidq1 ð6Þ controller is:
686 O.A. Giddani et al. / Electrical Power and Energy Systems 53 (2013) 684–690

 
K pi
s þ KK ii 3
L1 pi pðtÞ ¼ v sd ðtÞ  isd ðtÞ ð16Þ
GðsÞ ¼ ðR1 þK pi Þ
ð13Þ 2
K ii
s2 þ L1
s þ L1
Hence, the dq current reference values are:
From the current characteristic Eq. (13) [14], the proportional and
integral gains of the current controller are defined as follow [15]:
 2P
kpi ¼ 2fxn L1  R1 isd ¼ ð17Þ
3v sd
ð14aÞ
kii ¼ x2n L1
In the dc and ac voltage controllers, the measured dc and ac volt-
where, xn and f are the natural frequency and damping factor,
ages are compared with the reference voltages, the error signals
respectively. These values must be selected carefully to ensure sta-
are processed by PI controllers to generate the d-axis and q-axis ref-
ble operation over the full operating range.  
erence currents ðisd & isq Þ. The mathematical equations of the dc
The operation mode of the converters is chosen such that VSC2
and ac voltage controllers to generate the dq-references currents
controls the dc voltage and the ac voltage at B2, whilst VSC1 con-
are:
trols the active power and the ac voltage at B1.
Z

3.1. Active power, dc and ac voltage controllers isd ¼ kpdc ðV dc  V dc Þ þ kidc ðV dc  V dc Þdt ð18Þ
Z
The instantaneous active and reactive power delivered to the 
isq ¼ kpac ðV ac  V ac Þ þ kiac ðV ac  V ac Þdt ð19Þ
point of common coupling (PCC), in the dq frame are given as:
3
pðtÞ ¼ ½v sd ðtÞ  isd ðtÞ þ v sq ðtÞ  isq ðtÞ where kpdc, kidc, kpac, kiac are the proportional and integral gains of
2 ð15aÞ the dc voltage controller and the ac voltage controller, respectively.
3
qðtÞ ¼ ½v sd ðtÞ  isq ðtÞ þ v sq ðtÞ  isd ðtÞ The feed-forward term in Eq. (18) is neglected in this paper due to
2 its slow dynamics compared to the inner current control loop. The
For balanced steady-state operation vsq = 0, therefore Eq. (15) can be complete control system (including inner and outer controllers)
expressed as [13]: for the sending and receiving ends VSCs is shown in Fig. 2.

(a)

(b)

Fig. 2. Schematic control system of the VSC–HVDC system: (a) sending-end converter control system; (b) receiving-end converter control system).
O.A. Giddani et al. / Electrical Power and Energy Systems 53 (2013) 684–690 687

Fig. 3. Key simulation results during active power management.

4. Power management and reactive power provision The active power flow change at B1 and B2 is shown in Fig. 3a and b.
As expected, the phase angles of the VSC converters change to en-
The active and the reactive power flow between the VSC and the able the converters to control the active power flow between the
ac system can be expressed as [16,17]: converters and the ac networks as shown in Fig. 3. The voltages at
B1 and B2 are maintained constant regardless of the change in the
V c  V s sinðdÞ
P¼ ð20Þ power level. The ac voltage controllers control the reactive power
Xt exchange between the converters and the buses to keep the voltage
V c  V s cosðdÞ V 2c profile constant as shown in Fig. 3d. Notice that the reactive power
Q¼  ð21Þ
Xt Xt changes together with the active power as shown in Fig. 3a and b.
The STATCOM functionality of the VSCs is assessed by switching
From Eqs. (20) and (21), it can be seen that:
the dc transmission system to sleep mode (in Fig. 3a the power is
switched to zero between t = 2.25 s and t = 3.0 s).
 The active power flow is controlled by the phase angle D. If D (0,
then the active power flows from the converter to the ac system 5. VSC–HVDC control to provide network frequency support
otherwise the power flow is in the opposite direction.
The capability of the VSC–HVDC to control the power flow is
 The reactive power flow is controlled by the ac source voltage valuable during load demand changes in the ac networks. Any
vs, and the VSC converter voltage Vc. The converter generates reac-
tive power if Vc > Vs and consumes it for Vc < Vs.

The active power flow control can be achieved by adjusting the


active power reference in Eq. (17). The VSC converters at both sides
regulate the reactive power generated or absorbed by the con-
verter to keep the voltage at B1 and B2 at the desired value.
To study the ability of the VSC–HVDC to control active power
flows and provide voltage support at the PCCs, the reference active
power is changed with time as follow:
8
< P ¼ 1:0 0 6 t 6 1:0;
> P ¼ 2t þ 3:0 10 6 t 6 1:25 P ¼ 0:5 1:25 6 t 6 2:0;
P ¼ 2t þ 4:5 2:0 6 t 6 2:25 P ¼ 0 2:25 6 t 6 3:0; P ¼ 4t  6:0 3:0 6 t 6 3:25
>
:
P ¼ 0:5 3:25 6 t 6 4:0; P ¼ 2t þ 7:5 4:0 6 t 6 4:25 P ¼ 1:0 4:25 6 t 6 5:0
Fig. 4. Frequency controller.
688 O.A. Giddani et al. / Electrical Power and Energy Systems 53 (2013) 684–690

change in the network load will result in acceleration or decelera- difference will generate the correction signal in order to stabilize

tion of the generation units to maintain power balance and to the system frequency. This correction factor Di is added to id1 old
stabilize the network frequency. which is obtained from the active power set-point to obtain a

VSC–HVDC transmission systems can be used to participate in new reference current id1 new that incorporates the effect of any ac-
frequency regulation together with conventional generation units. tive power mismatch DPL. The maximum value for the correction
The dynamic response of the dc system during a load change is factor is set such that the converter station VSC1 can increase or de-
described by: crease its output power at any time by ±20% of the converter rating
without exceeding its current limit.
dDx Fig. 5 shows the simulation results obtained during system
2Hc ¼ DPdc  DPL ð22Þ
dt over/and under frequency events initiated by the loss or addition
where Dx is the frequency deviation, DPdc is the change on the dc of (60 + j25) MVA load at time t = 5 s in the sending-end network.
transmitted power, DPL is the load change, and Hc is the effective dc It can be observed that the converter station VSC1 and the synchro-
inertia constant, defined as [7]: nous machine SG1 adjust their output powers to stabilize the net-
work frequency during the loss or addition of load at ac network 1,
Total ac system inertia as shown in Fig. 5b and c. Also, it can be noticed that VSC1 has
Hc ¼ ð23Þ
MW rating of the dc system responded much faster than SG1 by providing most of the power
required to stabilize the frequency during the first transient period
A PI frequency controller could be included within the active power
after the load change, due to its small inertia ð12 CV2dc =S ¼ 38msÞ
controller to enable the VSC–HVDC system to respond to frequency
compared to that of SG1 with H = 4.25 s.
fluctuations in the ac1 network frequency (Fig. 4). The frequency
Fig. 5a shows the ac network frequency of the ac network 1 dur-
controller is based on the active power-frequency characteristics gi-
ing sudden loss/ and addition of load into ac network 1. The partic-
ven in [7] which are represented by a linear equation as
ipation of the VSC–HVDC in frequency support is very useful,
f ¼ f0 þ KðP  P0 Þ. The correction signal of the frequency controller
especially in networks high penetration of wind and nuclear power
is derived as:
generation (as nuclear is preferred to be operated at constant out-
Z
put power). Fig. 5d shows the frequency of ac network 1 during a
Di ¼ kpf ðf   f Þ þ kif ðf   f Þdt ð24Þ
sudden load change with/and without the frequency controller
implemented in the VSC. It can be observed that with the fre-
where, kpf and kif are the proportional and integral gains of the quency controller in operation, the time required for the frequency
frequency controller. The VSC1 converter senses the network to recover to its pre-disturbance value is shorter and with a lower
frequency and compares it with the nominal frequency, any overshoot than without the frequency controller.

Fig. 5. Key simulation results demonstrate frequency support at sending end side during over and under frequency.
O.A. Giddani et al. / Electrical Power and Energy Systems 53 (2013) 684–690 689

Fig. 6. Key simulation demonstrates the transient behaviour of the VSC–HVDC during three-phase fault at B2.

6. System behavior during an AC fault at the receiving end This operation complies with Grid Codes requirements, which state
that the voltage must recover to 90% after fault clearance within
If a short circuit occurs somewhere in the ac grid, the fault may less than 0.5 s.
extend across the system until the fault is terminated by circuit The dc link voltage of the receiving-end converter (VSC2) has in-
breakers. In this investigation, a VSC–HVDC is used to improve the creased during the fault to compensate for adjustment of the load
Fault Ride-Through capability of the ac system during abnormal angle between the voltage Vs at the receiving-end bus and the volt-
conditions by isolating the two systems. To demonstrate the tran- age at converter terminals VC. The dc capacitor tries to maintain the
sient behaviour of the VSC–HVDC during abnormal disturbances, dc link voltage during the fault and this leads to oscillations in the
the test system in Fig. 1 is subjected to a three-phase fault at bus active power as shown in Fig. 6b. The active power at the sending-
B2, at t = 0.6 s with duration of 100 ms (5 cycles). Fig. 6 shows the end converter (VSC1), which is less sensitive to the fault at the receiv-
key waveforms obtained from this case. The voltage at ing end, reduces to zero during the fault by blocking the dc convert-
the sending-end (bus B1) is less sensitive to the ac fault than at the ers (Fig. 6b) to prevent the excessive increase in the dc voltage and
receiving-end (bus B2) as illustrated in Fig. 6a. This reflects that the active power at the receiving end after the clearance of the fault.
the VSC–HVDC link actually manages to improve the ac ride through
capability of the sending-end by completely isolating it from
the receiving end (decoupled operation). The converters need to 7. Conclusions
be blocked during ac system faults to protect the IGBT switches from
excessive over-currents. In the test system the dc voltage increase This paper presented the design and modelling of a VSC–HVDC
during the fault is acceptable and not dangerous to the converter transmission system multi-tasking controllers that are able to reg-
equipment, hence a chopper was not used in the DC link circuit to ulate ac current, active power, dc link voltage, ac voltage and ac
prevent the excessive increase in the dc link voltage during the ac network frequency. The proposed multi-tasking control approach
fault. of the HVDC systems can be used as the main provider for fre-
The ac voltage at the receiving-end bus collapses during the quency support in ac networks highly populated by nuclear and
fault and recovers to the pre-fault value after fault clearance. The other renewable power plants. The proposed multi-tasking con-
ac voltage and power after fault removal recover to a value greater trollers can be extended to regulate ac frequency in both sending
than the pre-fault value with noticeable transient oscillations and receiving ends without significantly compromising the decou-
(Fig. 6a and b); this causes the controllers to reverse the direction pling feature of VSC–HVDC systems. But this may require high-
of the modulation index to reduce the overshoot until the system is bandwidth communication systems. The robustness of the pro-
totally stabilized [2]. After fault clearance the ac voltage on the posed controllers has been tested under large disturbances such
receiving-end recovers to 100% the pre-fault value within 0.1 s. as major load changes and ac faults.
690 O.A. Giddani et al. / Electrical Power and Energy Systems 53 (2013) 684–690

Appendix A. Test system parameters (Fig. 1) References

[1] Flourentzou N et al. VSC-Based HVDC power transmission systems: an


SG data 2400 MVA, 13.8 kV, 50 Hz, xd = 1.79, x
d = 0.220,
overview. IEEE Trans on Power Electro 2009;24:592–602.
k k [2] Arrillage YHLLJ, Watson NR. Flexible power transmission systems – the HVDC
xd = 0.193, xq = 1.715, x
q = 0.243, xd = 0.243, options. John Wiley & Sons, Publication; 2007.
k k [3] Bresesti P et al. HVDC connection of offshore wind farms to the transmission
xl = 0.18 T 
d0 = 0.595, T d0 = 0.035, T q0 = 0.31, system. Energy Convers IEEE Trans 2007;22:37–43.
Rs = 0.003, H = 4.25 [4] Agelidis VG, et al. Recent advances in high-voltage direct-current power
ac1 network transmission systems. In: Industrial technology, 2006. ICIT 2006. IEEE
international conference on; 2006. p. 206–13.
T3 data 275 kV, 3000 MVA, RT3 = 0.0005 pu,
[5] Bahrman MP, Johnson BK. The ABCs of HVDC transmission technologies. Power
(13.8/ LTce:inf>3 = 0.3 pu), TL data (0.01273 x/km & Energy Mag IEEE 2007;5:32–44.
0.9334 e3 H/km, l = 50 km) Vs1 = 275 kV, Vc1 = 132 kV, T1 [6] Cole S, Belmans R. Transmission of bulk power. Ind Electron Mag IEEE
(275/132 kV, 30 0MVA, RT1 = 0.0005 pu, LT1 = 0.3 pu), SR1 2009;3:19–24.
(LF1 = 0.3 pu based on 300 MVA & 132 kV), [7] Cuiqing D et al. A new control strategy of a VSC–HVDC system for high-quality
SL1 = 1995+j85 MVA supply of industrial plants. Power Deliv IEEE Trans 2007;22:2386–94.
ac2 network [8] Kundur P. Power system stability and control: electric power research
institute. Power Syst Eng Ser 1994.
Vs2 = 400 kV, Vc2 = 132 kV, the transformer, T2 (132/400 kV,
[9] Thomas JL, et al. Analysis of a robust DC-bus voltage control system for a VSC
300 MVA, RT2 = 0.0005 pu, LT2 = 0.3 pu), SR2 (LF2 = 0.3 pu based transmission scheme. In: AC–DC power transmission, 2001. Seventh
on 300 MVA & 132 kV) international conference on (conf. publ. No. 485); 2001. p. 119–24.
dc circuit Converter rating (S) = 350 MVA, Vdc = 300 kV, the [10] Lie X et al. VSC transmission operating under unbalanced AC conditions –
capacitor C = 800 lF, cable data (0.015 x/km, analysis and control design. Power Deliv IEEE Trans 2005;20:427–34.
[11] Yazdani A, Iravani R. Dynamic model and control of the NPC-based back-to-
150 km) back HVDC system. Power Deliv IEEE Trans 2006;21:414–24.
[12] de la Villa Jaen A et al. Voltage source converter modeling for power system
state estimation: STATCOM and VSC–HVDC. Power Syst IEEE Trans
Appendix B. synchronous generator AVR turbine-governor 2008;23:1552–9.
control system [13] Cuiqing D, et al. Analysis of the control algorithms of voltage-source converter
HVDC. In: Power Tech, 2005 IEEE Russia; 2005. p. 1–7.
[14] Cominos P, Munro N. PID controllers: recent tuning methods and design to
specification. Control Theory Appl IEE Proc 2002;149:46–53.
[15] Douangsyla S, et al. Modeling for PWM voltage source converter controlled
power transfer. In: Communications and information technology, 2004. ISCIT
2004. IEEE international symposium on; 2004. p. 875–8.
[16] Andersen BR, et al. Topologies for VSC transmission. In: AC–DC Power
Transmission, 2001. Seventh international conference on (conf. publ. No.
485); 2001. p. 298–304.
[17] Cetin A, Ermis M. VSC-based D-STATCOM with selective harmonic elimination.
Ind Appl IEEE Trans 2009;45:1000–15.

Excitation system parameters: Ka = 250, Ta = 5 s, Tb = 1.5 s,


Tf = 0.025 s.

Steam turbine-governor system parameters: K3 = 25, Tg = 0.25 s,


Thp = 0.25 s, Tr = 6.0 s, Khp = 0.35.

You might also like