0% found this document useful (0 votes)
308 views1 page

Buton de Incendiu Adresabil Detectomat PL 3300 MCP-kit

This document provides information on the PL 3300 MCP-kit push button detector for loop 3000 systems. The detector has automatic and manual addressing options and can output an alarm signal. It is powered by the loop at 15-30V, uses 370uA of current normally and 5mA during an alarm. It operates between -10°C and +55°C, has an IP24 rating, and measures 88x88x54mm. The detector zones must be programmed as MCP zones via the dpt 3000 system.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
308 views1 page

Buton de Incendiu Adresabil Detectomat PL 3300 MCP-kit

This document provides information on the PL 3300 MCP-kit push button detector for loop 3000 systems. The detector has automatic and manual addressing options and can output an alarm signal. It is powered by the loop at 15-30V, uses 370uA of current normally and 5mA during an alarm. It operates between -10°C and +55°C, has an IP24 rating, and measures 88x88x54mm. The detector zones must be programmed as MCP zones via the dpt 3000 system.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Push Button Detector

PL 3300 MCP-kit
order number : 32065

Intelligent push button detector for loop 3000 with bidirectional isolator, labeled symbol
"Burning House":

· loop 3000 is a highly functional detection-system


· automatic addressing (soft-addressing)
· manual addressing (Easy Check)
· output for alarm at the detector

technical data

remarks The detector zone(s) the MCP-Kit has been


programmed in, need to be programmed as an MCP
zone (conventional) via dpt 3000. The I-Check software
identifies the kit as an AMD 3311.
operation voltage 15 up to 30 V loop powered
quiescent current 370 µA
alarm current 5 mA
operation temperature -10°C up to +55°C
humidity max. 95 % non-condensing
protection class IP 24 D
colour housing red, RAL 3000
material ABS
DIN-EN 54-11
dimensions (H x W x D): 88 mm x 88 mm x 54 mm
catalogue page 52
weight 0 kg

errors and alterations excepted

detectomat GmbH [email protected] Tel +49(0)4102/2114-60


An der Strusbek 5 www.detectomat.de Fax +49(0)4102/2114670
D-22926 Ahrensburg Mittwoch, 18. Juli 2007
page 1 of 1