This document is a designers reference handbook for the DEIF multi-line 2 Automatic Gen-set Controller.
INDEX:
1        Getting started.......................................................................................................................................................................................... 6
1.1      Warnings and legal information .................................................................................................................................................................. 7
1.2      Standard functions ..................................................................................................................................................................................... 7
1.2.1    Language ................................................................................................................................................................................................... 7
1.2.2    Standard functions ..................................................................................................................................................................................... 7
1.3      Optional function list ................................................................................................................................................................................... 8
1.4      Hardware.................................................................................................................................................................................................... 8
1.5      Terminal strip overview............................................................................................................................................................................. 10
1.5.1    Slots #1, #2, #5 and #6............................................................................................................................................................................. 10
1.5.2    Slots #3, #4, #7 and #8............................................................................................................................................................................. 10
1.6      Terminal strip, explanation........................................................................................................................................................................ 11
1.6.1    Slot #1, power supply and binary I/O ........................................................................................................................................................ 11
1.6.2    Slot #2, serial communication (option H) .................................................................................................................................................. 12
           1.6.2.1           Can-open (option H1 - not available at the moment) ........................................................................................................ 12
           1.6.2.2           Mod-bus (option H2) ........................................................................................................................................................ 12
           1.6.2.3           Profi-bus (option H3) ........................................................................................................................................................ 12
1.6.3    Slot #3, load sharing control (option G3)................................................................................................................................................... 13
1.6.4    Slot #3, 13 binary inputs and 4 relay outputs (option M12) ....................................................................................................................... 14
1.6.5    Slot #4, governor and AVR control relay outputs ...................................................................................................................................... 14
1.6.6    Slot #4, analogue outputs for governor and AVR control (option E) .......................................................................................................... 14
1.6.7    Slot #4, analogue output for governor and one transducer output (option EF2) ........................................................................................ 15
1.6.8    Slot #4, PWM output (option EF3 and option D) ....................................................................................................................................... 15
1.6.9    Slot #4, PWM output (option EF3 and not option D) ................................................................................................................................. 15
1.6.10   Slot #4, governor/AVR output (option EF4)............................................................................................................................................... 15
1.6.11   Slot #5, AC measuring.............................................................................................................................................................................. 16
1.6.12   Slot #6, optional I/O PCBs........................................................................................................................................................................ 16
           1.6.12.1          Option M13, 7 binary inputs ............................................................................................................................................. 16
           1.6.12.2          Option M14, 4 relay outputs ............................................................................................................................................. 17
           1.6.12.3          Option M15, 4 analogue inputs 4...20 mA ........................................................................................................................ 17
           1.6.12.4          Option F1, analogue transducer output ............................................................................................................................ 17
           1.6.12.5          Option EF3, droop output................................................................................................................................................. 17
1.6.13   Slot #7, engine interface card ................................................................................................................................................................... 18
           1.6.13.1          Standard card with PT100 inputs ..................................................................................................................................... 18
           1.6.13.2          Optional card with VDO inputs ......................................................................................................................................... 19
           1.6.13.3          Access lock (binary input 6) ............................................................................................................................................. 20
1.6.14   Slot #8, power management (option G4) .................................................................................................................................................. 20
                                  ®
1.6.15   Slot #8, Caterpillar CCM communication ................................................................................................................................................ 20
1.7      Wirings ..................................................................................................................................................................................................... 21
1.7.1    AC connections ........................................................................................................................................................................................ 21
           1.7.1.1           AMF, peak shaving and fixed power application............................................................................................................... 21
           1.7.1.2           Island mode application ................................................................................................................................................... 21
1.7.2    Load sharing lines .................................................................................................................................................................................... 22
1.7.3    Binary inputs ............................................................................................................................................................................................ 22
1.7.4    Optocoupler outputs for external counter.................................................................................................................................................. 22
1.7.5    Display cable (option J) ............................................................................................................................................................................ 23
1.7.6    Serial cable for PC with utility software (option J3) ................................................................................................................................... 23
1.8      Application examples................................................................................................................................................................................ 24
1.8.1    Application for Automatic Mains Failure operation .................................................................................................................................... 24
           1.8.1.1           Single gen-set .................................................................................................................................................................. 24
1.8.2    Applications for peak shaving operation ................................................................................................................................................... 25
           1.8.2.1           Single gen-set .................................................................................................................................................................. 25
1.9      Applications for the AGC .......................................................................................................................................................................... 26
1.9.1    Single running gen-sets............................................................................................................................................................................ 26
           1.9.1.1           Automatic mains failure, AMF operation (factory setting) ................................................................................................. 26
           1.9.1.2           Island mode ..................................................................................................................................................................... 26
           1.9.1.3           Peak shaving ................................................................................................................................................................... 27
           1.9.1.4           Mains power export .......................................................................................................................................................... 27
           1.9.1.5           Fixed power operation...................................................................................................................................................... 28
1.9.2    Multi running gen-sets .............................................................................................................................................................................. 28
           1.9.2.1           Island mode ..................................................................................................................................................................... 28
           1.9.2.2           Automatic mains failure operation .................................................................................................................................... 29
1.10     Power management ................................................................................................................................................................................. 29
1.10.1   Schematic view of the PMS option G4 ..................................................................................................................................................... 29
1.10.2   Introduction of the PMS option G4............................................................................................................................................................ 30
1.10.3   Mode selection ......................................................................................................................................................................................... 30
1.10.4   Function ................................................................................................................................................................................................... 30
1.10.5   Load sharing/var sharing .......................................................................................................................................................................... 31
1.10.6   Test sequence.......................................................................................................................................................................................... 31
1.11     Configurable inputs/outputs ...................................................................................................................................................................... 31
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                                                                                                    Page 2 of 121
                         DESIGNERS REFERENCE HANDBOOK
                         Automatic Gen-set Controller, multi-line 2                                                                                                                           4189340258H
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                                                                                                  Page 3 of 121
                           DESIGNERS REFERENCE HANDBOOK
                           Automatic Gen-set Controller, multi-line 2                                                                                                                         4189340258H
  DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                                                                                                 Page 4 of 121
                           DESIGNERS REFERENCE HANDBOOK
                           Automatic Gen-set Controller, multi-line 2                                                                                                                            4189340258H
  DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                                                                                                    Page 5 of 121
              DESIGNERS REFERENCE HANDBOOK
              Automatic Gen-set Controller, multi-line 2                      4189340258H
1 Getting started
DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]   Page 6 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                            4189340258H
Installing and operating the multi-line 2 AGC product implies work with dangerous currents and voltages, and therefore qualified
personnel should do it only.
Care must be taken during the installation to protect the terminals against static discharges. Once the units are installed and
connected, these precautions are no longer necessary.
DEIF takes no responsibility for operation or installation of the generator set. If there is any doubt about how to install or operate the
system on which the multi-line 2 AGC product is measuring, the company responsible for the installation or the operation must be
contacted.
      •   Stand-alone gen-set
      •   Gen-set in island operation, load sharing
      •   Automatic mains failure with starting of the gen-set. No back synchronising when the mains returns
      •   Automatic mains failure with starting of the gen-set and back synchronising when the mains returns
      •   Gen-set in parallel with mains in fixed load mode
      •   Gen-set in parallel with mains in peak shaving mode
The selection of the application type is done in the system setup. The AGC is only intended to be configured to one of the above
application types. It is possible to operate the AGC in three modes:
      • Auto (only AMF and peak shaving mode – the AGC controls the gen-set and the breakers according to the operational state)
      • Semi-auto (manual control and activation of the sequences)
      • Test (manual starting and loading of the gen-set)
The multi-line 2 measuring system is true RMS 3-phase measurement of generator voltage, generator current and mains voltage.
1.2.1      Language
English, German, French or Spanish language can be chosen via the system menu structure.
      • Engine protection. The engine alarm extension card has the following configurable inputs and outputs:
        - 4 4…20 mA inputs
        - 1 tacho input
        - 1 binary input
        - 2 PT100 inputs
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                             Page 7 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                       4189340258H
      • Island mode
        - Semi-auto operation
        - Operation of the generator breaker
      • Fixed power
        - Semi-auto operation
        - Operation of the mains and generator breaker
      • Test running
        - Automatic start-up and loading
        - Programmable load and running time
1.4       Hardware
The multi-line 2 housing is divided into board slot positions, some of which are standard (non-changeable) and some intended for
options. The unit is divided like this:
* If analogue governor outputs (option E) or PWM outputs (option EF3) are selected, the standard relay output PCB in slot #4 is
  exchanged to the analogue PCB.
Besides the slots there is an additional board where the communication ports are placed. I.e. RS232 PC service port for the utility
software and the display port.
For slots #1, #2, #3, #5, #7, #8 and #9: Only specific boards can be mounted.
For slots #4 and #6: The boards are interchangeable.
An overview of the terminals can be seen on the next page. The slots are positioned in the unit as follows (seen from the top of the
unit):
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                        Page 8 of 121
                                                                                        1    2   3   4   5   6   7   8   9 10 11 12 13 14                        15 16 17 18 19 20 21 22 23 24 25 26 27 28                     29 30 31 32 33 34 35 36
                                                                              SLOT #1                                                                                                                                                                            SLOT #2
                                                                              SLOT #3                                                                                                                                                                            SLOT #4
                                                                                        37 38 39 40 41 42 43 44 45 46 47 48 49 50                                51 52 53 54 55 56 57 58 59 60 61 62 63 64                     65 66 67 68 69 70 71 72
                                                                                                                                                                                                                                 Ethernet
                                                                                                                                                                                    Service port             Display
SLOT #9
ok
                                                                                                                                  er
                                                                                                                                                             ibi
                                                                                                                                   w
                                                                                                                                             ck
                                                                                                                                                         inh
                                                                                                                                Po
                                                                                                                                           he
                                                                                                                                                         m
                                                                                                                                           c
                                                                                                                                                       ar
                                                                                                                                       elf
                                                                                                                                                    Al
                                                                                                                                       S
                                                                                        73 74 75 76 77 78                      79 80 81 82 83 84                                      85 86 87 88 89                           90 91 92 93 94 95 96 97
                                                                              SLOT #5                                                                                                                                                                            SLOT #6
                                                                              SLOT #7                                                                                                                                                                            SLOT #8
                                                                                        98   99 100 101 102 103 104 105 106 107 108 109 110 111                      112 113 114 115 116 117 118 119 120 121 122 123 124 125   126 127 128 129 130 131 132 133
DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]
                                                                                                                                                                                                                                                                           DESIGNERS REFERENCE HANDBOOK
                                                                                                                                                                                                                                                                           Automatic Gen-set Controller, multi-line 2
              Page 9 of 121
                                                                                                                                                                                                                                                                            4189340258H
                DESIGNERS REFERENCE HANDBOOK
                Automatic Gen-set Controller, multi-line 2                      4189340258H
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]   Page 10 of 121
                  DESIGNERS REFERENCE HANDBOOK
                  Automatic Gen-set Controller, multi-line 2                                                             4189340258H
The functionality of the alarm inhibit input is described in the table below:
AGC
Alarm inhibit input       ON          OFF
Generator low f           -           ACT
Generator low U           -           ACT
Generator high f          ACT         ACT
Generator high U          ACT         ACT
4…20 mA input             -           ACT
Binary input              -           ACT
PT100 input               -           ACT
Tacho input               -           ACT
NOTE:
These inputs are not inhibited:
    • Tacho input
    • Emergency stop
    • Running feedback
    • Remove starter (if configured)
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                            Page 11 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                    4189340258H
The serial communication line should be terminated between DATA + and DATA - with a resistor equal to the cable impedance. The
terminals 29/32, 30/33 and 31/34 are internally connected on all communication PCBs.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                 Page 12 of 121
               DESIGNERS REFERENCE HANDBOOK
               Automatic Gen-set Controller, multi-line 2                            4189340258H
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]        Page 13 of 121
                DESIGNERS REFERENCE HANDBOOK
                Automatic Gen-set Controller, multi-line 2                                                        4189340258H
1.6.4 Slot #3, 13 binary inputs and 4 relay outputs (option M12)
1.6.6 Slot #4, analogue outputs for governor and AVR control (option E)
The analogue current outputs can, if needed, be converted to voltage using a resistor across the terminals (250 Ω will convert the
+/-20 mA into +/-5 VDC).
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                     Page 14 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                             4189340258H
1.6.7 Slot #4, analogue output for governor and one transducer output (option EF2)
1.6.9 Slot #4, PWM output (option EF3 and not option D)
The PWM signal has a frequency of 500 +/-50Hz, and the resolution of the duty cycle is 12 bits which gives the output 4095 different
levels. The output is an open collector with a 1kΩ pull-up resistor. The low level of the signal is between 0 and 0.05 volt, and the high
level is between 5.7 and 6 volt. The PWM droop signal is placed in slot #6.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                           Page 15 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                  4189340258H
The two configuration combinations shown above in option EF4 are chosen in channel 2210.
NOTE:
Current inputs are galvanically separated. Max. 0.3 VA per phase.
  DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                 Page 16 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                            4189340258H
Via software selection the outputs can be selected to be 0…20 mA or 4…20 mA.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                          Page 17 of 121
                  DESIGNERS REFERENCE HANDBOOK
                  Automatic Gen-set Controller, multi-line 2                                                           4189340258H
The minimum and maximum values of the 4...20 mA input can be adjusted:
The inputs can be used for a high or low alarm. As a “high alarm” the alarm appears when the measured value is higher than the
alarm limit, and as a “low alarm” the alarm appears when the measured values are lower than the alarm limit.
    • Start
    • Stop solenoid
    • Start prepare
The binary inputs use 24 volt constant signal. They do not use pulse inputs.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                          Page 18 of 121
                  DESIGNERS REFERENCE HANDBOOK
                  Automatic Gen-set Controller, multi-line 2                                                      4189340258H
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                     Page 19 of 121
                  DESIGNERS REFERENCE HANDBOOK
                  Automatic Gen-set Controller, multi-line 2                                                            4189340258H
The communication between AGC units is used for the option G4.
                             ®
1.6.15     Slot #8, Caterpillar CCM communication
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                           Page 20 of 121
                    DESIGNERS REFERENCE HANDBOOK
                    Automatic Gen-set Controller, multi-line 2                  4189340258H
1.7 Wirings
1.7.1 AC connections
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]   Page 21 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                       4189340258H
The binary inputs use fixed signals. They do not use pulse signals.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                     Page 22 of 121
                DESIGNERS REFERENCE HANDBOOK
                Automatic Gen-set Controller, multi-line 2                                                         4189340258H
                   2
Wires min. 0.22 mm , max. cable length 6 m.
Cable types: Belden 9540, BICC H8146, Brand Rex BE57540 or equivalent.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                      Page 23 of 121
                  DESIGNERS REFERENCE HANDBOOK
                  Automatic Gen-set Controller, multi-line 2                                                      4189340258H
The mains failure must be present in the period “FAIL DELAY” before the MB is opened. The timer “FAIL DELAY” will be reset each
time till mains is restored.
The mains must have been present in the period “MAINS OK DELAY” before the MB synchronises.
When the gen-set is running it will control the frequency and voltage to the nominal set point.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                     Page 24 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                     4189340258H
When the load decreases below the stop gen-set limit, the following sequence is run through:
When the gen-set is running it will be loaded between the minimum load limit (e.g. 5%) and the maximum nominal generator load.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                     Page 25 of 121
                  DESIGNERS REFERENCE HANDBOOK
                  Automatic Gen-set Controller, multi-line 2                                                          4189340258H
It is only possible to use the multi-line 2 AGC for one of the purposes, e.g. automatic mains failure operation. The selection must be
made on site. All multi-line 2 AGCs are supplied with the factory setting:
      • Single gen-set
      • Automatic mains failure operation
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                        Page 26 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                     4189340258H
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]   Page 27 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                     4189340258H
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]   Page 28 of 121
                  DESIGNERS REFERENCE HANDBOOK
                  Automatic Gen-set Controller, multi-line 2                                                        4189340258H
CAN-bus
AGC1 AGC2
G1 G2
The AGC 1 is measuring the mains voltage and the generator 1 voltage.
The AGC 2 is measuring the busbar voltage and the generator 2 voltage.
The communication is canbus. The connections are shown in the I/O list 1.6.14.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                       Page 29 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                           4189340258H
Mode selection
Function                              AGC 1                               AGC 2
AMF                                   Auto                                Auto
AMF                                   Auto                                Semi-auto
No AMF                                Semi-auto                           Auto
No AMF                                Semi-auto                           Semi-auto
1.10.4    Function
The time charts describe the functionality at a mains failure and at a mains return. Back synchronisation is deactivated.
The timer tMBC is only active if back synchronisation is deactivated (channel 4433). If back synchronisation is active the MB will be
synchronised, and the GB is deloaded and opened and the gen-set is cooled down and stopped.
  Mains OK
                                                                                             tMCB
     MB On
GB On
Gen running
Gen f/U OK
                                               tFU
                Mains failure                                         Mains OK
                detected
  DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                          Page 30 of 121
                  DESIGNERS REFERENCE HANDBOOK
                  Automatic Gen-set Controller, multi-line 2                                                                  4189340258H
Mains OK
       MB On
                                                                                            tMBC
       GB On
                                                       tGBC
Gen start seq
                                tFD
Gen stop seq
                                                                               tFOD
 Gen running
 Gen f/U OK
                                             tFU
                Mains failure                                      Mains OK
                detected
When a mains failure occurs, all gen-sets are started. If the AGC 1 in “AUTO” operation fails during the mains failure sequence, the
AGC 2 closes on the black busbar. This is controlled from the AGC 1. Resetting a start failure alarm on the AGC 1 will cause the gen-
set 1 to start without subsequent automatic synchronisation.
NOTE:
At a mains failure situation when testing gen-set 2, the gen-set 1 will start without subsequent automatic synchronisation to the
busbar.
Binary inputs:
     - The texts can be edited to a user defined name.
     - Default all inputs are alarm inputs.
     - All inputs can be configured as described below:
Input                     Description
Fire pump                 All alarms and fail classes are overruled. The only alarms the gen-set will react on are “Emergency stop” on
                          terminal 117 or a “Tacho failure”. Also the gen-set has 7 start attempts before “Start failure”
Remote start              The gen-set can be started externally if semi-auto mode is selected
Remote stop               The gen-set can be stopped externally if semi-auto mode is selected
Semi-auto mode            The mode can be changed externally
Test mode                 The mode can be changed externally
Auto mode                 The mode can be changed externally
Remote GB On              The GB can be set On externally if semi-auto mode is selected
Remote GB Off             The GB can be set Off externally if semi-auto mode is selected
Remote MB On              The MB can be set On externally if semi-auto mode is selected
Remote MB Off             The MB can be set Off externally if semi-auto mode is selected
Remote alarm ack.         All alarms are reset if the input is set
Gen-set start             Automatic starting of the gen-set and subsequent operation in the selected gen-set mode (load take over,
sequence                  fixed power, mains power export) can only be used in auto mode
  DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                             Page 31 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                             4189340258H
Analogue inputs:
     - The texts can be edited to a user defined name. This name will only be used for the alarm menus.
     - The unit, min. and max. values can be edited.
Binary outputs:
     - The outputs can be configured as “Alarm” relay.
     - The outputs can be configured as “Limit” relay.
NOTE:
The configuration of the binary inputs is done in the utility software. Connect the AGC to the computer and select inputs in the settings
menu.
The standard AGC has three configurable binary inputs, four 4…20 mA inputs and two configurable relay outputs.
To be able to use this feature, one multi-line 2 must be installed with the TCP/IP hardware, and all multi-line 2 must be installed with
modbus communication. The communication with the world wide web is done through the TCP/IP unit. This unit communicates
through modbus with the other units in the system.
The web pages show the installation with the gen-sets, the breakers and the multi-line 2 units. Clicking on the icons on the screen
gives access to the following:
Status:           Screen showing the alarms and the status of all control inputs.
Messages:         Creates and sends e-mail messages if alarms occur.
Settings:         Screen showing setup menus.
Measurements:     The relevant values can be chosen between all measured gen-set values.
If the display is to be used as remote display, a standard computer extension cable with male/female plug can be used for the
connection (option J).
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                           Page 32 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                                4189340258H
INFO: Shifts the display 3 lower lines to show the alarm list (up to 30 alarms can be in the list).
JUMP:            Enters a menu number selection. All settings have a specific number attached to them. Using the JUMP button
                 enables the user to select and display any setting without navigating all the way through the menus (see later).
LOG:             Shifts the display 3 lower lines to show the event and alarm list. The list holds 100 events. These events are erased
                 when the main unit is switched off.
      :          Increases the value of the selected set-point (in the setting menus). In the daily use display it is used for scrolling the
                 second line displaying of generator values.
SEL:             Is used to select the chosen function (underscored selection in the lower line of the display).
      :          Decreases the value of the selected set-point (in the setting menus). In the daily use display it is used for scrolling
                 the second line displaying of generator values
BACK: Jumps one step backwards in the menu (to previous display or to the entry window).
(GB) ON: Manual activation of close breaker and open breaker sequence if “SEMI-AUTO” is selected. *
(MB) ON: Manual activation of close breaker and open breaker sequence if “SEMI-AUTO” is selected. *
MODE: Changes the menu line (line 4) in the display to mode selection.
Alarm inh.: LED fixed light indicates that the inhibit input is ON.
(GEN.) OK: LED green light indicates that the voltage/frequency is present and OK.
(MAINS) OK:           LED is green if the mains are present and OK.
                      LED is red at a mains failure.
                      LED is flashing green when the mains return during the “Mains OK delay” time.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                              Page 33 of 121
                    DESIGNERS REFERENCE HANDBOOK
                    Automatic Gen-set Controller, multi-line 2                                                        4189340258H
Alarm inhibit: LED fixed light indicates that the inhibit input is ON.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                         Page 34 of 121
                    DESIGNERS REFERENCE HANDBOOK
                    Automatic Gen-set Controller, multi-line 2                                                          4189340258H
Choises are:
Protection setup:
For protective function the first entry shows the “gen high volt 1” setting (provided the option is chosen). In this case the fourth line
shows:
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                           Page 35 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                             4189340258H
Control setup:
For control functions one entry shows the “Synchronisation” function. In this case the fourth line shows:
Power setup:
For power setup the first entry shows the “Mains power” setting. In this case the fourth line shows:
“DAY”, setting of the maximum allowed imported power during the daytime period
“NIGHT”, setting of the maximum allowed imported power during the nighttime period
“TRANS”, setting of the transducer scale for the transducer used in the peak shaving system
System setup:
For system setup the first entry shows the “Nominal settings”. In this case the fourth line shows:
The above settings are used by the AGC to calculate the nominal apparent power and the power factor.
The menu navigating starts from the fourth line in the start window and is carried out using the “SEL”,  ,    ,     ,     and
“BACK” pushbuttons. It is also possible to use the “JUMP” pushbutton and then enter the specific channel number (e.g. 1411) or
channel group number (e.g. 1410).
The start window shows the software version in the first line. The second line shows date and time. In line four it is possible to select
one of four menus:
Enter the setup menu by moving the cursor to “SETUP” and press “SEL”. Enter the view windows by moving the cursor to “V1”, “V2”
or “V3”. “V1” shows up to 15 selectable windows. These windows are exchanged with the        and       pushbuttons. “V2” and “V3”
show the 5 first windows also shown in “V1”. These windows are exchanged automatically by the operational change.
The view function is the daily use display. It is possible to make the relevant configuration of all measuring values and text lines
through the utility software.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                           Page 36 of 121
                  DESIGNERS REFERENCE HANDBOOK
                  Automatic Gen-set Controller, multi-line 2                                                                  4189340258H
* The default window is automatically selected when the genset is in normal operation, e.g. fixed power mode, but after the ramping
up.
When the display shows the entry window or one of the view windows the fourth line always gives access to the setup menu or one of
the view windows. When working in the setup menu it is possible to enter the view windows by using the “BACK” pushbutton until the
entry window is displayed.
The configuration of the “VIEW” windows is done through the utility software. It is not possible to configure the windows through the
display.
During synchronisation view 3 will show a synchronoscope in the first line. The synchronoscope can also be selected in all the
configurable windows. This is useful during manual synchronising.
Entering view 1 gives access of up to 15 configurable windows. These windows are selected with the                    and         pushbuttons.
The window shown when leaving “V1” will be the window shown when returning to “V1”.
The selectable values and measurements are shown in the table in chapter 1.13.3.1 in this handbook.
If the text “No text” is selected in all three lines in a window it will not be displayed. This is to get a continuous displaying if a window is
no longer to be shown.
If no actions have been taken within 3 minutes, the password entry will be de-activated, and a new password entry will be needed.
The menu overview is divided according to the daily use display selections in the fourth line (“PROT”, “CTRL”, “POWER”, “SYST”).
The following menus can only be reached using the “JUMP” pushbutton:
Use the and buttons to change the settings and the “SEL” button to store the new setting.
BEWARE:
Write down the new password. If you forget it, contact DEIF Support for details.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                                 Page 37 of 121
                  DESIGNERS REFERENCE HANDBOOK
                  Automatic Gen-set Controller, multi-line 2                                                         4189340258H
Starting from the daily use display fourth line, select the menu indicated with underscore: (Move the underscore with the   and
pushbuttons).
BACK
SEL
      First               Yes
      entry?
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                        Page 38 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                         4189340258H
  BACK
                   SEL
  G 439 440 440 V
  f-L1 50.02Hz                                                                                             P 103 kW
  PROTECTION SETUP                                                                                         S 115 kVA
  PROT CTRL POWER SYST                                                                                     SETUP V3 V2 V1
SETUP V3 V2 V1
U-SUPPLY 24 V
SETUP V3 V2 V1
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                       Page 39 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                           4189340258H
       • Semi-auto
       • Test
       • Auto
Pushing the “MODE” pushbutton will change the original text displayed in line 3 and line 4. After pushing “MODE”, the display will (in
line 4) show the three modes which can be selected. In line 3 the underscored (fourth line) selection will be displayed. Now two
possibilities are available.
If “BACK” is pushed, the display returns to the original text without changing the mode.
or
                        G       0        0         0V   1. push        G      0        0         0V   2. push
                            f-L1 0.00Hz                                     f-L1 0.00Hz
                        PROTECTION SETUP                “MODE”         SEMI-AUTO MODE                 “BACK”
                        PROT CTRL POWER SYST              Æ            SEMI TEST AUTO                   Æ
If “SEL” is pushed the underlined mode is selected and the display returns to the original text. In this example the SEMI-AUTO mode
is selected.
or
                        G       0        0         0V   3. push        G      0        0         0V   4. push
                            f-L1 0.00Hz                                     f-L1 0.00Hz
                        PROTECTION SETUP                “MODE”         SEMI-AUTO MODE                 “SEL”
                        PROT CTRL POWER SYST              Æ            SEMI TEST AUTO                   Æ
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                        Page 40 of 121
                    DESIGNERS REFERENCE HANDBOOK
                    Automatic Gen-set Controller, multi-line 2                                                              4189340258H
                                                                          Action
Fail class        Alarm horn     Alarm            Block          Deload       Trip of mains      Trip of gen.       Stop        Shutdown
                     relay       display        engine start                     breaker           breaker        generator
1 Alarm                X            X                X
2 Warning              X            X
3 Trip of GB           X            X                                                                  X
4 Trip and             X            X                               X                                  X               X
  stop
5 Shut down             X           X                                                                  X                             X
6 Trip of MB            X           X                                                X
The fail classes in the menu set-points are represented with one of the numbers 1…6 from the table above even though the fail class
texts are shown in the display. E.g. WARNING.
As the relays have been given a unique number, the number of relays available is not always the same as the max. number shown on
the display. An example could be if M14 is not selected together with M12, the relays R1 to R4 are still selectable on the display. If it is
attempted to download a relay number which is not available, an error will occur on the display, and the relay number will be set to the
standard R0.
 No.                            Setting                          Min. setting       Max. setting       Third setting       Factory setting
1010       Bus   high volt. 1     Selection display                    -                 -                   -                    -
1011       Bus   high volt. 1     Set-point                        100.0%             120.0%                 -                103.0%
1012       Bus   high volt. 1     Timer                             0.10 s            99.99 s                -                 10.00 s
1013       Bus   high volt. 1     Relay output A                  R0 (none)         R0 (none) *              -               R0 (none)
1014       Bus   high volt. 1     Relay output B                  R0 (none)         R0 (none) *              -               R0 (none)
1015       Bus   high volt. 1     Enable                             OFF                ON                 RUN                  OFF
1016       Bus   high volt. 1     Fail class                          1                  5                   -                    2
 No.                            Setting                          Min. setting       Max. setting       Third setting       Factory setting
1020       Bus   high volt. 2     Selection display                    -                 -                   -                    -
1021       Bus   high volt. 2     Set-point                        100.0%             120.0%                 -                105.0%
1022       Bus   high volt. 2     Timer                             0.00 s            99.99 s                -                 5.00 s
1023       Bus   high volt. 2     Relay output A                  R0 (none)         R0 (none) *              -               R0 (none)
1024       Bus   high volt. 2     Relay output B                  R0 (none)         R0 (none) *              -               R0 (none)
1025       Bus   high volt. 2     Enable                             OFF                ON                 RUN                  OFF
1026       Bus   high volt. 2     Fail class                          1                  5                   -                   2
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                               Page 41 of 121
                    DESIGNERS REFERENCE HANDBOOK
                    Automatic Gen-set Controller, multi-line 2                                            4189340258H
 No.                            Setting                   Min. setting    Max. setting   Third setting   Factory setting
1030       Bus   low volt. 1      Selection display             -              -               -                -
1031       Bus   low volt. 1      Set-point                 80.0%           100.0%             -             97.0%
1032       Bus   low volt. 1      Timer                     0.10 s          99.99 s            -             10.00 s
1033       Bus   low volt. 1      Relay output A           R0 (none)      R0 (none) *          -           R0 (none)
1034       Bus   low volt. 1      Relay output B           R0 (none)      R0 (none) *          -           R0 (none)
1035       Bus   low volt. 1      Enable                     OFF              ON             RUN              OFF
1036       Bus   low volt. 1      Fail class                   1               5               -                2
 No.                            Setting                   Min. setting    Max. setting   Third setting   Factory setting
1040       Bus   low volt. 2      Selection display             -              -               -                -
1041       Bus   low volt. 2      Set-point                 50.0%           100.0%             -             95.0%
1042       Bus   low volt. 2      Timer                     0.00 s          99.99 s            -             5.00 s
1043       Bus   low volt. 2      Relay output A           R0 (none)      R0 (none) *          -           R0 (none)
1044       Bus   low volt. 2      Relay output B           R0 (none)      R0 (none) *          -           R0 (none)
1045       Bus   low volt. 2      Enable                     OFF              ON             RUN              OFF
1046       Bus   low volt. 2      Fail class                   1               5               -               2
 No.                            Setting                   Min. setting    Max. setting   Third setting   Factory setting
1050       Bus   high freq. 1     Selection display             -              -               -                -
1051       Bus   high freq. 1     Set-point                 100.0%          120.0%             -            103.0%
1052       Bus   high freq. 1     Timer                      0.10 s         99.99 s            -             10.00 s
1053       Bus   high freq. 1     Relay output A           R0 (none)      R0 (none) *          -           R0 (none)
1054       Bus   high freq. 1     Relay output B           R0 (none)      R0 (none) *          -           R0 (none)
1055       Bus   high freq. 1     Enable                      OFF             ON             RUN              OFF
1056       Bus   high freq. 1     Fail class                   1               5               -                2
 No.                            Setting                   Min. setting    Max. setting   Third setting   Factory setting
1060       Bus   high freq. 2     Selection display             -              -               -                -
1061       Bus   high freq. 2     Set-point                 100.0%          120.0%             -            105.0%
1062       Bus   high freq. 2     Timer                      0.00 s         99.99 s            -             5.00 s
1063       Bus   high freq. 2     Relay output A           R0 (none)      R0 (none) *          -           R0 (none)
1064       Bus   high freq. 2     Relay output B           R0 (none)      R0 (none) *          -           R0 (none)
1065       Bus   high freq. 2     Enable                      OFF             ON             RUN              OFF
1066       Bus   high freq. 2     Fail class                   1               5               -               2
 No.                            Setting                   Min. setting    Max. setting   Third setting   Factory setting
1070       Bus   low freq. 1      Selection display             -              -               -                -
1071       Bus   low freq. 1      Set-point                 80.0%           100.0%             -             97.0%
1072       Bus   low freq. 1      Timer                     0.10 s          99.99 s            -             10.00 s
1073       Bus   low freq. 1      Relay output A           R0 (none)      R0 (none) *          -           R0 (none)
1074       Bus   low freq. 1      Relay output B           R0 (none)      R0 (none) *          -           R0 (none)
1075       Bus   low freq. 1      Enable                     OFF              ON             RUN              OFF
1076       Bus   low freq. 1      Fail class                   1               5               -                2
 No.                            Setting                   Min. setting    Max. setting   Third setting   Factory setting
1080       Bus   low freq. 2      Selection display             -              -               -                -
1081       Bus   low freq. 2      Set-point                 80.0%           100.0%             -             95.0%
1082       Bus   low freq. 2      Timer                     0.00 s          99.99 s            -             5.00 s
1083       Bus   low freq. 2      Relay output A           R0 (none)      R0 (none) *          -           R0 (none)
1084       Bus   low freq. 2      Relay output B           R0 (none)      R0 (none) *          -           R0 (none)
1085       Bus   low freq. 2      Enable                     OFF              ON             RUN              OFF
1086       Bus   low freq.2       Fail class                   1               5               -               2
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                             Page 42 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                             4189340258H
 No.                           Setting                    Min. setting    Max. setting   Third setting   Factory setting
1310       Gen. high volt. 1     Selection display              -              -               -                -
1311       Gen. high volt. 1     Set-point                  100.0%          120.0%             -            103.0%
1312       Gen. high volt. 1     Timer                       0.1 s          100.0 s            -             10.0 s
1313       Gen. high volt. 1     Relay output A            R0 (none)      R0 (none) *          -           R0 (none)
1314       Gen. high volt. 1     Relay output B            R0 (none)      R0 (none) *          -           R0 (none)
1315       Gen. high volt. 1     Enable                      OFF              ON             RUN              OFF
1316       Gen. high volt. 1     Fail class                    1               5               -                 2
 No.                           Setting                    Min. setting    Max. setting   Third setting   Factory setting
1320       Gen. high volt. 2     Selection display              -              -               -                -
1321       Gen. high volt. 2     Set-point                  100.0%          120.0%             -            105.0%
1322       Gen. high volt. 2     Timer                       0.1 s          100.0 s            -              5.0 s
1323       Gen. high volt. 2     Relay output A            R0 (none)      R0 (none) *          -           R0 (none)
1324       Gen. high volt. 2     Relay output B            R0 (none)      R0 (none) *          -           R0 (none)
1325       Gen. high volt. 2     Enable                      OFF              ON             RUN              OFF
1326       Gen. high volt. 2     Fail class                    1               5               -                2
 No.                           Setting                    Min. setting    Max. setting   Third setting   Factory setting
1330       Gen. low volt. 1      Selection display              -              -               -                -
1331       Gen. low volt. 1      Set-point                  80.0%           100.0%             -             97.0%
1332       Gen. low volt. 1      Timer                       0.1 s          100.0 s            -             10.0 s
1333       Gen. low volt. 1      Relay output A            R0 (none)      R0 (none) *          -           R0 (none)
1334       Gen. low volt. 1      Relay output B            R0 (none)      R0 (none) *          -           R0 (none)
1335       Gen. low volt. 1      Enable                      OFF              ON             RUN              OFF
1336       Gen. low volt. 1      Fail class                    1               5               -               2
 No.                           Setting                    Min. setting    Max. setting   Third setting   Factory setting
1340       Gen. low volt. 2      Selection display              -              -               -                -
1341       Gen. low volt. 2      Set-point                  50.0%           100.0%             -             95.0%
1342       Gen. low volt. 2      Timer                       0.1 s          100.0 s            -              5.0 s
1343       Gen. low volt. 2      Relay output A            R0 (none)      R0 (none) *          -           R0 (none)
1344       Gen. low volt. 2      Relay output B            R0 (none)      R0 (none) *          -           R0 (none)
1345       Gen. low volt. 2      Enable                      OFF              ON             RUN              OFF
1346       Gen. low volt.2       Fail class                    1               5               -                2
 No.                           Setting                    Min. setting    Max. setting   Third setting   Factory setting
1350       Gen. high freq. 1     Selection display              -              -               -                -
1351       Gen. high freq. 1     Set-point                  100.0%          120.0%             -            103.0%
1352       Gen. high freq. 1     Timer                       0.2 s          100.0 s            -             10.0 s
1353       Gen. high freq. 1     Relay output A            R0 (none)      R0 (none) *          -           R0 (none)
1354       Gen. high freq. 1     Relay output B            R0 (none)      R0 (none) *          -           R0 (none)
1355       Gen. high freq. 1     Enable                      OFF              ON             RUN              OFF
1356       Gen. high freq. 1     Fail class                    1               5               -               2
 No.                           Setting                    Min. setting    Max. setting   Third setting   Factory setting
1360       Gen. high freq. 2     Selection display              -              -               -                -
1361       Gen. high freq. 2     Set-point                  100.0%          120.0%             -            105.0%
1362       Gen. high freq. 2     Timer                       0.2 s          100.0 s            -              5.0 s
1363       Gen. high freq. 2     Relay output A            R0 (none)      R0 (none) *          -           R0 (none)
1364       Gen. high freq. 2     Relay output B            R0 (none)      R0 (none) *          -           R0 (none)
1365       Gen. high freq. 2     Enable                      OFF              ON             RUN              OFF
1366       Gen. high freq. 2     Fail class                    1               5               -                2
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                             Page 43 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                  4189340258H
 No.                           Setting                         Min. setting   Max. setting    Third setting   Factory setting
1370       Gen. low freq. 1      Selection display                   -             -                -                -
1371       Gen. low freq. 1      Set-point                       80.0%          100.0%              -             97.0%
1372       Gen. low freq. 1      Timer                            0.2 s         100.0 s             -             10.0 s
1373       Gen. low freq. 1      Relay output A                 R0 (none)     R0 (none) *           -           R0 (none)
1374       Gen. low freq. 1      Relay output B                 R0 (none)     R0 (none) *           -           R0 (none)
1375       Gen. low freq. 1      Enable                           OFF             ON              RUN              OFF
1376       Gen. low freq. 1      Fail class                         1              5                -               2
 No.                           Setting                         Min. setting   Max. setting    Third setting   Factory setting
1380       Gen. low freq. 2      Selection display                   -             -                -                -
1381       Gen. low freq. 2      Set-point                       80.0%          100.0%              -             95.0%
1382       Gen. low freq. 2      Timer                            0.2 s         100.0 s             -              5.0 s
1383       Gen. low freq. 2      Relay output A                 R0 (none)     R0 (none) *           -           R0 (none)
1384       Gen. low freq. 2      Relay output B                 R0 (none)     R0 (none) *           -           R0 (none)
1385       Gen. low freq. 2      Enable                           OFF             ON              RUN              OFF
1386       Gen. low freq. 2      Fail class                         1              5                -                2
 No.                           Setting                         Min. setting    Max. setting   Third setting   Factory setting
1090       Reverse power         Selection display                   -              -               -                -
1091       Reverse power         Set-point                       -50.0%           0.0%              -             -5.0%
1092       Reverse power         Timer                            0.1 s          100.0 s            -             10.0 s
1093       Reverse power         Relay output A                 R0 (none)      R0 (none) *          -           R0 (none)
1094       Reverse power         Relay output B                 R0 (none)      R0 (none) *          -           R0 (none)
1095       Reverse power         Enable                           OFF              ON             RUN              ON
1096       Reverse power         Fail class                         1               5               -                3
 No.                           Setting                         Min. setting    Max. setting   Third setting   Factory setting
1100       Over current 1        Selection display                   -              -               -                -
1101       Over current 1        Set-point                       50.0%           200.0%             -            115.0%
1102       Over current 1        Timer                            0.1 s          100.0 s            -             10.0 s
1103       Over current 1        Relay output A                 R0 (none)      R0 (none) *          -           R0 (none)
1104       Over current 1        Relay output B                 R0 (none)      R0 (none) *          -           R0 (none)
1105       Over current 1        Enable                           OFF              ON             RUN              ON
1106       Over current 1        Fail class                         1               5               -               2
 No.                           Setting                       Min. setting     Max. setting    Third setting   Factory setting
1110       Over current 2        Selection display                  -               -               -                -
1111       Over current 2        Set-point                       50.0%           200.0%             -            120.0%
1112       Over current 2        Timer                            0.1 s          100.0 s            -              5.0 s
1113       Over current 2        Relay output A                R0 (none)       R0 (none) *          -           R0 (none)
1114       Over current 2        Relay output B                R0 (none)       R0 (none) *          -           R0 (none)
1115       Over current 2        Enable                           OFF              ON             RUN               ON
1116       Over current 2        Fail class                         1               5               -                3
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                  Page 44 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                  4189340258H
 No.                           Setting                        Min. setting     Max. setting   Third setting   Factory setting
1160       Over load 1           Selection display                  -               -               -                -
1161       Over load 1           Set-point                       1.0%            200.0%             -            100.0%
1162       Over load 1           Timer                           0.1 s           100.0 s            -             10.0 s
1163       Over load 1           Relay output A                R0 (none)       R0 (none) *          -           R0 (none)
1164       Over load 1           Relay output B                R0 (none)       R0 (none) *          -           R0 (none)
1165       Over load 1           Enable                          OFF               ON             RUN              OFF
1166       Over load 1           Fail class                        1                5               -               2
 No.                           Setting                        Min. setting     Max. setting   Third setting   Factory setting
1170       Over load 2           Selection display                  -               -               -                -
1171       Over load 2           Set-point                       1.0%            200.0%             -            110.0%
1172       Over load 2           Timer                           0.1 s           100.0 s            -              5.0 s
1173       Over load 2           Relay output A                R0 (none)       R0 (none) *          -           R0 (none)
1174       Over load 2           Relay output B                R0 (none)       R0 (none) *          -           R0 (none)
1175       Over load 2           Enable                          OFF               ON             RUN              OFF
1176       Over load 2           Fail class                        1                5               -                3
 No.                           Setting                        Min. setting     Max. setting   Third setting   Factory setting
1220       Current unbalance      Selection display                 -               -               -                -
1221       Current unbalance      Set-point                      0.0%            100.0%             -             30.0%
1222       Current unbalance      Timer                          0.1 s           100.0 s            -             10.0 s
1223       Current unbalance      Relay output A               R0 (none)       R0 (none) *          -           R0 (none)
1224       Current unbalance      Relay output B               R0 (none)       R0 (none) *          -           R0 (none)
1225       Current unbalance      Enable                         OFF               ON             RUN              OFF
1226       Current unbalance      Fail class                       1                5               -               3
 No.                           Setting                        Min. setting     Max. setting   Third setting   Factory setting
1230       Voltage unbalance      Selection display                 -               -               -                -
1231       Voltage unbalance      Set-point                      0.0%            50.0%              -             10.0%
1232       Voltage unbalance      Timer                          0.1 s           100.0 s            -             10.0 s
1233       Voltage unbalance      Relay output A               R0 (none)       R0 (none) *          -           R0 (none)
1234       Voltage unbalance      Relay output B               R0 (none)       R0 (none) *          -           R0 (none)
1235       Voltage unbalance      Enable                         OFF               ON             RUN              OFF
1236       Voltage unbalance      Fail class                       1                5               -               3
1.17.1.10 Generator reactive power import (loss of excitation) protection (option C1)
Settings relate to nominal generator power value (kW).
 No.                           Setting                        Min. setting     Max. setting   Third setting   Factory setting
1240       var import            Selection display                  -               -               -                -
1241       var import            Set-point                       0.0%            150.0%             -             50.0%
1242       var import            Timer                           0.1 s           100.0 s            -             10.0 s
1243       var import            Relay output A                R0 (none)       R0 (none) *          -           R0 (none)
1244       var import            Relay output B                R0 (none)       R0 (none) *          -           R0 (none)
1245       var import            Enable                          OFF               ON             RUN              OFF
1246       var import            Fail class                        1                5               -               2
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                  Page 45 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                            4189340258H
 No.                              Setting                       Min. setting      Max. setting      Third setting    Factory setting
1250    var export                  Selection display                 -                -                  -                 -
1251    var export                  Set-point                      0.0%             100.0%                -              60.0%
1252    var export                  Timer                          0.1 s            100.0 s               -              10.0 s
1253    var export                  Relay output A               R0 (none)        R0 (none) *             -            R0 (none)
1254    var export                  Relay output B               R0 (none)        R0 (none) *             -            R0 (none)
1255    var export                  Enable                         OFF                ON                RUN               OFF
1256    var export                  Fail class                       1                 5                  -                2
NOTE:
Time delay is in periods (per).
 No.                              Setting                       Min. setting      Max. setting       Third setting    Factory setting
1260    df/dt (ROCOF)                Selection display                -                -                   -                 -
1261    df/dt (ROCOF)                Set-point +/-                0.1 Hz/s         10.0 Hz/s               -             5.0 Hz/s
1262    df/dt (ROCOF)                Timer                         1 per            20 per                 -               6 per
1263    df/dt (ROCOF)                Relay output A              R0 (none)        R0 (none) *              -            R0 (none)
1264    df/dt (ROCOF)                Relay output B              R0 (none)        R0 (none) *              -            R0 (none)
1265    df/dt (ROCOF)                Enable                         OFF               ON                 RUN               OFF
1266    df/dt (ROCOF)                Fail class                       1                6                   -                 6
 No.                              Setting                       Min. setting      Max. setting      Third setting     Factory setting
1270    Vector jump                 Selection display                 -                -                  -                  -
1271    Vector jump                 Set-point                     1.0 deg.         90.0 deg.              -              10.0 deg.
1272    Vector jump                 Relay output A               R0 (none)        R0 (none) *             -             R0 (none)
1273    Vector jump                 Relay output B               R0 (none)        R0 (none) *             -             R0 (none)
1274    Vector jump                 Enable                          OFF               ON                RUN                OFF
1275    Vector jump                 Fail class                       1                 6                  -                  6
 No.                              Setting                       Min. setting      Max. setting      Third setting    Factory setting
1400    4…20 mA input 1.1           Selection display                 -                -                  -                 -
1401    4…20 mA input 1.1           Set-point                      4 mA             20 mA                 -              10 mA
1402    4…20 mA input 1.1           Timer                          0.0 s            600.0 s               -              120.0 s
1403    4…20 mA input 1.1           Relay output A               R0 (none)        R0 (none) *             -            R0 (none)
1404    4…20 mA input 1.1           Relay output B               R0 (none)        R0 (none) *             -            R0 (none)
1405    4…20 mA input 1.1           Enable                         OFF                ON                RUN               OFF
1406    4…20 mA input 1.1           Fail class                       1                 5                  -                2
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                          Page 46 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                4189340258H
 No.                         Setting                       Min. setting   Max. setting   Third setting   Factory setting
1410    Oil pressure 1          Selection display                -             -               -                -
1411    Oil pressure 1          Set-point                    0.0 bar       50.0 bar            -             6.0 bar
1412    Oil pressure 1          Timer                         0.0 s         180.0 s            -              5.0 s
1413    Oil pressure 1          Relay output A              R0 (none)     R0 (none) *          -           R0 (none)
1414    Oil pressure 1          Relay output B              R0 (none)     R0 (none) *          -           R0 (none)
1415    Oil pressure 1          Enable                        OFF             ON             RUN              OFF
1416    Oil pressure 1          Fail class                      1              5               -                2
 No.                        Setting                        Min. setting   Max. setting   Third setting   Factory setting
1420    Fuel level 1          Selection display                  -             -               -                -
1421    Fuel level 1          Set-point                       0.0%          120.0%             -             20.0%
1422    Fuel level 1          Timer                           0.0 s         600.0 s            -             120.0 s
1423    Fuel level 1          Relay output A                R0 (none)     R0 (none) *          -           R0 (none)
1424    Fuel level 1          Relay output B                R0 (none)     R0 (none) *          -           R0 (none)
1425    Fuel level 1          Enable                          OFF             ON             RUN              OFF
1426    Fuel level 1          Fail class                        1              5               -               2
 No.                        Setting                        Min. setting   Max. setting   Third setting   Factory setting
1430    4…20 mA input 4.1     Selection display                  -             -               -                -
1431    4…20 mA input 4.1     Set-point                       4 mA          20 mA              -             10 mA
1432    4…20 mA input 4.1     Timer                           0.2 s         100.0 s            -             10.0 s
1433    4…20 mA input 4.1     Relay output A                R0 (none)     R0 (none) *          -           R0 (none)
1434    4…20 mA input 4.1     Relay output B                R0 (none)     R0 (none) *          -           R0 (none)
1435    4…20 mA input 4.1     Enable                          OFF             ON             RUN              OFF
1436    4…20 mA input 4.1     Fail class                        1              5               -               2
 No.                        Setting                        Min. setting   Max. setting   Third setting   Factory setting
1880    4…20 mA input 1.2     Selection display                  -             -               -                -
1881    4…20 mA input 1.2     Set-point                       4 mA          20 mA              -             10 mA
1882    4…20 mA input 1.2     Timer                           0.0 s         600.0 s            -             120.0 s
1883    4…20 mA input 1.2     Relay output A                R0 (none)     R0 (none) *          -           R0 (none)
1884    4…20 mA input 1.2     Relay output B                R0 (none)     R0 (none) *          -           R0 (none)
1885    4…20 mA input 1.2     Enable                          OFF             ON             RUN              OFF
1886    4…20 mA input 1.2     Fail class                        1              5               -               2
 No.                        Setting                        Min. setting   Max. setting   Third setting   Factory setting
1890    Oil pressure 2        Selection display                  -             -               -                -
1891    Oil pressure 2        Set-point                       4 mA          20 mA              -             10 mA
1892    Oil pressure 2        Timer                           0.0 s         600.0 s            -             120.0 s
1893    Oil pressure 2        Relay output A                R0 (none)     R0 (none) *          -           R0 (none)
1894    Oil pressure 2        Relay output B                R0 (none)     R0 (none) *          -           R0 (none)
1895    Oil pressure 2        Enable                          OFF             ON             RUN              OFF
1896    Oil pressure 2        Fail class                        1              5               -               2
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                             Page 47 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                    4189340258H
 No.                          Setting                           Min. setting   Max. setting   Third setting   Factory setting
1900    Fuel level 2            Selection display                     -             -               -                -
1901    Fuel level 2            Set-point                          4 mA          20 mA              -             10 mA
1902    Fuel level 2            Timer                              0.0 s         600.0 s            -             120.0 s
1903    Fuel level 2            Relay output A                   R0 (none)     R0 (none) *          -           R0 (none)
1904    Fuel level 2            Relay output B                   R0 (none)     R0 (none) *          -           R0 (none)
1905    Fuel level 2            Enable                             OFF             ON             RUN              OFF
1906    Fuel level 2            Fail class                           1              5               -               2
 No.                          Setting                           Min. setting   Max. setting   Third setting   Factory setting
1910    4…20 mA input 4.2       Selection display                     -             -               -                -
1911    4…20 mA input 4.2       Set-point                          4 mA          20 mA              -             10 mA
1912    4…20 mA input 4.2       Timer                              0.0 s         600.0 s            -             120.0 s
1913    4…20 mA input 4.2       Relay output A                   R0 (none)     R0 (none) *          -           R0 (none)
1914    4…20 mA input 4.2       Relay output B                   R0 (none)     R0 (none) *          -           R0 (none)
1915    4…20 mA input 4.2       Enable                             OFF             ON             RUN              OFF
1916    4…20 mA input 4.2       Fail class                           1              5               -               2
 No.                          Setting                           Min. setting   Max. setting   Third setting   Factory setting
1440    Water temp.             Selection display                     -             -               -                -
1441    Water temp.             Set-point                          -40°C         250°C              -              80°C
1442    Water temp.             Timer                               0.0 s         5.0 s             -             180.0 s
1443    Water temp.             Relay output A                   R0 (none)     R0 (none) *          -           R0 (none)
1444    Water temp.             Relay output B                   R0 (none)     R0 (none) *          -           R0 (none)
1445    Water temp.             Enable                              OFF            ON             RUN              OFF
1446    Water temp.             Fail class                            1             5               -                2
 No.                          Setting                           Min. setting   Max. setting   Third setting   Factory setting
1450    PT100 input 2           Selection display                     -             -               -                -
1451    PT100 input 2           Set-point                          -40°C         250°C              -              80°C
1452    PT100 input 2           Timer                               0.2 s        100.0 s            -             10.0 s
1453    PT100 input 2           Relay output A                   R0 (none)     R0 (none) *          -           R0 (none)
1454    PT100 input 2           Relay output B                   R0 (none)     R0 (none) *          -           R0 (none)
1455    PT100 input 2           Enable                              OFF            ON             RUN              OFF
1456    PT100 input 2           Fail class                            1             5               -                2
 No.                          Setting                           Min. setting   Max. setting   Third setting   Factory setting
1460    Spare speed level       Selection display                     -             -               -                -
1461    Spare speed level       Set-point                         1 RPM         4000 RPM            -           1450 RPM
1462    Spare speed level       Timer                              0.0 s         100.0 s            -              5.0 s
1463    Spare speed level       Relay output A                   R0 (none)     R0 (none) *          -           R0 (none)
1464    Spare speed level       Relay output B                   R0 (none)     R0 (none) *          -           R0 (none)
1465    Spare speed level       Enable                             OFF             ON             RUN              OFF
1466    Spare speed level       Fail class                           1              5               -                2
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                  Page 48 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                     4189340258H
 No.                          Setting                        Min. setting    Max. setting     Third setting    Factory setting
1470    Overspeed                Selection display                 -              -                 -                 -
1471    Overspeed                Set-point                     1 RPM          2000 RPM              -            1600 RPM
1472    Overspeed                Timer                          0.2 s          100.0 s              -              15.0 s
1473    Overspeed                Relay output A               R0 (none)      R0 (none) *            -            R0 (none)
1474    Overspeed                Relay output B               R0 (none)      R0 (none) *            -            R0 (none)
1475    Overspeed                Enable                         OFF              ON               RUN               OFF
1476    Overspeed                Fail class                       1               5                 -                5
Also take notice of the menu “Remove Starter” set-point, menu 4350.
 No.                          Setting                        Min. setting    Max. setting     Third setting    Factory setting
1490    Engine failure          Selection display                  -              -                 -                 -
1491    Engine failure          Timer                           0.0 s          180.0 s              -              10.0 s
1492    Engine failure          Relay output A                R0 (none)      R0 (none) *            -            R0 (none)
1493    Engine failure          Relay output B                R0 (none)      R0 (none) *            -            R0 (none)
1494    Engine failure          Enable                          OFF              ON               RUN               OFF
1495    Engine failure          Fail class                        1               5                 -                5
 No.                          Setting                        Min. setting    Max. setting     Third setting    Factory setting
1500    Emergency STOP           Selection display                 -              -                 -                 -
1501    Emergency STOP           Timer                          0.0 s          60.0 s               -               2.0 s
1502    Emergency STOP           Relay output A               R0 (none)      R0 (none) *            -            R0 (none)
1503    Emergency STOP           Relay output B               R0 (none)      R0 (none) *            -            R0 (none)
1504    Emergency STOP           Enable                         OFF              ON               RUN               OFF
1505    Emergency STOP           Fail class                       1               5                 -                 2
 No.                          Setting                        Min. setting   Max. setting     Third setting     Factory setting
1510    Dig. input no. 10       Selection display                  -             -                 -                  -
1511    Dig. input no. 10       Timer                           0.0 s         100.0 s              -               10.0 s
1512    Dig. input no. 10       Relay output A                R0 (none)     R0 (none) *            -             R0 (none)
1513    Dig. input no. 10       Relay output B                R0 (none)     R0 (none) *            -             R0 (none)
1514    Dig. input no. 10       Enable                          OFF             ON               RUN                OFF
1515    Dig. input no. 10       Fail class                        1              5                 -                 2
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                   Page 49 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                             4189340258H
 No.                            Setting                  Min. setting     Max. setting   Third setting   Factory setting
1520       Fast overcurr.         Selection display            -               -               -                -
1521       Fast overcurr.         Set-point                50.0%            200.0%             -            150.0%
1522       Fast overcurr.          Timer                    0.0 s           100.0 s            -              0.0 s
1523       Fast overcurr.         Relay output A          R0 (none)       R0 (none) *          -           R0 (none)
1524       Fast overcurr.         Relay output B          R0 (none)       R0 (none) *          -           R0 (none)
1525       Fast overcurr.         Enable                    OFF               ON             RUN               ON
1526       Fast overcurr.          Fail class                 1                5               -                3
 No.                            Setting                  Min. setting     Max. setting   Third setting   Factory setting
1530       High overcurr.         Selection display            -               -               -                -
1531       High overcurr.         Set-point                50.0%            200.0%             -            150.0%
1532       High overcurr.          Timer                    0.1 s           100.0 s            -              1.0 s
1533       High overcurr.         Relay output A          R0 (none)       R0 (none) *          -           R0 (none)
1534       High overcurr.         Relay output B          R0 (none)       R0 (none) *          -           R0 (none)
1535       High overcurr.         Enable                    OFF               ON             RUN               ON
1536       High overcurr.          Fail class                 1                5               -                3
 No.                            Setting                  Min. setting     Max. setting   Third setting   Factory setting
1600       Dig. input no. 11      Selection display            -               -               -                -
1601       Dig. input no. 11      Timer                     0.0 s           100.0 s            -             10.0 s
1602       Dig. input no. 11      Relay output A          R0 (none)       R0 (none) *          -           R0 (none)
1603       Dig. input no. 11      Relay output B          R0 (none)       R0 (none) *          -           R0 (none)
1604       Dig. input no. 11      Enable                    OFF               ON             RUN              OFF
1605       Dig. input no. 11      Fail class                  1                5               -               2
 No.                            Setting                  Min. setting     Max. setting   Third setting   Factory setting
1610       Dig. input no. 12      Selection display            -               -               -                -
1611       Dig. input no. 12      Timer                     0.0 s           100.0 s            -             10.0 s
1612       Dig. input no. 12      Relay output A          R0 (none)       R0 (none) *          -           R0 (none)
1613       Dig. input no. 12      Relay output B          R0 (none)       R0 (none) *          -           R0 (none)
1614       Dig. input no. 12      Enable                    OFF               ON             RUN              OFF
1615       Dig. input no. 12      Fail class                  1                5               -               2
 No.                            Setting                  Min. setting     Max. setting   Third setting   Factory setting
1620       Dig. input no. 13      Selection display            -               -               -                -
1621       Dig. input no. 13      Timer                     0.0 s           100.0 s            -             10.0 s
1622       Dig. input no. 13      Relay output A          R0 (none)       R0 (none) *          -           R0 (none)
1623       Dig. input no. 13      Relay output B          R0 (none)       R0 (none) *          -           R0 (none)
1624       Dig. input no. 13      Enable                    OFF               ON             RUN              OFF
1625       Dig. input no. 13      Fail class                  1                5               -               4
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                             Page 50 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                    4189340258H
 No.                            Setting                         Min. setting   Max. setting     Third setting   Factory setting
1630       Dig. input no. 14      Selection display                   -             -                 -                -
1631       Dig. input no. 14      Timer                            0.0 s         100.0 s              -             10.0 s
1632       Dig. input no. 14      Relay output A                 R0 (none)     R0 (none) *            -           R0 (none)
1633       Dig. input no. 14      Relay output B                 R0 (none)     R0 (none) *            -           R0 (none)
1634       Dig. input no. 14      Enable                           OFF             ON               RUN              OFF
1635       Dig. input no. 14      Fail class                         1              5                 -               2
 No.                            Setting                         Min. setting   Max. setting     Third setting   Factory setting
1640       Dig. input no. 15      Selection display                   -             -                 -                -
1641       Dig. input no. 15      Timer                            0.0 s         100.0 s              -             10.0 s
1642       Dig. input no. 15      Relay output A                 R0 (none)     R0 (none) *            -           R0 (none)
1643       Dig. input no. 15      Relay output B                 R0 (none)     R0 (none) *            -           R0 (none)
1644       Dig. input no. 15      Enable                           OFF             ON               RUN              OFF
1645       Dig. input no. 15      Fail class                         1              5                 -               2
 No.                            Setting                         Min. setting   Max. setting     Third setting   Factory setting
1650       Dig. input no. 16      Selection display                   -             -                 -                -
1651       Dig. input no. 16      Timer                            0.0 s         100.0 s              -             10.0 s
1652       Dig. input no. 16      Relay output A                 R0 (none)     R0 (none) *            -           R0 (none)
1653       Dig. input no. 16      Relay output B                 R0 (none)     R0 (none) *            -           R0 (none)
1654       Dig. input no. 16      Enable                           OFF             ON               RUN              OFF
1655       Dig. input no. 16      Fail class                         1              5                 -               2
 No.                            Setting                         Min. setting   Max. setting     Third setting   Factory setting
1660       Dig. input no. 17      Selection display                   -             -                 -                -
1661       Dig. input no. 17      Timer                            0.0 s         100.0 s              -             10.0 s
1662       Dig. input no. 17      Relay output A                 R0 (none)     R0 (none) *            -           R0 (none)
1663       Dig. input no. 17      Relay output B                 R0 (none)     R0 (none) *            -           R0 (none)
1664       Dig. input no. 17      Enable                           OFF             ON               RUN              OFF
1665       Dig. input no. 17      Fail class                         1              5                 -               2
 No.                            Setting                         Min. setting   Max. setting     Third setting   Factory setting
1670       Dig. input no. 18      Selection display                   -              -                -                -
1671       Dig. input no. 18      Timer                            0.0 s         100.0 s              -             10.0 s
1672       Dig. input no. 18      Relay output A                 R0 (none)     R8 (relay 8) *         -           R0 (none)
1673       Dig. input no. 18      Relay output B                 R0 (none)     R8 (relay 8) *         -           R0 (none)
1674       Dig. input no. 18      Enable                           OFF              ON              RUN              OFF
1675       Dig. input no. 18      Fail class                         1               5                -               5
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                    Page 51 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                               4189340258H
 No.                            Setting                  Min. setting     Max. setting     Third setting   Factory setting
1680       Dig. input no. 19      Selection display            -                -                -                -
1681       Dig. input no. 19      Timer                     0.0 s           100.0 s              -             10.0 s
1682       Dig. input no. 19      Relay output A          R0 (none)       R8 (relay 8) *         -           R0 (none)
1683       Dig. input no. 19      Relay output B          R0 (none)       R8 (relay 8) *         -           R0 (none)
1684       Dig. input no. 19      Enable                    OFF                ON              RUN              OFF
1685       Dig. input no. 19      Fail class                  1                 5                -               2
 No.                            Setting                  Min. setting     Max. setting     Third setting   Factory setting
1690       Dig. input no. 20      Selection display            -                -                -                -
1691       Dig. input no. 20      Timer                     0.0 s           100.0 s              -             10.0 s
1692       Dig. input no. 20      Relay output A          R0 (none)       R8 (relay 8) *         -           R0 (none)
1693       Dig. input no. 20      Relay output B          R0 (none)       R8 (relay 8) *         -           R0 (none)
1694       Dig. input no. 20      Enable                    OFF                ON              RUN              OFF
1695       Dig. input no. 20      Fail class                  1                 5                -               2
 No.                            Setting                  Min. setting     Max. setting     Third setting   Factory setting
1700       Dig. input no. 21      Selection display            -                -                -                -
1701       Dig. input no. 21      Timer                     0.0 s           100.0 s              -             10.0 s
1702       Dig. input no. 21      Relay output A          R0 (none)       R8 (relay 8) *         -           R0 (none)
1703       Dig. input no. 21      Relay output B          R0 (none)       R8 (relay 8) *         -           R0 (none)
1704       Dig. input no. 21      Enable                    OFF                ON              RUN              OFF
1705       Dig. input no. 21      Fail class                  1                 5                -               2
 No.                            Setting                  Min. setting     Max. setting     Third setting   Factory setting
1710       Dig. input no. 22      Selection display            -                -                -                -
1711       Dig. input no. 22      Timer                     0.0 s           100.0 s              -             10.0 s
1712       Dig. input no. 22      Relay output A          R0 (none)       R8 (relay 8) *         -           R0 (none)
1713       Dig. input no. 22      Relay output B          R0 (none)       R8 (relay 8) *         -           R0 (none)
1714       Dig. input no. 22      Enable                    OFF                ON              RUN              OFF
1715       Dig. input no. 22      Fail class                  1                 5                -               2
 No.                            Setting                  Min. setting     Max. setting     Third setting   Factory setting
1720       Dig. input no. 23      Selection display            -                -                -                -
1721       Dig. input no. 23      Timer                     0.0 s           100.0 s              -             10.0 s
1722       Dig. input no. 23      Relay output A          R0 (none)       R8 (relay 8) *         -           R0 (none)
1723       Dig. input no. 23      Relay output B          R0 (none)       R8 (relay 8) *         -           R0 (none)
1724       Dig. input no. 23      Enable                    OFF                ON              RUN              OFF
1725       Dig. input no. 23      Fail class                  1                 5                -               5
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                               Page 52 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                               4189340258H
 No.                            Setting                  Min. setting     Max. setting     Third setting   Factory setting
1730       Dig. input no. 24      Selection display            -                -                -                -
1731       Dig. input no. 24      Timer                     0.0 s           100.0 s              -             10.0 s
1732       Dig. input no. 24      Relay output A          R0 (none)       R8 (relay 8) *         -           R0 (none)
1733       Dig. input no. 24      Relay output B          R0 (none)       R8 (relay 8) *         -           R0 (none)
1734       Dig. input no. 24      Enable                    OFF                ON              RUN              OFF
1735       Dig. input no. 24      Fail class                  1                 5                -               2
 No.                            Setting                  Min. setting     Max. setting     Third setting   Factory setting
1740       Dig. input no. 25      Selection display            -                -                -                -
1741       Dig. input no. 25      Timer                     0.0 s           100.0 s              -             10.0 s
1742       Dig. input no. 25      Relay output A          R0 (none)       R8 (relay 8) *         -           R0 (none)
1743       Dig. input no. 25      Relay output B          R0 (none)       R8 (relay 8) *         -           R0 (none)
1744       Dig. input no. 25      Enable                    OFF                ON              RUN              OFF
1745       Dig. input no. 25      Fail class                  1                 5                -               2
 No.                            Setting                  Min. setting     Max. setting     Third setting   Factory setting
1750       Dig. input no. 26      Selection display            -                -                -                -
1751       Dig. input no. 26      Timer                     0.0 s           100.0 s              -             10.0 s
1752       Dig. input no. 26      Relay output A          R0 (none)       R8 (relay 8) *         -           R0 (none)
1753       Dig. input no. 26      Relay output B          R0 (none)       R8 (relay 8) *         -           R0 (none)
1754       Dig. input no. 26      Enable                    OFF                ON              RUN              OFF
1755       Dig. input no. 26      Fail class                  1                 5                -               2
 No.                            Setting                  Min. setting     Max. setting     Third setting   Factory setting
1760       Dig. input no. 27      Selection display            -                -                -                -
1761       Dig. input no. 27      Timer                     0.0 s           100.0 s              -             10.0 s
1762       Dig. input no. 27      Relay output A          R0 (none)       R8 (relay 8) *         -           R0 (none)
1763       Dig. input no. 27      Relay output B          R0 (none)       R8 (relay 8) *         -           R0 (none)
1764       Dig. input no. 27      Enable                    OFF                ON              RUN              OFF
1765       Dig. input no. 27      Fail class                  1                 5                -               2
 No.                            Setting                  Min. setting     Max. setting     Third setting   Factory setting
1770       Dig. input no. 28      Selection display            -                -                -                -
1771       Dig. input no. 28      Timer                     0.0 s           100.0 s              -             10.0 s
1772       Dig. input no. 28      Relay output A          R0 (none)       R8 (relay 8) *         -           R0 (none)
1773       Dig. input no. 28      Relay output B          R0 (none)       R8 (relay 8) *         -           R0 (none)
1774       Dig. input no. 28      Enable                    OFF                ON              RUN              OFF
1775       Dig. input no. 28      Fail class                  1                 5                -               4
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                               Page 53 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                 4189340258H
 No.                           Setting                       Min. setting   Max. setting     Third setting   Factory setting
1780       Dig. input no. 29     Selection display                 -              -                -                -
1781       Dig. input no. 29     Timer                          0.0 s         100.0 s              -             10.0 s
1782       Dig. input no. 29     Relay output A               R0 (none)     R8 (relay 8) *         -           R0 (none)
1783       Dig. input no. 29     Relay output B               R0 (none)     R8 (relay 8) *         -           R0 (none)
1784       Dig. input no. 29     Enable                         OFF              ON              RUN              OFF
1785       Dig. input no. 29     Fail class                       1               5                -               2
 No.                           Setting                       Min. setting   Max. setting     Third setting   Factory setting
1790       Dig. input no. 30     Selection display                 -              -                -                -
1791       Dig. input no. 30     Timer                          0.0 s         100.0 s              -             10.0 s
1792       Dig. input no. 30     Relay output A               R0 (none)     R8 (relay 8) *         -           R0 (none)
1793       Dig. input no. 30     Relay output B               R0 (none)     R8 (relay 8) *         -           R0 (none)
1794       Dig. input no. 30     Enable                         OFF              ON              RUN              OFF
1795       Dig. input no. 30     Fail class                       1               5                -               2
 No.                           Setting                       Min. setting   Max. setting     Third setting   Factory setting
1800     4…20 mA input 5         Selection display                 -             -                 -                -
1801     4…20 mA input 5         Set-point                      4 mA          20 mA                -             10 mA
1802     4…20 mA input 5         Timer                          0.0 s         600.0 s              -             120.0 s
1803     4…20 mA input 5         Relay output A               R0 (none)     R0 (none) *            -           R0 (none)
1804     4…20 mA input 5         Relay output B               R0 (none)     R0 (none) *            -           R0 (none)
1805     4…20 mA input 5         Enable                         OFF             ON               RUN              OFF
1806     4…20 mA input 5         Fail class                       1              5                 -               2
 No.                           Setting                       Min. setting   Max. setting     Third setting   Factory setting
1810     4…20 mA input 6         Selection display                 -             -                 -                -
1811     4…20 mA input 6         Set-point                      4 mA          20 mA                -             10 mA
1812     4…20 mA input 6         Timer                          0.0 s         600.0 s              -             120.0 s
1813     4…20 mA input 6         Relay output A               R0 (none)     R0 (none) *            -           R0 (none)
1814     4…20 mA input 6         Relay output B               R0 (none)     R0 (none) *            -           R0 (none)
1815     4…20 mA input 6         Enable                         OFF             ON               RUN              OFF
1816     4…20 mA input 6         Fail class                       1              5                 -               2
 No.                           Setting                       Min. setting   Max. setting     Third setting   Factory setting
1820     4…20 mA input 7         Selection display                 -             -                 -                -
1821     4…20 mA input 7         Set-point                      4 mA          20 mA                -             10 mA
1822     4…20 mA input 7         Timer                          0.0 s         600.0 s              -             120.0 s
1823     4…20 mA input 7         Relay output A               R0 (none)     R0 (none) *            -           R0 (none)
1824     4…20 mA input 7         Relay output B               R0 (none)     R0 (none) *            -           R0 (none)
1825     4…20 mA input 7         Enable                         OFF             ON               RUN              OFF
1826     4…20 mA input 7         Fail class                       1              5                 -               2
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                 Page 54 of 121
                DESIGNERS REFERENCE HANDBOOK
                Automatic Gen-set Controller, multi-line 2                                                4189340258H
 No.                        Setting                       Min. setting    Max. setting   Third setting   Factory setting
1830   4…20 mA input 8        Selection display                 -              -               -                -
1831   4…20 mA input 8        Set-point                      4 mA           20 mA              -             10 mA
1832   4…20 mA input 8        Timer                          0.0 s          600.0 s            -             120.0 s
1833   4…20 mA input 8        Relay output A               R0 (none)      R0 (none) *          -           R0 (none)
1834   4…20 mA input 8        Relay output B               R0 (none)      R0 (none) *          -           R0 (none)
1835   4…20 mA input 8        Enable                         OFF              ON             RUN              OFF
1836   4…20 mA input 8        Fail class                       1               5               -               2
 No.                        Setting                       Min. setting    Max. setting   Third setting   Factory setting
1840   4…20 mA input 5        Selection display                 -              -               -                -
1841   4…20 mA input 5        Set-point                      4 mA           20 mA              -             10 mA
1842   4…20 mA input 5        Timer                          0.0 s          600.0 s            -             120.0 s
1843   4…20 mA input 5        Relay output A               R0 (none)      R0 (none) *          -           R0 (none)
1844   4…20 mA input 5        Relay output B               R0 (none)      R0 (none) *          -           R0 (none)
1845   4…20 mA input 5        Enable                         OFF              ON             RUN              OFF
1846   4…20 mA input 5        Fail class                       1               5               -               2
 No.                        Setting                       Min. setting    Max. setting   Third setting   Factory setting
1850   4…20 mA input 6        Selection display                 -              -               -                -
1851   4…20 mA input 6        Set-point                      4 mA           20 mA              -             10 mA
1852   4…20 mA input 6        Timer                          0.0 s          600.0 s            -             120.0 s
1853   4…20 mA input 6        Relay output A               R0 (none)      R0 (none) *          -           R0 (none)
1854   4…20 mA input 6        Relay output B               R0 (none)      R0 (none) *          -           R0 (none)
1855   4…20 mA input 6        Enable                         OFF              ON             RUN              OFF
1856   4…20 mA input 6        Fail class                       1               5               -               2
 No.                        Setting                       Min. setting    Max. setting   Third setting   Factory setting
1860   4…20 mA input 7        Selection display                 -              -               -                -
1861   4…20 mA input 7        Set-point                      4 mA           20 mA              -             10 mA
1862   4…20 mA input 7        Timer                          0.0 s          600.0 s            -             120.0 s
1863   4…20 mA input 7        Relay output A               R0 (none)      R0 (none) *          -           R0 (none)
1864   4…20 mA input 7        Relay output B               R0 (none)      R0 (none) *          -           R0 (none)
1865   4…20 mA input 7        Enable                         OFF              ON             RUN              OFF
1866   4…20 mA input 7        Fail class                       1               5               -               2
 No.                        Setting                       Min. setting    Max. setting   Third setting   Factory setting
1870   4…20 mA input 8        Selection display                 -              -               -                -
1871   4…20 mA input 8        Set-point                      4 mA           20 mA              -             10 mA
1872   4…20 mA input 8        Timer                          0.0 s          600.0 s            -             120.0 s
1873   4…20 mA input 8        Relay output A               R0 (none)      R0 (none) *          -           R0 (none)
1874   4…20 mA input 8        Relay output B               R0 (none)      R0 (none) *          -           R0 (none)
1875   4…20 mA input 8        Enable                         OFF              ON             RUN              OFF
1876   4…20 mA input 8        Fail class                       1               5               -               2
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                             Page 55 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                          4189340258H
The 3 inputs are pre-defined, for pressure (1), temperature (2) and fuel tank level (3). The name texts can be changed in the PC utility
software.
Curve:
Resistance
(Ohm)
  4
  3
  2
  1       1      2      3       4       5      6       7       8           Value
                                                                           (Bar or deg.C
                                                                           or %)
NOTE:
The 8 curve settings for VDO no. 1, 2 and 3 cannot be changed in the display, only in the PC utility software. The alarm settings can
be changed both in display and PC utility software.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                          Page 56 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                       4189340258H
1. After the time delay expires all the alarms above which are selected to “RUN” will be enabled.
   2. An output relay can be selected if available. In that case the settings Output A and Output B must be selected to the desired
      relay; typically the function of this relay must be selected to “Limit” function to avoid a “RUN STATUS ALARM” when the gen-
      set starts. Refer to menus 4600 ff.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                       Page 57 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                             4189340258H
If dynamic synchronisation is chosen, the next menu will be 2020. If static synchronisation is chosen, the next menu will be 2030.
The “dU max.” setting is related to nominal generator voltage. The “dU max.“ setting is +/- nominal generator voltage.
The multi-line 2 compensates for the breaker delay time when synchronising.
Refer to paragraph 1.17.10 for further explanation of the PI controller settings (KP and KI).
Synchronisation will happen when the generator voltage is within the close window and the frequency difference is within the df and
dU settings. (See illustration on the next page).
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                             Page 58 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                            4189340258H
Max dU UBB
UGEN
If blackout closing of breaker is enabled on more units, external precautions must be taken to avoid two or more generators closing
on a black busbar. In that case synchronism will not be present.
Each controller consists of a proportional factor, KP, and an integral factor, KI.
The proportional factor, KP, decides the size of the proportional part at a regulation deviation, and the integral factor, KI, decides the
integral part. The individual function of KP and KI is described in the drawings on the next page. The drawings show the change of the
output when the input value deviates from the set-point, e.g. because of a frequency change.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                            Page 59 of 121
                DESIGNERS REFERENCE HANDBOOK
                Automatic Gen-set Controller, multi-line 2                                                  4189340258H
Drawing 1
Output
I-part
P-part Time
Output Output
P-part
                                                   Time                                                          Time
  The P-part of the output can be changed by                    The P-part of the output can be changed by
  changing the KP factor. Increasing KP increases the           changing the KP factor. Decreasing KP decreases the
  P-part.                                                       P-part of the regulation.
Output Output
I-part
                                                              I-part
Time Time
  The I-part of the output can be changed by changing           The I-part of the output can be changed by changing
  the KI factor. Increasing the KI factor makes the             the KI factor. Decreasing the KI factor makes the
  regulation faster.                                            regulation slower.
DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                Page 60 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                              4189340258H
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                            Page 61 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                                 4189340258H
var deadband % settings relate to nominal generator power value, i.e. it is assumed that the generator var value is the same as the
kW value. This is not correct, but the assumption is made for control purposes only.
The var controller is active when the generator is parallel to mains controlling the PF.
   •   (2201) PWM min. This is the minimum output level of the PWM signal. Default it is set to 10%.
   •   (2202) PWM init. This is the initial output level which is the level where the PWM signal will start the regulation. Default it is set
       to 35%.
   •   (2203) PWM max. This is the maximum output level of the PWM signal. Default it is set to 90%.
   •   (2204) Enable. This sets the PWM on or off. If it is disabled the PWM output PCB will work as option EF4 (see option EF4
       below), until it is enabled again. Default setting of the output is enabled (ON).
   •   (2205) Droop duty cycle. The second PWM output must be used to let the cat governor operate in speed droop.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                              Page 62 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                              4189340258H
The PWM signal has a frequency of 500 +/-50Hz. The resolution of the duty cycle is 12 bits which gives the output 4095 different
levels. The output is an open collector output with a 1k-ohm pull-up resistor.
The low level of the signal is between 0 and 0.05 volt and the high level is between 5.7 and 6 volt.
Channel 2210 is only available if the PWM output is OFF in channel 2204.
If relay outputs are used, it is necessary to adjust a relay minimum ON time and a regulation period time. This adjustment can be
done on both the GOV and the AVR outputs. Diagrams 6 and 7 show the principle of the relay control.
When using relay control outputs it is also necessary to tune in the PI controller set-points, KP and KI. Higher value (for both) = faster
(and more unstable) control.
This setting is used to tune in the GOV ON time when relay outputs are being used for control. The total relay ON time will depend on
the deviation from the set-point. tN is the minimum time the relay can be activated.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                            Page 63 of 121
                DESIGNERS REFERENCE HANDBOOK
                Automatic Gen-set Controller, multi-line 2                                                         4189340258H
Set-point deviation
           Relay
           pulses
                                                                                                     Time
  Deadband
The diagram shows that the length of the relay pulses is depending on the deviation from the set-point. The minimum relay output
(close to the deadband) is equal to the setting tN, the maximum relay output is constantly ON.
Relay output
tP
tN
Relay activated
  Relay deactivated
                                                                                                        Time
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                      Page 64 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                          4189340258H
It is possible to have two set-points, a daytime and a nighttime set-point. The purpose of this is to adapt the mains import to the
different load conditions in different periods.
The AGC needs a 4...20 mA signal on terminal 98-99 from a power transducer, measuring the imported power from the mains. The
calibration of the power transducer must be:
    • 4 mA        = 0.0 MW
    • 20 mA       = Transducer scale, set-point in channel 3013
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                        Page 65 of 121
                    DESIGNERS REFERENCE HANDBOOK
                    Automatic Gen-set Controller, multi-line 2                                                   4189340258H
The test mode is activated by selecting TEST with the “MODE” pushbutton on the display. The TEST mode can be used in peak
shaving and AMF mode. After the test run the AGC returns to AUTO operation.
1.17.12.7 Fixed power set-point (set-point for active generator power and power factor)
The fixed power set-points are used when the AGC is configured to fixed power operation. The PF (power factor) set-point is used
when the generator is running parallel to mains.
The mains power SET-POINT is the REFERENCE POINT (3091/3092) * START GEN MPE.
Example:
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                    Page 66 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                                4189340258H
The minimum load set-point (menu 3103) is used when the gen-set is paralleling to another generator and this generator (e.g. a
windmill) is exporting the load equal to or higher than the mains power export set-point (menu 3091/3092).
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                          Page 67 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                           4189340258H
NOTE:
Selecting communication control ON will overrule external and internal settings.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                         Page 68 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                           4189340258H
1.17.14 Enable ID
If an AGC unit for some reason is disconnected, a “CAN ID x missing” alarm will occur. To deactivate the alarm it is necessary to
disable the ID number (channel 4080) in all the other enabled AGCs. When the disconnected unit is put back into operation it is
automatically enabled.
The alarm is for the auxiliary power supply. To avoid damage of the multi-line 2 AGC it is necessary to use a 1 A fuse if the
voltage is able to fall below 15 VDC.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                         Page 69 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                             4189340258H
1.17.14.5 Language
The functionality of the multi-line 2 AGC is depending on the running mode setup.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                           Page 70 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                             4189340258H
In “SEMI-AUTO” mode the gen-set follows the peak shaving load curve but it does not start/stop when the start/stop limit is reached.
The two breakers (MB and GB) will not react automatically but only by using the two breaker pushbuttons.
Using the peak shaving mode it is possible to select between two different peak shaving sequences by using menu 4430 “MB
control”.
The first sequence (mode shift off) is a mode which only reacts on the peak shaving sequence. If a mains failure occurs, the MB will
open and the gen-set will cool down and stop.
The second sequence (peak – AMF – peak) is a mode which reacts on the peak shaving sequence but also reacts as AMF mode if a
mains failure occurs. The normal operation is peak shaving. At a mains failure it changes to AMF operation and finally it returns to
peak shaving operation when the mains supply is restored.
In the mains power export mode the AGC requires a binary start command to start up the gen-set.
Single gen-set:
Requires a binary start command to start. The mains power export set-point will be the reference point (3091/3092) multiplied with the
start up percentage (3101).
Multiple gen-set:
This could e.g. be when paralleling to a windmill. Then the AGC will control its gen-set according to the total exported power.
The mains power export set-point of the AGC will be the reference point (3091/3092) multiplied with the start up percentage (3101).
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                           Page 71 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                            4189340258H
                 Power import
                                                   Windmill power
                                                   Mains export power
                                                   DG power
Start
Stop
Power export
NOTE:
In the drawing above the graphics for the mains export power and the windmill power are displaced a little when the mains power
export decreases, until the gen-set starts and when the mains power export increases. This is for illustrative reasons.
NOTE:
A 4…20 mA transducer is needed as an indication of the actual mains load.
The load take over mode can be combined with the short time paralleling function (menu 4940).
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                          Page 72 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                          4189340258H
    •   START sequence
    •   GB ON sequence
    •   GB OFF sequence
    •   MB ON sequence
    •   MB OFF sequence
    •   STOP sequence
Breaker sequences - the multi-line 2 AGC is able to control the breakers in the system:
If island operation is selected, it is necessary to make a short circuit on terminal 24 (mains breaker open). A “Mains breaker failure”
will occur if the connection is not made.
The “remove starter” set-point is used to deactivate the start relay. The number of teeth is used to configure the tacho input. This
function can also be used with a digital input.
The settings “start prepare”, “start ON time” and “start OFF time” are the periods the relays on the engine interface card slot #7 are
activated.
The start prepare output can e.g. be used for prelubricating or preheating. The start relay output is for activating the starter of the
engine. The start sequence can be activated manually by pressing the “START” pushbutton in SEMI-AUTO.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                         Page 73 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                              4189340258H
            The automatic start sequence - here programmed to max. 3 start attempts, but the engine starts
                                             during the second attempt.
If the gen-set does not start after the last start attempt, a start failure alarm is activated. The start sequence can be stopped manually
by pressing the “STOP” pushbutton if SEMI-AUTO mode is selected.
1.17.15.2 GB ON sequence
The GB ON sequence will synchronise and/or close the generator breaker. The breaker is closed directly without synchronising if the
mains breaker is open or if no mains breaker is present (island mode), if the voltage on the busbar/mains is not present.
The GB ON sequence is automatically initiated (except in SEMI-AUTO mode) when the automatic start sequence has been
completed and the engine is running.
In SEMI-AUTO mode the operator may initiate the GB ON sequence by pressing the "GB" pushbutton on the display.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                            Page 74 of 121
                  DESIGNERS REFERENCE HANDBOOK
                  Automatic Gen-set Controller, multi-line 2                                                       4189340258H
    •   Synchronisation alarm
    •   GB ON alarm
    •   GB pushbutton pressed in SEMI-AUTO
    •   f/U failure
In SEMI-AUTO mode the operator may initiate the GB OFF sequence by pressing the "GB" pushbutton on the display.
    • A DELOAD alarm
    • A GB OFF alarm
    • GB pushbutton is pressed in SEMI-AUTO mode
1.17.15.4 MB ON sequence
The MB ON sequence will synchronise and/or close the mains breaker.
In AUTO mode the MB ON sequence is automatically initiated if the multi-line 2 AGC is in AMF operation and the mains returns after
a mains failure. In peak shaving mode the MB ON sequence is automatically initiated when the mains is OK.
If the generator breaker is open and the mains is present the MB will be closed immediately in AUTO mode.
In SEMI-AUTO mode the operator may initiate the MB ON sequence by pressing the "MB" pushbutton on the display. Pressing the
MB pushbutton in SEMI-AUTO will close the MB immediately, if the GB is open and the mains is present.
    • No active MB alarms
    • Mains OK
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                      Page 75 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                             4189340258H
    • MB OFF alarm
    • Pressing the MB pushbutton in SEMI-AUTO operation
The stop sequence is carried out when the multi-line 2 AGC has completed the GB OFF sequence and the generator breaker is open.
In AUTO mode the stop sequence is initiated automatically. In SEMI-AUTO mode a stop command with the "STOP" pushbutton will
stop the engine without cooling down. If the generator is running with the generator breaker closed and the “STOP” pushbutton is
pressed, the generator is opened without deloading, and the engine is stopped without cooling down.
A start command will interrupt an ongoing cool down period and leave the engine in idle speed. A GB ON signal will synchronise and
close the breaker.
A stop failure is displayed if the running feedback signal or the generator voltage and frequency are still present.
If the coil type is configured as “running coil”, the stop relay will be energized during starting and running and de-energized during
stopping.
STOP parameters
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                           Page 76 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                           4189340258H
    • MB is opened
    • Start sequence is initiated
    • GB is closed
In case of MB open fail the sequence is stopped and an “MB OPEN FAILURE” alarm is displayed.
When the mains returns, the change over sequence is started. The sequence is started when the timer “MAINS OK DELAY” expires:
    •   MB is synchronised
    •   GB is de-loaded (if parallel running is allowed – channel 4425)
    •   GB is opened
    •   Stop sequence is initiated
In case of a sequence alarm the sequence will be stopped. If GB OFF fail and parallel running is not allowed, the MB is opened.
For description of mode shift in combination with the peak shaving operation, please refer to chapter 1.17.14.10.
All modes can handle the mode shift function. The mode shift will be active when the unit is in auto. The function is that the AGC
automatically goes into Automatic Mains Failure mode at a mains failure situation. The AGC will start up and supply the load. When
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                         Page 77 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                        4189340258H
the mains returns, the AGC goes to mains supply (black change over or synchronising) and subsequently returns to the original
mode.
The setting is the maximum time the horn is sounding at an alarm. If the setting is adjusted to 0 s, the horn will sound continuously
until the alarm is acknowledged.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                        Page 78 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                           4189340258H
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                         Page 79 of 121
                  DESIGNERS REFERENCE HANDBOOK
                  Automatic Gen-set Controller, multi-line 2                                                         4189340258H
Alarm relay function: When an alarm activates the relay, it is activated as long as the alarm is present and unacknowledged.
Limit function:                When an alarm activates the relay, no alarm message is displayed. After the condition activating this
                               relay has returned to normal, the relay will deactivate when the “Off delay” has expired.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                        Page 80 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                          4189340258H
The relays 9-10 are available if options D1 and D2 are not selected and analogue governor outputs are not used.
                       ®
1.17.19.9 Caterpillar CCM setup (option H4)
The setup of the lists is done in the same way as list 1, channel 4770. The following lists are available:
The short time paralleling can be used in the load take over mode and the AMF mode. Be aware that the test function will still parallel
to the mains, no matter the adjustment of the above setting.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                         Page 81 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                         4189340258H
In the alarm selection you can see all the alarm timers and their remaining time if they are counting.
The input and output selections show the present status of the inputs and outputs. E.g. mode inputs, relay outputs and load sharing
lines.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                       Page 82 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                           4189340258H
Frequency: 30…70 Hz
Measuring current: From current transformers …/1 A or …/5 A. Consumption max. 0.3 VA per phase
Binary inputs: Input voltage 12…32 VDC. Impedance 2.4 kΩ, bi-directional
Safety: To EN 61010-1 installation category (overvoltage category) III, 600 V, pollution degree 2
Galvanic separation:       Between AC voltage, AC current and other I/Os: 3250 VAC – 50 Hz – 1 min. Between analogue outputs:
                           500 VDC – 1 min.
Response times: From the set-point is reached till the output is activated and the delay set to 0.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                           Page 83 of 121
               DESIGNERS REFERENCE HANDBOOK
               Automatic Gen-set Controller, multi-line 2                       4189340258H
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]   Page 84 of 121
               DESIGNERS REFERENCE HANDBOOK
               Automatic Gen-set Controller, multi-line 2                       4189340258H
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]   Page 85 of 121
              DESIGNERS REFERENCE HANDBOOK
              Automatic Gen-set Controller, multi-line 2                       4189340258H
2 Modbus protocol
DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]   Page 86 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                             4189340258H
The Modbus Protocol establishes the format for the master's query by placing into it the device address, a function code defining the
requested action, any data to be sent and an error checking field. The slave's response message is also constructed using Modbus
Protocol. It contains fields confirming the action taken, any data to be returned and an error checking field. If an error occurred on
receipt of the message, an exception response is generated in the slave.
                 Query                                                                 Response
                 Device address                                                        Device address
                 Function                                                              Function
                 Eight-bit                                                             Eight-bit
                 data byte                                                             data byte
The query
The function code in the query tells the addressed slave device what kind of action to perform. The data bytes contain any additional
information that the slave will need to perform the function. For example, function code 03 will query the slave to read registers and
respond with their contents. The data field must contain the information telling the slave which register to start at and how many
registers to read. The error check field provides a method for the slave to validate the integrity of the message contents.
The response
If the slave makes a normal response, the function code in the response is an echo of the function code in the query. The data bytes
contain the data collected by the slave, such as register values or status. If an error occurs, the function code is modified to indicate
that the response is an error response and the data bytes contain a code that describes the error. The error check field allows the
master to confirm that the message contents are valid.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                           Page 87 of 121
                  DESIGNERS REFERENCE HANDBOOK
                  Automatic Gen-set Controller, multi-line 2                                                            4189340258H
before completion of the frame, the receiving device flushes the incomplete message and assumes that the next byte will be the
address field of a new message.
Similarly, if a new message begins earlier than 3.5 character times following a previous message, the receiving device will consider it
a continuation of the previous message. This will set an error, as the value in the final CRC field will not be valid for the combined
messages. A typical message frame is shown below.
Start 1 2 3 4 5 6 7 8 Stop
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                           Page 88 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                                4189340258H
2.2 Functions
The query message specifies the starting flag and quantity of flags to be read. Example of a query to read 10...22 from multi-line 2
slave device 4:
Response
The flag status response message is packed as one flag per bit of the data field. Status is indicated as: 1 is the value ON, and 0 is the
value OFF. The LSB of the first data byte contains the flag addressed in the query. The other flags follow toward the high-order end of
this byte and from low order to high order in subsequent bytes. If the returned flag quantity is not a multiple of eight, the remaining bits
in the final data byte will be padded with zeroes (toward the high-order end of the byte). The byte count field specifies the quantity of
complete bytes of data.
The status of flags 17...10 is shown as the byte value 0A hex or binary 00001010. Flag 17 is the MSB of this byte, and flag 10 is the
LSB. Left to right, the status of flags 17...10 is:
OFF-OFF-OFF-OFF-ON-OFF-ON-OFF.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                              Page 89 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                            4189340258H
Query
The query message specifies the starting register and quantity of registers to be read. Example of a request to read 0...1 from multi-
line 2 slave device 1:
Response
The register data in the response message are packed as two bytes per register, with the binary contents right justified within each
byte. For each register the first byte contains the high-order bits, and the second contains the low-order bits.
The contents of register 0 are shown as the two byte values of 00 06 hex. The contents of register 1 are 00 05 hex.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                          Page 90 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                           4189340258H
Query
The query message specifies the flag references to be forced.
The requested ON/OFF status is specified by contents of the query data field. A logical 1 in a bit position of the field requests the
corresponding flag to be ON - A logical = requests it to be OFF. The following page shows an example of a request to force a series
of ten flags stating a flag in slave device 1. The query data contents are two bytes: 01 04 hex (1001 0000 binary). The binary bits
correspond to the flags in the following way:
Bit: 0 1 1 0 0 0 0 0 1 0 0 1 0 0 0 0
Flag: 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
The first byte transmitted (0 hex) addresses flags 7...0, with the least significant bit addressing the lowest flag (0) in this set.
The next byte transmitted (01 hex) addresses flags 14 and 8, with the least significant bit addressing the lowest flag (8) in the set.
Unused bits in the last data byte should be zero-filled.
Response
The normal response returns the slave address, function code, starting address and quantity of flags forced. Here is an example of a
response to the query shown above.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                        Page 91 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                                 4189340258H
Example of a request to preset two registers starting at timer no to 00 60 and 00 70 hex, in slave multi-line 2 device 1:
Response
The normal response returns the slave address. Function code, starting address and quantity of registers preset.
2.3 Exception
If the slave device receives the query without a communication error and can handle the query normally, it returns a normal response.
If the slave does not receive the query due to a communication error, no response is returned. The master program will eventually
process a time-out condition for the query.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                            Page 92 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                             4189340258H
If the slave receives the query, but detects a communication error (CRC), no response is returned. The master program will eventually
process a time-out condition for the query.
If the slave receives the query without a communication error, but cannot handle it (for example if the request is to read a non-existent
register), the slave will return an exception response informing the master of the nature of the error.
The exception response message has two fields that differentiate it from a normal response:
Function code field: In a normal response the slave echoes the function code of the original query in the function code field of the
response. All function codes have a most-significant bit (MSB) of 0. This makes the function code value in an exception response
exactly 80 hexadecimal higher than the value would be for a normal response.
With the function code's MSB set, the master's application program can recognize the exception response and can examine the data
field for the exception code.
Data field: In a normal response the slave may return data or statistics in the data field (any information that was requested in the
query). In an exception response the slave returns an exception code in the data field. This defines the slave condition that caused
the exception.
Query
Response
The master addresses a query to slave device 01h. The function code (03) is for a Read Registers, it requests the status of the
register at an address which is out of range.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                           Page 93 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                      4189340258H
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                      Page 94 of 121
               DESIGNERS REFERENCE HANDBOOK
               Automatic Gen-set Controller, multi-line 2                                               4189340258H
DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                            Page 95 of 121
               DESIGNERS REFERENCE HANDBOOK
               Automatic Gen-set Controller, multi-line 2                                               4189340258H
DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                            Page 96 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                               4189340258H
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                               Page 97 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                           4189340258H
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                           Page 98 of 121
              DESIGNERS REFERENCE HANDBOOK
              Automatic Gen-set Controller, multi-line 2                                               4189340258H
DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                           Page 99 of 121
              DESIGNERS REFERENCE HANDBOOK
              Automatic Gen-set Controller, multi-line 2                                               4189340258H
DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                          Page 100 of 121
              DESIGNERS REFERENCE HANDBOOK
              Automatic Gen-set Controller, multi-line 2                                               4189340258H
DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                          Page 101 of 121
              DESIGNERS REFERENCE HANDBOOK
              Automatic Gen-set Controller, multi-line 2                                                4189340258H
DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                          Page 102 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                             4189340258H
Refer to the user's manual of your multi-line AGC for information on:
    • Availability of channels
    • Min./max. settings
    • Factory settings
However, it is possible to write to channels where the option is not set, it is not possible to enable the channel. E.g. if an attempt is
made to write a "1" to the enable flag, the "1" will be discarded, and the enable flag remains "0".
It is not possible to write to offset 0. These values are used for DEIF internal version control.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                          Page 103 of 121
               DESIGNERS REFERENCE HANDBOOK
               Automatic Gen-set Controller, multi-line 2                        4189340258H
Examples:
   • Write nominal frequency (4016) 60Hz
      ID = 1, 60Hz = 600Hz/10 = 0258h
      Address 2000 + 80 = 2080d = 0820h
      Tx:     01h 10h 08h 20h 00h 01h 02h 02h 58h 28h 6Ah
      Rx:     01h 10h 08h 20h 00h 01h 02h 63h
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]   Page 104 of 121
                  DESIGNERS REFERENCE HANDBOOK
                  Automatic Gen-set Controller, multi-line 2                             4189340258H
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]           Page 105 of 121
                  DESIGNERS REFERENCE HANDBOOK
                  Automatic Gen-set Controller, multi-line 2                              4189340258H
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]            Page 106 of 121
              DESIGNERS REFERENCE HANDBOOK
              Automatic Gen-set Controller, multi-line 2                        4189340258H
3 Profibus protocol
• Profibus DP
DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]   Page 107 of 121
                    DESIGNERS REFERENCE HANDBOOK
                    Automatic Gen-set Controller, multi-line 2                                                    4189340258H
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                   Page 108 of 121
              DESIGNERS REFERENCE HANDBOOK
              Automatic Gen-set Controller, multi-line 2                                               4189340258H
DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                          Page 109 of 121
              DESIGNERS REFERENCE HANDBOOK
              Automatic Gen-set Controller, multi-line 2                                                 4189340258H
DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                            Page 110 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                          4189340258H
NOTE:
Be aware that all addresses must include a legal value even though the control function is not used. E.g. in address 4 it is still
necessary to write a value between 60 and 100 also when not running in power factor mode.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                         Page 111 of 121
              DESIGNERS REFERENCE HANDBOOK
              Automatic Gen-set Controller, multi-line 2                        4189340258H
                        ®
4 Caterpillar CCM protocol (option H4)
• CCM protocol
• Hardware description
• Settings
DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]   Page 112 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                                                                                                                                                                                                                4189340258H
4.1     Hardware
The multi-line 2 Can open communication is carried out using a plug-in printed circuit board. The board is placed in slot #8 (terminals
126-133).
An overview of the terminals can be seen below. The slots are positioned in the unit as follows (seen from the top of the unit):
SLOT #2
                                                                                                                                                                                                                     SLOT #6
                                                                                   SLOT #4
                                                                                                                                                                                                                     SLOT #8
                                                                                                                                                                                           90 91 92 93 94 95 96 97
65 66 67 68 69 70 71 72
Ethernet
                                                                                                                                                                                                                               112 113 114 115 116 117 118 119 120 121 122 123 124 125
                                       15 16 17 18 19 20 21 22 23 24 25 26 27 28
51 52 53 54 55 56 57 58 59 60 61 62 63 64
Display
                                                                                                                                                                                         85 86 87 88 89
                                                                                                                                                      Service port
79 80 81 82 83 84
                                                                                                                                                                            t
                                                                                                                                                                        ibi
                                                                                                                                                                     inh
                                                                                                                                                                                   rm
                                                                                                                                                                                                                               99 100 101 102 103 104 105 106 107 108 109 110 111
                                                                                               37 38 39 40 41 42 43 44 45 46 47 48 49 50
                                                                                                                                                                                Ala
                                       9 10 11 12 13 14
                                                                                                                                                                          ok
                                                                                                                                                                       ck
                                                                                                                                                                     he
                                                                                                                                                                                  lf c
                                                                                                                                                                                Se
                                                                                                                                                                          r
                                                                                                                                                                        we
                                                                                                                                                                      Po
                                       8
                                                                                                                                                                                         73 74 75 76 77 78
                                       7
                                       6
                                       5
                                       4
                                       3
                                       2
                                                                                                                                                                                                                               98
                                       1
SLOT #1
                                                                                                                                                                                                                     SLOT #5
                                                                                   SLOT #3
SLOT #7
                             ®
4.1.1    Slot #8, Caterpillar CCM communication
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                                                                                                                                                                                             Page 113 of 121
                  DESIGNERS REFERENCE HANDBOOK
                  Automatic Gen-set Controller, multi-line 2                                                              4189340258H
4.2     Wirings
Principle:
                            CCM
                            module                               PLC
CAT gen-set
                     ®
4.3.1       Caterpillar CCM setup
It is possible to change the parameters used in the communication between the multi-line 2 and the CCM. The parameters can be
changed via the utility software or by menus 4770-4930 in the system menu.
Baud:           Set the baud rate to 9600 or 19200, default setting 9600 1
MID/unit:       The ID of the gen-set that the list corresponds to
                Default the ID is set to 36 (24 hex) for single gen-set, the value must be entered in decimal numbers
ACT:            Turn the list ON/OFF. Default all lists are turned OFF 2
Rate:           This time setting indicates how often the CCM must return an update of the data
                Default the update time is set to 2 sec 3
NOTE:
1
  Note that some CCMs can only use 9600 baud.
2
  Note that only the new CCM can use more than 8 lists. When using an old CCM, be sure that lists 9-16 are turned off.
3
  Note that the CCM can provide a maximum of 50 parameters per second.
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                            Page 114 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                          4189340258H
The H4 will create the lists in the CCM and collect the data when it is broadcasted from the CCM, this is done via the implementation
of some of the M5X protocol functions, Instruction Identifier: IID $10, IID $11, IID $12 and IID $13 are implemented.
If no changes are made the lists will consist of the default PIDs which are shown in the table below. When the lists are turned on, the
CCM will start to return the data for the PIDs to the multi-line 2 and here the values are stored in Modbus. The values which the CCM
transmits for every PID will be placed in the Modbus register corresponding to the PID.
         Example:
         Use of the default PID list:
         The system battery voltage PID F013 is defined as PID #7 (list 1), the value that the CCM returns might be 48, this value will
         be placed in Modbus register 18506. This PID has a resolution of 0.5 V per bit, the master system which reads the value can
         calculate the voltage to 0.5 * Modbus register (18506) = 24 V in this example.
    DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                     Page 115 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                               4189340258H
    DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                           Page 116 of 121
                     DESIGNERS REFERENCE HANDBOOK
                     Automatic Gen-set Controller, multi-line 2                                                        4189340258H
The new CCM which is used on NES (New Engine System), has the possibility to use PIDs consisting of 3 bytes; these PIDs’ MSB
(Most Significant Byte) has a hex value between D0 and D4. This type of PIDs can only be used in lists 9-16, the two MSB must be
placed in the first Modbus register, and the LSB must be placed in the “space for extra PID byte”. If 3 bytes PIDs are not used, “space
for extra PID byte” must be 0.
Example:
         To place the PID D0 01 0A (fuel valve differential pressure) as the first PID in list 9 (PID #65), D0 01 must be written to
         Modbus register (17564), and 0A must be written to Modbus register (17565).
    DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                                      Page 117 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                              4189340258H
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                           Page 118 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                               4189340258H
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                            Page 119 of 121
                 DESIGNERS REFERENCE HANDBOOK
                 Automatic Gen-set Controller, multi-line 2                                               4189340258H
 DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected]                            Page 120 of 121
                   DESIGNERS REFERENCE HANDBOOK
                   Automatic Gen-set Controller, multi-line 2                                                             4189340258H
Example 1:
If the only parameter of interest is the engine RPM:
The PID for RPM (40 hex) must be written to Modbus register 17500, and 0 must be written to the rest of the PIDs in list #1. Note that
the CCM ignores any PIDs in a list which comes after a PID = 0.
The update rate of list 1 can be set to the minimum value of 0.5 sec, then a new RPM value can be read at Modbus register 18500
every ½ second.
Example 2:
Change a PID in list #2:
To place the engine RPM (PID 40 hex) as the second PID in list 2, PID #10, 40 hex must be written to Modbus register 17509. Then
the RPM returned from the CCM can be read from the Modbus register 18509.
NOTE:
When a list is being changed, it must be turned off and then turned on again after the setup. Refer to chapter 4.4.1.
WARNING:
If just one of the PIDs in a list is not a correct request for this engine/EMC type, the CCM will stop the whole list from being
transmitted. For example, if one of the PIDs in list #1 is the request for “Cylinder #20 exhaust port temperature”, and this is asked from
a 16 cylinder engine, then no values will be returned for list #1.
DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: [email protected] Page 121 of 121