XR60C - XR60D: Digital Controller With Defrost and Fans Management

The document describes the front panel commands and LED functions of the XR60C and XR60D digital controllers. The SET key is used to display the target set point or select parameters in programming mode. The (DEF) key starts a manual defrost. The (UP) and (DOWN) keys browse parameters or increase/decrease values. LEDs indicate active components, programming mode, alarms, and other statuses. The controllers can record temperature alarms along with duration and maximum value for HACCP compliance.

Uploaded by

Haiam Borda
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
215 views4 pages

XR60C - XR60D: Digital Controller With Defrost and Fans Management

The document describes the front panel commands and LED functions of the XR60C and XR60D digital controllers. The SET key is used to display the target set point or select parameters in programming mode. The (DEF) key starts a manual defrost. The (UP) and (DOWN) keys browse parameters or increase/decrease values. LEDs indicate active components, programming mode, alarms, and other statuses. The controllers can record temperature alarms along with duration and maximum value for HACCP compliance.

Uploaded by

Haiam Borda
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

4.

FRONT PANEL COMMANDS


Digital controller with defrost and fans management
XR60C – XR60D
1. GENERAL WARNING

1.1 PLEASE READ BEFORE USING THIS MANUAL


 This manual is part of the product and should be kept near the instrument for easy and quick XR60C XR60D
reference.
SET: To display target set point; in programming mode it selects a parameter or confirm an
 The instrument shall not be used for purposes different from those described hereunder. It
operation.
cannot be used as a safety device.
 Check the application limits before proceeding. (DEF) To start a manual defrost
 Dixell Srl reserves the right to change the composition of its products, even without notice, o (UP): To see the last temperature alarm happened; in programming mode it browses the
ensuring the same and unchanged functionality. parameter codes or increases the displayed value.
n (DOWN) To see the last temperature alarm happened; in programming mode it browses
1.2 SAFETY PRECAUTIONS the parameter codes or decreases the displayed value.
 Check the supply voltage is correct before connecting the instrument. KEY COMBINATIONS:
 Do not expose to water or moisture: use the controller only within the operating limits avoiding o + n To lock & unlock the keyboard.
sudden temperature changes with high atmospheric humidity to prevent formation of
condensation SET + n To enter in programming mode.
 Warning: disconnect all electrical connections before any kind of maintenance. SET + o To return to the room temperature display.
 Fit the probe where it is not accessible by the End User. The instrument must not be opened.
 In case of failure or faulty operation send the instrument back to the distributor or to “Dixell 4.1 USE OF LEDS
S.r.l.” (see address) with a detailed description of the fault.
Each LED function is described in the following table.
 Consider the maximum current which can be applied to each relay (see Technical Data).
 Ensure that the wires for probes, loads and the power supply are separated and far enough LED MODE FUNCTION
from each other, without crossing or intertwining. ON Compressor enabled
 In case of applications in industrial environments, the use of mains filters (our mod. FT1) in
parallel with inductive loads could be useful. Flashing -Programming Phase (flashing with )
- Anti-short cycle delay enabled
2. GENERAL DESCRIPTION ON Defrost enabled
Models XR60C, format 32 x 74 mm, and XR60D, DIN rail format, are microprocessor based Flashing - Programming Phase (flashing with )
controller, suitable for applications on medium or low temperature ventilated refrigerating - Drip time in progress
units. They have three relay outputs to control compressor, fan, and defrost, which can be
ON Fans enabled
either electrical or reverse cycle (hot gas). It is also provided with two NTC or PTC probe
inputs, one for temperature control, the other, to be located onto the evaporator, to control the Flashing Fans delay after defrost in progress.
defrost termination temperature and to managed the fan. The instrument is fully configurable ON An temperature alarm happened
through special parameters that can be easily programmed through the keyboard.

3. CONTROLLING LOADS 5. TEMPERATURE ALARM AND ITS DURATION RECORDING (HACCP)


XR60C signals and records temperature alarms, together with their duration and max value
3.1 COMPRESSOR reached. See drawing:
The regulation is performed
Ex. High temperature alarm
according to the temperature Temperature
measured by the thermostat probe
Max
with a positive differential from the Temperature X

set point: if the temperature


increases and reaches set point plus ALu X X
High temp. alarm
differential the compressor is started
and then turned off when the Set Safe food zone
temperature reaches the set point
ALL
value again. Low temp. alarm
In case of fault in the thermostat probe the start and stop of the compressor are timed through
parameters “COn” and “COF”. Alarm duration
Time

3.2 DEFROST 5.1 HOW TO SEE THE ALARM DURATION AND MAX (MIN) TEMPERATURE
Two defrost modes are available through the “tdF” parameter: defrost through electrical If the alarm LED is on, an alarm has taken place. To see the kind of alarm, the max (min)
heater (tdF = EL) and hot gas defrost (tdF = in). Other parameters are used to control the reached temperature and alarm duration do as follows:
interval between defrost cycles (IdF), its maximum length (MdF) and two defrost modes: timed 1. Push the Up or Down key.
or controlled by the evaporator’s probe (P2P). 2. On the display the following message is shown: “HAL” for high temperature alarm
At the end of defrost dripping time is started, its length is set in the FSt parameter. With FSt (“LAL” for the minimum allarm), followed by the Maximum (minimum) temperature,
=0 the dripping time is disabled. then the “tiM” (tiMe) message is displayed, followed by the “Duration” in h.mm.
3. Then the instrument displays the temperature once again.
3.3 CONTROL OF EVAPORATOR FANS
The fan control mode is selected by means of the “FnC” parameter: NOTE1: if an alarm is still occurring the “tim” shows the partial duration.
FnC = C_n: fans will switch ON and OFF with the compressor and not run during defrost; NOTE2: the alarm is recorded when the temperature come back to normal values
FnC = o_n fans will run even if the compressor is off, and not run during defrost;
After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fnd” 5.2 HOW TO RESET A RECORDED ALARM OR ONE THAT IS STILL
parameter. OCCURRING
FnC = C_Y fans will switch ON and OFF with the compressor and run during defrost; 1. Hold the SET key pressed for more than 3s, while the recorded alarm is displayed. (the
FnC = o_Y fans will run continuously also during defrost rSt message will be displayed)
2. To confirm the operation, the “rSt” message starts blinking and the normal temperature
An additional parameter “FSt” provides the setting of temperature, detected by the evaporator will be displayed.
probe, above which the fans are always OFF. This is used to make sure circulation of air only
if his temperature is lower than set in “FSt”. 6. MAIN FUNCTIONS

3.3.1 Forced activation of fans 6.1 HOW TO SEE THE SETPOINT


This function managed by the Fct parameter is designed to avoid short cycles of fans, that 1. Push and immediately release the SET key: the display will show
could happen when the controller is switched on or after a defrost, when the room air warms the Set point value;
the evaporator. Functioning: if the difference of temperature between the evaporator and the 2. Push and immediately release the SET key or wait for 5 seconds to
room probes is more than the value of the Fct parameter, the fans are switched on. With display the probe value again.
Fct=0 the function is disabled.

1592007251 XR60C-D GB r1.0 08.04.2015 XR60C – XR60D 1/4


6.2 HOW TO CHANGE THE SETPOINT  OE Evaporator probe calibration: (-12.0÷12.0°C; -120÷120°F). allows to adjust
possible offset of the evaporator probe.
1. Push the SET key for more than 2 seconds to change the Set point value;
 OdS Outputs activation delay at start up: (0÷255min) This function is enabled at
2. The value of the set point will be displayed and the LED starts blinking;
the initial start up of the instrument and inhibits any output activation for the period of
3. To change the Set value push the o or n arrows within 10s. time set in the parameter.
4. To memorise the new set point value push the SET key again or wait 10s. AC Anti-short cycle delay: (0÷50 min) minimum interval between the compressor stop and
the following restart.
6.3 HOW TO START A MANUAL DEFROST  CCt Compressor ON time during continuous cycle: (0.0÷24.0h; res. 10min) Allows
Push the DEF key for more than 2 seconds and a manual defrost will to set the length of the continuous cycle: compressor stays on without interruption for the
start. CCt time. Can be used, for instance, when the room is filled with new products.
 COn Compressor ON time with faulty probe: (0÷255 min) time during which the
6.4 HOW TO CHANGE A PARAMETER VALUE compressor is active in case of faulty thermostat probe. With COn=0 compressor is
always OFF.
To change the parameter’s value operate as follows:
 COF Compressor OFF time with faulty probe: (0÷255 min) time during which the
1. Enter the Programming mode by pressing the Set and DOWN key for
compressor is OFF in case of faulty thermostat probe. With COF=0 compressor is
3s ( and start blinking). always active.
2. Select the required parameter.
DISPLAY
3. Press the “SET” key to display its value (now only the LED is
 CF Temperature measurement unit:
blinking). °C=Celsius; °F=Fahrenheit. WARNING: When the measurement unit is changed the
4. Use “UP” or “DOWN” to change its value. SET point and the values of the parameters Hy, LS, US, Ot, ALU and ALL have to be
5. Press “SET” to store the new value and move to the following parameter. checked and modified if necessary).
To exit: Press SET + UP or wait 15s without pressing a key. rES Resolution (for °C): (in = 1°C; dE = 0.1 °C) allows decimal point display.
NOTE: the set value is stored even when the procedure is exited by waiting the time-out to  Lod Display : select which probe is displayed by the instrument: P1 = Thermostat
expire. probe; P2 = Evaporator probe
DEFROST
6.5 THE HIDDEN MENU
tdF Defrost type: EL = electrical heater; in = hot gas
The hidden menu Includes all the parameters of the instrument.
dtE Defrost termination temperature: (-50÷50 °C/
6.5.1 HOW TO ENTER THE HIDDEN MENU -58÷122°F) (Enabled only when EdF=Pb) sets the temperature measured by the
1. Enter the Programming mode by pressing the Set + n key for 3s evaporator probe, which causes the end of defrost.
(LED 1 and start blinking). IdF Interval between defrost cycles: (0÷120h) Determines the time interval between the
2. When a parameter is displayed keep pressed the Set+n for more beginning of two defrost cycles.
than 7s. MdF (Maximum) length for defrost: (0÷255min) When P2P = n, (not evaporator probe:
The Pr2 label will be displayed immediately followed from the HY timed defrost) it sets the defrost duration, when P2P = y (defrost end based on
parameter. NOW YOU ARE IN THE HIDDEN MENU. temperature) it sets the maximum length for defrost.
3. Select the required parameter.  dSd Start defrost delay: ( 0÷99min) This is useful when different defrost start times are
4. Press the “SET” key to display its value (Now only the LED is blinking). necessary to avoid overloading the plant.
5. Use o or n to change its value.  dFd Temperature displayed during defrost: (rt = real temperature; it = temperature at
6. Press “SET” to store the new value and move to the following parameter. defrost start; SEt = set point; dEF = “dEF” label)
To exit: Press SET + o or wait 15s without pressing a key.  dAd MAX display delay after defrost: (0÷255min). Sets the maximum time between
NOTE: the set value is stored even when the procedure is exited by waiting the time-out to the end of defrost and the restarting of the real room temperature display.
expire.  Fdt Drip time: (0120 min) time interval between reaching defrost termination
temperature and the restoring of the control’s normal operation. This time allows the
6.5.2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO evaporator to eliminate water drops that might have formed due to defrost.
THE FIRST LEVEL AND VICEVERSA.
 dPo First defrost after start-up: (y = immediately; n = after the IdF time)
Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST
 dAF Defrost delay after continuous cycle: (023.5h) time interval between the end
LEVEL” (user level) by pressing “SET + n”.
of the fast freezing cycle and the following defrost related to it.
In HIDDEN MENU when a parameter is present in First Level the decimal point is on.
FANS
6.6 HOW TO LOCK THE KEYBOARD FnC Fans operating mode: C-n= runs with the compressor, OFF during defrost;
o-n = continuous mode, OFF during defrost;
C-Y = runs with the compressor, ON during defrost;
o-Y = continuous mode, ON during defrost;
1. Keep pressed for more than 3 s the UP and DOWN keys. Fnd Fans delay after defrost: (0÷255min) Time interval between end of defrost and
2. The “POF” message will be displayed and the keyboard will be locked. At this point it will evaporator fans start.
be possible only to see the set point or the MAX o Min temperature stored Fct Temperature differential avoiding short cycles of fans (0÷59°C; Fct=0 function
disabled). If the difference of temperature between the evaporator and the room probes
3. If a key is pressed more than 3s the “POF” message will be displayed.
is more than the value of the Fct parameter, the fans are switched on.
6.7 TO UNLOCK THE KEYBOARD FSt Fans stop temperature: (-50÷50°C/122°F) setting of temperature, detected by
evaporator probe, above which fans are always OFF.
Keep pressed together for more than 3s the o and n keys, till the “Pon” message will be
ALARMS
displayed.
 ALC Temperature alarms configuration: (Ab; rE)
6.8 THE CONTINUOUS CYCLE Ab= absolute temperature: alarm temperature is given by the ALL or ALU values. rE =
When defrost is not in progress, it can be activated by holding the “o” temperature alarms are referred to the set point. Temperature alarm is enabled when the
key pressed for about 3 seconds. temperature exceeds the “SET+ALU” or “SET-ALL” values.
ALU MAXIMUM temperature alarm: (SET÷110°C; SET÷230°F) when this temperature is
The compressor operates in continuous mode for the time set through the “CCt” parameter. reached the alarm is enabled, after the “ALd” delay time.
The cycle can be terminated before the end of the set time using the same activation key “o” ALL Minimum temperature alarm: (-50.0 ÷ SET°C; -58÷230°F when this temperature is
for 3 seconds. reached the alarm is enabled, after the “ALd” delay time.
 ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an
7. PARAMETERS alarm condition and alarm signalling.
NOTE: the parameters preceded by dots are in the Hidden Menu.  dAO Exclusion of temperature alarm at startup: (from 0.0 min to 23.5h) time interval
between the detection of the temperature alarm condition after instrument power on and
REGULATION
alarm signalling.
Hy Differential: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point. Compressor
DIGITAL INPUT
Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the temperature
reaches the set point. i1P Digital input polarity: oP: the digital input is activated by opening the contact; CL: the
 LS Minimum set point: (- 50°C÷SET/-58°F÷SET): Sets the minimum acceptable value digital input is activated by closing the contact.
for the set point. i1F Digital input configuration: EAL = external alarm: “EA” message is displayed; bAL =
 US Maximum set point: (SET÷110°C/ SET÷230°F). Set the maximum acceptable serious alarm “CA” message is displayed. PAL = pressure switch alarm, “CA” message
value for set point. is displayed; dor = door switch function; dEF = activation of a defrost cycle; LHt =not
Ot Thermostat probe calibration: (-12.0÷12.0°C; enabled; Htr = kind of action inversion (cooling – heating).
-120÷120°F) allows to adjust possible offset of the thermostat probe. did: (0255 min) with i1F= EAL or i1F = bAL digital input alarm delay: delay between the
P2P Evaporator probe presence: n= not present: the defrost stops by time; y= present: the detection of the external alarm condition and its signalling.
defrost stops by temperature. with i1F= dor: door open signalling delay

1592007251 XR60C-D GB r1.0 08.04.2015 XR60C – XR60D 2/4


with i1F = PAL: time for pressure switch function: time interval to calculate the 10. ELECTRICAL CONNECTIONS
number of the pressure switch activation. The instrument is provided with screw terminal block to connect cables with a cross section up
nPS Pressure switch number: (0 15) Number of activation of the pressure switch, during to 2,5 mm2. Before connecting cables make sure the power supply complies with the
the “did” interval, before signalling the alarm event (I2F= PAL). instrument’s requirements. Separate the probe cables from the power supply cables, from the
If the nPS activation in the did time is reached, switch off and on the instrument to outputs and the power connections. Do not exceed the maximum current allowed on each
restart normal regulation. relay, in case of heavier loads use a suitable external relay.
 odc Compressor and fan status when open door: no = normal; Fan = Fan OFF;
CPr = Compressor OFF; F_C = Compressor and fan OFF. 10.1 PROBE CONNECTION
OTHER The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid
PbC Type of probe: it allows to set the kind of probe used by the instrument: PbC = PBC infiltration. It is recommended to place the thermostat probe away from air streams to correctly
probe, ntC = NTC probe. measure the average room temperature. Place the defrost termination probe among the
 dP1 First probe display evaporator fins in the coldest place, where most ice is formed, far from heaters or from the
 dP2 Second probe display warmest place during defrost, to prevent premature defrost termination.
 rEL Software release for internal use.
 Ptb Parameter table code: readable only. 11. HOW TO USE THE HOT KEY
8. DIGITAL INPUT 11.1 HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)
The free contact digital input is programmable in five different configurations by the “i1F” 1. Program one controller with the front keypad.
parameter. 2. When the controller is ON, insert the “Hot key” and push o key; the "uPL" message
appears followed a by flashing “End”
8.1 DOOR SWITCH INPUT (i1F = dor) 3. Push “SET” key and the End will stop flashing.
It signals the door status and the corresponding relay output status through the “odc” 4. Turn OFF the instrument remove the “Hot Key”, then turn it ON again.
parameter: no = normal (any change); Fan = Fan OFF;
CPr = Compressor OFF; F_C = Compressor and fan OFF. NOTE: the “Err” message is displayed for failed programming. In this case push again o key
Since the door is opened, after the delay time set through parameter “did”, the door alarm is if you want to restart the upload again or remove the “Hot key” to abort the operation.
enabled, the display shows the message “dA” and the regulation restarts. The alarm stops
as soon as the external digital input is disabled again. With the door open, the high and low 11.2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY
temperature alarms are disabled. (DOWNLOAD)
1. Turn OFF the instrument.
8.2 GENERIC ALARM (i1F = EAL) 2. Insert a programmed “Hot Key” into the 5 PIN receptacle and then turn the
As soon as the digital input is activated the unit will wait for “did” time delay before signalling Controller ON.
the “EAL” alarm message. The outputs status don’t change. The alarm stops just after the 3. Automatically the parameter list of the “Hot Key” is downloaded into the Controller
digital input is de-activated. memory, the “doL” message is blinking followed a by flashing “End”.
4. After 10 seconds the instrument will restart working with the new parameters.
8.3 SERIOUS ALARM MODE (i1F = bAL) 5. Remove the “Hot Key”..
When the digital input is activated, the unit will wait for “did” delay before signalling the “CA”
alarm message. The relay outputs are switched OFF. The alarm will stop as soon as the NOTE the message “Err” is displayed for failed programming. In this case turn the unit off and
digital input is de-activated. then on if you want to restart the download again or remove the “Hot key” to abort the
operation.
8.4 PRESSURE SWITCH (i1F = PAL)
If during the interval time set by “did” parameter, the pressure switch has reached the number 12. ALARM SIGNALS
of activation of the “nPS” parameter, the “CA” pressure alarm message will be displayed. The Message Cause Outputs
compressor and the regulation are stopped. When the digital input is ON the compressor is “P1” Room probe failure Compressor output according to par.
always OFF. “Con” and “COF”
If the nPS activation in the did time is reached, switch off and on the instrument to “P2” Evaporator probe failure Defrost end is timed
restart normal regulation. “HA” Maximum temperature alarm Outputs unchanged.
“LA” Minimum temperature alarm Outputs unchanged.
8.5 START DEFROST (i1F = dFr)
“dA” Door open Compressor and fans restarts
It starts a defrost if there are the right conditions. After the defrost is finished, the normal
“EA” External alarm Output unchanged.
regulation will restart only if the digital input is disabled otherwise the instrument will wait until
“CA” Serious external alarm (i1F=bAL) All outputs OFF.
the “MdF” safety time is expired.
“CA” Pressure switch alarm (i1F=PAL) All outputs OFF
8.6 INVERSION OF THE KIND OF ACTION: HEATING-COOLING (i1F = Htr)
This function allows to invert the regulation of the controller: from cooling to heating and 12.1 ALARM RECOVERY
viceversa. Probe alarms “P1” and “P2” start some seconds after the fault in the related probe; they
automatically stop some seconds after the probe restarts normal operation. Check
8.7 DIGITAL INPUTS POLARITY connections before replacing the probe.
The digital input polarity depends on the “i1P” parameter. Temperature alarms “HA” and “LA” automatically stop as soon as the thermostat temperature
i1P=CL: the input is activated by closing the contact. returns to normal values and when defrost starts.
i1P=OP: the input is activated by opening the contact Alarms “EA” and “CA” (with i1F=bAL) recover as soon as the digital input is disabled.
Alarm “CA” (with i1F=PAL) recovers only by switching off and on the instrument.
9. INSTALLATION AND MOUNTING
Instrument XR60C shall be mounted on vertical panel, in a 29x71 mm hole, and fixed using
the special bracket supplied.
To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-C) as shown
in figure.
Instrument XR60D shall be mounted on an omega DIN rail.

The temperature range allowed for correct operation is 060 °C. Avoid places subject to
strong vibrations, corrosive gases, excessive dirt or humidity. The same recommendations
apply to probes. Let air circulate by the cooling holes.

1592007251 XR60C-D GB r1.0 08.04.2015 XR60C – XR60D 3/4


13. TECHNICAL DATA 14.4 XR60D: 20A COMPRESSOR
Housing: self extinguishing ABS.
Case: XR60C frontal 32x74 mm; depth 60mm;
XR60D 4 DIN modules 70x85 mm; depth 61mm Power
Mounting: XR60C panel mounting in a 71x29mm panel cut-out Supply
XR60D DIN RAIL mounted in a omega (3) din rail
1 2 3 4 5 6 11 12
Protection: IP20; Frontal protection: XR60C IP65 with frontal gasket RG-C (optional).
Connections: Screw terminal block  2,5 mm2 wiring.

HOT KEY
Power supply: according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%; 230Vac 10%, 20(8)A/250Vac 8(3)A/250Vac 8(3)A/250Vac
50/60Hz, 110Vac 10%, 50/60Hz
Power absorption: 3VA max 15 16 17 18 19 20 21
Display: 3 digits, red LED, 14,2 mm high; Inputs: 2 NTC or PTC probes.
Digital input: free contact n.c.
Relay outputs: compressor SPST relay 8(3) A, 250Vac or SPST relay 16(6)A 250Vac Comp
defrost: SPDT relay 8(3) A, 250Vac Line
fan: SPST relay 8(3) A, 250Vac
Data storing: on the non-volatile memory (EEPROM). 24Vac/dc supply: connect to the terminals 11 and 12.
Kind of action: 1B; Pollution grade: normal;Software class: A. 120Vac supply: connect to the terminals 11 and 12.
Operating temperature: 0÷60 °C;Storage temperature: -30÷85 °C. 230Vac supply: connect to the terminals 11 and 12.
Relative humidity: 2085% (no condensing) 15. DEFAULT SETTING VALUES
Measuring and regulation range: NTC probe: -40÷110°C (-40÷230°F);
PTC probe: -50÷150°C (-58÷302°F) Label Name Range °C/°F
Resolution: 0,1 °C or 1°C or 1 °F (selectable). Set Set point LS÷US -5/0
Accuracy (ambient temp. 25°C): ±0,7 °C ±1 digit Hy Differential 0,125.5°C/ 1 255°F 2/4
LS Minimum set point -50°CSET/-58°FSET -50/-58
14. CONNECTIONS US Maximum set point SET110°C/ SET  230°F 110/230
Ot Thermostat probe calibration -1212°C /-120120°F 0
14.1 XR60C – 12VAC/DV OR 24 VAC/DV P2P Evaporator probe presence n=not present; Y=pres. y
OE Evaporator probe calibration -1212°C /-120120°F 0
OdS Outputs delay at start up 0÷255 min 0
Room
Evap.

AC Anti-short cycle delay 0  50 min 1


CCt Continuos cycle duration 0.0÷24.0h 0.0
8(3)A 9 101112
COn Compressor ON time with faulty probe 0  255 min 15
M ax 8(3)A ~
250V
16A COF Compressor OFF time with faulty probe 0  255 min 30
CF Temperature measurement unit °C  °F °C/°F
1 2 3 4 5 6 7 8 rES Resolution in=integer; dE= dec.point dE/-
H
otKey Lod Probe displayed P1;P2 P1
N.C.
D
ef FanC
omp tdF Defrost type EL=el. heater; in= hot gas EL
Line
dtE Defrost termination temperature -50  50 °C 8/46
NOTE: The compressor relay is 8(3)A or 16(6)A according to the model. IdF Interval between defrost cycles 1  120 ore 6
24Vac/dc supply: connect to the terminals 7 and 8. MdF (Maximum) length for defrost 0  255 min 30
dSd Start defrost delay 0÷99min 0
14.2 XR60C – 120VAC OR 230 VAC dFd Displaying during defrost rt, it, SEt, DEF it
dAd MAX display delay after defrost 0 ÷ 255 min 30
Fdt Draining time 0÷120 min 0
Room
Evap.

dPo First defrost after startup n=after IdF; y=immed. n


dAF Defrost delay after fast freezing 0 ÷ 23h e 50’ 0.0
8(3)A 9 101112
Fnc Fan operating mode C-n, o-n, C-y, o-Y o-n
M ax 8(3)A ~
250V
16A Fnd Fan delay after defrost 0÷255min 10
Fct Differential of temperature for forced 0÷50°C 10
1 2 3 4 5 6 6 7 activation of fans
H
otKey FSt Fan stop temperature -50÷50°C/-58÷122°F 2/35
N.C. ALc Temperat. alarms configuration rE= related to set; Ab
D
ef FanC
omp
Line Ab = absolute
ALU MAXIMUM temperature alarm Set110.0°C; Set÷230°F 110/230
NOTE: The compressor relay is 8(3)A or 16(6)A according to the model.
ALL Minimum temperature alarm -50.0°CSet/ -58°FSet -50/-58
120Vac supply: connect to the terminals 6 and 7.
ALd Temperature alarm delay 0  255 min 15
14.3 XR60D: 8A COMPRESSOR dAO Delay of temperature alarm at start up 0  23h e 50’ 1.30
i1P Digital input polarity oP=opening;CL=closing CL
i1F Digital input configuration EAL=extern. alarm; bAL=lock regulation; dor
PAL=press. switch; dor=door switch;
Power dEF=defrost; LHt=disabled; Htr = heating
Supply - cooling
did Digital input alarm delay 0÷255min 15
1 2 3 4 5 6 11 12
Nps Number of activation of pressure switch 0 ÷15 15
odc Compressor and fan status when open no = normal; Fan = Fan OFF; CPr = F-C
HOT KEY

8(3)A/250Vac 8(3)A/250Vac 8(3)A/250Vac door: Compr. OFF; F_C = Compr & fan OFF
PbC Kind of probe Ptc; ntc ntc/Ptc
13 14 15 16 17 18 19 20 21 dP1 Room probe display -- --
dP2 Evaporator probe display -- --
n.c. n.c. rEL Software release -- 2.7
Comp Ptb Map code -- -
Line Hidden parameters
24Vac/dc supply: connect to the terminals 11 and 12.
120Vac supply: connect to the terminals 11 and 12.
230Vac supply: connect to the terminals 11 and 12.

1592007251 XR60C-D GB r1.0 08.04.2015 XR60C – XR60D 4/4