XR60C - XR60D: Digital Controller With Defrost and Fans Management
XR60C - XR60D: Digital Controller With Defrost and Fans Management
3.2 DEFROST 5.1 HOW TO SEE THE ALARM DURATION AND MAX (MIN) TEMPERATURE
Two defrost modes are available through the “tdF” parameter: defrost through electrical If the alarm LED is on, an alarm has taken place. To see the kind of alarm, the max (min)
heater (tdF = EL) and hot gas defrost (tdF = in). Other parameters are used to control the reached temperature and alarm duration do as follows:
interval between defrost cycles (IdF), its maximum length (MdF) and two defrost modes: timed 1. Push the Up or Down key.
or controlled by the evaporator’s probe (P2P). 2. On the display the following message is shown: “HAL” for high temperature alarm
At the end of defrost dripping time is started, its length is set in the FSt parameter. With FSt (“LAL” for the minimum allarm), followed by the Maximum (minimum) temperature,
=0 the dripping time is disabled. then the “tiM” (tiMe) message is displayed, followed by the “Duration” in h.mm.
3. Then the instrument displays the temperature once again.
3.3 CONTROL OF EVAPORATOR FANS
The fan control mode is selected by means of the “FnC” parameter: NOTE1: if an alarm is still occurring the “tim” shows the partial duration.
FnC = C_n: fans will switch ON and OFF with the compressor and not run during defrost; NOTE2: the alarm is recorded when the temperature come back to normal values
FnC = o_n fans will run even if the compressor is off, and not run during defrost;
After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fnd” 5.2 HOW TO RESET A RECORDED ALARM OR ONE THAT IS STILL
parameter. OCCURRING
FnC = C_Y fans will switch ON and OFF with the compressor and run during defrost; 1. Hold the SET key pressed for more than 3s, while the recorded alarm is displayed. (the
FnC = o_Y fans will run continuously also during defrost rSt message will be displayed)
2. To confirm the operation, the “rSt” message starts blinking and the normal temperature
An additional parameter “FSt” provides the setting of temperature, detected by the evaporator will be displayed.
probe, above which the fans are always OFF. This is used to make sure circulation of air only
if his temperature is lower than set in “FSt”. 6. MAIN FUNCTIONS
The temperature range allowed for correct operation is 060 °C. Avoid places subject to
strong vibrations, corrosive gases, excessive dirt or humidity. The same recommendations
apply to probes. Let air circulate by the cooling holes.
HOT KEY
Power supply: according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%; 230Vac 10%, 20(8)A/250Vac 8(3)A/250Vac 8(3)A/250Vac
50/60Hz, 110Vac 10%, 50/60Hz
Power absorption: 3VA max 15 16 17 18 19 20 21
Display: 3 digits, red LED, 14,2 mm high; Inputs: 2 NTC or PTC probes.
Digital input: free contact n.c.
Relay outputs: compressor SPST relay 8(3) A, 250Vac or SPST relay 16(6)A 250Vac Comp
defrost: SPDT relay 8(3) A, 250Vac Line
fan: SPST relay 8(3) A, 250Vac
Data storing: on the non-volatile memory (EEPROM). 24Vac/dc supply: connect to the terminals 11 and 12.
Kind of action: 1B; Pollution grade: normal;Software class: A. 120Vac supply: connect to the terminals 11 and 12.
Operating temperature: 0÷60 °C;Storage temperature: -30÷85 °C. 230Vac supply: connect to the terminals 11 and 12.
Relative humidity: 2085% (no condensing) 15. DEFAULT SETTING VALUES
Measuring and regulation range: NTC probe: -40÷110°C (-40÷230°F);
PTC probe: -50÷150°C (-58÷302°F) Label Name Range °C/°F
Resolution: 0,1 °C or 1°C or 1 °F (selectable). Set Set point LS÷US -5/0
Accuracy (ambient temp. 25°C): ±0,7 °C ±1 digit Hy Differential 0,125.5°C/ 1 255°F 2/4
LS Minimum set point -50°CSET/-58°FSET -50/-58
14. CONNECTIONS US Maximum set point SET110°C/ SET 230°F 110/230
Ot Thermostat probe calibration -1212°C /-120120°F 0
14.1 XR60C – 12VAC/DV OR 24 VAC/DV P2P Evaporator probe presence n=not present; Y=pres. y
OE Evaporator probe calibration -1212°C /-120120°F 0
OdS Outputs delay at start up 0÷255 min 0
Room
Evap.
8(3)A/250Vac 8(3)A/250Vac 8(3)A/250Vac door: Compr. OFF; F_C = Compr & fan OFF
PbC Kind of probe Ptc; ntc ntc/Ptc
13 14 15 16 17 18 19 20 21 dP1 Room probe display -- --
dP2 Evaporator probe display -- --
n.c. n.c. rEL Software release -- 2.7
Comp Ptb Map code -- -
Line Hidden parameters
24Vac/dc supply: connect to the terminals 11 and 12.
120Vac supply: connect to the terminals 11 and 12.
230Vac supply: connect to the terminals 11 and 12.