Modicon X80 I/O Platform Overview
Modicon X80 I/O Platform Overview
platform
Catalog
July 2018
Quick access to Product information
Select your Catalog, your Training
http://digi-cat.schneider-electric.com/download.html
then click on
General contents
Presentation. . . . . . . . . . . . . . . . . . . . . . . 1
I/O modules . . . . . . . . . . . . . . . . . . . . . . . 3
Communication . . . . . . . . . . . . . . . . . . . . 5
Ruggedized modules . . . . . . . . . . . . . . . 6
Services, index. . . . . . . . . . . . . . . . . . . . . 9
10
In this catalog, each time words which refer to Safety without precision, must be
understood according to “Functional Safety”: IEC61508 & IEC61511.
1
1
10
1/0
1/2
Contents 1 - Presentation
10
1/3
1/1
Overview Modicon X80 I/O platform
Compact, robust, sustainable
Modicon X80 I/O, a new Remote I/O The Modicon X80 I/O platform serves as a common platform for Modicon M340,
system Modicon Quantum Ethernet I/O, Modicon M580 PACs, and future Modicon Mx80
1 controllers. With a common platform, a much smaller stock of spare parts needs to
be held, and maintenance and training costs are significantly reduced. A common
configuration tool is used for all PAC modules using Unity Pro with a high level of
services such as bit forcing, structured device DDT, etc. This platform offers a wide
choice between several Schneider Electric I/O modules (discrete, analog, expert,
communication).
2 m
-m
e-to ark Compact
et
Ti
>>With the latest I/O technology, the Modicon X80 I/O platform is extremely
compact
>>Reduction in cabinet dimensions, with up to 64 discrete I/O for some modules
na
nce Exce Robust
te
lle
nce
>>Certified for Hazardous Location Class I Division 2 Groups ABCD and for ATEX/
5 IECEx zone 2/22 (depending on the model, see pages 8/2 to 8/9)
Values required by
Mechanical constraints Levels reached IEC 60068-2
Shock 30 g 15 g
6 Vibrations 3g 1g
ATEX and IECEx zone 2/22 Electrical immunity Levels reached IEC 61131-2
Radiated field 15 V/m 10 V/m
Electrostatic discharges 6 kV 4 kV
by contact
7 Environmental immunity Working values IEC 61131-2
Temperature 0…60 °C/32… 140 °F 5…55 °C/41… 131 °F
8 na
nce Exce
tm
ent Prote Sustainable
te
lle
cti
Inve
nce
on
>>Hot swappable
>>Existing solutions for migrating from legacy I/O to the Modicon X80 I/O platform
>>Green Premium Eco Label
9
10
Common I/O platform
1/2
Overview (continued) Modicon X80 I/O platform
Common safety
Good practices dictate that control systems must be designed to keep process
control functions separate and operationally independent from safety functions. 1
This is usually done using a controller for the process and a separate system for
safety.
ity
4
Unity XLS
Operator
Engineering system clients
station servers
P2P
RTU 5
HMI
Ethernet Extension
backplane rack
6
ERT
Device
network
Modbus + Proxy
NRP
7
CanOpen
NOM Modbus SL
HMI
8
Profibus DP
Profibus PA
AS-i
Weighing
10
Mix standard process and safety in a single M580 safety project
1/3
Overview Modicon X80 I/O platform
Certifications and standards
cti
1
Inve
on
Depending on the model, Modicon X80 modules respect the following standards:
>>Merchant navy: IACS E10 and agencies: ABS, BV, DNV, GL, LR, RINA, RMRS
and CCS
>>International certification: CE, UL, CSA, RCM, EAC
>>Power generation market: IEC 61000-6-5, IEC 61850-3
For further information, see pages 8/2 to 8/9.
2 Merchant navy
ABS BV DNV.GL
4
International certifications
5 e UL CSA
6 RCM EAC
10
High level Unity services
1/4
Overview Modicon X80 I/O platform
Market segments
cti
1
Inve
>>The Unity Pro function block software libraries make the Modicon X80 I/O
on
10
Simplified offer from small to large applications
1/5
Presentation, Modicon X80 I/O platform 0
description Composition
Presentation
1
The Modicon X80 I/O platform serves as the common base for automation platforms
by simply adding a dedicated processor (1).
It may also:
bb form part of a Quantum and Modicon M580 Ethernet I/O architecture as an
Ethernet RIO (EIO) drop with a CRA bus terminal module
bb form an Ethernet Modbus/TCP DIO drop with a PRA module
2
Modicon X80 I/O platform with Modicon M580 processor The Modicon X80 I/O platform is available in single-rack or multi-rack configuration.
One Modicon X80 drop may support two racks separated by a cumulative distance
of up to 30 m/98.42 ft.
Based on the latest I/O technology, the Modicon X80 I/O platform offers:
bb high-quality ruggedness and compactness
4 bb compliance with international certifications (ATEX, IEC, etc.)
bb a wide selection of modules: discrete or analog I/O, expert modules,
communication modules, etc.
Modicon X80 EIO drop with CRA bus terminal module This platform is programmed and configured using Unity Pro software.
8
The additional modules offered include:
bb Ethernet (Modbus/TCP, Ethernet/IP) and CANopen master communication and
supplementary modules dedicated to several automation platforms such as
Modicon M340 or Modicon M580
bb Ethernet Global Data module specifically designed to provide the Global Data
service for inter-controller communication
bb communication via fiber optic transceiver modules
bb application-specific modules: counter, motion control, SSI encoder, time
9 stamping, frequency input
bb CAPP (Collaborative Automation Partner Program) partner modules: weighing,
Wi-Fi
Compatibility: Racks and power supply I/O modules: Communication: Ruggedized modules:
page 1/8 modules: page 2/2 page 3/2 page 5/8 page 6/2
1/6
Description Modicon X80 I/O platform 0
Software configuration
Unity Pro programming software is required to set up the Modicon X80 I/O platform.
7
The Unity Pro function block software libraries make it possible to meet the needs of
specialist applications in various fields of application such as:
bb Water and Waste Water (WWW)
Unity Pro bb Food & Beverage (F&B)
bb Mining, Minerals, Metals (MMM)
bb Oil & Gas (O&G)
8
10
Compatibility: Racks and power supply I/O modules: Communication: Ruggedized modules:
page 1/8 modules: page 2/2 page 3/2 page 5/8 page 6/2
1/7
Compatibility Modicon X80 I/O platform
Product compatibility according to network
architecture
Product X80 module Short description of M340 M580 M580 Quantum Ethernet I/O M340 + M580 +
type reference X80 module Quantum +
1 1
Premium
Local rack with CPU X80 drops on Ethernet remote I/O X80 drops on Ethernet remote I/O X80 drops on
distributed I/O
Standalone HSBY Standalone or HSBY Standalone HSBY X-bus rack BMXXBPpppp X-bus + Ethernet X-bus rack
X-bus rack BMXXBPpppp X-bus + Ethernet rack rack BMEXBPpppp BMXXBPpppp
BMEXBPpppp
X-bus rack X-bus + X-bus rack X-bus + BMXCRA31200 BMXCRA31210 BMECRA31210 BMXCRA31200 BMXCRA31210 BMECRA31210 BMXPRA0100
BMXXBPpppp Ethernet rack BMXXBPpppp Ethernet rack
4 BMEXBP0800 (H)
BMEXBP1200 (H)
X-bus+Eth backplane
X-bus+Eth backplane
4
BMEXBP0602 (H)* X-bus+Eth dual power
supplies backplane
BMEXBP1002 (H)* X-bus+Eth dual power
supplies backplane
BMXXEM010 Protective cover
6 BMXART0414 (H)
BMXART0814 (H)
Analog I/O
Analog I/O
6
BMXDAI0805 Discrete I/O
BMXDAI1602 (H) Discrete I/O
BMXDAI1603 (H) Discrete I/O
BMXDAI1604 (H) Discrete I/O
7 7
BMXDAI1614 (H) Discrete I/O
BMXDAI1615 (H) Discrete I/O
BMXDAI0814 Discrete I/O
BMXDAO1605 (H) Discrete I/O
BMXDAO1615 (H) Discrete I/O
BMXDDI1602 (H) Discrete I/O
BMXDDI1603 (H) Discrete I/O
8 8
BMXDDI1604T Discrete I/O
BMXDDI3202K Discrete I/O
BMXDDI6402K Discrete I/O
BMXDDM16022 (H) Discrete I/O
BMXDDM16025 (H) Discrete I/O
BMXDDM3202K Discrete I/O
BMXDDO1602 (H) Discrete I/O
9 9
BMXDDO1612 (H) Discrete I/O
BMXDDO3202K Discrete I/O
BMXDDO6402K Discrete I/O
BMXDRA0804T Discrete I/O
BMXDRA0805 (H) Discrete I/O
BMXDRA0815 (H) Discrete I/O
BMXDRA1605 (H) Discrete I/O
10 10
BMXDRC0805 (H) Discrete I/O
BMEAHI0812 HART I/O
BMEAHO0412 HART I/O
1/8 1/8
1/9
Compatibility (continued) Modicon X80 I/O platform
Product compatibility according to network
architecture
Product X80 module Short description of M340 M580 M580 Quantum Ethernet I/O M340 + M580 +
type reference X80 module Quantum +
1 1
Premium
Local rack with CPU X80 drops on Ethernet remote I/O X80 drops on Ethernet remote I/O X80 drops on
distributed I/O
Standalone HSBY Standalone or HSBY Standalone HSBY
X-bus rack BMXXBPpppp X-bus + Ethernet rack X-bus rack BMXXBPpppp X-bus + Ethernet X-bus rack
BMEXBPpppp rack BMEXBPpppp BMXXBPpppp
X-bus rack X-bus + X-bus rack X-bus + BMXCRA31200 BMXCRA31210 BMECRA31210 BMXCRA31200 BMXCRA31210 BMECRA31210 BMXPRA0100
2 2
BMXXBPpppp Ethernet rack BMXXBPpppp Ethernet rack
BMEXBPpppp BMEXBPpppp
Expert modules BMXEAE0300 (H) SSI encoder
BMXEHC0200 (H) Counter
BMXEHC0800 (H) Counter
BMXERT1604T Time stamping
BMXMSP0200 PTO
3 BMXETM0200H
PMXCDA0400
Frequency input
AIDIAG (M340 + M580)
3
PMESWT0100 Weighing
Communication BMXNOC0401 Ethernet
modules BMXNOE0100 (H) Ethernet
BMXNOE0110 (H) Ethernet
4 4
BMENOC0301 (C) Ethernet standard web server
BMENOC0311 (C) Ethernet FC web server
BMENOC0321 (C) Ethernet Control router
BMENOS0300 (C) eDRS switch
BMXNGD0100 Ethernet Global Data services
BMXNOM0200 (H) Serial
BMENOP0300 (C) IEC 61850
5 BMXNOR0200H RTU 5
BMXEIA0100 ASi
BMECXM0100 (H) CANopen Master
BMXNRP0200 Optical transceiver
BMXNRP0201 Optical transceiver
PMEUCM0202 Ethernet TCP open universal
6 PMXNOW0300
module
Wireless 6
Compatible Not compatible
7 7
8 8
9 9
10 10
1/10
1/9 1/11
1/9
1
10
2/0
2/2
Contents 2 - Racks and power modules
Single-rack configuration
bb Presentation, description, reference.................................................... page 2/2
bb Accessories............................................................................................ page 2/5 1
Multi-rack configuration
bb Presentation, description...................................................................... page 2/6
bb References.............................................................................................. page 2/8
10
2/3
2/1
Presentation, Modicon X80 I/O platform
description Single-rack configuration
Presentation
The Modicon X80 I/O platform is compatible with two types of backplanes: dual
1 Ethernet and X-bus backplanes or X-bus backplanes (1). One Ethernet switch is
embedded inside the backplane with connectivity to some slots on the backplane,
and not all slots have Ethernet connectivity.
The X-bus functionality is preserved and conforms to the legacy implementation and
specification. The X-bus will be used in a subset of modules on the Ethernet
backplane.
The backplanes provide power supply for the modules in the rack.
2 BMXXBPpp00 racks are basic elements in Modicon X80 I/O platform single-rack
and multi-rack configurations. They provide a rack number to X-bus slots. They also
perform the following functions:
b Mechanical function: they are used to install modules in a PLC station (power
supply, processor, discrete, analog and application-specific I/O). These racks can be
mounted on a panel, plate or DIN rail:
3 v Inside enclosures
v On machine frames, etc.
b Electrical function: the racks incorporate X-bus (proprietary bus). They are used to:
v Distribute the power supplies required for each module in the same rack
v Distribute data and service signals for the entire PLC station
v Hot swap modules during operation
BMEXBPpp02 contain two CPS slots for two redundant power supplies, the dual
power supply rack is:
bb Compatible only with redundancy power supply
5 bb Ensure security of power supply in high availability applications
Description
2 1 5 3 X-bus backplanes
8 3 4 holes (big enough for M6 screws) for mounting the rack on a frame
4 2 fixing points for the shielding connection bar
4 7 8 6 4 5 Tapped holes to take the locking screw on each module
BMXXBP0600 rack with 6 slots 6 A connector for a rack expansion module, marked XBE
7 40-way female ½ DIN connectors forming the electrical connection between the rack
and each module, marked CPS, 00…11 (the rack is delivered with each connector
protected by a cover which needs to be removed before inserting the module)
10
2/2
Description(continued) Modicon X80 I/O platform
Single-rack configuration
8 7 2a
Description (continued)
Dual Ethernet and X-bus backplanes
The quantity of X-bus and Ethernet slots found on a backplane depends on the
backplane size.
1
The BMEXBP0400/BMEXBP0800 are 4/8-slot dual Ethernet and X-bus backplanes
with:
1 CPS slot for power supply
2 4 slots (BMEXBP0400) / 8 slots (BMEXBP0800) with:
94 5 1 2 4 63
2
2a 4/8 Ethernet and X-bus connectors for mixed modules
BMEXBP0400 backplane 3 Extension: 1 connector for a X-bus backplane expansion
4 2 fixing points for the shielding connection bar
5 Protective earth screw
6 Slots for anchoring the module pin
7 Tapped holes for the locking screw on each module
8 4 holes for M4, M5, M6 or UNC #6-32 screws (from 4.32 mm to 6.35 mm/0.170 to
0.250 in.)
9 Rack fastened to 35 mm/1.38 in. wide and 15 mm/0.59 in. deep DIN rails.
Mounting on a 35 mm/1.38 in. wide and 7.5 mm/0.295 in. deep DIN rail is possible
3
(in this case, the product withstands less mechanical stress).
4 5 1 2 46 3
6 Slots for anchoring the module pin
7 Tapped holes for the locking screw on each module
5
8 4 holes for M4, M5, M6 or UNC #6-32 screws (from 4.32 mm to 6.35 mm/0.170 to
BMEXBP1200 backplane 0.250 in.)
8 7 2a
BMEXBP0602 is 6-slot dual Ethernet and X-bus backplane with: 6
1 2 CPS slots for only redundancy power supply BMXCPS4002p
2 6 slots with:
2a 6 Ethernet and X-bus connectors for mixed modules
3 Expansion: 1 connector for an X-bus backplane expansion
4 2 fixing points for the shielding connection bar
7
5 Protective earth screw
6 Slots for anchoring the module pin
7 Tapped holes for the locking screw on each module
8 4 holes for M4, M5, M6 or UNC #6-32 screws (4.32 to 6.35 mm/0.170 to 0.250 in.)
4 5 1 1 2 46 3 9 Rack is fastened to 35 mm/1.38 in. wide and 15 mm/0.59 in. deep DIN rails.
BMEXBP0602 backplane Mounting on a 35 mm/1.38 in. wide and 7.5 mm/0.295 in. deep DIN rail is
possible (in this case, the product withstands less mechanical stress)
8 7 2a
BMEXBP1002 is a 10-slot dual Ethernet and X-bus backplane with: 8
1 2 CPS slots for only redundancy power supply BMXCPS4002p
2 10 slots with:
2a 8 Ethernet and X-bus connectors for mixed modules
2b 2 X-bus connectors for X-bus modules
3 Expansion: 1 connector for an X-bus backplane expansion
9
4 2 fixing points for the shielding connection bar
5 Protective earth screw
2b 6 Slots for anchoring the module pin
7 Tapped holes for the locking screw on each module
4 5 1 1 2 46 3 8 4 holes for M4, M5, M6 or UNC #6-32 screws (4.32 to 6.35 mm/0.170 to 0.250 in.)
BMEXBP1002 backplane
10
2/3
References Modicon X80 I/O platform
Single-rack configuration
X-bus racks
Description Type of module No. of Power Reference Weight
1 to be inserted slots
(1)
consump-
tion (2)
kg/lb
2
2.094
modules (counter,
12 – BMXXBP1200 1.270/
motion control and
2.780
serial)
BMXXBP0600
3
BMXXBP0800
4
BMXXBP1200
(6)
PF122506
6
BMEXBP0400 modules and 8 8 3.9 W BMEXBP0800 1.064/
8-slot
Ethernet + application-specific 2.350
X-bus modules (counter,
motion control and
PF122507
backplane
serial)
12-slot 8 12 3.9 W BMEXBP1200 1.398/
(8 Ethernet + 3.080
BMEXBP0800 X-bus/4
7 X-bus)
backplane
6-slot BMXCPS4002 6 6 3.9 W BMEXBP0602 1.377/
PF122508
8 10-slot (8
Ethernet +
modules and
application-specific
8 10 3.9 W BMEXBP1002 1.377/
3.036
X-bus/2 modules (counter,
PF122508
9
(1) Number of slots taking the processor module, I/O modules, communication modules and
application-specific modules (excluding power supply module).
PF122508
10
modules.
(6) Power consumption of anti-condensation resistor(s).
2/4
Description, Modicon X80 I/O platform
References Accessories
Description
Dual Ethernet and X-bus backplanes
To be ordered separately: 1
A BMXXSPpp00 cable shielding connection kit, used to protect against electrostatic
discharge when connecting the shielding on cordsets for connecting:
b Analog, counter and motion control modules
b A Magelis XBT operator interface to the processor (via BMXXCAUSBH0pp
shielded USB cable)
Accessories
4
Description For use with Reference Weight
kg/lb
Shielding connection kits BMpXBP0400 rack BMXXSP0400 0.280/
comprising: 0.617
- 1 metal bar BMXXBP0600 rack BMXXSP0600 0.310/
- 2 support sub-bases BMEXBP0602 rack
BMpXBP0800 rack BMXXSP0800
0.683
0.340/ 5
0.750
BMpXBP1200 rack BMXXSP1200 0.400/
BMEXBP1002 rack 0.882
Spring clamping rings Cables, cross-section STBXSP3010 0.050/
Sold in lots of 10 1.5...6 mm2/16...10 AWG 0.110
6
Cables, cross-section STBXSP3020 0.070/
(1) 5...11 mm2/10...7 AWG 0.154
STBXSP3000 + STBXSP30p0
Protective covers Unoccupied slots on BMXXEM010 0.005/
(replacement parts) BMXXBPpp00 rack 0.011
Sold in lots of 5
7
(1) The earthing terminal is not included in the shielding connection kits.
10
2/5
Presentation, Modicon X80 I/O platform
description Multi-rack configuration
Note: The processor module is always positioned in the rack at address 0. However, in an X-bus
daisy chain, the order of the racks has no effect on operation. For example, the order of the daisy
chain can be 0-1-2-3, 2-0-3-1, or 3-1-2-0, etc.
6 To extend the configuration using additional racks, users can use a bus extender
module (BMXXBE1000) and X-bus cables. The backplane extender should be plugged
into the dedicated connector on the right side of the backplane. It does not occupy any
module slot. The XBE extender module is not hot-swappable, like the rest of the X80 I/O
platform. Each backplane has to include a power supply module and will support up to
12 modules.
An expansion rack can be connected to the main backplane and the X80 drop (EIO).
7 1 4 3
The rack address is assigned as follows:
b Each rack will be assigned a physical address using 4 microswitches located in the
bus extender module
Modicon M580 + expansion rack
b The main rack containing the CPU will be assigned the address 0
1 4 b The other racks will be assigned addresses 1 to 7
Each rack is equipped with:
1 A BMXCPSppppp power supply or two BMXCPS4002 redundant power supplies (2)
10
1 4 3
Modicon X80 drop + expansion rack
2/6
Presentation, Modicon X80 I/O platform
description Multi-rack configuration
Ethernet racks
Modicon M580 CPUs support dual bus backplanes (Ethernet and X-bus), as well as
Ethernet ring or star architecture on their Ethernet port.
BMEp58pp2p CPUs support Ethernet star or ring architectures (RSTP loop is
1
supported on ports 2 and 3). The embedded scanner allows scanning of distributed
equipment. The CPU directly drives these devices (“NOC” embedded function).
BMEp58pp4p CPUs support an embedded scanner that allows scanning of X80
drops on Ethernet RIO (EIO) and distributed equipment.
Modicon M580 CPUs have an additional third Ethernet port dedicated to the
connection of a service tool such as a PC, HMI, or network analyzer. This port is
2
labeled “ETH 1”. It does not support RSTP.
Modicon M580 CPUs can communicate on the main Ethernet backplane. They
cannot be installed in an expansion rack.
It is necessary to use an Ethernet backplane:
Reference
BMEXBP0400
Description
Standard 4 -slot backplane
3
BMEXBP0800 Standard 8-slot backplane
BMEXBP1200 Standard 12-slot backplane
BMEXBP0602 Dual power supply 6-slot backplane
BMEXBP1002 Dual power supply 10-slot backplane
BMEXBP0400H
BMEXBP0800H
Ruggedized 4-slot backplane
Ruggedized 8-slot backplane 4
BMEXBP1200H Ruggedized 12-slot backplane
BMEXBP0602H Ruggedized dual power supply 6-slot backplane
BMEXBP1002H Ruggedized dual power supply 10-slot backplane
10
2/7
Presentation, Modicon X80 I/O platform
description Multi-rack configuration
4
rack and up to 3 expansion racks. If you are using 4, 6, or 8-slot Premium expansion
racks, you can install 2 physical racks at each assigned rack address, allowing up to
Premium racks
6 Premium expansion racks (up to 6 backplanes and 100 m/328 ft. between 2 drops).
Premium X-bus expansion example
b The BMEP583020, BMEP583040, BMEP584020, and BMEP584040 CPUs
support a main local rack with up to 7 expansion racks. If you are using 4, 6, or 8-slot
Premium expansion racks, you can install 2 physical racks at each assigned rack
address, allowing up to 14 Premium expansion racks.
10
2/8
References Modicon X80 I/O platform
Multi-rack configuration
Rack expansion
Description Use Reference Weight
3
- 2 BMXXBE1000 rack expansion modules
- 1 BMXXBC008K extension cordset, length
0.8 m/2.62 ft
- 1 TSXTLYEX line terminator (set of 2)
5
30 m/98.42 ft 3/ BMXXBC030K 0.420/
BMXXBCpppK max. 9.84 0.926
5/ BMXXBC050K 0.650/
16.40 1.433
12/ BMXXBC120K 1.440/
39.37 3.175
Description Use
connectors
10
assembly kit TSXCBYK9 1 pen
connectors (1)
(1) To fix the connectors to the cable, you also need a wire stripper, a pair of scissors, and
a digital ohmmeter.
2/9
Presentation, Modicon X80 I/O platform 0
Presentation
BMXCPSpppp power supply modules provide the power supply for each
1 BMEXBPpp00 or BMXXBPpp00 Modicon X80 I/O rack and the modules installed
on it. (BMEXBPpp02 supports only BMXCPSppp2)
The Modicon X80 I/O power supply module offer comprises:
b Five power supply modules for DC line supplies:
v 24 V c, 17 W isolated power supply module, BMXCPS2010
v 24...48 V c, 32 W isolated power supply module, BMXCPS3020
4 1
BMXCPSpppp power supply modules have the following on the front panel:
1 A display block comprising:
v OK LED (green), lit if rack voltages are present and correct
v 24 V LED (green), lit when the sensor voltage is present
(BMXCPS2000/3500/3540T power supply modules only)
v RD LED (green), lit when all the internal power supply modules function normally
5
(BMXCPS4002/BMXCPS4022/BMXCPS3522 redundant power supply modules only)
2 v ACT LED (green), lit when the power supply is the Master power supply, off when it
act as a slave supply in redundant application
3
(BMXCPS4002/BMXCPS4022/BMXCPS3522 redundant power supply modules only)
2 A pencil-point RESET pushbutton for a cold restart of the application
4 3 A 2-way connector that can take a removable terminal block (caged or spring-
BMXCPS2000 type) for connecting the alarm relay
4 A 5-way connector that can take a removable terminal block (caged or spring-
6 type) for connecting the following:
v c or a line supply
v Protective earth ground
v Dedicated 24 V c power supply for the input sensors (for
1 BMXCPS2000/3500/3540T power supply modules only)
8
3 The redundant AC power supply could be used alone in single power supply rack or
dual power supply rack as a pair. For high available applications, two independent
redundant power supplies could be used to increase the security of power supply. In
case the master power supply fails to provide the whole current, the slave power
4 supply will change to master mode and continue to function.
BMXCPS4002 Type Standalone power supply Redundant power supply
(BMXCPSppp0) (BMXCPSppp2)
10
(1) This power consumption calculation for the rack can also be performed by the Unity Pro
programming software.
2/10
Functions, Modicon X80 I/O platform 0
Functions
Alarm relay
The alarm relay incorporated in each power supply module has a volt-free contact accessible on the front panel, 1
on the 2-way connector.
The operating principle is as follows:
In normal operation, with the PLC in RUN, the alarm relay is energized and its contact is closed (state 1).
The relay de-energizes and its associated contact opens (state 0) whenever the application stops, even partially,
due to any of the following:
2
b Occurrence of a detected blocking fault
b Incorrect rack output voltages
b Loss of supply voltage
RESET pushbutton
The power supply module in each rack has a RESET button on the front panel which, when pressed, triggers an
initialization sequence on the processor and the modules in the rack it supplies.
Pressing this pushbutton triggers a sequence of service signals, which is the same as that for:
BMXCPS2010/3020
b A power break, when the pushbutton is pressed
b A power-up, when the pushbutton is released
3
In terms of the application, these operations represent a cold start (forcing the I/O modules to state 0 and
initializing the processor).
Sensor power supply
BMXCPS2000/3500 AC power supply modules and BMXCPS3540T DC power supply modules have an
integrated 24 V c supply for powering the input sensors.
Connection to this 24 V c sensor power supply is via the 5-way connector on the front panel. 4
The available power depends on the power supply module (0.45 A or 0.9 A).
References
BMXCPS2000/3500 Each BMEXBPpp00 or BMXXBPpp00 rack must be equipped with a power supply module. BMEXBPpp02 must
be equipped with 1 or 2 redundant power supply modules. These modules are inserted in the leftmost power
supply slots of each rack (marked CPS).
The power required to supply each rack depends on the type and number of modules installed in the rack. It is 5
therefore necessary to draw up a power consumption table for each rack in order to determine which
BMXCPSpppp power supply module is the most suitable for each rack (please consult our website www.
schneider-electric.com).
Power supply modules (1)
Line supply Available power (2) Nominal current Reference Weight
3.3 V c (3) 24 V c rack 24 V c
(3) sensors (4)
Total 24 V c rack
(3) kg/lb 6
24 V c 8.3 W 17 W – 17 W 0.7 A BMXCPS2010 0.290/
isolated 0.639
24...48 V c 15 W 32 W – 32 W 1.3 A BMXCPS3020 0.340/
BMXCPS4002 isolated 0.750
24...48 V c 18 W 40 W – 40 W 1.67 A BMXCPS4022 0.810/
7
1.786
100...150 V c 15 W 31.2 W 21.6 W 36 W (5) 1.3 A BMXCPS3540T (5) 0.340/
0.750
180 W 40 W – 40 W 1.67 A BMXCPS3522 0.610/
1.345
100...240 V a 8.3 W 16.8 W 10.8 W 20 W 0.7 A BMXCPS2000 0.300/
0.661
15 W 31.2 W 21.6 W 36 W 1.3 A BMXCPS3500 0.360/
8
0.794
18 W 40 W – 40 W 1.67 A BMXCPS4002 0.360/
0.794
Separate part
BMXCPS4022 Description Type Composition Reference Weight
kg/lb
Set of 2 removable Spring-type One 5-way terminal block and BMXXTSCPS20 0.015/
9
connectors one 2-way terminal block 0.033
Caged One 5-way terminal block and BMXXTSCPS10 0.020/
one 2-way terminal block 0.044
(1) Include a set of 2 caged removable connectors. Spring-type connectors available separately under reference BMXXTSCPS20.
(2) The sum of the power consumed on each voltage (3.3 V c and 24 V c) must not exceed the total power of the module. See
the power consumption table available on our website www.schneider-electric.com.
(3) 3.3 V c and 24 V c rack voltages for powering modules in the Modicon X80 I/O rack.
(4) 24 V c sensor voltage for powering the input sensors (voltage available via the 2-way removable connector on the front panel).
(5) Extended operating temperature -25 to +70 °C/-13 to +158 °F (with power derating at extreme temperatures: 27 W between
-25 and 0 °C/-13 and 0 °F and between 60 and 70 °C/140 and 158 °F). 10
BMXCPS3522
2/11
1
10
3/0
3/2
Contents 3 - I/O modules
3/3
3/1
Selection guide Modicon X80 I/O platform 0
Applications 8-channel input modules 16-channel input modules 16-channel input modules
Connection via caged, screw clamp, or spring-type removable block terminal Connection via caged, screw clamp, or spring-type removable block Connection via caged or spring-type removable Connection via caged,
2 2
3 Type a a c a or c a c
3
Voltage 200…240 V 100...120 V 24 V 48 V 24 V (a or c) 48 V 100…120 V 100…120 V a 200…240 V a 125 V
Current per channel 10.4 mA 5 mA 3.5 mA 2.5 mA 3 mA (a or c) 5 mA 2…15 mA 3…15 mA 2.4 mA
(for U = 220 V to 50 Hz)
4 Modularity
(Number of channels and
commons)
8 isolated inputs and
1 common
8 isolated channels
and no common point
16 isolated inputs and
1 common
16 isolated inputs and
1 common
16 isolated inputs 16 isolated inputs and
1 common 4
Connection Via 20-way caged, screw clamp, or spring-type removable terminal block Via BMXFTB2000/2010/2020 20-way caged, screw clamp, or spring-type Via 40-way connector Via
BMXFTB2000/2010/2020 removable block terminal BMXFTB2000/2010/2020
20-way caged, screw
clamp, or spring-type
5 Isolated inputs IEC/EN 61131-2 conformity Type 2 Type 3 Type 3 Type 1 Type 1 (a) Type 3 Type 1
removable block terminal
– 5
Logic – – Positive (sink) Negative (source) (c) – Positive (sink)
Type of input Capacitive Capacitive Current sink Resistive Capacitive Current sink
6 6
Sensor compatibility 2-wire a 2-wire a 2-wire c, 3-wire c PNP any type 2-wire c/a, 3-wire c 2-wire a 2-wire, 3-wire –
IEC/EN 60947-5-2 PNP or
NPN any type
Sensor power supply 170…264 V 85...132 V (no sensor 19…30 V 38…60 V 19...30 V c 40…52 V 85…132 V 100...120 V a 200...240 V a 88…150 V
(ripple included) power monitoring) 20…26 V a
Protection of inputs Use one 0.5 A Use one 0.25 A Use one 0.5 A fast-blow fuse per group of Use one 0.5 A fast-blow fuse per group of channels Use one 0.25 A fast-blow Use one 0.5 A fast-blow fuse per group of channels
8 Compatibility with
Modicon Telefast ABE7
Passive connection
sub-bases
– –
8
pre-wired system Adapter sub-bases with – –
relays
References BMXDAI0805 BMXDAI0814 BMXDDI1602 BMXDDI1603 BMXDAI1602 BMXDAI1603 BMXDAI1604 BMXDAI1614 BMXDAI1615 BMXDDI1604T
9 9
Pages 3/12 3/12
10 10
3/2 3/2
3/3
Selection guide (continued) Modicon X80 I/O platform 0
1 preassembled cordsets
1
2 2
6 Isolated outputs Fallback – Configurable output fallback, continuous monitoring of output control, and resetting of outputs in case of internal detected fault 6
IEC/EN 61131-2 conformity – Yes
Protection – Protected Not protected Protected
Logic – Positive – Positive
Preactuator power supply – 19…30 V 19...30 V c 19…30 V
(ripple included) 24...240 V a
7 Output fuse protection – Use a 2 A fast-blow fuse Use a 12 A fast-blow fuse Use a 2 A fast-blow fuse
7
Maximum dissipated power 3.9 W 4.3 W 3.7 W 3.1 W 4 W
3/3
3/4 3/3
3/5
Selection guide (continued) Modicon X80 I/O platform 0
1 1
2 2
Type c transistor c transistor a triac c relay c/a relay
Voltage 24 V 24 V 100…240 V 24...240 V 100…150 V 24 V c, 24...240 V a/ 24 V c, 24…240 V a/
24…240 V a 24... 125 V c 24…240 V a 24…125 V c
3 Current per channel 0.1 A 0.5 A 0.6 A 3A 0.3 A (Ith) 2 A (Ith) 2 A (Ith) 2 A (Ith) 2 A (Ith) 3
Modularity 32 protected outputs and 64 protected outputs and 16 protected outputs and 16 non- 16 isolated 8 non-protected outputs, 8 normally open 16 non- 8 normally open/
(Number of channels and 2 commons 4 commons 1 common protected outputs without common isolated relay protected normally closed
commons) outputs and outputs outputs and 2 isolated relay
4 commons commons outputs
Connection Via one 40-way connector Via two 40-way connectors Via BMXFTB2000/2010/2020 20-way caged, screw Via 40-way Via BMXFTB2000/2010/2020 20-way caged, screw clamp, or Via
4 clamp, or spring-type removable block terminal connector spring-type removable block terminal BMXFTB4000/
4020 40-way
caged or spring
4
removable
terminal block
Outputs Fallback Configurable output fallback, continuous monitoring of output control, and resetting of outputs in Configurable output fallback, Configurable output fallback
case of internal detected fault continuous monitoring of output
control, and resetting of outputs in
5 5
case of internal detected fault
IEC/EN 61131-2 conformity Yes Yes
Protection Yes Yes –
Logic Positive Positive Negative (sink) –
(source)
Preactuator power supply 19…30 V c 19…30 V 100…240 V 24...240 V 100…150 V 19...30 V c 19...264 V a 19...30 V c 19...264 V a
(ripple included) 24...240 V a 5...150 V c 24...240 V a 5...150 V c
6 Output fuse protection Use one 2 A fast-blow fuse per group of channels Use one 6.3 A fast-blow fuse per
group of channels
Use one 3 A
fast-blow fuse
per group of
Use one 4 A
fast-blow fuse
per channel or
Use one 0.5 A,
250 V DC
Use one 3 A
fast-blow fuse
fast-blow fuse on on each channel
Use one
fast-blow fuse
for each output
Use one 12 A
fast-blow fuse
on each group
Use one
fast-blow fuse
for each output
6
channels per group of each relay channel of channels channel
channels
Maximum dissipated power 3.6 W 6.85 W 4 W 2.26 W – 3.17 W 2.7 W 3.6 W 3 W 3.6 W
7 Compatibility with LU9 G02 splitter boxes (8 motor starters) and BMXFCCpp1/pp3 preassembled cordsets. –
-13…158 °F
7
TeSys Quickfit See pages 3/9 and 3/13.
installation system
Compatibility with Passive connection Depending on model, passive sub-bases with 8 or 16 channels, with or without LED, with –
Modicon Telefast ABE7 sub-bases common or with 2 terminals per channel.
pre-wired system (1) Adapter sub-bases with Depending on model, active sub-bases with solid state or electromagnetic relays (fixed or removable). –
8 8
relays 16 channels with 1 common or 2 terminals per channel, screw or spring-type connection.
References BMXDDO3202K BMXDDO6402K BMXDDO1602 BMXDDO1612 BMXDAO1605 BMXDAO1615 BMXDRA0804T BMXDRA0805 BMXDRA0815 BMXDRA1605 BMXDRC0805
9 or more information, please refer to the “Telefast Pre-wired system -- Modicon ABE7 IP20 connection sub-bases” catalog or consult our
(1) F
website www.schneider-electric.com. 9
10 10
3/4
3/6 3/4
3/7
Presentation, Modicon X80 I/O platform
description Discrete I/O modules
Presentation
Discrete I/O modules in the Modicon X80 I/O offer are standard modules occupying a
1 single slot on the rack. These modules are equipped with either of the following:
bb A connector for a screw or spring-type 20-way removable terminal block
bb One or two 40-way connectors
This wide range of “discrete” I/O can be used to meet whatever requirements arise in terms
of:
bb Functions, AC or DC I/O, positive or negative logic
2 bb Modularity, 8, 16, 32 or 64 channels per module
The inputs receive signals from the sensors and perform the following functions:
bb Acquisition
bb Adaptation
bb Electrical isolation
bb Filtering
3 bb Protection against interference signals
The outputs memorize commands issued by the processor to enable control of the
preactuators via the decoupling and amplification circuits.
4 Description
BMXDpI/DpO/DRA discrete I/O modules are standard format (1 slot). They have an
IP 20 case to protect the electronics, and are locked into position with a captive
screw.
1
To be ordered separately:
5 5 A BMXFTB20p0 20-way removable terminal block (identification label supplied
with each I/O module) or a preassembled cordset with a 20-way removable
terminal block at one end and flying leads at the other (see page 3/9).
Module for connection via 20-way removable terminal
7 block
I/O modules connected via 40-way connector(s)
1
1 Rigid body providing support and protection for the electronic card
2 5 2 Module reference marking (a label is also visible on the right-hand side of the
module)
3 3 Channel status display block
8
4 One or two 40-way connectors (32 or 64 channels) (1) for connection of sensors
or preactuators
5 With the 64-channel module, a pushbutton which, with successive presses,
4 displays the state of channels 0...31 or 32...63 on the display block 3 (see
page 3/10)
10
3/8
Connections Modicon X80 I/O platform
Discrete I/O modules
A
A: One version of the removable terminal block is equipped with 3, 5 or 10 m cordsets with
color-coded flying leads (BMXFTWpp1). Use limited to voltages of y 48 V.
2
Caged terminal blocks
The capacity of each terminal is:
Preassembled cordset with bb Minimum: One 0.34 mm2 wire (AWG 22)
bb Maximum: One 1 mm2 wire (AWG 18)
3
20-way removable terminal block at one end and
flying leads at the other BMXFTB2000 caged connectors are equipped with captive screws
(maximum tightening torque 0.5 N.m/0.37 lb-ft).
5
4
bb Maximum: One 1 mm2 wire (AWG 18)
Preassembled cordset with
40-way connector and two ends with flying leads
Connecting modules with 40-way connectors
Preassembled cordsets with 40-way connector at one end and flying leads at
the other
1 B: Preassembled cordsets can be used for easy direct wire-to-wire connection
between the I/O of modules with 40-way connectors 1 and the sensors, preactuators
or intermediate terminal blocks. 6
2
These preassembled cordsets comprise:
5 bb At one end, a 40-way connector 2 with either of the following:
bb One sheath containing 20 wires with a cross-section of 0.34 mm2 (AWG 22)
3 (BMXFCWpp1)
C bb Two sheaths 3, each containing 20 wires with a cross-section of 0.34 mm2
(AWG 22) (BMXFCWpp3)
bb At the other end, color-coded flying leads 4 conforming to standard DIN47100. 7
Preassembled cordset with
40-way connectors and HE10 connectors for
Modicon Telefast ABE7 system
Preassembled cordsets with 40-way connector and HE 10 connector(s)
C: Two types of cordset can be used for connecting the I/O of modules 1 with
40‑way connectors to Modicon Telefast ABE7 rapid wiring connection and adaptation
1 interfaces.(1)
These preassembled cordsets comprise:
8
bb At one end, a 40-way connector 2 with either of the following:
-- One sheath containing 20 wires (BMXFCCpp1)
-- Two sheaths 3 each containing 20 wires (BMXFCCpp3)
bb At the other end, one or two HE 10 connectors 5.
7
6
Connection to TeSys Quickfit system 9
D: 1 BMXDDI3202K/6402K input modules, BMXDDO3202K/6402K output modules
and BMXDDM3202K mixed I/O modules with 40-way connectors are designed,
D amongst other things, for use in conjunction with the TeSys Quickfit mounting system
via the LU9G02 splitter module 6 (for 8 motor starters).
The splitter modules are easily connected using 7 BMXFCCpp1/pp3 preassembled
10
cordsets.
(1) For more information, please refer to the “Telefast Pre-wired system -- Modicon ABE7 IP20
Example of connection to the TeSys Quickfit installation help connection sub-bases” catalog or consult our website www.schneider-electric.com.
system
3/9
Functions Modicon X80 I/O platform
Discrete I/O modules
Functions (1)
The discrete I/O modules provide the following functions:
1 bb Hot swapping: Due to their special integrated devices, I/O modules (including
application-specific modules) can be removed or added while the power is on.
bb I/O assignment: The channels of discrete I/O modules are grouped into blocks of
4, 8 or 16 consecutive channels depending on the type of module. Each group of
channels can be assigned to a specific application task, namely master or fast.
2 bb Protection of DC inputs: The 24 V c and 48 V c inputs are constant-current
type. This characteristic limits the current consumed at the inputs.
4 bb Output fallback: This parameter defines the fallback mode used by the DC
transistor outputs when the PLC stops. It can assume the “fallback” value at state 0
or state 1 for the corresponding group of 8 channels or the “maintain” value
representing the state of the outputs before the PLC stops.
bb I/O module diagnostics: Each discrete I/O module is equipped with a display
block on the front panel centralizing the information necessary for module control,
bb Compatibility with 2-wire and 3-wire sensors: The discrete input modules can
be used in conjunction with OsiSense XS inductive proximity sensors (for
7 compatibility, see page 7/4) and with OsiSense XU photo-electric sensors (for
compatibility, see page 7/2).
10
3/10
Characteristics Modicon X80 I/O platform
Discrete I/O modules
Complementary characteristics
The following characteristics complement those introduced in the selection guide on
pages 3/2 to 3/7. 1
DC input modules BMXDDI16pp/1604T/3202K/6402K and BMXDAI1602
bb Input impedance at nominal voltage: 6.4 to 19.2 kΩ, depending on model
bb Reverse polarity: Protection for modules BMXDDI1602/1603/3202K
bb Paralleling of inputs (1): Yes, for modules BMXDDI1602/1603
bb Dielectric strength between groups of channels: 500 V c for modules
BMXDDI3202K/6402K
bb Temperature derating for module BMXDDI1604T: No derating up to 40°C/104°F,
2
a maximum of 25% of inputs at state 1 at 70°C/158°F
7
bb Input impedance at nominal voltage: 6.8 to 9.6 kΩ, depending on model
bb Reverse polarity on the inputs: Protection
bb Paralleling of outputs: Yes, for a maximum of 2 outputs for module BMXDDM16022
and a maximum of 3 outputs for module BMXDDM3202K
(1) This characteristic allows several inputs to be wired in parallel on the same module or on
different modules for input redundancy.
10
3/11
References Modicon X80 I/O platform
Discrete I/O modules
Input modules and output modules
References
Discrete input modules (1)
1 Type of
current
Input voltage Connection via
(2)
IEC/EN
61131-2
No. of channels
(common)
Reference Weight
conformity kg/lb
c 24 V Caged, screw or spring-type Type 3 16 isolated inputs BMXDDI1602 0.115/
(positive logic) 20-way removable terminal block (1 x 16) 0.254
One 40-way connector Type 3 32 isolated inputs BMXDDI3202K 0.110/
(2 x 16) 0.243
4
20-way removable terminal block (1 x 16) 0.254
BMXDDI3202K BMXDDI6402K
Caged or spring-type Type 1 16 isolated inputs BMXDAI1614 0.150/
40-way removable terminal block (1 x 16) 0.331
200…240 V Caged, screw or spring-type Type 2 8 isolated inputs BMXDAI0805 0.152/
20-way removable terminal block (1 x 8) 0.335
Caged or spring-type Type 1 16 isolated inputs BMXDAI1615 0.156/
40-way removable terminal block (1 x 16) 0.344
7 0805/1605 (2 x 16)
Two 40-way connectors Yes 64 protected BMXDDO6402K 0.150/
outputs 0.331
(4 x 16)
a triac 100…240 V 20-way removable terminal Yes 16 outputs BMXDAO1605 0.140/
block, caged, screw or (4 x 4) 0.309
spring-type
24…240 V 40-way removable terminal Yes 16 isolated BMXDAO1615 0.250/
10
5...125 V c /0.3 A block, caged or spring-type normally closed 0.417
isolated relay
outputs
(1) Typical consumption: See the power consumption table available on our website www.schneider-electric.com.
(2) 64-channel modules have 2 connectors and therefore require 2 connection cables.
3/12
References (continued) Modicon X80 I/O platform
Discrete I/O modules
Mixed I/O modules, accessories
References (continued)
Discrete mixed I/O modules (1)
Number of connection
I/O
No. of input channels
(common)
No. of output
channels
IEC/EN
61131-2
Reference Weight
kg/lb
1
(common) conformity
16 Caged, screw 8 (positive logic) 8, transistor Inputs, BMXDDM16022 0.115/
or spring-type (1 x 8) 24 V c/0.5 A type 3 0.254
20‑way (1 x 8)
removable 8, relay 24 V c or Inputs, BMXDDM16025 0.135/
terminal block
2
24…240 V a type 3 0.298
(1 x 8)
BMXDDM1602p BMXDDM3202K 32 One 40-way 16 (positive logic) 16, transistor Inputs, BMXDDM3202K 0.110/
connector (1 x 16) 24 V c/0.1 A type 3 0.243
(1 x 16)
Removable terminal blocks
Description For use with Type Reference Weight
kg/lb
20-way removable terminal For module with 20-way removable terminal
blocks block
Caged BMXFTB2000 0.093/
0.205 3
Screw clamp BMXFTB2010 0.075/
0.165
Spring BMXFTB2020 0.060/
0.132
40-way removable terminal For standard version of module only with 40-way Caged BMXFTB4000 0.166/
BMXFTB2000 blocks removable terminal block 0.366
Spring BMXFTB4020 0.098/
0.216
4
Preassembled cordsets for 16-channel I/O modules with removable terminal block
Description Composition Cross- Length Reference Weight
section m/ft kg/lb
Preassembled cordsets One 20-way spring-type removable 0.324 mm2/ 3/9.84 BMXFTW301 0.850/
with one end with flying terminal block (BMXFTB2020) and AWG 22 1.874
5
leads for 16-channel I/O one end with color-coded flying 5/16.40 BMXFTW501 1.400/
modules leads 3.086
BMXFTWp01
Operating voltage y 48 V 10/32.81 BMXFTW1001 2.780/
6.129
Preassembled cordsets for 16, 32 and 64-channel I/O modules with 40-way connectors
7
wires (32 connector and AWG 22 1.984
channels) two ends with color- 5/16.40 BMXFCW503 1.490/
(2) coded flying leads 3.285
BMXFCWp03 10/32.81 BMXFCW1003 2.960/
6.526
Preassembled cordsets for 1 x 20 One 40-way connector 0.324 mm / 0.5/1.64
2
BMXFCC051 0.140/
Modicon Telefast ABE7 wires (16 and one HE 10 AWG 22 0.309
sub-bases channels) connector 1/3.28 BMXFCC101 0.195/
8
0.430
2/6.56 BMXFCC201 0.560/
1.235
3/9.84 BMXFCC301 0.840/
1.852
BMXFCCp01
5/16.40 BMXFCC501 1.390/
3.064
10/32.81 BMXFCC1001 2.780/
9
6.123
2 x 20 One 40-way connector 0.324 mm2/ 0.5/1.64 BMXFCC053 0.210/
wires (32 and two HE 10 connectors AWG 22 0.463
channels) 1/3.28 BMXFCC103 0.350/
(2) 0.772
2/6.56 BMXFCC203 0.630/
1.389
3/9.84 BMXFCC303 0.940/
10
2.072
5/16.40 BMXFCC503 1.530/
3.373
10/32.81 BMXFCC1003 3.000/
6.614
(1) Typical consumption: See the power consumption table available on our website www.schneider-electric.com.
(2) 64-channel modules have 2 connectors and therefore require 2 connection cables.
3/13
Selection guide Modicon X80 I/O platform 0
1 1
2 2
Type of input Isolated low-level inputs, voltage, thermocouples, temperature probes, resistors Isolated high-level inputs Non-isolated high-level inputs Isolated high-level inputs
4 Thermocouple
Temperature probe
Resistor
Thermocouples, type B, E, J, K, L, N, R, S, T, U
2, 3 or 4-wire temperature probes, type Pt100, JPt100, Pt1000, JPt1000, Ni100, Ni1000
(in accordance with DIN43760) and Cu 10
–
4
2, 3 or 4-wire resistors, 400 Ω or 4000 Ω
Acquisition period 400 ms for the 4 inputs 400 ms for the 8 inputs Fast: 1 + (1 x no. of declared channels) ms Fast: 1 + (1 x no. of declared channels) ms
5 Default: 5 ms for the 4 channels Default: 9 ms for the 8 channels
5
Conversion time – –
7 Via preassembled cordsets Cordsets with one end with color-coded flying leads Cordsets with one end with color-coded flying leads Cordsets with one end with color-coded flying leads 7
BMXFCWp01S (3 or 5 m/9.84 or 16.40 ft long) BMXFTWp01S (3 or 5 m/9.84 or 16.40 ft long) BMXFTWp08S (3 or 5 m/9.84 or 16.40 ft long)
Compatibility with Modicon Connection sub-base 4-channel sub-base for direct connection of 4 thermocouples plus connection and provision of 4-channel sub-base for direct connection of 4 inputs, 8-channel sub-base for direct connection of 8 current/voltage inputs
Telefast ABE7 pre-wired cold junction compensation delivers and distributes 4 protected isolated power
system (1) supplies
(1) For more information, please refer to the “Telefast Pre-wired system -- Modicon ABE7 IP20 connection sub-bases” catalog or consult our website
www.schneider-electric.com.
10 10
3/14 3/14
3/15
Selection guide Modicon X80 I/O platform 0
1 1
2 2
Type of I/O Isolated high-level outputs Isolated high-level outputs Non-isolated high-level Non-isolated high-level inputs and outputs
3 3
outputs
Conversion time y 1 ms y 4 ms y 1 ms
(outputs)
Between channels and bus: 1400 V c Between channels and bus: 1400 V c
6 Between channels and ground: 1400 V c Between channels and ground: 1400 V c
6
Connection Directly to the module Via 20-way removable terminal block (screw or spring-type) Via 20-way removable terminal block (screw or spring-type) BMXFTB20p0
BMXFTB20p0
Via preassembled cordsets Cordsets with one end with color-coded flying leads BMXFTWp01S cordsets with one end with color-coded flying leads (3 or 5 m/9.84 or 16.40 ft long)
BMXFTWp01S (3 or 5 m/9.84 or 16.40 ft long)
7 Compatibility with Modicon Connection sub-base 4-channel sub-base for direct connection of 2/4 current/voltage 8-channel sub-base for direct –
7
Telefast ABE7 pre-wired outputs connection of
system (1) 8 current/voltage inputs
Type of connection sub-base ABE7CPA21 ABE7CPA02 –
9 (1) For more information, please refer to the “Telefast Pre-wired system -- Modicon ABE7 IP20 connection sub-bases” catalog or consult our website
www.schneider-electric.com.
9
10 10
3/15
3/16 3/15
3/17
Presentation Modicon X80 I/O platform
Analog I/O modules
Presentation
The Modicon X80 I/O analog I/O module offer comprises:
1 bb 5 analog input modules:
vv 2 modules with 4 and 8 isolated channels, low-level voltage, thermocouples, Pt,
JPt, Ni, or Cu temperature probes and resistors, 15 bits + sign BMXART0414/0814
vv 1 module with 4 high-speed isolated analog channels, high-level voltage or
current, 16 bits BMXAMI0410
vv 2 modules with 8 high-speed non-isolated analog channels, high-level voltage or
current, 15 bits + sign BMXAMI0800/0810
2 bb 3 analog output modules:
vv 1 module with 2 isolated analog channels, high-level voltage or current, 15 bits +
sign BMXAMO0210
vv 1 module with 4 isolated analog channels, high-level voltage or current, 15 bits +
sign BMXAMO0410
vv 1 module with 8 non-isolated analog channels, high-level current, 15 bits + sign
BMXAMO0802
3 bb 1 mixed analog I/O module with 4 input channels and 2 output channels
(non‑isolated), voltage or current, 12 to 14 bits according to type of channel and
range BMXAMM0600
Analog I/O modules are equipped with a connector for a 20 or 28-way removable
terminal block, except for BMXART0414/0814 analog input modules for
thermocouples/temperature probes, which are equipped with one or two 40-way
4 connector(s).
The power supply for the analog functions is supplied by the backplane bus (3.3 V
5 and 24 V). Analog I/O modules are hot-swappable (see page 3/10).
10
3/18
Description Modicon X80 I/O platform
Analog I/O modules
Description
BMXAMp/ART analog I/O modules are standard format (1 slot). They have a case,
which provides IP 20 protection of the electronics, and are locked into position by a
captive screw.
1
I/O modules connected via 20 or 28-way removable terminal block
BMXAMp analog I/O modules feature the following:
1
1 A rigid body providing support and protection for the electronic card
2
2 2 A module reference marking (a label is also visible on the right-hand side of the
module)
3 3 A module and channel status display block
4 A connector taking the 20 or 28-way removable screw or spring-type terminal
block for directly connecting the sensors or preactuators to the module
To be ordered separately:
4 5 A BMXFTB20p0 or BMXFTB28p0 20 or 28-way removable terminal block
(referencing label supplied with each I/O module) or pre-wired cables with:
-- A 20-way terminal block at one end and flying leads at the other
3
5
(BMXFTWp01S)
-- A 28-way terminal block at one end and flying leads at the other
(BMXFTWp08S)
Module for connection via 20 or 28-way
-- A 20 or 28-way terminal block and a 25-way SUB-D connector (BMXFCApp0
or BMXFTApp0), for connection to Modicon Telefast ABE7 sub-bases (see
4
removable terminal block
page 3/23).
5
module)
3 3 A module and channel status display block
4 One (or two) 40-way connector(s) for connecting the sensors
To be ordered separately:
5 Pre-wired cables with:
4 5 -- A 40-way connector at one end and flying leads at the other (BMXFCWp01S)
-- A 40-way connector and a 25-way SUB-D connector (BMXFCApp2) for direct
connection to the Modicon Telefast ABE7 sub-bases (see page 3/23) 6
Must be ordered separately:
bb A shielding connection kit to help protect against electrostatic discharge,
consisting of a metal bar and two sub-bases for mounting on the rack supporting the
Module for connection for 40-way connector analog modules
bb A set of STBXSP3020 clamping rings for the shielding braids of analog signal
cables
7
10
3/19
Connections, Modicon X80 I/O platform
combinations Analog I/O modules
5 Using the Modicon Telefast ABE7 pre-wired system makes it easier to install
the modules since the inputs (or outputs) can be accessed via screw
terminals. 7 special sub-bases are available:
2
Modicon Telefast ABE7CPA410 sub-base
BMXFCWp01S cordset
(with 40-way connector at one end and flying leads at the The Modicon Telefast ABE7CPA410 sub-base is mainly used in conjunction with
other) the BMXAMI0410 voltage/current analog 4-input module. This sub-base allows you
6 to:
bb Directly connect 4 sensors
bb Remotely locate the input terminals in voltage mode
bb Power the 4 to 20 mA conditioning units one channel at a time with a 24 V voltage,
protected and limited to 25 mA, while maintaining isolation between channels
bb Help protect the current impedance matching resistors integrated in the sub-base
against overvoltages
7 Connection is via the BMXFCApp0 cordset (1.5, 3, or 5 m/4.92, 9.84, or 16.40 ft
long).
3/20
Combinations (continued), Modicon X80 I/O platform
characteristics Analog I/O modules
4
long BMXFTApp0 cables.
Complementary characteristics
BMXART0414/0814 analog input modules
The BMXART0414/0814 modules are multirange input modules with 4 or 8 low-level 6
isolated inputs (15 bits + sign) respectively.
Depending on the choice made during configuration, the modules offer, for each of
the inputs, the following ranges:
bb Temperature probe: Pt100, JPt100, Pt1000, JPt1000, Cu10, Ni100, or Ni1000 (in
accordance with DIN43760), with open-circuit detection
7
bb Thermocouple: B, E, J, K, L, N, R, S, T, or U with broken wire detection
bb Resistor: 0…400 or 0…4000 W, 2, 3, or 4-wire
bb Voltage: ± 40 mV, ± 80 mV, ± 160 mV, ± 320 mV, ± 640 mV, ± 1.28 V
3/21
Characteristics (continued), Modicon X80 I/O platform
references Analog I/O modules
Input modules, output modules, and mixed module
5
Isolated high-level ± 10 V, 0…10 V, 16 bits Removable terminal block, 4 channels BMXAMI0410 0.143/
inputs 0…5 V, 1…5 V, 20-way, caged, screw clamp, 0.315
± 5 V, 0 – 20 mA, or spring-type
4– 20 mA, ± 20 mA
Non-isolated ± 10 V, 0…10 V, 15 bits Removable terminal block, 8 channels BMXAMI0800 0.175/
high-level inputs 0…5 V, 1…5 V, + sign 28-way, caged or spring-type 0.386
± 5 V, 0 – 20 mA
6 Isolated high-level
inputs
± 10 V, 0…10 V,
0…5 V, 1…5 V,
15 bits +
sign
Removable terminal block, 8 channels
28 way, caged or spring-type
BMXAMI0810 0.175/
0.386
BMXAMp0pp0 ± 5 V, 0 – 20 mA
Isolated low-level Temperature probe, 15 bits 40-way connector 4 channels BMXART0414 0.135/
inputs thermocouple, + sign 0.298
± 40 mV, ± 80 mV, 8 channels BMXART0814 0.165/
7 ± 160 mV, ± 320 mV,
± 640 mV, ± 1.28 V
0.364
Non-isolated BMXAMO0802
9
0 – 20 mA, 15 bits Removable terminal block, 8 channels 0.175/
high-level inputs 4– 20 mA + sign 20-way, caged, screw clamp, 0.386
or spring-type
Analog mixed I/O module (1)
Type of I/O Signal range Resolution Connection No. of Reference Weight
channels kg/lb
Mixed I/O, non-isolated ± 10 V, 0…10 V, 14 bits or Removable terminal block, Inputs: BMXAMM0600 0.155/
0…5 V, 1…5 V, 12 bits 20-way, caged, screw clamp, 4 channels 0.342
10 0 – 20 mA,
4– 20 mA
depending or spring-type
on the range
Outputs:
2 channels
(1) Typical consumption: See the power consumption table available on our website www.schneider-electric.com.
3/22
References (continued) Modicon X80 I/O platform
Analog I/O modules
Accessories
References (continued)
Connection accessories for analog modules (1)
Description For use with
modules
Type, composition Length Reference Weight
kg/lb
1
20-way removable BMXAMI0410 Caged – BMXFTB2000 0.093/
terminal blocks BMXAMO0210 0.205
BMXAMO0410 BMXFTB2010
Screw clamp – 0.075/
BMXAMO0802
0.165
BMXAMM0600
Spring – BMXFTB2020 0.060/
BMXFTB20p0
BMXAMI0800
25 mA to the 8 current inputs
Direct connection of 8 inputs Screws ABE7CPA31 0.498/ 7
BMXAMI0810 Delivers 8x 24 V c power supplies 1.098
isolated and limited to 25 mA to the ABE7CPA31E
Spring 0.508/
8 current inputs
1.120
Preassembled BMXAMI0410 One 20-way removable terminal 1.5 m/4.92 ft BMXFCA150 0.320/
cordsets for BMXAMO0210 block and one 25-way SUB-D 0.705
8
Modicon Telefast BMXAMO0410 connector for ABE7CPA410/CPA21 3 m/9.84 ft BMXFCA300 0.500/
ABE7 sub-bases sub-base 1.102
BMXFCApp0 5 m/16.40 ft BMXFCA500 0.730/
1.609
BMXART0414 One 40-way connector and one 1.5 m/4.92 ft BMXFCA152 0.330/
BMXART0814 (2) 25-way SUB-D connector for 0.728
ABE7CPA412 sub-base 3 m/9.84 ft BMXFCA302 0.510/
1.124
5 m/16.40 ft BMXFCA502 0.740/
1.631
9
BMXAMI0800 One 28-way removable terminal 1.5 m/4.92 ft BMXFTA150 0.374/
BMXAMI0810 block and one 25-way SUB-D 0.825
connector for sub-bases 3 m/9.84 ft BMXFTA300 0.500/
BMXFCApp2 ABE7CPA02/03/31/31E 1.102
BMXAMO0802 One 20-way removable terminal 1.5 m/4.92 ft BMXFTA152 0.374/
block and one 25-way SUB-D
connector for ABE7CPA02 3 m/9.84 ft BMXFTA302
0.825
0.500/
10
sub-bases 1.102
(1) The shielding on the cordsets carrying the analog signals must always be connected to the BMXXSPpp00 shielding
connection kit mounted under the rack holding the analog modules (see page 2/3).
(2) The BMXART0814 8-channel module requires two ABE7CPA412 sub-bases and two BMXFCApp2 cordsets.
3/23
Selection guide Modicon X80 I/O platform
HART analog I/O modules
1 1
2 2
Type of I/O Isolated analog inputs with HART Isolated analog outputs with HART
Number of channels 8 4
Compatible devices BMEP58pppp processors, BMECRA31210 drop module, BMEXBPpp00(H) Ethernet + X-bus BMEP58pppp processors, BMECRA31210 drop module, BMEXBPpp00(H) Ethernet + X-bus backplanes, 140NOC78000 Quantum Ethernet DIO module
backplanes, 140NOC78000 Quantum Ethernet DIO module
Between channels and bus 1400 V c for 1 minute 1400 V c for 1 minute
Between channels and earth 1400 V c for 1 minute 1400 V c for 1 minute
5 Connection Directly to the module Via 20-way removable terminal blocks (screw or spring-type) BMXFTB20p0 Via 20-way removable terminal blocks (screw or spring-type) BMXFTB20p0
5
Compatibility with Connection sub-base 8-channel sub-base for direct connection of 8 current/voltage inputs 4-channel sub-base for direct connection of 2/4 current/voltage outputs
pre-wired ABE7
Type of connection sub-base ABE7CPA02/03/31 ABE7CPA21
Type of preassembled cordsets BMXFTA1522/3022 (1.5 or 3 m/4.92 or 9.84 ft long) BMXFCA150/300/500 (1.5, 3 or 5 m/4.92, 9.84 or 16.4 ft long)
7 7
References BMEAHI0812 BMEAHO0412
8 8
9 9
10 10
3/24 3/24
3/25
Presentation, Modicon X80 I/O platform
description HART analog I/O modules
1 Presentation
BMEAHp0p12 HART analog I/O modules contain transceivers that master HART
1
2
3
devices and information through the module. They can be managed by the AMS
(Asset Management System) or by the automation platform CPU.
These modules require an Ethernet + X-bus backplane and can only be installed in
the main local rack with the CPU or in RIO drops with a BMECRA31210
performance EIO adapter module. They cannot be installed in expansion racks.
4
2 Description
5
BMEAHp0p12 HART analog I/O modules are standard format (1 slot). They have a
case, which provides IP 20 protection of the electronics, and are locked into position
Module for connection via 20-way removable
terminal block by a captive screw. They are connected via a 20-way removable terminal block.
3
BMEAHp0p12 HART analog I/O modules feature the following:
1 A rigid body providing support and protection for the electronic card
2 A
module reference marking (a label is also visible on the right-hand side of the
module)
4 4 A
connector taking the 20-way removable screw or spring-type terminal block for
directly connecting the sensors or preactuators to the module
To be ordered separately:
5 A BMXFTB20p0 20-way removable terminal block
(referencing label supplied with each I/O module) or pre-wired cables with:
vv A 20-way terminal block at one end and flying leads at the other (BMXFTWp01S)
5 vv A 20-way terminal block and a 25-way SUB-D connector (BMXFCApp0 or
BMXFTApp22), for connection to Modicon Telefast ABE 7 sub-bases
BMXFTWp01S One version of the removable terminal block is equipped with a 3 or 5 m/9.84 or
16.4 ft cordset with color-coded flying leads (BMXFTWp01S). These preassembled
cordsets with reinforced shielding have color-coded flying leads at the other end.
7
Use with Modicon Telefast ABE7 sub-bases
Modicon Telefast ABE7CPA21 sub-base
The Modicon Telefast ABE7CPA21 sub-base is compatible with the BMEAHO0412
BMXFCApp0 output module.
3/26
References Modicon X80 I/O platform
HART analog I/O modules
Additional characteristics
4
BMEAHI0812 HART analog input module
The BMEAHI0812 module is a module with 8 high-level isolated inputs (15 bits + sign).
The BMEAHI0812 module offers the current range 4 - 20 mA for each of the inputs depending on the choice made
during configuration.
References
HART analog input module
6
Type of input Input signal Resolution Connection No. of Reference Weight
range channels kg/lb
Isolated 4 - 20 mA 15 bits Removable terminal 8 channels BMEAHI0812 0.233/
high-level inputs + sign block, 20-way, caged, 0.514
screw clamp, or
spring-type
8
(1) The BMEAHI0812 HART analog input module loses its isolation between channels when connected to the Modicon Telefast
ABE7CPA03 sub-base.
10
3/27
Presentation, Modicon X80 I/O platform
description BMXEHC0200/0800 counter modules
Presentation
BMXEHC0200 and BMXEHC0800 counter modules for the Modicon X80 I/O
1 platform are used to count the pulses generated by a sensor or to process the
signals from an incremental encoder.
The two modules differ in their number of counter channels, maximum input
frequencies, functions, and auxiliary input and output interfaces:
Counter No. of Maximum Integrated No. of No. of
module channels frequency functions physical physical
2
inputs outputs
BMXEHC0200 2 60 KHz Upcounting 6 2
Downcounting
Period meter
Frequency meter
Frequency generator
Axis control
BMXEHC0800 8 10 KHz Upcounting 2 –
3 Downcounting
Measurement
The sensors used on each channel can be:
bb 2-wire 24 V proximity sensors
bb 3-wire 24 V proximity sensors
bb 10/30 V output signal incremental encoders with push-pull outputs
BMXEHC0200/0800 counter modules can be used to meet the demands of
Description
6 1
BMXEHC0200/0800 counter modules are standard format. They occupy a single
slot in BMpXBPppp racks. They come in a plastic case, which provides IP 20
protection of the electronics, and are locked into position by a captive screw.
2
BMXEHC0200 module, 2 channels, 60 KHz
The front panel of the BMXEHC0200 counter module features:
3
7
1 Module and channel status display block
2 16-way connector for connecting the sensors of counter 0
4 3 16-way connector for connecting the sensors of counter 1
4 10-way connector for connecting:
-- Auxiliary outputs
BMXEHC0200 -- Sensor power supplies
To be ordered separately:
8 bb A BMXXTSHSC20 kit containing two 16-pin connectors and one 10-pin
connector
bb A BMXXSPpp00 shielding connection kit if the rack is not already equipped with
one (see page 2/3)
1
BMXEHC0800 module, 8 channels, 10 KHz
9
The front panel of the BMXEHC0800 counter module features:
1 Module and channel status display block
2 Connector taking the BMXFTB20p0 20-way removable terminal block 3 (same
as that of I/O modules)
2
To be ordered separately:
3
bb A 20-way removable terminal block 3 (caged, screw clamp, or spring-type)
BMXFTB20p0
10 bb A BMXXSPpp00 shielding connection kit if the rack is not already equipped with
one (see page 2/3)
BMXEHC0800 BMXFTB20p0
3/28
Functions Modicon X80 I/O platform
BMXEHC0200/0800 counter modules
Event counting This mode is used to determine the number of events received.
In this mode, the counter calculates the number of pulses applied to the IN_A input at time
intervals defined by the user.
The module counts the pulses applied to the IN_A input each time the pulse for this input lasts
2
longer than 5 μs (without anti-bounce filter).
3
bb Time and measure the execution time of a process
It measures the time elapsed during an event or between 2 events (IN_A input) according to a
selectable time base of 1 μs, 100 μs, or 1 ms.
The IN_SYNC input can be used to enable or stop a measurement.
The module can carry out a maximum of 1 measurement every 5 ms.
The shortest measurable pulse is 100 μs, even if the unit defined by the user is 1 μs.
The maximum measurable duration is 4,294,967,295 units (unit to be defined).
Ratio counting Ratio counting mode only uses the IN_A and IN_B inputs. There are 2 possible modes:
bb Ratio 1: Used to divide 2 frequencies. This is intended for applications such as flowmeters,
mixers, etc.
bb Ratio 2: Used to subtract 2 frequencies. This is intended for the same applications, but for
4
those requiring more precise regulation (more similar frequencies).
Ratio 1 mode gives the results in thousandths for better accuracy (a display of 2000 corresponds
to a value of 2) and ratio 2 mode gives the results in Hz.
The maximum frequency that the module can measure on the IN_A and IN_B inputs is 60 kHz.
Downcounting This mode is used to list a group of operations. In this mode, activating the synchronization
function starts the counter which, starting from a user-defined preset value, decreases with
5
each pulse applied to the IN_A input, until it reaches 0. This downcounting is made possible
when the enable function has been activated. The counting register is thus updated at 1 ms
intervals.
One basic use of this mode is to signal, using an output, the end of a group of operations (when
the counter reaches 0).
Loop (modulo) counting This mode is used in packaging and labelling applications where actions are repeated on sets
of moving objects:
bb In upcounting, the counter increases until it reaches the user-defined “modulo - 1” value. On
the next pulse, the counter is reset to 0 and upcounting restarts.
bb In downcounting, the counter decreases until it reaches 0. On the next pulse, the counter is
reset to the user-defined “modulo - 1” value. Downcounting can then restart.
7
The maximum frequency applied to the IN_A and IN_B inputs is 60 kHz.
The maximum frequency of the modulo event is 1 event every 5 ms.
The maximum modulo value is 4,294,967,296 (possible by declaring 0 in the modulo adjust
value).
The maximum frequency applied simultaneously to the IN_A and IN_B inputs is 60 kHz.
8
The maximum frequency of the referencing event is 1 event every 5 ms.
The counter value is between - 2,147,483,648 and + 2,147,483,647.
Width modulation In this operating mode, the module uses an internal clock generator to supply a periodic signal
on the module's O0 output. Only the O0 output is affected by this mode, as the O1 output is
independent of it.
10
3/29
Functions (continued) Modicon X80 I/O platform
BMXEHC0200/0800 counter modules
Event counting This mode is used to determine the number of events received.
In this mode, the counter calculates the number of pulses applied to the IN_A input at time
2
intervals defined by the user.
As an option, it is possible to use the IN_AUX input during a period of time, provided that the
enable bit has been configured.
The module counts the pulses applied to the IN_A input each time the pulse for this input lasts
longer than 50 μs (without anti-bounce filter).
Pulses with less than 100 ms synchronization are lost.
Downcounting This mode is used to list a group of operations. In this mode, when counting is enabled
3 (software validation via the valid_sync command), a rising or falling edge on the IN_AUX input
causes a value, defined by the user, to be loaded in the counter. The latter decreases with each
pulse applied to the IN_A input until it reaches the value 0. Downcounting is made possible
when the force_enable command is high (software positioning).
The smallest pulse applied to the IN_AUX input varies according to the selected filter level.
The maximum frequency applied to the IN_AUX input is 1 pulse every 25 ms.
4
Loop (modulo) counting This mode is used in packaging and labelling applications where actions are repeated on sets
of moving objects.
The counter increases with each pulse applied to the IN_A input until it reaches the user-
defined “modulo - 1” value. On the next pulse in the upcounting direction, the counter is reset to
0 and upcounting restarts.
Up/down counter This mode is used for an accumulation, upcounting, or downcounting operation on a single
input.
Each pulse applied to the IN_A input produces:
bb Upcounting of pulses if the IN_AUX input is high
bb Downcounting of pulses if the IN_AUX input is low
6
The counter values vary between the limits - 65,536 and + 65,535.
The maximum frequency applied to the IN_A input is 10 kHz.
Pulses applied to the IN_A input after a change of direction are only upcounted or downcounted
after a period corresponding to the delay for taking account of the state of the IN_AUX input due
to the programmable filter level on this input.
One 32-bit mode 32-bit counter counting 32-bit counter counting mode is available for channels 0, 2, 4, and 6 (channels 1, 3, 5, and 7 are
now inactive). It behaves in the same way as the up/down counting mode using up to 3 physical
7 inputs. It enables simultaneous upcounting and downcounting.
The counter values vary between the limits - 2,147,483,648 and + 2,147,483,647 (31 bits +
sign).
The maximum frequency applied to the IN_A and IN_B inputs is 10 kHz.
The smallest pulse applied to the IN_AUX input is defined according to the filtering applied to
this input.
The maximum frequency of loading the preset value is 1 every 25 ms.
10
3/30
References Modicon X80 I/O platform
BMXEHC0200/0800 counter modules
References
BMXEHC0200/0800 counter modules (1)
Description No. of
channels
Characteristics Reference Weight
kg/lb
1
Counter modules 2 60 kHz counting BMXEHC0200 0.112/
for 24 V c 0.247
2 and 3-wire sensors and 8 10 kHz counting BMXEHC0800 0.113/
10/30 V c incremental 0.249
encoders with push-pull
outputs
2
BMXEHC0200
Shielding connection kit Comprising a metal bar and two See page 2/3 –
for BMXEHC0200/0800 support bases for mounting on rack
modules
(1) Typical consumption: See the power consumption table available on our website
5
www.schneider-electric.com.
(2) The shielding on the cordsets carrying the counter signals must always be connected to the
BMXXSPpp00 shielding connection kit mounted under the rack that holds the BMXEHC0200
BMXFTB20p0 module (see page 2/3).
10
3/31
Presentation Modicon X80 I/O platform 3
Presentation
The time stamping system is a complete solution providing a SCADA with a
1 sequence of events that are time-stamped at source, enabling the user to analyze
the source of any abnormal behavior in an automated system.
The SOE (sequence of events) is displayed in the alarms log or in the list of events
for a client such as a SCADA.
Each event in the SOE is a change of value (transition) of a discrete I/O detected by
2 a time stamping module.
Advantages
Using the time stamping system has the following advantages:
bb No PLC programming
bb Direct communication between the time stamping modules and the client; if the
3 time stamping modules are in a Quantum Ethernet I/O drop, the bandwidth of the
PLC communication is not used
bb Consistency of the I/O values between the process (time stamping modules) and
the client
BMXERT1604T module bb Consistency is maintained irrespective of the operating mode
bb No loss of events under normal operating conditions
bb Management of Hot Standby configurations on the PLC and/or SCADA
4 redundancy
BMXERT1604T module
This module has 16 discrete inputs which carry out the time stamping at source
outputs with a resolution of 1 ms.
6
To help ensure no event is lost, all events are stored and kept in a buffer located in
the product until OFS takes them.
This module can be placed either in an RIO drop, or in a local rack equipped with a
BMpCRA31210 module.
The CRA module is synchronized via the DCF 77 or IRIG-B standards.
OFS V3.60
7 OFS V3.60 is used to access events stored in the various buffers in the architecture
and to place them in the SCADA via the standard OPC DA protocol. For further
information, consult our website www.schneider-electric.com.
10
3/32
Performance, Modicon X80 I/O platform 3
Performance
Performance Event source Value
module
Between two identical source modules BMXERT1604T 1.6 < resolution < 3.3 ms
1
in the same rack BMpCRA31210 10 ms
10
3/33
Presentation, Modicon X80 I/O platform
description BMXEAE0300 SSI encoder interface module
Presentation
The BMXEAE0300 SSI encoder interface module 1 for the Modicon automation
1 platform (1) is a 3-channel standard synchronous serial interface module designed
for use with SSI absolute encoders 2.
The BMXEAE0300 module enables SSI encoder values to be processed on PAC
platforms for applications requiring accurate and reliable position/angular control,
such as:
bb Hydro power, e.g. dam inlet gate position control
2 bb Wind power, e.g. wind turbine blade pitch control
bb Complex motion loop control, e.g. ship elevator, blast furnace, flame cutting, etc.
The BMXEAE0300 module provides a migration path from Premium (with
TSXCTY2C measurement and counter module) to the Modicon X80 I/O platform SSI
solution to compete in the above market segments.
Like any other application-specific module, the BMXEAE0300 module is installed in
3 the rack slots (01 to 11). The number of modules is limited by the maxiumum number
of application-specific channels, permitted according to the CPU type (consult our
website www.schneider-electric.com).
Dam inlet gate control
Modicon X80 I/O platform with Modicon M340 processor
Inlet gate control enables the water level in a dam to be monitored and controlled:
bb The SSI encoder provides the PLC with accurate feedback of the gate position
5
efficiency.
bb The SSI absolute encoder is frequently used to feedback the position of the blade
due to its reliability and robustness.
bb Typically, the position of each of the 3 blades are read by the SSI encoders and
then transmitted to the CPU via the SSI interface for motion loop control.
Sometimes, 3 additional SSI inputs act as backup. Therefore, this new offer is
adequately sized for the channel density.
6 Description
The BMXEAE0300 SSI encoder interface module is standard format (1 slot). Its
housing provides IP 20 protection of the electronics and it is locked in each slot (01
to 11) by a captive screw.
The front panel of the BMXEAE0300 module features:
1 A rigid housing providing support and protection for the electronic card
7 2 The module reference marking (a label is also visible on the right-hand side of the
module)
1 3 A display block indicating:
vv Module status, 4 LEDs:
2
-- RUN (green): module’s operational status
-- ERR (red): internal fault detected in the module or a fault detected between
3 the module and the rest of the configuration
8 -- I/O (red): external fault detected
-- DL (green): firmware download status
vv Status of the 3 SSI channels, 8 LEDs:
-- Sx (green): channel x input (x = 0, 1, or 2)
4 -- Qx (green): reflex output for channel x (x = 0, 1, or 2)
-- I0/1 (green): capture inputs for the 3 SSI channels
5 4 A connector for a 28-way terminal block, for connecting to a removable caged or
9 spring terminal block on sensors and preactuators
To be ordered separately:
BMXEAE0300 BMXFTB28p0
5 A 28-way removable caged terminal block BMXFTB2800 or spring terminal block
BMXFTB2820, supplied with a channel identification label
vv A shielding connection kit to help protect against electrostatic discharge,
consisting of a metal bar and two sub-bases for mounting on the rack:
10
BMXXSPpp00 (reference dependent on the number of slots in the rack) (see page
2/5)
vv A set of clamping rings STBXSP30p0 for the connection cable shielding braids
(reference dependent on the cable diameter) (see page 2/3)
(1) Only for the Modicon automation platforms compatible with Modicon X80 I/O platform
3/34
Functions, Modicon X80 I/O platform
references BMXEAE0300 SSI encoder interface module
Main features
bb Supported by Unity Pro V6.0 (or higher).
6
bb Supports absolute encoder 24 V model with standard SSI interface, including Telemecanique
Sensors OsiSense SSI encoders. For further information, consult the website www.tesensors.com.
bb Standards and approvals: e, UL, CSA, C-Tick, GOST, etc.
References
SSI encoder interface module (1) 7
Description Number Description Reference Weight
of channels per channel kg/lb
SSI encoder 3 SSI 1 reflex output for each SSI channel BMXEAE0300 0.138/
interface module channels 2 capture inputs for the 3 SSI channels 0.304
8 to 31 bits data width
8
4 ranks of baud rates:100 kHz, 200 kHz,
500 kHz, 1 MHz
Capture and compare functions
Cabling accessories
Description Description, use Reference Weight
BMXEAE0300 BMXFTB28p0 kg/lb
28-way removable Caged BMXFTB2800 0.111/
terminal block
Spring BMXFTB2820
0.245
0.080/
9
0.176
Shielding Comprising a metal bar and two support bases See page 2/3 –
connection kit for mounting on rack
for module
BMXEAE0300
(2)
(1) Typical consumption: See the power consumption table available on our website www.schneider-electric.com.
10
(2) The shielding on the cables carrying the power supply to the module, each SSI channel, the capture inputs and
the reflex outputs (if any of them is wired) must always be connected to the BMXXSPpp00 shielding connection
kit mounted under the rack holding the BMXEAE0300 module (see page 2/3).
3/35
Presentation, Modicon X80 I/O platform
description BMXMSP0200 motion control module
Presentation
The 1 BMXMSP0200 motion control pulse train output (PTO) module for the
1 Modicon X80 I/O platform is used for controlling third-party variable speed drives 2,
which have an integrated position loop and inputs that are compatible with open
collector outputs.
The BMXMSP0200 control module is also directly compatible with the Lexium 32C
and 32M 3 servo drive ranges, which have an integrated pulse control interface.
2 The BMXMSP0200 motion control PTO module has two independent PTO channels.
Like any other application-specific module, it is installed in the rack slots (labelled 01
to 11). The number of modules is limited by the maximum number of application-
specific channels permitted according to the CPU type:
bb Standard BMXP341000: Maximum of 20 application-specific channels (1)
bb Performance BMXP3420p0: Maximum of 36 application-specific channels (1)
bb BMEP5810: Maximum of 24 application-specific channels (1)
3 bb BMEP5820: Maximum of 32 application-specific channels (1)
bb BMEP5830 and BMEP5840: Maximum of 64 application-specific channels (1)
bb BMEP585040: Maximum of 180 application-specific channels (1)
bb BMEP586040: Maximum of 216 application-specific channels (1)
Servo motors
Description
4 The BMXMSP0200 motion control module is standard format (1 slot). Its housing
provides IP 20 protection of the electronics and it is locked in each slot (01 to 11) by a
4 captive screw.
5 The front panel of the BMXMSP0200 motion control module features:
4 A rigid body providing support and protection for the electronic card
6
5 5 A module reference marking (a label is also visible on the right-hand side of the
module)
6 A display block indicating:
bb Module status, 4 LEDs (RUN, ERR, I/O and DL)
7 bb Status of the auxiliary inputs, 4 per channel
bb Status of the PTO outputs, 2 per channel
bb Status of the auxiliary outputs, 2 per channel
BMXMSP0200
BMXFTB28p0
To be ordered separately:
8 A 28-way removable caged terminal block BMXFTB2800 or spring terminal
block BMXFTB2820, supplied with a channel identification label
bb A shielding connection kit to help protect against electrostatic discharge,
7
consisting of a metal bar and two sub-bases for mounting on the rack: BMXXSPpp00
(reference dependent on the number of slots in the rack) (see page 2/3)
bb A set of clamping rings STBXSP30p0 for the connection cable shielding braids
(reference dependent on the cable diameter) (see page 2/3)
8
counter modules, BMXMSP0200 (2-channel) motion control module, BMXNOM0200
(2-channel) and BMXNOR0200H (1-channel) serial communication modules,
BMEAHI0812 (8-channel) analog input module and BMEAHO0412 (4-channel) analog
output module, BMXEAE0300 (3-channel) SSI module and BMXERT1604T (16-channel)
discrete input module.
10
3/36
Operation, Modicon X80 I/O platform
references BMXMSP0200 motion control module
Operation
Block diagram of a BMXMSP0200 module channel
Integrator
PTO output CCWp Servo
Pulses
motor
Proximity sensor
Proximity
Position switch
BMXMSP0200
4
References
Motion control modules (1)
Description Number of Description Reference Weight
channels per channel kg/lb
PTO module
(PTO = Pulse
2 2 x 200 kHz max. PTO outputs
2 x 24 V c/50 mA auxiliary outputs
BMXMSP0200 0.145/
0.320
5
Train Output) 4 x 24 V c auxiliary inputs
Cabling accessories
Description Description, use Length Reference Weight
kg/lb
28-way
removable
Caged – BMXFTB2800 0.111/
0.245 6
terminal block Spring – BMXFTB2820 0.080/
0.176
BMXMSP0200 BMXFTB28p0 Connection From BMXMSP0200 (screw terminal block) 3 m/9.84 ft VW3M8223R30 –
cable module to Lexium 32C or 32M (RJ45 connector)
(cable with flying leads at one end and an RJ45
7
for daisy chain
or pulse connector at the other)
control (2)
Shielding Comprising a metal bar and two support bases – See page 2/3 –
connection kit for mounting on rack
for module
BMXMSP0200
(1) Typical consumption: See the power consumption table available on our website www.schneider-electric.com.
8
(2) The shielding on the cordsets carrying the motion control signals must always be connected to the
BMXXSPpp00 shielding connection kit mounted under the rack holding the BMXMSP0200 module (see page
2/3).
10
3/37
Presentation, Modicon X80 I/O platform 0
download blocks.
Setting up drives on the CANopen network is facilitated through Motion Tree
Manager organization in the Unity Pro browser, making it easy for users to access
3 the application drives.
Applications
Lexium SD328A
The features of the Motion Function Blocks library are particularly suitable for
machines with independent axes. In the case of these modular/special machines,
Lexium 32 MFB function blocks are an ideal solution for controlling single axes. The following
are typical applications for this type of architecture:
5 Functions
The table below lists the function blocks of the MFB library and the drives compatible
with them. The prefix indicates the block family:
bb MC: Function block defined by the Motion Function Blocks PLC Open standard
bb TE: Function block specific to Schneider Electric products
bb Lxm: Function block specific to Lexium servo drives
6 Type Function Function block Altivar 312 Altivar 71 Lexium 32 Lexium ILA/ Lexium
ILE/ILS SD328A
Management Read an internal parameter MC_ReadParameter
and motion Write an internal parameter MC_WriteParameter
Read the current position MC_ReadActualPosition
Read the instantaneous speed MC_ReadActualVelocity
7 Acknowledge detected error
messages
MC_Reset
8
Additional movement MC_MoveAdditive
Homing MC_Home
Movement at given speed MC_MoveVelocity
Read diagnostic data MC_ReadAxisError
Read servo drive status MC_ReadStatus
Torque control MC_TorqueControl
Read actual torque value MC_ReadActualTorque
9 Save and
Manual control
Read drive parameters and store
MC_Jog
TE_UploadDriveParam
restore in PLC memory
parameters Write drive parameters TE_DownloadDriveParam
(FDR) from PLC memory
Advanced Read a motion task Lxm_UploadMTask
Lexium Write a motion task Lxm_DownloadMTask
functions
10
Start a motion task Lxm_StartMTask (1)
Set the reduction ratio, signed Lxm_GearPosS (1)
System Communication with the servo drive TE_CAN_Handler
Compatible (1) The Lxm_StartMTask and Lxm_GearPosS function blocks are only compatible with the type Lexium 32
(LXM32M) servo drives.
3/38
Setup Modicon X80 I/O platform 0
Motion Tree Manager automatically creates links between the CANopen bus
configuration and the MFB function block data using a limited amount of
configuration data. 2
General axis parameters
In this tab, the designer is prompted to define:
bb The name of the axis that will identify it in the browser for the entire application
bb The address of the drive on the CANopen bus
Axis parameters
3
The drop-down lists in this tab are used to determine the exact type of drive: family,
version.
4
Variable names
This last tab is used to identify data structures:
bb Axis_Reference: Used by the function block instances for the axis in question
bb CAN_Handler: Used to manage communication with the drive via the CANopen
Motion Tree Manager integrated in the Unity Pro browser network
Recipe definition 5
The “recipes” attached to the axis are the data structures containing the adjustment
parameters of a given drive. This data is used when:
bb Changing the drive with restoration of the context during “Faulty Device
Replacement” (FDR) maintenance
bb Changing the manufacturing program of the machine and calling up an
appropriate set of parameters: servo control gains, limitations, etc. adapted to the
weight and size of the moving parts 6
bb Saving parameters in the initial values of the PLC application
7
Programming, diagnostics, and maintenance
Communication between the PLC and drive is automatically set up by the system as
General parameters: Axis name and address
soon as a TE_CAN_Handler instance is declared in the Unity Pro task with which the
axis is associated. Movements are then programmed by sequencing function blocks
from the library in the user's chosen Unity Pro editor (LD, ST, FBD).
10
3/39
Presentation, Modicon X80 I/O platform
description BMXETM0200H frequency input module
Presentation
The BMXETM0200H frequency input module offers turbine shaft and engine speed
1 monitoring functionality for general purpose turbomachinery control (TMC)
applications. It can be integrated into Modicon M340 and M580 standard and
high-availability systems.
TMC application include prime movers, driven equipment, auxiliaries, mechanical
retrofits, and protection. With the Modicon Package solution, the frequency input and
measurement function is available for the following general purpose TMC application
types:
2 bb Large hydro turbines
bb Small steam turbine generators
bb Small hydro turbines
bb Small mechanical drive gas turbines
bb Diesel generators
bb Reciprocating compressors
bb Packaged air compressors
3 bb Single-stage mechanical drive turbines: pumps
Integration
Sampling
Inlet steam
Shaft speed
TTV
M340 local rack
To AI card (inlet pressure)
CV
To AO card (turbine control)
BMXETM0200H
Functionality
The purpose of the BMXETM0200H module is to monitor the turbine shaft or engine
6 speed. It is designed to receive electrical pulses generated by the gear tooth sensing
probe, cam, and crank etc. and convert these pulses into a numerical value. The
measured value of the turbine shaft rotating velocity is highly accurate with a fast
refresh rate.
7 governor. This control mechanism will automatically track and direct the speed of
driven equipment (such as a generator or compressor) and a prime mover (such as a
turbine or engine) under varying load conditions with the aim of:
bb maintaining the selected speed
bb limiting slow and fast speeds.
BMXETM0200H bb helping to protect mechanical parts and customer investment by anticipating
overspeeds by means of its acceleration and jerk detection capability
10
3/40
References Modicon X80 I/O platform
BMXETM0200H frequency input module
Module specifications
Availability and compatibility
Available for Modicon M340 and M580 standalone and HSBY platforms, on local
rack or RIO rack with hot swapping supported.
1
Ambient operating temperature
Hardened with extended temperature range from -25…70 °C/-13…158 °F and
conformal coating.
Measurement performance
2 frequency input channels for 1V & 1Hz signal up to a maximum of 500 KHz with
100 KHz, 10 KHz, and 1 KHz input filters.
2
Supported signal source device type
Speed sensor inputs support passive pickup, active speed sensor (output OC, TTL,
ST), potential transformer, and incremental encoder.
Digital reflex outputs
1 positive 24 VDC reflex digital output per channel controlled from an embedded
comparator. 3
Error detection
Detects broken wire and probe health status.
Dedicated TMC functions
A set of dedicated TMC functions for turbine shaft monitoring, including:
4
bb Frequency pattern recognition up to 512 pulses per pattern
bb Acceleration and jerk detection
bb Phase angle and ratio detection between channels
bb Scaling factor for RPM measurement up to 1,024 teeth per revolution
bb Alarm bits that can be time stamped by the Modicon M580 controller
Software configuration
Configurable using Unity Pro V11 (S, L, and XL) with TMC Hotfix integrated.
Reference
5
Frequency input module
Description Composition Reference Weight
kg/lb
Ruggedized 1 ms cycle time BMXETM0200H 0.124/
turbomachinery 2 digital reflex outputs 0.273
frequency input
module (2 channels)
2 discrete inputs (for frequency
measurement functions)
6
10
3/41
Presentation, Modicon X80 I/O platform
description PMESWT0100 weighing module
Presentation
1
The PMESWT0100 Scaime partner weighing module is integrated in a Modicon X80
I/O platform with an Ethernet + X-bus BMEXBPpp00(H) rack and a Modicon M580
PMESWT0100 Scaime partner BMEP58p0p0 PLC or in a Modicon X80 RIO drop with an Ethernet + X-bus
weighing module BMEXBPpp00(H) rack and a BMECRA31210 adapter.
With this module it is possible to go beyond the scope a of simple weighing
application.
It is suitable for static weighing applications such as silo level measurement and
2 scale weighing and it also suits well for low speed dynamic weighing applications
such as filling, dosing, and material transfer.
The Modicon X80 I/O platform can manage the whole weighing environment as well
as the whole machine or industrial process associated with the weighing system.
Indeed, weighing data is accessible by the PLC via implicit exchanges or explicit
commands. Once the weighing signal is received, it is processed and transferred by
the weighing module to the Modicon M580 PLC via the Ethernet backbone.
4 2
The PMESWT0100 weighing module features the following:
1 A rigid body providing support and protection for the electronic card
2 A module reference marking (a label is also visible on the right-hand side of the
3
module)
3 A module and channel status display block
4 4 Screw terminals for connecting an external HMI output
5 5 Screw terminals for connecting discrete reflex inputs
5 6
6 Screw terminals for connecting discrete reflex outputs
7 Screw terminals for connecting input load cells
Main characteristics
7
Measurement input
1 weighing channel per module, comprising up to 8 load cells connected via junction
box
6 PMESWT0100
Input load cell supply voltage
5Vc
Internal resolution
24 bit converter
User resolution
up to 1,000,000, factory-calibrated 500,000 at 2 mV/V
7 Internal measurement rate
6 to 400 measurements per second
External measurement rate
100 measurements per second
Discrete reflex outputs
Number of applications
8 4 positive logic outputs, 2 for dosing and 2 for threshold monitoring
Maximum voltage
55 V c
Nominal current
400 mA
9
Response time
2 ms discrimination
Discrete inputs
Number of applications
2 positive logic inputs, weighing functions
Low voltage range
10 0…3 V c
High voltage range
9…28 V c
High current
20 mA at 24 V c
3/42
References Modicon X80 I/O platform
PMESWT0100 weighing module
References
Weighing module
Description Composition Reference Weight
kg/lb
1
Scaime partner - Load cell input 100 measurements/s PMESWT0100 (1) 0.233/
weighing module (for 1 to 8 load cells) 0.514
(1 weighing channel per - 4 discrete reflex outputs (for threshold
module) monitoring and dosing)
- 2 discrete inputs (for weighing
2
functions)
- 1 output for an external HMI
(1) To order this product, please consult our Customer Care Centre.
PMESWT0100
3
10
3/43
1
10
4/0
4/2
Contents 4 - Safety I/O and power modules
10
4/3
4/1
Selection guide Modicon X80 I/O platform
Safety I/O modules
Applications 16-channel safety digital input module 8-channel safety digital output module 4-channel safety relay output module 4-channel safety analog input module
1 1
2 2
Voltage 24 V 24 V 24 V c/24...230 V a –
3 Current per channel 3.5 mA 0.5 A 5A –
3
Range Voltage – – – 6
Current – – 4...20 mA
Acquisition period Hot-swap RAID HDD and battery backup – – – 5 ms for the 4 inputs
5 Connection Via 20-way caged, screw clamp, or spring-type removal terminal block Via 20-way caged, screw clamp, or spring-type removal terminal block BMXFTB2000/2010/2020 5
BMXFTB2000/2010/2020
Logic Positive –
7 Protection – Yes – 7
Logic – Positive –
Between channels and bus 1500 Vrms 1500 Vrms 3000 Vrms 1500 Vrms
8 8
Between channels and ground 1500 Vrms 1500 Vrms 3000 Vrms 1500 Vrms
Protection of inputs Use a fast blow fuse, max 0.5 A, depending on the module current load –
9 Output fuse protection – Use a fast blow fuse, max 6 A, depending on the
module current load
Use a fast blow fuse, max 6 A, depending on the relay
contact current load
–
9
Maximum dissipated power 3.57 W 4.40 W 3.90 W 3.98 W
4/2 4/3
Presentation, Modicon X80 I/O platform
description Safety power supply
Presentation
The safety power supply in the Modicon X80 I/O offer is the BMXCPSppp2S.
1 The BMXCPS4022S power supply module:
b Converts 24...48 V c power into two output voltages, 24 V c and 3.3 V c,
which are distributed over the backplane
b Detects over voltage, overload, and short-circuit conditions on both the 3.3 V c
and 24 V c backplane lines
The BMXCPS3522S power supply module:
2 b Converts 100...150 V a power into two output voltages, 24 V c and 3.3 V c,
which are distributed over the backplane
b Detects over voltage, overload, and short-circuit conditions on both the 3.3 V c
and 24 V c backplane lines
The BMXCPS4002S power supply module:
b Converts 110...240 V a power into two output voltages, 24 V c and 3.3 V c,
6
M580_62098_CPSCT16005C
Description
The BMXCPSppp2S power supply module includes:
1 1 Display panel comprising LEDs whose combinations provide a quick diagnostic
4 status of the supply power module:
-- ACTIVE LED (green), on when the power supply is the master power supply,
off when it acts as a slave supply in redundant application
-- OK LED (green), on if rack voltages are present and correct
-- RD LED (green), on when all the internal power supply modules function
2
normally
2 Printed serial number and product version
5 3
3 Pencil-point Reset pushbutton for a cold restart of the application.
4 2-way connector that can take a removable terminal block (caged or spring-type)
4 for connecting the alarm relay.
5 A 5-way connector that can take a removable terminal block (caged or spring-
type) for connecting the following:
-- AC or DC line supply
-- Protective earth ground
6
5
BMXCPSppp2S 6 1 hook and 1 screw for mechanical attachment and grounding connection to
backplane.
Included with each power supply module: Set of two caged removable terminal
blocks (5-way and 2-way) BMXXTSCPS10
To be ordered separately (if necessary): Set of two spring-type removable
terminal blocks (5-way and 2-way) BMXXTSCPS20
7 Compatibility of the power supply with the rack
The BMXCPSppp2S is a safety certified power supply that can be used as:
b a main local rack
b an extended local rack
b a main remote rack
b an extended remote rack
8 The BMXCPSppp2S is a redundant power supply module. It can be installed alone
in single power supply rack or dual power supply rack as a pair (master and slave)
For high available applications, two independent redundant power supplies can be
used to increase the security of power supply. In case the master power supply fails
to provide the whole current, the slave power supply changes to master mode and
9 continue to function.
The power supply module has to be inserted in the leftmost power supply slots of
each rack (marked CPS).
Advanced diagnostics
The BMXCPSppp2S can provide advanced diagnostics such as current load,
10 temperatures, remaining life time, under voltage thresholds. These are also
representing unique values that will simplify the maintenance by predicting when to
replace the power supply before it fails.
Note: LED diagnostic display is provided for the module and for each input channel.
4/4
Functions, Modicon X80 I/O platform
references Safety power supply
Functions
Alarm relay
The alarm relay incorporated in each power supply module has a volt-free contact accessible on the front panel,
on the 2-way connector.
1
The operating principle is as follows:
b The alarm relay is energized and its contact is closed (state 1) in normal operation, with the PLC in RUN.
b The relay de-energizes and its associated contact opens (state 0) whenever the application stops, even
partially, due to any of the following:
v Occurrence of a blocking fault (RAM detected error in memory check, Safety watchdog overrun detected on
CPU, etc.)
2
v Incorrect rack output voltages
v Loss of supply voltage
Reset pushbutton
The power supply module in each rack has a Reset button on the front panel.
3
Pressing the Reset button on the power supply causes re-initialization of all modules in same rack as the power
supply. If the BMXCPSppp2S power supply module is in the main local rack, pressing the Reset button causes
re-initialization of the CPU.
In a redundant design, with two BMXCPSppp2S power supply modules, you can press the Reset button on
4
either, or both, power supply modules to execute the reset function.
Pressing this pushbutton triggers a sequence of service signals, which is the same as that for:
b A power break, when the pushbutton is pressed.
b A power-up, when the pushbutton is released
In terms of the application, these operations represent a cold start (forcing the I/O modules to state 0 and
initializing the processor).
References
Safety power supply module (1)
5
Line supply Available power (2) Nominal current Reference Weight
kg/lb
3.3 V c (3) 24 V c rack (3) Total 24 V c rack (3)
24...48 V c 18 W 40 W 40 W 1.67 A BMXCPS4022S 0.810/
1.786
100...150 V a 180 W 40 W 40 W 1.67 A BMXCPS3522S 0.610/
1.345
6
100...240 V c 18 W 40 W 40 W 1.67 A BMXCPS4002S 0.510/
1.124
(1) Include a set of 2 caged removable connectors. Spring-type connectors available separately under reference
8
BMXXTSCPS20.
(2) The sum of the power consumed on each voltage (3.3 V c and 24 V c) must not exceed the total power of the module. See
the power consumption table available on our website www.schneider-electric.com.
(3) 3.3 V c and 24 V c rack voltages for powering modules in the Modicon X80 I/O rack.
10
4/5
Presentation Modicon X80 I/O platform
Safety I/O modules
Safety discrete I/O modules
In the Modicon X80 offer, a safety project can include both safety modules and
non-safety modules:
b Safety modules in the SAFE task.
b Non-safety modules only for the non-safe tasks (MAST, FAST, AUX0, and AUX1).
Modicon M580 Safety configuration with a mix of standard Only non-safety modules that do not interfere with the safety function can be added
2 X80 & Safety I/O
to a safety project
Safety I/O modules can be used to connect the safety PAC to the sensors and
actuators that are part of the safety loop.
Each safety I/O module incorporates a dedicated safety processor.
M580_62098_SPSCT17008
Safety I/O modules can be installed in the local backplane or in RIO drops.
3 All safety I/O modules supports SIL3 standards according to IEC61508. Evaluation
is indicated by category (Cat) and performance level (PL).
Each safety I/O module provides module and channel LED diagnostics on the front
Modicon Safety configuration with full safety X80
modules with removable terminal blocks face of the module:
b The top four LEDs (Run, Err, I/O, and Lck) together describe the state of the
4 module.
b The bottom rows of LEDs combine with the top four LEDs to describe the state
and health of each input or output channel.
5
b BMXSDI1602 digital input module
b BMXSDO0802 digital output module
b BMXSRA0405 digital relay output module.
These modules can only be used with a safety CPU.
BMXSDI1602
The BMXSDI1602 safety digital input module presents these features:
BMXSDO0802
The BMXSDO0802 safety digital output module presents these features:
b 8 non-electrically isolated 0.5 A outputs.
b 24 V c rated output voltage.
b Achieves SIL3, Cat4/PLe evaluation.
8 b Monitors the external pre-actuator power supply.
BMXSRA0405
The BMXSRA0405 safety digital relay output module presents these features:
b 4 relay outputs with 5 A current.
b Rated output voltage of 24 V c and 24...230 V a (over voltage category II).
9 b Achieves SIL2, Cat2/PLc evaluation using 1 relay and SIL3, Cat4/PLe using 2 relays.
b Support for 8 pre-defined application wiring configuration selections.
b Configurable automatic self-test monitoring of the relay capacity to execute the
commanded output state (depending on the selected application wiring
configuration).
b Configurable module settings for fallback mode and fallback timeout (in ms).
4/6
Description, Modicon X80 I/O platform
connections Safety discrete I/O modules
1 Description
Safety discrete I/O modules are standard format with one slot. They have an IP 20
2 case to protect the electronics, and are locked into position with a captive screw. 1
3
To be ordered separately: A BMXFTB20p0 20-way removable terminal block
4 (identification label supplied with each I/O module) or a preassembled cordset with
a 20-way removable terminal block at one end and flying leads at the other (see
connections page 4/8):
The BMXSDI1602, BMXSDO0802 and BMXSRA0405 safety discrete modules
include:
1 Lock/unlock configuration button. 2
2 Rigid body providing support and protection for the electronic card
3 Module reference marking (a label is also visible on the right-hand side of the
module)
5 4 Display panel comprising LEDs whose varying combinations provide a quick
diagnostic status of the module and each channel:
- RUN LED (green): module in operation
- ERR LED (red): module detected error 3
- I/O LED (red): detected I/O module error
- LCK LED (bi-color green/red): indicates the configuration status
- 1 LED per channel (bi-color green/red): indicates the channel status
5 Connector taking the 20-way removable terminal block for connecting sensors or
preactuators
6
Caged (1) One 0.34 mm² wire (AWG 22) One 1 mm² wire (AWG 18)
Screw clamp (1) One or two 0.34 mm² wires (AWG 22) Two 1.5 mm² wires (AWG 15)
Spring-type One 0.34 mm² wire (AWG 22) One 1 mm² wire (AWG 18)
(1) Connectors are equipped with captive screws: max. tightening torque 0.5 N.m/0.37 lb-ft.
BMXFTB2000
Note: No cordset is provided for cabling safety X80 I/O modules. Too many options are
possible according to the kind of:
- applications: full safety, safety mixed with availability, etc.
7
- safety level: SIL3/Cat2, SIL3/Cat4, SIL2, etc.
For more information on the different cabling options, please refer to detailed user manuals
published on our website: www.schneider-electric.com.
10
4/7
References Modicon X80 I/O platform
Safety discrete I/O modules
Safety analog input module
References
M580_62098_CPSCT16001D
BMXSDI1602
Safety discrete output modules
Type of Input Connnection IEC/EN N° of Reference Weight
current voltage via 61131-2 channels kg/lb
M580_62098_CPSCT16002A
3
conformity (common)
DC 24 V (logic Cage, screw or Yes 8 BMXSDO0802 0.120/
positive) spring-type non-isolated 0.264
20-way outputs
removable (1 x 8)
terminal block
removable
terminal block
BMXSDO0802
7
BMXSRA0405
10
4/8
Presentation, Modicon X80 I/O platform
description, Safety analog input module
connections,
references
Presentation
1
M580_62098_CPSCT16001D
The safety analog input module in the Modicon X80 I/O offer is the BMXSAI0410:
2
The BMXSAI0410 safety analog input module presents these features:
b 4 isolated analog 4...20 mA current input channels.
1
b 16 bit resolution (12,500 counts), spanning the data range of 0...25 mA
3 b Current out of range detection, for current values less than 3.75 mA or greater
4 than 20.75 mA
b Achieves SIL3, Cat2/PLd evaluation using 1 input channel and SIL3, Cat4/PLe
using 2 input channels
This module can only be used with a safety CPU. 2
Description
The BMXSAI0410 safety analog input module includes:
1 Lock/unlock configuration button.
5 2 Rigid body providing support and protection for the electronic card
3 Module reference marking (a label is also visible on the right-hand side of the
module)
4 Display pannel comprising LEDs whose varying combinations provide a quick
3
diagnostic status of the module and each channel (1):
- RUN LED (green): module in operation
- ERR LED (red): module detected error
- I/O LED (red): detected I/O module error
- LCK LED (bi-color green/red): indicates the configuration status
BMXSAI0410
- 1 LED per channel (bi-color green/red): indicates the channel status
5 Connector taking the 20-way removable terminal block for connecting sensors or
4
preactuators
Connections
20-way removable terminal blocks are used to connect the 3 safety discrete I/O
modules. (2)
M580_62098_OPFJR17001A
Spring-type One 0.34 mm² wire (AWG 22) One 1 mm² wire (AWG 18)
SDI1602 red label Red labels are provided for safety I/O modules.
References 7
Safety analog input modules
Type of Input signal Resolution Connection Nb of Reference Weight
input range channels kg/lb
PF106141D
10
BMXFTB2000 (2) No cordset is provided for cabling safety X80 I/O modules. Too many options are possible
according to the kind of:
- applications: full safety, safety mixed with availability, etc.
- safety level: SIL3/Cat2, SIL3/Cat4, SIL2, etc.
For more information on the different cabling options, please refer to detailed user manuals
published on our website: www.schneider-electric.com.
(3) Connectors are equipped with captive screws: max. tightening torque 0.5 N.m/0.37 lb-ft.
4/9
1
10
5/0
5/2
Contents 5 - Communication
Drop adapters
bb Modicon X80 CRA Ethernet drop adapters........................................... page 5/2
bb Modbus/TCP and EtherNet/IP network modules.................................. page 5/4 1
bb Modicon X80 NRP EIO drop fiber optic repeaters................................ page 5/5
bb NOS Ethernet network option switch.................................................... page 5/5
bb Peripheral Remote I/O Adapter.............................................................. page 5/6
5
bb Modbus and Character mode serial links........................................... page 5/18
vv Presentation, description........................................................................ page 5/18
vv Complementary characteristics, references........................................... page 5/19
bb BMECXM0100 CANopen master module............................................ page 5/20
vv Presentation, description........................................................................ page 5/20
vv References............................................................................................. page 5/21 6
bb BMENOP0300 IEC 61850 communication module............................. page 5/22
vv Presentation .......................................................................................... page 5/22
vv Description, references .......................................................................... page 5/23
bb PMXNOW0300 Wi-Fi access point....................................................... page 5/24
vv Presentation, characteristics.................................................................. page 5/24
7
vv References............................................................................................. page 5/25
10
5/3
5/1
Presentation, Modicon X80 I/O platform
description Modicon X80 CRA Ethernet drop adapters
Description
10
Compatibility: Racks and power supply I/O modules: Communication: Ruggedized modules:
page 1/8 modules: page 2/2 page 3/2 page 5/8 page 6/2
5/2
Presentation, Modicon X80 I/O platform
description (continued) Modicon X80 CRA Ethernet drop adapters
7
input
bb HART – – BMEAHI0812/
integrated analog BMEAHO0412
I/O modules
CCOTF function – Yes Yes
Time and date stamping – 10 ms 10 ms
Description
1
1 LED display block indicating the module status
2 Rotary switches for setting the address of an EIO drop (00…159) 8
3 Dedicated RJ45 service port (ETH 1) for remote service tools such as a PC, HMI
2 terminal module, or Ethernet DIO devices
4 RJ45 device network port (ETH 2) for connection to the Ethernet network
3 5 RJ45 device network port (ETH 3) for connection to the Ethernet network
4 References
Ethernet drop adapter
9
5
Description SERVICE Reference Weight
port kg/lb
X80 EIO drop adapter 1 BMECRA31210 –
BMECRA31210 Provide one module per
Modicon X80 EIO drop
(1) This module is also compatible with X-bus backplanes. In this case it has the same
functionality as a BMXCRA31210 performance Ethernet drop adapter. For more details see
10
our website www.schneider-electric.com.
Compatibility: Racks and power supply I/O modules: Communication: Ruggedized modules:
page 1/8 modules: page 2/2 page 3/2 page 5/8 page 6/2
5/3
Presentation, Modicon X80 I/O platform
functions, description Modbus/TCP and EtherNet/IP network modules
1 Presentation
BMENOC03p1 network modules act as an interface between the M580 PLC and
1 2a
other Ethernet network devices via the Modbus/TCP and EtherNet/IP communication
protocols.
BMENOC03p1 network modules are standard format and occupy a single slot in the
rack of the Modicon M580 platform. They have to be installed in the main Ethernet +
X-bus backplane rack.
Functions
5/4
Presentation, Modicon X80 I/O platform
description, Modicon X80 NRP EIO drop fiber optic repeaters,
NOS Ethernet network option switch
references
Description
1 1 Module reference
2 Display block indicating the module status
4
2
3 RJ45 Ethernet ports. 2 LEDs, LNK and ACT, indicate the status of each port
4 Fiber optic ports with SFP transceiver for LC type connector
3
References (1)
Modicon X80 EIO drop fiber optic repeaters (2) 5
4 Description Optical fiber Reference Weight
kg/lb
Modicon X80 EIO drop Multimode BMXNRP0200 –
fiber optic repeaters
Single-mode BMXNRP0201 –
BMXNRP020p
Ethernet network option switch
Presentation
6
The BMENOS0300 Ethernet network option switch offers an economic alternative to
external DRSs for copper Ethernet communication over short distances. Based on
the rotary switches on the front panel, the application of the 2 device network ports
can be configured intuitively as:
7
bb RIO ring
bb DIO ring
bb DIO ports
Depending on the architecture, the BMENOS0300 switch can be used to
communicate with the distributed I/O by simply inserting it in the local main rack or
remote drops.
1
2 Description
4 1 Module reference 8
3 2 Display block indicating the module status
3 Rotary switch for configuring the ETH 1 service port
5
4 Rotary switch for configuring the 2 device network ports (ETH 2 and ETH 3)
5 ETH 1: Service port (Ethernet)
6 6 ETH 2/ ETH 3: Device network port (Ethernet)
References (1) 9
Ethernet network option switch
Description SERVICE Device Reference Weight
BMENOS0300 port network kg/lb
port
(Ethernet)
10
Ethernet network option 1 2 BMENOS0300 –
switch
5/5
Presentation, Modicon X80 I/O platform 0
Quantum Presentation
1
Premium The Peripheral Remote I/O Adapter (PRA) is specifically dedicated for Modicon X80
M340
DIO drops in a Quantum/Premium/M340/M580 I/O architecture using Ethernet
M580
Modbus TCP.
Ethernet Modbus TCP The BMXPRA0100 module manages a remote X80 I/O rack on Ethernet Modbus
TCP which includes:
bb discrete I/O modules
Modicon X80 DIO drops with PRA modules
bb analog I/O modules
Principal characteristics
4 Up to 256
Intern memory
Up to 448 kBits
Dissipated power
2.3 W
Description
1 1 Module reference
2 2 Display block indicating the module status
7 3
3
4
Protected memory card port
RJ45 Ethernet port
4
10
Compatibility: Racks and power supply I/O modules: Communication: Ruggedized modules:
page 1/8 modules: page 2/2 page 3/2 page 5/8 page 6/2
5/6
Reference Modicon X80 I/O platform 0
Reference (1)
PF122533A
BMXPRA0100
10
Compatibility: Racks and power supply I/O modules: Communication: Ruggedized modules:
page 1/8 modules: page 2/2 page 3/2 page 5/8 page 6/2
5/7
Selection guide Modicon X80 I/O platform
Communication, integrated ports, and modules
Applications RTU communication Applications AS-Interface Serial link CANopen IEC 61850
Type of device RTU module communication communication communication communication
2 2
Network protocols Modbus/TCP, IEC 60870-5-104, Serial link, external modem link,
DNP3 (subset level 3) IEC 60870-5-101, DNP3 (subset level 3)
3 3
Structure Physical interface 10BASE-T/100BASE-TX (Modbus/TCP), Non-isolated RS 232/485 (serial link), Network protocols
PPPoE (Point-to-Point Protocol over Ethernet) non-isolated RS 232 (radio, PSTN, GSM, AS-Interface Modbus and CANopen Ethernet Modbus/
for ADSL external modem link GPRS/3G external modem link) Character mode TCP, IEC 61850
Type of connector One RJ45 connector One RJ45 connector Structure Physical interface AS-Interface V3 Non-isolated RS 232, ISO 11898 (9-way 10BASE-T/
standard 8-wire SUB-D connector) 100BASE-TX
Access method CSMA-CD (Modbus/TCP), Master/slave (IEC101/DNP3)
Isolated RS 485, 2-wire
Master/slave (IEC 104/DNP3)
Type of connector 3-way SUB-D 2 RJ45 and 1 RJ45 Master/slave 3 RJ45 connectors
Data rate 10/100 Mbps (Modbus/TCP) 0.3…38.4 Kbps (serial link) (2 connectors for a ring
4 4
Medium Double twisted pair copper cable, category Double shielded twisted pair copper cable, topology) plus Ethernet
CAT 5E, optical fiber via ConneXium cabling crossover serial cable (serial link), direct serial backplane connection
system cable (external modem link) Access method Master/slave – 9-way SUB-D CSMA-CD
Configuration Maximum number of devices 128 (Modbus/TCP), 64 slaves/servers (IEC 32 max. Data rate 167 Kbps 0.3...115.2 Kbps in RS 232 500 Kbps at 100 m/328 ft 10/100 Mbps
104/DNP3) 0.3...57.6 Kbps in RS 485 1 Mbps at 20 m/65.62 ft
Max. length 100 m/328 ft (copper cable), 4,000 m/13,123 ft 1,000 m/3,281 ft (serial link with insulating
Medium 2-wire AS-Interface Shielded twisted pair Twisted shielded pair Double twisted pair
(multimode optical fiber), 32,500 m/106,627 ft case)
cable copper cable cable copper cable, category
(single-mode optical fiber)
CAT 5E
5 5
Number of modules of the same type 2 Ethernet or RTU modules per station with Depending on application-specific channels
Configuration Maximum number of devices 62 slaves 2 per drop, 16 per 63 slaves 16 clients, 32 IED
per station any BMXP34 or BMEP58 processor (20/64 application-specific channels with
Ethernet remote I/O servers
BMXP34/BMEP58)
(RIO) network max.
Standard services Modbus/TCP messaging Reading/writing discrete and analog I/O,
Max. length 100 m/328 ft, 15 m/49.21 ft with 100 m/328 ft 100 m/328 ft (copper
counters
500 m/1,640 ft max. non-isolated RS 232, 2,500 m/8,202 ft with cable), 4,000 m/13,123 ft
Transparent Ready conformity class C30 – with 2 repeaters 1,000 m/3,280 ft with repeater (multimode optical fiber),
non-isolated RS 485 32,500 m/106,627 ft
Embedded web Standard services Rack Viewer PLC diagnostics, Data Editor –
(single-mode optical
server services access to PLC data and variables
6 Configurable services – –
Number of links of the same type per BMXP341000 20/36 application- –
fiber)
– 6
station processor: specific channels with
Hosting and display of user web pages – 2 AS‑Interface BMXP341000/
modules P342pppp (1
Transparent Ready I/O Scanning – application-specific
communication channel = 1 counter,
Global Data – motion control module,
services
NTP time synchronization Yes –
7 7
or serial link channel)
FDR Yes (client) – BMXP3420p0 or 36 application specific – Up to 4 Ethernet
SMTP e-mail notification Yes – BMEP58 channels max. modules per station
processor: 2 BMXNOM0200 depending on
SOAP/XML web service Server –
4 AS‑Interface modules per processor
SNMP network management Yes (agent) – modules BMpCRA31210
RSTP redundancy – Ethernet drop adapter
QoS (Quality of Service) – BMpCRA31210 All M580 processors: – –
8 8
Ethernet drop 36 application-specific
RTU communication Master or Slave configuration Yes, IEC101/104 and DNP3
adapter: channels
services Time and date stamped data exchange Interrogation via polling and exchanges on change of status (RBE), unsolicited messaging 2 AS-Interface
IEC 60870-5-104,
RTU time synchronization Yes, IEC101/104 and DNP3 modules
DNP3 IP or
IEC 60870-5-101, Management and buffering of time Yes, IEC101/104 and DNP3 Standard services Transparent Read/write bits and Transparent IEC 61850 MMS Client,
DNP3 serial and date stamped events exchanges with the words, diagnostics in exchanges with Server, GOOSE
sensors/actuators Modbus mode CANopen slaves and SNMP, RSTP, NTP
Automatic transfer of time and date Yes, IEC101/104 and DNP3
Send and receive Ethernet-based Client
stamped events to the Master/SCADA Buffer holding 10,000 events (per connected client, 4 clients max.)
character string in processors
5/8 5/8
5/9
Presentation Modicon X80 I/O platform
RTU communication systems
Presentation
RTU systems are designed to meet the needs of the water industry, the oil and gas
1 sector, and other infrastructures, where remote monitoring and telecontrol are
essential to the good management of sites and substations spread over a wide
geographical area.
RTU protocols and Telemetry systems provide robust, reliable means of communication
which are suitable for the process values, maintenance, and remote monitoring needs
of infrastructures disseminated over a vast geographical area which may be difficult
2 to access.
Ethernet 1 Ethernet 2
RTU RTU
5
RTU RTU
Radio network 1
RTU
Radio network 2
8
operator consoles
vv Use of discrete or analog I/O, serial links, fieldbuses, and LANs
vv Event detection, time and date stamping, prioritization, and logging as required by
the application
bb Other functions:
vv IEC 1131-3 programmable control: forcing, access control, load sharing, servo control
vv Data logging
9 vv
vv
Alarm and report notification by e-mail/SMS
Web HMI: displaying the process, alarm handling, trend analysis, telecontrol
10
5/10
Presentation (continued) Modicon X80 I/O platform
RTU communication protocols
Presentation (continued)
Currently, people working in the industrial Telemetry sectors use standard protocols
for communication between control centres (SCADA) and RTU stations. 1
The most commonly used protocols are as follows:
bb IEC 60870-5: IEC (International Electrotechnical Commission), in particular
IEC 60870-5-101/104 (commonly known as IEC 101 or 104)
bb DNP3: Distributed Network Protocol version 3
DNP3 is the predominant protocol in North America, Australia, and South Africa
whereas, in certain European countries, the IEC protocol is required by the legislation.
2
IEC is also commonly used in the Middle East.
Both protocols offer native data management and time and date stamped events: 5
bb Time synchronization between the master station and auxiliary stations via
protocol functions
bb Time and date stamping of data and events
bb Automatic transfer of time and date stamped events between the RTU stations
and SCADA (control room)
10
5/11
Presentation (continued), Modicon X80 I/O platform
functions, RTU communication module
description
Le Presentation (continued)
The BMXNOR0200H communication module integrates the RTU (Remote Terminal
1 Unit) functions and protocols in the Modicon X80 I/O platform for industrial Telemetry
applications and other widely distributed infrastructures.
The BMXNOR0200H module can be used to connect an RTU X80 I/O PLC directly
to a Telemetry supervisor or to other RTU stations, via the standard DPN3 protocols
(subset level 3) or IEC 60870-5-101/104 with different connection methods: Ethernet
TCP/IP, LAN, WAN, serial link, or modem connections (radio, PSTN, GSM, GPRS/3G,
2 ADSL).
Functions
4 memory card
bb Event notifications via e-mail or SMS
bb Embedded Web server for setting the RTU protocol parameters, diagnostics, and
monitoring
5
vv Modbus/TCP protocol (client and server)
vv Integrated RTU protocols for Ethernet communications: DNP3 IP (client or server)
and IEC 60870-5-104 (over IP) (client or server)
vv Connection of ADSL external modem on the Ethernet port, via the PPPoE
(Point-to-Point Protocol over Ethernet) protocol
vv Advanced Ethernet functions: NTP client, FTP client or server, HTTP server,
SOAP/XML server, SNMP agent, SMTP agent
7 Description
1 The BMXNOR0200H module can be installed in either a standard or “ruggedized”
configuration, equipped with a standard BMXP34ppppp /BMEP58pppp or
2 “ruggedized” BMXP34pppppH/BMEP58ppppH processor.
9 On the rear panel, 2 rotary switches for selecting the IP address assignment
method for the module.
10
5/12
References Modicon X80 I/O platform
RTU communication module
References
Description Communication Protocol Reference Weight
RTU
port
Ethernet bb Modbus/TCP (client or BMXNOR0200H
kg/lb
0.205/
1
communi- 10BASE- server), Transparent Ready (2) 0.452
cation module 100BASE-TX class C30
(1) bb DNP3 IP (client or server)
bb IEC 60870-5-104 (over IP)
(client or server)
10
5/13
Presentation Modicon X80 I/O platform
BMXNGD0100
Ethernet Global Data module
Presentation
Global Data service
1 Distribution group 1
IP multicast 239.255.255.251
Modicon Premium
2
Modicon Quantum
Ethernet Modbus/TCP
Modicon Premium
3
IP multicast 239.255.255.250 Modicon X80 I/O platform +
Modicon M580 processor
Data exchange 4 KB max.
Distribution group 2
4 The Global Data service performs data exchanges in real time between stations
belonging to the same distribution group. It is used to synchronize remote applications,
or to share a common database between a number of distributed applications.
Exchanges are based on a standard producer/consumer protocol, helping to ensure
optimum performance with a minimum load on the network. This RTPS (Real Time
Publisher Subscriber) protocol is promoted by Modbus-IDA (Interface for Distributed
Automation), and is already a standard adopted by several manufacturers.
5 Characteristics
A maximum of 64 stations can participate in Global Data within a single distribution
group. Each station can:
bb Publish one 1024-byte variable. The publication rate can be configured between
10 ms and 1500 ms in increments of 10 ms.
bb Subscribe to between 1 and 64 variables. The validity of each variable is
6 controlled by status bits (Health Status bits) linked to a refresh timeout configurable
between 50 ms and 15 s. Access to an element of the variable is not possible. The
total size of subscribed variables amounts to 4 K contiguous bytes.
To further optimize the performance of the Ethernet network, Global Data can be
configured with the “multicast filtering” option which, together with switches in the
ConneXium range, broadcasts data only to Ethernet ports where there is a Global
7 Data service subscriber station. If these switches are not used, Global Data is sent in
“multicast” mode to all switch ports.
10
5/14
Description, Modicon X80 I/O platform
references BMXNGD0100
Ethernet Global Data module
Description
BMXNGD0100
1
Global Data flows on control network
Premium CPU The BMXNGD0100 Ethernet Global Data module is specifically designed to
Modicon M580
modernize the large and complex Modicon installed base (mainly Premium and
Quantum) by running the Global Data service more easily.
In addition to the Global Data service, the BMXNGD0100 module also has the
following embedded services, as it can also be used for inter-controller
communication to provide solutions for complex processing and high-end
Quantum CPU
applications: 2
bb Ipconfig
bb Modbus TCP explicit messaging (client and server)
Example of architecture to implement BMXNGD0100
Designed as a neat solution specifically for the Global Data service, some services,
such as IO-Scanner, Web, FDR, and NTP, are not supported by the BMXNGD0100
module. This module is only compatible with BMEXBPpppp Ethernet racks in
standalone architectures on the X80 platform, to keep the global data transferring
3
internally only, isolated from the external world to help ensure a strict level of
cybersecurity.
If these functions are required, please check with our Customer Care Center for
alternative products that can fulfill these needs.
References
4
Description Usage Reference Weight
kg/lb
10
5/15
Presentation, Modicon X80 I/O platform
description 4
BMXEIA0100 master module
for AS-Interface cabling system
Presentation
1
The BMXEIA0100 master module for AS-Interface cabling system provides the
AS-Interface system master function for the Modicon X80 I/O platform.
2
AS-Interface
3
Motor starter Phaseo
AS-Interface
power supply
The AS-Interface cabling system consists of a master station (Modicon X80 I/O
platform) and slave stations. The master supporting the AS-Interface profile
interrogates the devices connected on the AS-Interface line one by one and stores
the information (actuator/sensor status, device operating status) in the PLC memory.
Communication on the AS-Interface line is managed totally transparently in relation
4 to the application PLC program.
The BMXEIA0100 master module supports the latest management profile for
AS-Interface devices (AS-Interface V3), which is able to manage level V1, V2, and
V3 AS-Interface slaves:
b Discrete slave devices (up to 62 devices of 4 inputs/4 outputs organized in
2 banks (A/B) of 31 addresses each)
5 b Analog devices (up to 31 devices (4 channels) in bank A)
b Safety interfaces (up to 31 devices in bank A)
An AS-Interface power supply is essential for powering the various devices on the
line. Ideally it should be placed near stations that consume a great deal of energy.
Please refer to the “Phaseo power supplies and transformers - AS-Interface range”
catalog.
Description
10
5/16
Diagnostics, Modicon X80 I/O platform
references BMXEIA0100 master module
for AS-Interface cabling system
Diagnostics
BMXEIA0100 module
The two LEDs 4 on the module front panel are used in conjunction with the two
pushbuttons 5 for module diagnostics:
1
LEDs Pushbuttons
4 ASI PWR: 4 FAULT: Detected 5 A/B: Selects the 5 MODE: Module
AS-Interface AS-Interface line fault group of slaves on the Offline/Online
power supply present display block 3
The display block on the front panel of the BMXEIA0100 master module can be used 2
to perform simplified local diagnostics by displaying the slave devices present on the
AS-Interface line.
Detailed diagnostics of each of the slave devices is also possible using:
b The ASITERV2 adjustment terminal
b A web browser using the Rack Viewer function in the standard Web server on the
Modicon X80 I/O platform. For further information, please consult our website
www.schneider-electric.com. 3
References
Description Usage Reference Weight
kg/lb
AS-Interface
master module
M4 AS-Interface profile
for level V1, V2, and V3
BMXEIA0100 0.340/
0.750
4
supplied with 3-way male slaves
SUB-D connector
10
5/17
Presentation, Modicon X80 I/O platform
description Modbus and Character mode serial links
Presentation
Magelis XBT
1
Modicon X80 I/O
LU9 GC3
Modbus
The Modbus serial link is used for master/slave architectures (it is necessary,
however, to check that the Modbus services used by the application have been
4 implemented on all relevant devices).
The bus consists of a master station and slave stations. Only the master station can
initiate the exchange (direct communication between slave stations is not possible).
Two exchange mechanisms are available:
b Question/response, where requests from the master are addressed to a given slave.
The master then waits for the response from the slave that has been interrogated.
5 b Broadcasting, where the master broadcasts a message to all slave stations on the
bus. The latter execute the order without transmitting a reply.
b It is necessary to use BMpCRA31210 modules as drop adapters. On one drop it is
possible to plug a maximum of two BMXNOM0200 modules.
The following services are not available in the slave stations:
v Modbus slave
v Modem services
6 Although most processors have a serial link that can support modems, the
BMXNOM0200 2-channel serial link module is particularly recommended for this
type of use.
Its performance and numerous parameter-setting options make it ideal for any type
of configuration, especially when using radio modems.
Description
7 1 BMXNOM0200 serial link module
The front panel of the BMXNOM0200 serial link module features:
1 A screw for locking the module in a slot in the rack
2
2 A display block with 4 LEDs:
v RUN (green) and ERR (red): Module status
3a
v For each of the two channels: SER COM (green): Activity on the serial link (lit)/
9 BMXNOM0200
To be ordered separately:
RS 485 cordsets (see our “Modicon M580 automation platform” catalog available on
our website www.schneider-electric.com) or RS 232 cordsets for DCE terminal
(see page 5/19).
10
5/18
Characteristics, Modicon X80 I/O platform
references Modbus and Character mode serial links
Complementary characteristics
The following characteristics complement those indicated in the selection guide on
page 5/9. 1
BMXNOM0200 module serial links
b Physical interface:
vv RS 232 port 0: RS 232 8-wire, non-isolated
vv RS 485 port 0 and port 1: RS 485 2-wire, isolated
2
b Frame:
vv Modbus: RTU/ASCII, full duplex in RS 232, half duplex in RS 485
vv Character mode: full duplex in RS 232, half duplex in RS 485
b Data rate:
vv RS 232 port 0: 0.3...115 Kbps (Modbus/Character mode)
vv RS 485 port 0 and port 1: 0.3...57.6 Kbps (Modbus/Character mode)
b Line polarization:
3
vv Modbus RS 485: automatic
vv RS 485 character mode: configurable with Unity Pro software
bb Maximum length of a tap link in RS 485 2-wire:
vv 15 m/49.21 ft in a non-isolated link
vv 40 m/131.23 ft in an isolated link
bb Expert mode (from version V1.2 of the module and version V5 of Unity Pro): used
to configure the time out links individually from the application and thus adapt to the
specific characteristics of certain modems.
4
References (1)
Serial link module
Designation Protocol Physical layer Reference Weight
kg/lb
2-channel serial link Modbus 1 non-isolated RS 232 BMXNOM0200 0.230/
module (2) master/slave
RTU/ASCII,
Character
channel (Port 0)
2 isolated RS 485
channels (Port 0 and
0.507
5
mode, Port 1)
GSM/GPRS
modem
BMXNOM0200
10
5/19
Presentation, Modicon X80 I/O platform
description BMECXM0100 CANopen master X80 module
for CANopen fieldbus communication
Presentation
Engineering System Operator
CANopen is an open network supported by more than 600 companies worldwide,
1 station servers Clients
and promoted by CAN in Automation (CiA). With the general acceptance of
CANopen, Schneider Electric has the accumulated and proven experience of
applying CANopen in machine solution platforms.
CXM
CANopen helps to ensure reliable and deterministic access to real-time data in field
M580
devices. As a consequence, products using CANopen are increasingly used in
control system architectures. The BMECXM0100 CANopen master module provides
2 Device network CXM
powerful access to the CANopen slaves from the M580 local rack or a remote X80
drop.
Advantages
BMECXM0100 is designed to fulfill customer needs by offering the following
advantages:
RIO bb Operational intelligence:
3 sub-ring
vv Complete software integration into Unity with a predefined catalog of preferred
devices and numerous automated operations such as device variable creation, IP/
CXM DHCP settings, and IO scanner configuration
vv Simple integration of third-party devices
bb Maintenance excellence:
vv Robust and well-designed with a long life cycle following X80 standards
Typical topology to connect CANopen devices to vv Built to withstand extreme temperatures (-25 ºC to +70 ºC/-13 ºF to +158 ºF),
4 M580/X80 platforms with BMECXM0100 ATEX certified
vv Easy diagnostics by maintenance engineers via a simple web browser (no need
for Unity) and the FDR (Fast Device Replacement) service
bb Investment protection: Totally flexible topologies with the possibility of using
several BMECXM0100 modules in a single M580, or in a remote I/O drop closest to
the process
bb Time-to-market: Simple, compact size, all in one, which reduces installation time
5 bb Enhanced protection and security: Integrated cybersecurity design helps to
protect plant operations
Description
The BMECXM0100 CANopen X80 master module is standard format (1 slot) and
supports one CANopen port (SUB-D9 male connector).
Standardized baudrates between 20 Kbd and 1 Mbd (20 Kbd, 50 Kbd, 125 Kbd, 250
Kbd, 500 Kbd, 1 Mbd) are supported.
CANopen configuration in Unity Pro with BMECXM0100
7
Depending on the performance level required by the process, the BMECXM0100
module can be scanned by the RIO or the DIO scanner of the M580 CPU. RIO
scanning helps to ensure optimum performance, in sync with the PLC task (MAST,
FAST or AUX).
Several BMECXM modules can be connected to the same or different I/O scanners
in the same M580 PAC.
8 BMECXM0100 modules are not compatible with redundant M580 architectures, and
cannot be scanned by an Ethernet module including BMENOC03p1 and
BMXNOC0402. See page 5/4 for more information.
10
5/20
Diagnostics, Modicon X80 I/O platform
references BMECXM0100 CANopen master X80 module
for CANopen fieldbus communication
Diagnostics
BMECXM0100
1 The 5 LEDs 1 on the module front panel are used for quick CANopen communication
diagnostics:
1
LED Color Description
I/O Red Indicates the exchange status with CANopen
devices
BS (Bus Status) Red /Green Indicates the EtherNet/IP connection status
Yellow Firmware upgrade in progress 2
2 CAN RUN Green Indicates the status of the CANopen fieldbus
CAN ERR Red Indicates the status of the CANopen physical layer
and indicates detected errors due to missing CAN
BMECXM0100 messages (SYNC, node-guarding, or heartbeat)
CAN COM Yellow Dedicated to SDO transmission
3
References
Description Usage Reference Weight
kg/lb
CANopen X80 master module CANopen communication BMECXM0100 –
supplied with male 9-way SUB-D module used in M580/X80 (1)
4
connector 2 Ethernet platform
(1) For the “Conformal coating” version BMECXM0100H, see page 6/9.
10
5/21
Presentation Modicon X80 I/O platform
BMENOP0300 IEC 61850 X80 module
Presentation
IEC 61850 is the latest worldwide standard for electrical utilities. It covers information
1 modeling, configuration language, and communication networks. Initially developed for
communication in substations, implementation of the standard has advanced at a
remarkable rate since its introduction, with huge numbers of IEC 61850 devices having
been installed. Now considered to be the de facto standard for substation automation, it
is encompassing an increasing number of new application areas, such as:
bb Wind power (IEC 61400-25)
The long-term active participation of Schneider Electric experts in IEC and UCA
working groups has resulted in a state-of-the-art Schneider Electric IEC 61850 offer
with full IEC 61850-8-1 functionality.
IEC 61850 with M580 helps reduce customer investment and operational costs by
3
easily connecting their power device to the process systems.
M580 IEC 61850 helps to improve system reliability and security by:
bb Getting the right data at the right time to be able to act proactively, thus increasing
the reliability and availability of both the process and the power system
bb Implementing robust M580 cybersecurity features to help ensure secure
communication
4 Functionality
IEC 61850 MMS server, client, and GOOSE services can work in either Ed. 2.0 or
Ed. 1.0 mode. M580 controllers support IEC 61850 standard engineering process
and data objects. They also support the following data models:
bb Substation automation systems (IEC 61850-7-4)
bb Hydroelectric power plants (IEC 61850-7-410)
bb Distributed energy resources (IEC 61850-7-420)
5 The BMENOP0300 module from the Schneider Electric EcoStruxure platform is
used to implement an engineering approach by enabling IEC 61850 compliant data
exchange across industrial, energy, and power system applications. This offer helps
our existing PLC customers from both process and energy applications to
modernize smoothly and sustainably to the new IEC 61850 standard.
6 Application cases
The BMENOP0300 module can provide different services under different roles,
primarily in the following three areas:
1 Electrical device integration
-- IEC 61850 Client is used to communication with IEDs.
-- GOOSE is also possible.
2 IEC 61850 based process control
7 -- Process control objects are modeled with IEC 61850 (hydro, DERs, etc.).
-- Server to SCADA and Client to IEDs is possible when needed.
3 M580 provides information to other systems.
-- IEC 61850 Server is used.
8
IEC 61850 configuration
OWS Modbus TCP EWS SCD, ICD, CID IEC 61850
IEC 61850 Messaging Power
IEC 61850 Server IEC 61850 Server management/
2 Substation
automation
1
IEC 61850 Client/GOOSE
9
Redundant processors
RIO
RIO
5/22
Description, Modicon X80 I/O platform
references BMENOP0300 IEC 61850 X80 module
Description
The BMENOP0300 IEC 61850 module is installed on the local Ethernet backplane
1
of an M580 system. 1
The 6 LEDs on the front panel 1 are used to diagnose operating conditions:
bb RUN LED (green): Operating status
bb ERR LED (red): Error detected
bb MS LED (green/red): Module status
bb NS LED (green/red): Network connection status
2
2
bb NS1 LED (green/red): Ethernet network status
bb NS2 LED (green/red): Ethernet network status
With three Ethernet ports 2 to link external intelligent electrical devices (IEDs), the
module provides interfaces for IEC 61850 communication as well as device
management software that utilizes the IEC 61850 standard (1).
BMENOP0300 The maximum number of BMENOP0300 modules that can be mounted on a local
rack is determined by the M580 processor model:
Capabilities
The capabilities per module are:
7
bb 16 logical devices
bb MMS server: 16 concurrent connections, 64 report control blocks instances, 8
instances for one report control block, 68 data sets, 256 data attributes/data set,
URCB and BRCB reports
bb Control model: DOes, SBOes, DOns, SBOns
bb MMS client: 32 concurrent connections
bb GOOSE: 4 control blocks for GOOSE publish and 32 control blocks for GOOSE
8
subscribe, up to 256 inputs/data set
References
Description Usage Reference Weight
kg/lb
M580 IEC 61850 communication IEC 61850 communication BMENOP0300 0.345/
module module used in M580 local (2) 0.761
rack Ethernet backplanes
(1) Requires Unity Pro software V12.0 or later, see our website www.schneider-electric.com.
9
(2) For the “Conformal coating” version BMENOP0300C, see page 6/9.
10
5/23
Presentation, Modicon X80 I/O platform
characteristics Wi-Fi network
PMXNOW0300 Wi-Fi access point
Presentation
The PMXNOW0300 Wi-Fi access point consists of a WLAN wireless connection
1 combined with a 3-port 10/100 Ethernet switch.
This module is designed to be integrated in the Modicon X80 I/O platform Modicon
processor (1). It retrieves the 24 V voltage from the backplane rack and occupies
one slot in it. An Ethernet cable, supplied with the module, must be used to connect
the Wi-Fi module to the processor or the communication module (BMXNOppppp).
This module offers the following functions:
bb access point
2 bb Ethernet bridge
bb Wi-Fi repeater
Main characteristics
4 Type of device
Wi-Fi access point, client and repeater
Wi-Fi standards
IEEE 802.11 a/b/g/h
Operating frequencies
2.4 GHz and 5 GHz
5 IP rating
IP 30
Mounting
On the rack
Number of radios
1
6 Nominal data rate
y108 Mbps (Super AG mode, 54 Mbps in standard mode)
Antenna connections
1 x RP-SMA
Ethernet connections
8 antenna type)
Dimensions
97 x 32 x 104 mm/3.82 x 1.26 x 4.09 in.
Storage temperature
- 40 °C to + 80 °C/- 40 °F to + 176 °F
Humidity
10 (1) Only for processors compatible with the Modicon X80 I/O platform (see page 1/8).
(2) For more information, please consult our website www.schneider-electric.com.
5/24
References Modicon X80 I/O platform
Wi-Fi network
PMXNOW0300 Wi-Fi access point
References
Wi-Fi access points
Description Number of
radios
Data rate IP rating Reference Weight 1
Mbps kg/lb
Wi-Fi 802.11a/b/g/h 1 y108 IP 30 PMXNOW0300 (1) 0.205/
access point (Super AG 0.452
with antenna and mode,
50 cm/19.69 in. long 54 Mbps in
2
Ethernet cable standard
equipped with two RJ45 mode)
connectors, plus
CD-ROM
(1) To order this product, please consult our Customer Care Centre.
3
10
5/25
1
10
6/0
6/2
Contents 6 - Ruggedized modules
10
6/3
6/1
Presentation Modicon X80 I/O platform
Treatment for severe environments
Ruggedized modules
Presentation
Protective treatment of Modicon X80 I/O platform
1 The Modicon X80 I/O platform complies with “TC” (Treatment for all Climates) treatment requirements. It is
designed as standard to operate in temperatures ranging from 0 to + 60 °C/32 to 140 °F.
For installations in industrial environments corresponding to “TH” (Treatment for Hot and humid environments),
devices must be housed in enclosures providing at least IP 54 protection as specified by standard
IEC/EN 60529, or an equivalent level of protection according to NEMA 250.
The Modicon X80 I/O platform offers IP 20 degree of protection (1). It can therefore be installed without an enclosure
2 in reserved access areas that do not exceed pollution level 2 (control room with no conductive dust). Pollution level 2
does not take account of harsher environments, such as those where the air is polluted with conductive dust, fumes,
corrosive or radioactive particles, vapors or salts, molds, insects, etc. All the safety hardware in-rack modules in red
color (processor, coprocessor, X80 I/O) are conformal coated for a default use in severe environments.
3
If the Modicon X80 I/O platform has to be used in more severe environments or is required to start and operate in
an extended temperature range, from
- 25 °C to + 70 °C/- 13 °F to 158 °F, the “ruggedized” offer features industrially hardened processor and power
supply modules, X-bus and Ethernet I/O modules and racks that have a protective coating on their circuit boards.
Note: Capable of starting within an extended temperature range (from - 25 °C to + 70 °C/
- 13 °F to 158 °F, a single-rack configuration is also able to operate at extremely low temperatures (as low as - 40 °C/- 40 °F) if
placed in an appropriate enclosure. Please contact our Customer Care Center.
4 The coated/harsh offer provides the Safety CPU/Coprocessor and Safety I/O modules with “AVR 80” coating on
their electronic cards.This treatment increases the isolation capability of the circuit boards and their resistance to:
bb Condensation
bb Dusty atmospheres (conducting foreign particles)
bb Chemical corrosion, in particular during use in sulfurous atmospheres (oil refinery, purification plant, etc.) or
atmospheres containing halogens (chlorine, etc.) or chemical vapors
This protection, combined with appropriate installation and maintenance, enables Modicon X80 I/O products to be
5
F19_ACC_CPMFS17008
9 For corrosive environment, additional protecting gel need to cover all electrical connection of M580 harsh
products.
This 25 g gel tube can be ordered separately under reference BMXGEL0025.
(1) Each slot in a BMpXBPpp00 rack is equipped as standard with a protective cover that should only be removed when inserting
a module. If any covers are subsequently misplaced, replacements can be ordered under reference BMXXEM010 (sold in lots
of 5).
10
6/2
Presentation (continued), Modicon X80 I/O platform
references Dedicated parts for severe environments
Ruggedized power supply modules
Composition
References and characteristics
To order ruggedized modules and racks, see the reference pages 6/3 to 6/11 (the references of the ruggedized 1
products available include the suffix “H” and the conformal coated products available include the suffix “C”).
The standard separate parts (cordsets, cables, sub-bases, etc.) that are compatible with the ruggedized modules
offer are listed in the reference pages (see pages 6/3 to 6/11).
The majority of operating and electrical characteristics of ruggedized modules are identical to those of their
equivalent standard versions. However, some characteristics are subject to either derating or limitation. Please
2
consult our website www.schneider-electric.com.
BMXCPS3020H
Ruggedized power supply modules
Each BMpXBPpp00H rack must be equipped with a power supply module. BMEXBPpp02H must be equipped
with 1 or 2 redundant power supply modules. These modules are inserted in the leftmost power supply slots of
each rack (marked CPS).
The available power values given below in bold italic correspond to operation at -25 °C/-13 °F and +70 °C/+158 °F
(see temperature derating curves on our website www.schneider-electric.com).
3
The power required to supply each rack depends on the type and number of modules installed in the rack. It is
therefore necessary to draw up a power consumption table for each rack in order to determine which is the most
appropriate BMXCPSppppH power supply module for your requirements (consult our website
www.schneider-electric.com).
BMXCPS3500H
Power supply modules (1)
Line supply Available power (2) Reference Weight
4
3.3 V c 24 V c rack 24 V c sensors Total kg/lb
(3) (3) (4)
24...48 V c 15 W 32 W – 32 W BMXCPS3020H 0.340/
isolated 11.3 W 23.4 W 23.4 W 0.750
18 W 40 W – 40 W BMXCPS4002H 0.360/
18 W 40 W 40 W 0.794
BMXCPS4002H
7
Standard separate part
Description Type Composition Reference Weight
kg/lb
Set of 2 removable connectors Spring-type One 5-way terminal block and one BMXXTSCPS20 0.015/
2-way terminal block 0.033
BMXCPS4022H
8
Standard replacement part
Description Type Composition Reference Weight
kg/lb
Set of 2 removable connectors Caged One 5-way terminal block and one BMXXTSCPS10 0.020/
2-way terminal block 0.044
9
(1) Includes a set of 2 removable caged connectors BMXXTSCPS10.
(2) The total power consumed on each voltage (3.3 V c and 24 V c) must not exceed the total power of the module. See the
power consumption table on our website www.schneider-electric.com.
(3) 3.3 V c and 24 V c rack voltages for powering Modicon M340 and M580 PLC modules.
(4) 24 V c sensor voltage for powering the input sensors (voltage available via the 2-way removable connector on the front
panel).
BMXCPS3522H
10
6/3
References Modicon X80 I/O platform
Dedicated parts for severe environments
Ruggedized racks and rack expansion module
Ruggedized racks
Description Type of module to be inserted No. of slots Power Reference Weight
1 (1) consumption
(2)
kg/lb
BMXXBP0400H Ruggedized X-bus BMXCPS power supply, BMXP34 or 4 1 W BMXXBP0400H 0.630/
racks BMEP58 processor, BMEH58 processor, 1.389
I/O modules, and application-specific 6 1.5 W BMXXBP0600H 0.790/
(counter and communication) modules 1.742
8 2 W BMXXBP0800H 0.950/
2 12 0.74 W BMXXBP1200H
2.094
1.270/
2.800
Ruggedized Ethernet BMXCPS power supply, BMEP58 4 2.8 W BMEXBP0400H 0.715/
+ X-bus racks processor, BMEH58 processor, 1.576
I/O modules, and application-specific 8 3.9 W BMEXBP0800H 1.070/
(counter and communication) modules 2.359
BMEXBP0800H
3
12 3.9 W BMEXBP1200H 1.387/
3.058
Ruggedized Ethernet BMEP58 processor, BMEH58 processor, 6 3.9 W BMEXBP0602H 1.387/
+ X-bus dual power BMXCPS400* redundant power supply, 3.058
supply racks I/O modules, and application-specific 10 3.9 W BMEXBP1002H 1.387/
(counter and communication) modules 3.058
BMXXBE1000H
5
Standard accessories for racks
Description For use with Sold in Reference Weight
lots of kg/lb
Shielding connection BMpXBP0400H rack – BMXXSP0400 0.280/
6 kits comprising:
- 1 metal bar
- 2 support bases
BMXXBP0600H rack – BMXXSP0600
0.617
0.310/
BMXXSP0p00 + BMXXSP30p0 0.683
BMpXBP0800H rack – BMXXSP0800 0.340/
BMEXBP0602H rack 0.750
BMpXBP1200H rack – BMXXSP1200 0.400/
BMEXBP1002H rack 0.882
7
Spring clamping Cables, cross-section 1.5...6 mm2/AWG 16...9 10 STBXSP3010 0.050/
rings 0.110
Cables, cross-section 5...11 mm2/AWG 10...7 10 STBXSP3020 0.070/
0.154
Protective covers Unoccupied slots on BMpXBPpp00H rack 5 BMXXEM010 0.005/
(replacement parts) 0.011
8 grease 25 g
(1) Number of slots taking the processor module, I/O modules, and application-specific modules (excluding power
supply module).
(2) Power consumption of anti-condensation resistor(s).
(3) Module and cordsets do not operate properly at temperatures lower than -25 °C/-13 °F.
10
6/4
References (continued) Modicon X80 I/O platform
Dedicated parts for severe environments
Ruggedized racks and rack expansion module
3
9.84 ft 0.573
5 m/ TSXCBY050K 0.360/
16.40 ft 0.794
12 m/ TSXCBY120K 1.260/
39.37 ft 2.778
18 m/ TSXCBY180K 1.860/
59.06 ft 4.101
28 m/ TSXCBY280KT 2.860/
5
Description Use Composition Sold in Reference Weight
lots of kg/lb
Line terminator Required on both 2 x 9-way SUB-D 2 TSXTLYEX 0.050/
BMpXBPppp0H connectors marked A/ and /B 0.110
modules at each
TSXTLYEX
end of the daisy
chain 6
X-bus For ends of 2 x 9-way SUB-D 2 TSXCBYK9 0.080/
straight connectors TSXCBY1000 straight connectors 0.176
cables
Connector For attaching 2 crimping pliers, 1 pen – TSXCBYACC10 –
assembly kit TSXCBYK9 (3)
connectors
(1) Module and cordsets do not operate properly at temperatures lower than -25 °C/-13 °F.
(2) Cable supplied with a set of 2 TSXTVSY100 electrical transient suppressors.
7
(3) To attach the connectors to the cable, you also need a wire stripper, a pair of scissors, and a digital ohmmeter.
10
6/5
References (continued) Modicon X80 I/O platform
Dedicated parts for severe environments
Ruggedized discrete I/O modules
References
Ruggedized discrete input modules
1 Type of
current
Input voltage Connection via
(1)
IEC/EN
61131-2
No. of channels
(common)
Reference Weight
kg/lb
conformity
c 24 V (positive Screw or spring-type 20-way Type 3 16 isolated inputs BMXDDI1602H 0.115/
logic) removable terminal block (1 x 16) 0.254
24 V (negative Screw or spring-type 20-way Non-IEC 16 isolated inputs BMXDAI1602H 0.115/
logic) removable terminal block (1 x 16) 0.254
2 BMXDpI160pH a
48 V (positive
logic)
24 V
Screw or spring-type 20-way Type 1
removable terminal block
Screw or spring-type 20-way Type 1
16 isolated inputs
(1 x 16)
16 isolated inputs
BMXDDI1603H
BMXDAI1602H
0.115/
0.254
0.115/
removable terminal block (1 x 16) 0.254
48 V Screw or spring-type 20-way Type 3 16 isolated inputs BMXDAI1603H 0.115/
removable terminal block (1 x 16) 0.254
100…120 V Screw or spring-type 20-way Type 3 16 isolated inputs BMXDAI1604H 0.115/
removable terminal block (1 x 16) 0.254
5
40-way removable terminal 0.551
BMXDDO16p2H BMXDRA0815H/
block
0805H/1605H
c or a 12…24 V c/2 A Screw or spring-type 20-way Yes 8 non-protected outputs BMXDRA0805H 0.145/
relay 24…240 V a/2 A removable terminal block (without common) 0.320
24...240 V a/2 A Screw or spring-type 20-way Yes 8 normally open BMXDRA0815H 0.210/
24...125 V c/0.3 A removable terminal block isolated relay outputs 0.463
24 V c/2 A, Screw or spring-type 20-way Yes 16 non-protected outputs BMXDRA1605H 0.150/
240 V a/2 A removable terminal block (2 x 8) 0.331
7
16 Screw or 8 (positive logic) 8, transistor Inputs, type 3 BMXDDM16022H 0.115/
spring-type (1 x 8) 24 V c /0.5 A 0.254
20-way (1 x 8)
removable 8, 24 V c or Inputs, type 3 BMXDDM16025H 0.135/
terminal block 24…240 V a 0.298
relay
(1 x 8)
9 40-way removable terminal For hardened version of module only with Caged
blocks (with gold plating) 40-way removable terminal block
BMXFTB4000H 0.166/
0.366
Spring BMXFTB4020H 0.098/
BMXFTB2000 0.216
Standard preformed cordsets for I/O modules with removable terminal block
Description Composition Length Reference Weight
kg/lb
10 Preassembled cordsets
with one end with flying
leads
One 20-way spring-type removable
terminal block (BMXFTB2020)
One end with color-coded flying leads
3 m/
9.84 ft
BMXFTW301 0.850/
1.874
5 m/ BMXFTW501 1.400/
16.40 ft 3.086
10 m/ BMXFTW1001 2.780/
32.80 ft 6.129
(1) By connector, module supplied with cover(s)
6/6
References (continued) Modicon X80 I/O platform
Dedicated parts for severe environments
Ruggedized analog I/O modules
References
Ruggedized analog input modules
Type of inputs Input signal range Resolution Connection No. of
channels
Reference Weight
kg/lb
1
Isolated high-level ± 10 V, 0…10 V, 16 bits Via caged, 4 high-speed BMXAMI0410H 0.143/
inputs 0…5 V, 1…5 V, ± 5 V screw clamp, or channels 0.315
0…20 mA, spring-type removable
4…20 mA, ± 20 mA terminal block
Via caged or
spring-type removable
8 isolated
high-speed
BMXAMI0810H 0.175/
0.386
2
BMXAMp0pp0H terminal block channels
Isolated low-level Temperature probe, 15 bits 40-way connector 4 channels BMXART0414H 0.135/
inputs thermocouple + sign 0.298
± 40 mV, ± 80 mV, 8 channels BMXART0814H 0.165/
± 160 mV, ± 320 mV,
± 640 mV, ± 1.28 V
0.364
3
Ruggedized analog output module
Type of outputs Output signal range Resolution Connection No. of Reference Weight
channels kg/lb
Isolated high-level ± 10 V, 16 bits Via caged, 2 channels BMXAMO0210H 0.144/
BMXART0414H
outputs 0…20 mA, 4…20 mA screw clamp, or
spring-type removable
0.317
4
terminal block 4 channels BMXAMO0410H 0.175/
0.386
10
6/7
References (continued) Modicon X80 I/O platform
Dedicated parts for severe environments
Ruggedized I/O modules
References
Standard connection accessories for analog modules (1)
1 BMXFTWp01S
Description For use with
modules
Type, composition Length Reference Weight
kg/lb
3
BMXART0814H (2) One end with color-coded 9.84 ft 1.058
flying leads 5 m/ BMXFCW501S 0.710/
16.40 ft 1.565
Modicon Telefast ABE7 pre-wired system
Modicon Telefast BMXAMI0410H Distribution of isolated power – ABE7CPA410 0.180/
ABE7 sub-bases supplies 0.397
Delivers 4 protected isolated power
supplies for 4...20 mA inputs
4 Direct connection of 4 inputs
5
for Modicon Telefast BMXAMO0210H block and one 25-way SUB-D 4.92 ft 0.705
ABE7CPA41p connector for ABE7CPA410/CPA21 3 m/ BMXFCA300 0.500/
sub-base 9.84 ft 1.102
5 m/ BMXFCA500 0.730/
16.40 ft 1.609
BMXFCApp2
BMXART0414H One 40-way connector and 1.5 m/ BMXFCA152 0.330/
BMXART0814H one 25-way SUB-D connector 4.92 ft 0.728
for ABE7CPA412 sub-base 3 m/ BMXFCA302 0.510/
6 9.84 ft
5 m/ BMXFCA502
1.124
0.740/
16.40 ft 1.631
(1) The shielding on the cordsets carrying the analog signals must always be connected to the BMXXSPpp00 shielding
connection kit mounted under the rack holding the analog modules (see page 2/3).
(2) The BMXART0814H 8-channel module requires two ABE7CPA412 sub-bases and two BMXFCApp2 cordsets.
10
6/8
References (continued) Modicon X80 I/O platform
Dedicated parts for severe environments
Ruggedized communication modules
Communication
BMXNOE0100H/0110H ruggedized Ethernet communication modules
Description Data rate Transparent Ready Reference
class
Weight
kg/lb
1
Ethernet Modbus/ 10/100 Mbps B30 BMXNOE0100H 0.200/
TCP network 0.441
modules C30 BMXNOE0110H 0.200/
0.441
BMXNOE0100H/0110H
2
BMXNOM0200H ruggedized serial link module
Description Protocol Physical layer Reference Weight
kg/lb
BMXNOM0200H
BMXNOR0200H ruggedized RTU communication module 4
Description Protocols Physical Reference Weight
layer kg/lb
6
Description Protocols Physical Reference Weight
layer kg/lb
CANopen CiA 301 V4.2 ISO 11898 (9-way BMECXM0100H 0.200/
communication standard (master or SUB-D connector) 0.441
module slave); Ethernet/IP
BMECXM0100H
7
10
6/9
References (continued) Modicon X80 I/O platform
Dedicated parts for severe environments
Ruggedized communication modules and network
gateway
Communication
“Conformal Coating” EIO drop adapters
1 Description SERVICE port Reference Weight
kg/lb
Modicon X80 EIO 1 BMECRA31210C –
drop adapter for
Ethernet + X-bus
racks
drop adapter
BMECRA31210 BMXCRA31210
3
(Ethernet) kg/lb
EtherNet/IP, 1 2 BMENOC0301C 0.345/
Modbus/TCP 0.761
network module
8 BMENOP0300C
Profibus DP V1
and Profibus PA
1 isolated RS 485
Profibus DP port
(via gateway)
10 TCSEGPA23F14FK
6/10
References (continued) Modicon X80 I/O platform
Dedicated parts for severe environments
Ruggedized application-specific modules
Application-specific modules
BMXEHC0200H/0800H ruggedized counter modules
Description No. of
channels
Characteristics Reference Weight
kg/lb
1
Counter modules 2 60 kHz counting BMXEHC0200H 0.112
for 24 V c 2- and 0.247
3-wire sensors and 8 10 kHz counting BMXEHC0800H 0.113
10/30 V c incremental 0.249
encoders with push-pull
2
outputs
BMXEHC0200H BMXEHC0800H
3
Speed and frequency 2 Input frequency: 0…500Hz, BMXETM0200H 0.124/
control module for reflex digital output 0.273
turbomachinery
application
BMXETM0200H
BMXEAE0300H ruggedized SSI encoder interface module
4
Description No. of Characteristics Reference Weight
channels kg/lb
SSI encoder interface 3 8 to 31 bits data width BMXEAE0300H 0.138/
module 4 baud rates: 0.304
100 kHz, 200 kHz,
500 kHz, 1 MHz
5
BMXEAE0300H
8
terminal blocks 0.245
for BMXEAE0300H Spring BMXFTB2820 0.080/
module 0.176
Shielding connection Comprising a metal bar and 2 support See page 2/3 –
kits for bases for mounting on rack
BMXEHC0200H/0800H
and BMXEAE0300H
modules
9
(1) The shielding on the cordsets carrying the counter signals must always be connected to the
BMXXSPpp00 shielding connection kit mounted under the rack holding the BMXEHC0200H
module (see page 2/3).
10
6/11
1
10
7/0
7/2
Contents 7 - Compatibility with OsiSense
XU/XS
10
7/3
7/1
Compatibility Modicon X80 I/O platform
Inputs and OsiSense XU photo-electric sensors
Photo-electric sensors c inputs, BMXDDI c inputs, BMXDDM c inputs, BMXAMI a inputs, BMXDAI
Type Reference 1602 1603 1604T 3202K 6402K 16022 16025 3202K 0810 0800 1602 1603 1604 0805 0814
1 General purpose
Design Metal 3 wire, PNP 24V XUB0/1/2/4/5/9BpPppp 1
Ø 18 3 wire, NPN 24V XUB0/1/2/4/5/9BpNppp
Plastic 3 wire, PNP 24V XUB0/1/2/4/5/9ApPppp
3 wire, NPN 24V XUB0/1/2/4/5/9ApNppp
Design Miniature 3 wire, PNP 24V XUM0/2/5/9APpppp
3 wire, NPN 24V XUM0/2/5/9ANpppp
3 Material
handling
Optical fork 3 wire, PNP 24V
3 wire, NPN 24V
XUVRppppPpp
XUVRppppNpp 3
3 wire, PNP 24V XUVAppppPpp
3 wire, NPN 24V XUVAppppNpp
4 wire, PNP, or NPN 24V XUYFppppp
4 wire, PNP, or NPN 24V XUVU06ppp
4 wire, PNP, or NPN 24V XUVKppp
4 4
3 wire, PNP 24V XUVHppp
3 wire, NPN 24V XUVJppp
4 wire, PNP, or NPN 24V XUVFppp
Packaging Fiber 4 wire, PNP, or NPN 24V XUYDCFppp
Compact 4 wire, PNP, or NPN 24V XUKpSpppp
M 18, threaded 3 wire, PNP 24V XU5M18U1D
Fiber 4 wire, PNP, or NPN 24V XUYAFLppp
5 5
M 18, threaded 3 wire, PNP 24V XUBTpPppp
3 wire, NPN 24V XUBTpNppp
Compact 4 wire, PNP, or NPN 24V XUKTppp
3 wire, PNP 24V XUKC1Nppp
3 wire, NPN 24V XUKC1Pppp
3 wire, PNP 24V XURC3Pppp
3 wire, NPN 24V XURC3Nppp
6 6
4 wire, PNP, or NPN 24V XUMWppp
M 18, threaded 3 wire, PNP 24V XUB0SPppp
3 wire, NPN 24V XUB0SNppp
3 wire, PNP 24V XUpN18Pppp
3 wire, NPN 24V XUpN18Nppp
M 8, threaded 3 wire, PNP 24V XUAHppp
3 wire, NPN 24V XUAJppp
7 7
Miniature 3 wire, PNP 24V XUYPppppPpp
3 wire, NPN 24V XUYPppppNpp
3 wire, PNP 24V XUM2/5/9BPppp
3 wire, NPN 24V XUM2/5/9BNppp
3 wire, PNP 24V XUYppp929pp
Hoisting M 18, threaded 3 wire, PNP 24V XUBLBPppp
3 wire, NPN 24V XUBLBNppp
8 8
Compact 2 wire 4…20 mA; 3 wire 0…10V XUJK803538
M 18, threaded 2 wire 4…20 mA XU5M18AB20D
PNP, 2 wire 4…20 mA XU2M18AB20D
Compact PNP, 2 wire 4…20 mA XUYPppp925
4 wire, PNP, or NPN 24V XUYPSppp
Fiber 3 wire, PNP 24V XUDApPppp
3 wire, NPN 24V XUDApNppp
4 wire, PNP, or NPN 24V XUYAFppp
9 Other formats 3 wire, programmable PNP/NPN DC
5 wire, programmable AC/DC
XUC2/8/9AKppp
XUC2/8/9ARCppp
9
3 wire, NPN 24V + analog XUEpAAppp
2 wire, AC XULAppp
5 wire, programmable AC/DC XULMppp
3 wire, programmable PNP/NPN DC XUYBpppS
5 wire, programmable AC/DC XUYBpppR
10 M 18, threaded 2 wire, AC/DC XU5/8/9M18MAppp 10
Compatible
Incompatible
7/2 7/2
7/3
Compatibility Modicon X80 I/O platform
Inputs and OsiSense XS inductive proximity
sensors
Proximity sensors c inputs, BMXDDI c inputs, BMXDDM c inputs, BMXAMI a inputs, BMXDAI
Type Reference 1602 1603 1604T 3202K 6402K 16022 16025 3202K 0810 0800 1602 1603 1604 0805 0814
1 General purpose
Cylindrical,
flush, standard
Ø 6.5 plain short 3 wire, PNP 24V XS506B1Pppp 1
3 wire, NPN 24V XS506B1Nppp
sensing distance, 2 wire, DC 24V XS506BSCppp
short barrel M8, threaded short 3 wire, PNP 24V XS508B1Pppp
3 wire, NPN 24V XS508B1Nppp
2 wire, DC 24V XS508BSCppp
M12, threaded short 3 wire, PNP 24V XS512B1Pppp
2 3 wire, NPN 24V
2 wire, DC 24V
XS512B1Nppp
XS512BSD/Cppp
2
M18, threaded short 3 wire, PNP 24V XS518B1Pppp
3 wire, NPN 24V XS518B1Nppp
2 wire, DC 24V XS518BSD/Cppp
M30, threaded short 3 wire, PNP 24V XS530B1Pppp
3 wire, NPN 24V XS530B1Nppp
3 Cylindrical,
flush, standard
M8, threaded long
2 wire, DC 24V
3 wire, PNP 24V-48V
XS530BSD/Cppp
XS508BLPppp 3
3 wire, NPN 24V-48V XS508BLNppp
sensing distance, 2 wire, DC 24V-48V XS508B1D/Cppp
long barrel M12, threaded long 3 wire, PNP 24V-48V XS512BLPppp
3 wire, NPN 24V-48V XS512BLNppp
2 wire, DC 24V-48V XS512B1D/Cppp
M18, threaded long 3 wire, PNP 24V-48V XS518BLPppp
4 3 wire, NPN 24V-48V
2 wire, DC 24V-48V
XS518BLNppp
XS518B1D/Cppp
4
M30, threaded long 3 wire, PNP 24V-48V XS530BLPppp
3 wire, NPN 24V-48V XS530BLNppp
2 wire, DC 24V-48V XS530B1D/Cppp
M12, threaded long 2 wire, AC/DC XS512B1Mppp
M18, threaded long 2 wire, AC/DC XS518B1Mppp
5 Cylindrical,
flush, extended
M30, threaded long
Ø 6,5 plain short
2 wire, AC/DC
3 wire, PNP 24V
XS530B1Mppp
XS106B3Pppp 5
3 wire, NPN 24V XS106B3Nppp
sensing distance, 2 wire, DC 24V XS606B3Cppp
short barrel M8, threaded short 3 wire, PNP 24V XS108B3Pppp
3 wire, NPN 24V XS108B3Nppp
2 wire, DC 24V XS608B3Cppp
M12, threaded short 3 wire, PNP 24V XS112B3Pppp
6 3 wire, NPN 24V
2 wire, DC 24V
XS112B3Nppp
XS612B3Dppp
6
M18, threaded short 3 wire, PNP 24V XS118B3Pppp
3 wire, NPN 24V XS118B3Nppp
2 wire, DC 24V XS618B3Dppp
M30, threaded short 3 wire, PNP 24V XS130B3Pppp
3 wire, NPN 24V XS130B3Nppp
7 Cylindrical,
flush, extended
M8, threaded long
2 wire, DC 24V
3 wire, PNP 24V-48V
XS630B3Dppp
XS608B1Pppp 7
3 wire, NPN 24V-48V XS608B1Nppp
sensing distance, 2 wire, DC 24V-48V XS608B1Dppp
long barrel M12, threaded long 3 wire, PNP 24V-48V XS612B1Pppp
3 wire, NPN 24V-48V XS612B1Nppp
2 wire, DC 24V-48V XS612B1Dppp
M18, threaded long 3 wire, PNP 24V-48V XS618B1Pppp
8 3 wire, NPN 24V-48V
2 wire, DC 24V-48V
XS618B1Nppp
XS618B1Dppp
8
M30, threaded long 3 wire, PNP 24V-48V XS630B1Pppp
3 wire, NPN 24V-48V XS630B1Nppp
2 wire, DC 24V-48V XS630B1Dppp
M12, threaded long 2 wire, AC/DC XS612B1Mppp
M18, threaded long 2 wire, AC/DC XS618B1Mppp
9 Cylindrical,
non flush, extended
M30, threaded long
M12, threaded long
2 wire, AC/DC
3 wire, PNP 24V-48V
XS630B1Mppp
XS612B4Pppp 9
3 wire, NPN 24V-48V XS612B4Nppp
sensing distance, M18, threaded long 3 wire, PNP 24V-48V XS618B4Pppp
long barrel 3 wire, NPN 24V-48V XS618B4Nppp
M30, threaded long 3 wire, PNP 24V-48V XS630B4Pppp
3 wire, NPN 24V-48V XS630B4Nppp
M12, threaded long 2 wire, AC/DC XS612B4Mppp
10 M18, threaded long
M30, threaded long
2 wire, AC/DC
2 wire, AC/DC
XS618B4Mppp
XS630B4Mppp
10
Compatible
Incompatible
7/3
7/4 7/3
7/5
Compatibility Modicon X80 I/O platform
Inputs and OsiSense XS inductive proximity
sensors (continued)
Proximity sensors c inputs, BMXDDI c inputs, BMXDDM c inputs, BMXAMI a inputs, BMXDAI
Type Reference 1602 1603 1604T 3202K 6402K 16022 16025 3202K 0810 0800 1602 1603 1604 0805 0814
1 General purpose
Flat, flush montable, Format J 8x22x8
standard sensing
3 wire, PNP 24V XS7J1A1Pppp 1
3 wire, NPN 24V XS7J1A1Nppp
distance 2 wire, DC 24V XS7J1A1Dppp
Format F 15x22x8 3 wire, PNP 24V XS7F1A1Pppp
3 wire, NPN 24V XS7F1A1Nppp
2 wire, DC 24V XS7F1A1Dppp
Format E 26x26x13 3 wire, PNP 24V XS7E1A1Pppp
2 3 wire, NPN 24V
2 wire, DC 24V
XS7E1A1Nppp
XS7E1A1D/Cppp
2
Format C 40x40x15 3 wire, PNP 24V XS7C1A1Pppp
3 wire, NPN 24V XS7C1A1Nppp
2 wire, DC 24V XS7C1A1D/Cppp
Format D 80x80x26 3 wire, PNP 24V XS7D1A1Pppp
3 wire, NPN 24V XS7D1A1Nppp
3 Format 40X40X70
and 40X40X117
NO + NC
2 wire, DC 24V
4 wire, PNP 24V-48V
XS7D1A1D/Cppp
XS7/XS8C2/C4A1/A4Pppp 3
4 wire, NPN 24V-48V XS7/XS8C2/C4A1/A4Nppp
Plastic, with turret NO/NC programmable 2 wire, DC 24V-48V XS7/XS8C2/C4A1/A4Dppp
head: 5 positions 2 wire, AC/DC XS7/XS8C2/C4A1/A4Mppp
Flat, flush montable, Format E 26x26x13 3 wire, PNP 24V XS8E1A1Pppp
extended sensing 3 wire, NPN 24V XS8E1A1Nppp
distance 2 wire, AC/DC XS8E1A1Mppp
4 Format C 40x40x15 3 wire, PNP 24V
3 wire, NPN 24V
XS8C1A1Pppp
XS8C1A1Nppp
4
2 wire, AC/DC XS8C1A1Mppp
Format D 80x80x26 3 wire, PNP 24V XS8D1A1Pppp
3 wire, NPN 24V XS8D1A1Nppp
2 wire, AC/DC XS8D1A1Mppp
Cylindrical M12, threaded 2 wire, AC/DC XS1/2M12Mp250
5 5
multi-voltage M18, threaded 2 wire, AC/DC XS1/2M18Mp250
M30, threaded 2 wire, AC/DC XS1/2M30Mp250
Cylindrical Metal, Ø 6.5, plain 4 wire, PNP 24V XS1L06PC410
4 wire 4 wire, NPN 24V XS1L06NC410
M8, threaded 4 wire, PNP 24V XS1/2M08PC410p
4 wire, NPN 24V XS1/2M08NC410p
M12, threaded 4 wire, PNP 24V XS1/2N12PC410p
4 wire, NPN 24V XS1/2N12NC410p
6 M18, threaded 4 wire, PNP 24V
4 wire, NPN 24V
XS1/2N18PC410p
XS1/2N18NC410p
6
M30, threaded 4 wire, PNP 24V XS1/2N30PC410p
4 wire, NPN 24V XS1/2N30NC410p
Cylindrical Metal, M12, threaded 4 wire, PNP+NPN, prog. 24V XS1/2/4M12KP340p
4 wire PNP + NPN M18, threaded 4 wire, PNP+NPN, prog. 24V XS1/2/4M18KP340p
M30, threaded 4 wire, PNP+NPN, prog. 24V XS1/2/4M30KP340p
7 Cylindrical Plastic,
non flush,
standard sensing
M8, threaded 3 wire, PNP 24V
3 wire, PNP 24V-48V
XS4P08Pp340p
XS4P08Pp370p 7
3 wire, NPN 24V XS4P08Np340p
distance 3 wire, NPN 24V-48V XS4P08Np370p
2 wire, AC/DC XS4P08Mp230ppp
M12, threaded 3 wire, PNP 24V XS4P12Pp340p
3 wire, PNP 24V-48V XS4P12Pp370p
3 wire, NPN 24V XS4P12Np340p
8 3 wire, NPN 24V-48V
2 wire, AC/DC
XS4P12Np370p
XS4P12Mp230ppp
8
M18, threaded 3 wire, PNP 24V XS4P18Pp340p
3 wire, PNP 24V-48V XS4P18Pp370p
3 wire, NPN 24V XS4P18Np340p
3 wire, NPN 24V-48V XS4P18Np370p
2 wire, AC/DC XS4P18Mp230ppp
Compatible
Incompatible
10 10
7/4
7/6 7/4
7/7
Compatibility Modicon X80 I/O platform
Inputs and OsiSense XS inductive proximity
sensors (continued)
Proximity sensors c inputs, BMXDDI c inputs, BMXDDM c inputs, BMXAMI a inputs, BMXDAI
Type Reference 1602 1603 1604T 3202K 6402K 16022 16025 3202K 0810 0800 1602 1603 1604 0805 0814
1 General purpose
Cylindrical basic
flush or non flush,
Ø 6.5 plain 3 wire, PNP 24V XS1/206BLPppp 1
3 wire, NPN 24V XS1/206BLNppp
standard sensing M8, threaded 3 wire, PNP 24V XS1/208A/BLPppp
distance, 3 wire, NPN 24V XS1/208A/BLNppp
Plastic or Metal
M12, threaded 3 wire, PNP 24V XS1/212A/BLPppp
3 wire, NPN 24V XS1/212A/BLNppp
M18, threaded 3 wire, PNP 24V XS1/218A/BLPppp
2 M30, threaded
3 wire, NPN 24V
3 wire, PNP 24V
XS1/218A/BLNppp
XS1/230A/BLPppp
2
3 wire, NPN 24V XS1/230A/BLNppp
Cylindrical, M18, threaded 3 wire, PNP 24V XS1N18Pp349p
almost flush, 3 wire, NPN 24V XS1N18Np349p
extended sensing M30, threaded 3 wire, PNP 24V XS1N30Pp349p
distance 3 wire, NPN 24V XS1N30Np349p
3 Cylindrical,
miniature
Ø 4 plain 3 wire, PNP 24V
3 wire, NPN 24V
XS1L04Pp31pp
XS1L04Np31pp 3
M5, threaded 3 wire, PNP 24V XS1N05Pp31pp
3 wire, NPN 24V XS1N05Np31pp
Ø 6.5 plain 3 wire, PNP 24V XS2L06Pp340p
3 wire, NPN 24V XS2L06Np340p
Application
Cylindrical, M12, threaded 3 wire, PNP 24V XS612B2Pppp
4 adjustable sensing
distance M18, threaded
3 wire, NPN 24V
3 wire, PNP 24V
XS612B2Nppp
XS618B2Pppp
4
3 wire, NPN 24V XS618B2Nppp
M30, threaded 3 wire, PNP 24V XS630B2Pppp
3 wire, NPN 24V XS630B2Nppp
Rotation monitoring M18, threaded 3 wire, PNP 24V-48V XSAV11/2373
2 wire, AC/DC XSAV11/2801
5 Format E 26x26x13
Format C 40x40x15
3 wire, PNP 24V
2 wire, AC/DC
XS9p11RPpppp
XS9p11RMpppp 5
Analog output M12, threaded 2 wire 4…20mA; 3 wire 0…10V XSp12ABpppp
M18, threaded 2 wire 4…20mA; 3 wire 0…10V XSp18ABpppp
M30, threaded 2 wire 4…20mA; 3 wire 0…10V XSp30ABpppp
Block format 2 wire 4…20mA; 3 wire 0…10V XS9C2/C4A2Apppp
2 wire 4…20mA; 3 wire 0…10V XS9p111Apppp
Food and beverage Cylindrical threaded Metal 3 wire, PNP 24V XS2ppSAPppp
6 3 wire, PNP 24V
3 wire, NPN 24V
XS908/12/18/30R/SpPppp
XS2ppSANppp
6
2 wire, AC/DC XS2ppSAMAppp
Cylindrical threaded Plastic 3 wire, PNP 24V-48V XS2ppAAPppp
3 wire, NPN 24V XS2ppAANppp
2 wire, AC/DC XS2ppAAMAppp
Factor 1 Cylindrical threaded Metal 4 wire, PNP+NPN 24V XS1MppKPM40
7 Format C, 40 x 117 x 41
Cylindrical threaded Metal
4 wire, PNP+NPN 24V
3 wire, PNP 24V
XS9C2/C4Apppp
XS1M18PASpp 7
Packaging Format 12x26x40 3 wire, PNP 24V XS7G12Pp140
3 wire, NPN 24V XS7G12Np140
4 wire, PNP 24V-48V XS7G12Pp440
4 wire, NPN 24V-48V XS7G12Np440
2 wire, AC/DC XS7G12Mp230
Material handling Format C 40x40x40 2 wire, DC 24V-48V XS7T4DAppp
8 4 wire, PNP 24V-48V
4 wire, NPN 24V-48V
XS7T4PCppp
XS7T4NCppp
8
Format D 80x80x26 2 wire, DC 24V-48V XS7D1pppp
Welding Cylindrical Metal 3 wire, PNP 24V XS1MppPAWpp
2 wire, DC 24V-48V XSLCppp
Compatible
9 Incompatible
9
10 10
7/5
7/8 7/5
7/9
1
10
8/0
8/2
Contents 8 - Standards and certifications
Technical appendices
bb Standards, certifications and environmental conditions.................... page 8/2
bb Certifications for automation products and EC regulations............... page 8/8 1
10
8/3
8/1
Standards and Modicon X80 I/O platform
certifications Standards, certifications, and environment
conditions
All safety modules are certified by TÜV Rheinland. The certificate reviews the following standards:
IEC 61511: Functional safety - Safety instrumented systems for the process industry sector
5 bb IEC 61511-1 - Part 1: Framework, definitions, system, hardware and software requirements
bb IEC 61511-2 - Part 2: Guidelines for the application of IEC 61511-1
bb IEC 61511-3 - Part 3: Guidance for the determination of the required safety integrity levels
6 bb ISO 13849-2: 2012 Safety Related parts of the Control Systems - Part 2: Validation
10
8/2
Standards and Modicon X80 I/O platform
certifications (continued) Standards, certifications, and environment
conditions
Characteristics
Service conditions and recommendations relating to the environment
Modicon X80 I/O platform Modicon M580 Safety
platform
Modicon X80 harsh I/O
platform
1
Temperature Operation °C 0...+ 60 -25...+60 -25...+70
Relative humidity Cyclical humidity % +5 ... +95 up to 55 °C/131 °F +5...+95 up to 55 °C/131 °F +5 ... +95 up to 55 °C/131 °F
(without condensation)
Altitude
Continuous humidity
Operation
%
m
+5 ... +93 up to 55 °C/131 °F +5...+93 up to 60 °C/140 °F
5
For installations in industrial production workshops or environments corresponding to “TH” treatment (treatment for hot and humid
environments), Modicon X80 I/O must be housed in enclosures with minimum IP 54 protection.
The Modicon X80 I/O platform offers protection to IP 20 level and protection against pins (enclosed equipment) (1). It can therefore be
installed without an enclosure in reserved-access areas that do not exceed pollution level 2 (control room with no dust-producing machine or
activity). Pollution level 2 does not take account of more severe environmental conditions: air pollution by dust, smoke, corrosive or radioactive
particles, vapors or salts, molds, insects, etc.
(1) In cases where a slot is not occupied by a module, a BMXXEM010 protective cover must be installed.
6
(e): tests required by European directives (e) and based on IEC/EN 61131-2 standards.
10
8/3
Environment tests Modicon X80 I/O platform
Standards, certifications, and environment
conditions
Environment tests
Name of test Standards Levels
1 Immunity to LF interference (e) (1)
Voltage and frequency variations IEC/EN 61131-2; IEC/EN 61000-6-2; IEC 61000-4-11 0.85...1.10 Un - 0.94...1.04 Fn; 4 steps t = 30 min
IACS E10; IEC 61000-4-11 0.80 Un...0.90 Fn; 1.20 Un...1.10 Fn; t = 1.5 s/5 s
Direct voltage variations IEC/EN 61131-2; IEC 61000-4-29; 0.85...1.2 Un + ripple: 5% peak; 2 steps t = 30 min
IACS E10 (PLC not connected to charging battery)
Third harmonic IEC/EN 61131-2 H3 (10% Un), 0°/180°; 2 steps t = 5 min
4
Voltage shut-down and start-up IEC/EN 61131-2 bb Un…0…Un; t = Un/60 s
bb Umin…0…Umin; t = Umin/5 s
bb Umin…0.9 Udl…Umin; t = Umin/60 s
Magnetic field IEC/EN 61131-2; IEC 61000-4-8 (for MV power stations: Power frequency: 50/60 Hz, 100 A/m continuous
IEC 61000-6-5; IEC 61850-3) ...1000 A/m; t = 3 s; 3 axes
For functional safety (DS criteria):
IEC 61000-6-7; IEC 61326-3-1
IEC 61000-4-10 Oscillatory: 100 kHz...1 MHz, 100 A/m; t = 9 s; 3 axes
6 (1) Devices must be installed, wired, and maintained in accordance with the instructions provided in the manual “Grounding and Electromagnetic Compatibility of PLC Systems”.
(2) These tests are performed without an enclosure, with devices fixed on a metal grid and wired as per the recommendations in the manual “Grounding and Electromagnetic Compatibility of
PLC systems”.
(e): tests required by European e directives and based on IEC/EN 61131-2.
10
8/4
Environment tests Modicon X80 I/O platform
(continued) Standards, certifications, and environment
conditions
3
For analog, c unshielded I/O, communication and
shielded lines:
bb 1 kV in common mode (3 kV DS criteria)
Surge IEC/EN 61131-2; IEC/EN 61000-6-2; IEC 61000-4-5; For a/c main and auxiliary supplies, a unshielded I/O:
IACS E10 bb 2 kV in common mode/1 kV in differential mode (4 kV
For functional safety (DS criteria): DS criteria with external protection)
IEC 61000-6-7; IEC 61326-3-1 For analog, c unshielded I/O:
bb 2 kV in common mode/2 kV in differential mode
4
For communication and shielded lines:
bb 1 kV in common mode (3 kV DS criteria)
Conducted disturbances induced by IEC/EN 61131-2; IEC/EN 61000-6-2; IEC 61000-4-6; 10 V; 0.15 MHz...80 MHz (20 V DS criteria)
radiated electromagnetic fields IACS E10 Sinus amplitude 80%, 1 kHz + spot frequencies
For functional safety (DS criteria):
IEC 61000-6-7; IEC 61326-3-1
Damped oscillatory wave IEC/EN 61131-2; IEC 61000-4-18; For a/c main supplies and a auxiliary supplies,
IACS E10 a unshielded I/O:
bb 2.5 kV in common mode/1 kV in differential mode
For c auxiliary supplies, analog, c unshielded I/O:
bb 1 kV in common mode/0.5 kV in differential mode
5
For communication and shielded lines:
bb 0.5 kV in common mode
(1) Devices must be installed, wired, and maintained in accordance with the instructions provided in the manual “Grounding and Electromagnetic Compatibility of PLC Systems”.
(2) These tests are performed without an enclosure, with devices fixed on a metal grid and wired as per the recommendations in the manual “Grounding and Electromagnetic Compatibility of
PLC systems”.
(e): tests required by European e directives and based on IEC/EN 61131-2.
10
8/5
Environment tests Modicon X80 I/O platform
(continued) Standards, certifications, and environment
conditions
Radiated emission IEC/EN 61131-2; IEC/EN 61000-6-4; CISPR 11 & 30 MHz ... 230 MHz: quasi-peak 40 dB (µV/m) (at 10 m);
7
Damp heat, cyclic IEC/EN 61131-2; IEC 60068-2-30 (Db) 55 °C…25 °C/77 °F...131 °F, 93…95% relative humidity,
(cyclical humidity) 2 cycles t = 12 hrs + 12 hrs
Change of temperature IEC/EN 61131-2; IEC 60068-2-14 (Na) -40 °C...85 °C/-40 °F...185 °F, 5 cycles t = 3 hrs + 3 hrs
(thermal shocks)
(1) D
evices must be installed, wired, and maintained in accordance with the instructions provided in the manual “Grounding and Electromagnetic Compatibility of
PLC Systems”.
(2) Refer also to the chapter “Treatment for severe environments”.
8 (e): tests required by European e directives and based on IEC/EN 61131-2 standards.
10
8/6
Environment tests Modicon X80 I/O platform
(continued) Standards, certifications, and environment
conditions
4
Withstand to mechanical constraints (power off)
Random free fall with packaging IEC/EN 61131-2; 1 m/3.28 ft, 5 falls
IEC 60068-2-32 (Method 1)
Flat free fall IEC/EN 61131-2; 10 cm/0.33 ft, 2 falls
IEC 60068-2-32 (Ed Method 1)
Controlled free fall IEC/EN 61131-2; 30° or 10 cm/0.33 ft, 2 falls
IEC 60068-2-31 (Ec)
Plugging/Unplugging IEC/EN 61131-2 For modules and connectors:
Operations: 50 for permanent connections, 500 for
non-permanent connections
5
Name of test Standards Levels
Equipment and personnel safety (1) (e)
Dielectric strength and insulation IEC/EN 61131-2; Dielectric: 2 Un + 1000 V; t = 1 min
resistance IEC 61010-2-201; UL; CSA Insulation: Un y 50 V: 10 MΩ, 50 V y Un y 250 V :
100 MΩ
Ground continuity IEC/EN 61131-2;
IEC 61010-2-201; UL; CSA
30A, R y 0,1Ω; t = 2 min
6
Leakage current IEC/EN 61131-2; y 0.5 mA in normal condition
IEC 61010-2-201; UL; CSA y 3.5 mA in single fault condition
Protection offered by enclosures IEC/EN 61131-2; IP20 and protection against standardized pins
IEC61010-2-201;
Impact withstand IEC/EN 61131-2; Sphere of 500 g, fall from 1.30 m (energy 6.8 J minimum)
7
IEC 61010-2-201; UL; CSA
Overload IEC/EN 61131-2; 50 cycles, Un, 1.5 In; t = 1 s ON + 9 s OFF
IEC 61010-2-201; UL; CSA
Endurance IEC/EN 61131-2; In, Un; 6000 cycles: t = 1 s ON + 9 s OFF
IEC 61010-2-201; UL; CSA
Temperature rise IEC/EN 61131-2; UL; CSA; ATEX; IECEx Ambient temperature 60 °C/140 °F
[for ruggedized range: 70 °C/158 °F ] (4)
Name of test Standards Levels
Specific environment (4)
Corrosion areas - gas, salt, dust ISA S71.4 Flowing mixed gas; class Gx, 25 °C/77 °F,
8
75% relative humidity, t = 14 days
IEC/EN 60721-3-3 Flowing mixed gas; class 3C3, 25 °C/77 °F,
IEC60068-2-60 75% relative humidity, t = 14 days
IEC/EN 60721-3-3 Flowing mixed gas; class 3C4, 25 °C/77 °F,
IEC60068-2-60 75% relative humidity, t = 7 days
IEC60068-2-52
IEC/EN 60721-3-3
Salt spray: test Kb, severity 2
Dust and sand, Arizona dust, class 3S4, 20 cycles
9
IEC60068-2-68
IEC/EN 60721-3-3 Mold growth, fungal spore, class 3B2, t=28 days
IEC60068-2-10
(1) D
evices must be installed, wired, and maintained in accordance with the instructions provided in the manual “Grounding and Electromagnetic Compatibility of
PLC Systems”.
(2) When using fast actuators (response time y 5 ms) driven by relay outputs: 15 g, 11 ms; 3 shocks/direction/axis.
(3) When using fast actuators (response time y 15 ms) driven by relay outputs: 15 g, 6 ms; 100 bumps/direction/axis.
(4) Refer also to the chapter “Treatment for severe environments”.
10
(e): tests required by European e directives and based on IEC/EN 61131-2 standards.
8/7
Technical appendices
Automation product certifications
EC regulations
Some countries require certain electrical components to undergo certification by law. This certification takes the form of a certificate of
conformity to the relevant standards and is issued by the official body in question. Where applicable, certified devices must be labeled
1
accordingly. Use of electrical equipment on board merchant vessels generally implies that it has gained prior approval (i.e. certification) by
certain shipping classification societies.
3
DNV Det Norske Veritas Norway
GL Germanischer Lloyd Germany
LR Lloyd’s Register UK
RINA Registro Italiano Navale Italy
RMRS Russian Maritime Register of Shipping Russia
RRR Russian River Register Russia
CCS China Classification Society China
Note: Due to the merger between DNV and GL certification, DNV/GL will be renewed as a single certificate from 2016.
The following tables provide an overview of the situation as of September 2016, in terms of which certifications (listed next to their respective
bodies) have been granted or are pending for our automation products.
Up-to-date information on which certifications have been obtained by products bearing the Schneider Electric brand can be viewed on our
website: www.schneider-electric.com
5 Product certifications
Certifications
Certified Hazardous
locations (1)
Certification pending Class I, div 2
6
UL CSA RCM EAC (6) TÜV Rheinland
USA Canada Australia Russia USA, Canada
Modicon OTB
Modicon STB FM Zone 2 (2)(5)
Modicon Telefast ABE 7
ConneXium (2)
Magelis PC/GTW (3) (2) (3) Zone 2/22 (2)
7 Magelis XBT GT
Magelis XBT GK
(3)
(3)
(2) (2) (3)
(3)
Zone 2/22 (2)(5)
8 Modicon M580
Modicon M580 Safety
CSA (8)
CSA (8)
Zone 2/22 (2)
Zone 2/22 (2) SIL 3, Cat.4, PLe
Modicon X80 I/O CSA (8) Zone 2/22 (2)
Modicon Momentum FM
Modicon Premium (2) CSA
Modicon Quantum (2) CSA (8) Zone 2/22 (2)
Modicon Quantum Safety (2) CSA Zone 2/22 (2) SIL 2, SIL 3 (7)
9 Preventa XPSMF
Modicon TSX Micro CSA
SIL 3 (7)
Phaseo (3)
Twido (4) (4) CSA/UL (4)
(1) Hazardous locations: According to ANSI/ISA 12.12.01 and/or CSA 22.2 No. 213, and/or FM 3611, certified products are only approved for use in hazardous
locations categorized as Class I, division 2, groups A, B, C, and D, or in non-classified locations.
10
(2) Depends on product; please visit our website: www.schneider-electric.com.
(3) North American certification cULus (Canada and USA).
(4) Except for AS-Interface module TWD NOI 10M3, e only.
(5) For zones not covered by this specification, Schneider Electric offers a solution as part of the CAPP (Collaborative Automation Partner Program). Please contact
our Customer Care Center.
(6) Refer to the instructions supplied with each ATEX and/or IECEx certified product.
(7) According to IEC 61508. Certified by TÜV Rheinland for integration into a safety function of up to SIL 2 or SIL 3.
(8) C SA Hazardous Location according to ANSI/ISA 12.12.01, CSA 22.2 No. 213, and FM 3611.
8/8
Technical appendices
Automation product certifications
EC regulations
2
Britain
Modicon OTB
Modicon STB
Modicon Telefast ABE 7
ConneXium
Magelis PC/GTW
Magelis XBT GT
Magelis XBT GK
Magelis XBT N/R
3
Magelis XBT RT
Magelis HMI GTO
Magelis HMI STO/STU
Modicon M340
Modicon M580
Modicon M580 Safety 4
Modicon X80 I/O
Modicon Momentum
Modicon Premium
Modicon Quantum
Modicon TSX Micro
Phaseo 5
Twido
EC regulations
European Directives
The open nature of the European markets assumes harmonization between the regulations set by the member states of the European Union.
European Directives are texts intended to remove restrictions on free circulation of goods and which must be applied within all European Union
states.
6
Member states are obligated to incorporate each Directive into their national legislation, and to simultaneously withdraw any regulations that
contradict it.
Directives - and particularly those of a technical nature with which we are concerned - merely set out the objectives to be fulfilled (referred to as
“essential requirements”). Manufacturers are responsible for taking the necessary measures to establish that their products conform to the
requirements of each Directive applicable to their equipment.
As a general rule, manufacturers certify compliance with the essential requirements of the Directive(s) that apply to their products by applying a
e mark. The e mark is affixed to our products where applicable.
7
Significance of the e mark
The e mark on a product indicates the manufacturer's certification that the product conforms to the relevant European Directives; this is a
prerequisite for placing a product that is subject to the requirements of one or more Directives on the market and allowing its free circulation
within European Union countries. The e mark is intended for use by those responsible for regulating national markets.
Where electrical equipment is concerned, conformity to standards indicates that the product is fit for use. Only a warranty by a well-known
manufacturer can provide reassurance of a high level of quality. 8
As far as our products are concerned, one or more Directives are likely to apply in each case; in particular:
bb The Low Voltage Directive (2014/35/EU)
bb The Electromagnetic Compatibility Directive (2014/30/EU)
bb The ATEX e Directive (2014/34/EU)
bb The Machinery Directive (2006/42/EU)
Hazardous substances
These products are compatible with:
9
bb The WEEE Directive (2012/19/EU)
bb The RoHS Directive (2011/65/EU)
bb The China RoHS Directive (Standard GB/T 26572-2011)
bb REACH regulations (EC 1907/2006)
10
Note: Documentation on sustainable development is available on our website www.schneider-electric.com (product environmental profiles and instructions for use,
RoHS and REACH directives).
End of life (WEEE)
End of life products containing electronic cards must be dealt with by specific treatment processes.
When products containing backup batteries are unusable or at end of life they must be collected and treated separately. Batteries do not contain
a percentage by weight of heavy metals above the limit specified by European Directive 2013/56/EU.
8/9
1
10
9/0
9/2
Contents 9 - Services, index
Index
bb Product reference index ........................................................................ page 9/4 2
10
9/3
9/1
Presentation A dedicated services offer for your
installed base
Schneider Electric, with its experts, products and dedicated tools, provides services
such as system design, consultancy, maintenance contracts, modernization of
1
facilities or delivering projects.
The Schneider Electric services offer is structured around several key areas:
bb Maintenance and support services:
vv A set of services to help maintain reliability and availability of automated control
systems. These services may be the subject of a bespoke maintenance contract to
meet your requirements more closely.
bb Consultancy services:
2 vv Diagnostics of the installed base
bb Modernization solutions:
vv Migration solutions including consultancy, expertise, tools and technical support
to help ensure a smooth transition to newer technology while keeping the wiring and
the encoding in most cases.
Customization services are also available to accommodate specific requirements.
3 For more information, please consult the specific pages on our website
www.schneider-electric.com/automationservices
6 bb On-site repair:
vv Our experts’ knowledge and expertise
vv Monitoring of specific repair procedures
vv Availability of our teams to respond 24/7
bb Exchanges:
vv With standard replacements, receive a new or reconditioned product before the
broken down product has even been sent back
7 vv Fast exchanges offer the option to receive the replacement product within
24 hours (in Europe)
Preventive maintenance Improving and guaranteeing the long-term reliability and performance of your
installations
Schneider Electric’s preventive maintenance expert assesses your site, the
equipment to be managed and sets up a maintenance program to accommodate
specific requirements. A list is provided of the tasks to be performed and their
8 frequency, including site-specific tasks, describing how preventive maintenance is to
be managed.
Extended warranty An additional manufacturer warranty covering replacement or repair of the
equipment
The extended warranty offers the option to take out a 3-year warranty. The warranty
period can vary according to the geographical area, consult your Customer Care
9 Online support
Centre.
Access to dedicated experts
Priority access to experts who can answer technical questions promptly concerning
equipment and software both on sale and no longer commercially available.
Software subscription Access to software upgrades and new features
10
By subscribing to software updates, users are able to:
bb Purchase licences
bb Receive updates, upgrades, software migrations and transitions
bb Download software from Schneider Electric’s software library
9/2
Presentation (continued) A dedicated services offer for your
installed base
Consultancy services
M2C (Maintenance and Modernization Professional tools and methods, proven experience of managing obsolescence and
Consultancy) updating installed bases, to reduce downtimes and improve performance
With our maintenance and modernization consultancy offer, Schneider Electric will
1
help you check the state of your installed base by:
bb Defining the scope and depth of the analysis in collaboration with you
bb Collecting the technical data without shutting down production
bb Analyzing and identifying avenues for improvement
bb Producing a recommendation plan
Customer benefits: 2
bb Learning about the components that make up the installed base and how
up-to-date they are
bb Better downtime anticipation
bb Expert advice designed to improve performance
Modernization solutions
Migration to EcoStruxure Proven expertise, tools and methods to give you a clear vision of the improvement
opportunities and guide you toward a successful modernization project
3
Schneider Electric offers gradual solutions of modernization through a set of
products, tools and services that allow you to upgrade your installations with our last
technologies. Our solutions offer you the choice to plan your modernization:
bb Partial modernization: replacement of an old set of components with a new one
4
bb Step by Step modernization: gradual incorporation of new Solutions or Offers in
To find out more about EcoStruxure the system
architectures, please visit our website bb Complete modernization: total renovation of the system
www.schneider-electric.com/EcoStruxure
Platform Premium
wiring system
6
TSX47 to TSX107
Quantum
Modicon 984 & 800 Series I/O
7
Modicon Compact
Symax (1)
April series 1000 (2)
April SMC
Merlin Gerin PB
AEG (1)
Rockwell SLC500
Rockwell PLC 5 (1)
8
Service available
Note: To check availability of services required, please contact our Customer Care Centre.
9/3
Index Product reference index
1 ABE7CPA03
ABE7CPA21
3/23
3/23
BMXCPS4022H
BMXCPS4022S
6/3
4/5
BMXFCA500 3/23
6/8 BMXFTW501S
6/6
3/23
STBXSP3010 2/5
6/4
BMXFCA502 3/23 6/8 STBXSP3020 2/5
ABE7CPA31 3/23 BMXCRA31210C 6/10 6/8 BMXFTW508S 3/23 6/4
ABE7CPA31E 3/23 BMXDAI0805 3/12 BMXFCC051 3/13 BMXFTW1001 3/13
ABE7CPA410 3/23 BMXDAI0814 3/12 BMXFCC053 3/13 6/6
6/8 T
BMXDAI1602 3/12 BMXFCC101 3/13 BMXGEL0025 6/4 TCSEGPA23F14FK 6/10
2
ABE7CPA412 3/23
BMXDAI1602H 6/6 BMXFCC103 3/13 BMXMSP0200 3/37
6/8 TCSMCN3M4F3C2 5/19
BMXDAI1603 3/12 BMXFCC201 3/13 BMXNGD0100 5/15
ASITERV2 5/17 TCSMCN3M4M3S2 5/19
BMXDAI1603H 6/6 BMXFCC203 3/13 BMXNOE0100H 6/9 6/10
BMXDAI1604 3/12 BMXFCC301 3/13 BMXNOE0110H 6/9 TCSXCN3M4F3S4 5/19
B
BMXDAI1604H 6/6 BMXFCC303 6/10
BMEAHI0812 3/27 3/13 BMXNOM0200 5/19
BMXDAI1614 3/12 TSXCBY010K 2/9
BMEAHO0412 3/27 BMXFCC501 3/13 BMXNOM0200H 6/9
6/5
3
BMXDAI1614H 6/6 BMXFCC503 3/13 BMXNOR0200H 5/13
BMECRA31210 5/3 TSXCBY030K 2/9
BMXDAI1615 3/12 BMXFCC1001 3/13 6/9
BMECRA31210C 6/10 6/5
BMXDAI1615H 6/6 BMXFCC1003 3/13 BMXNRP0200 5/5
BMECXM0100 5/21 TSXCBY050K 2/9
BMXDAO1605 3/12 BMXFCW301 3/13 BMXNRP0201 5/5 6/5
BMECXM0100H 6/9
BMXDAO1605H 6/6 BMXFCW301S 3/23 BMXPRA0100 5/7 TSXCBY120K 2/9
BMENOC0301C 6/10
BMXDAO1615 3/12 6/8 BMXRWS128MWF 5/13 6/5
BMENOC0311C 6/10
BMXDAO1615H 6/6 BMXFCW303 3/13 BMXRWSC016M 5/15 TSXCBY180K 2/9
4
BMENOC0321C 6/10 6/5
BMXDDI1602 3/12 BMXFCW501 3/13 BMXSAI0410 4/9
BMENOP0300 5/23 TSXCBY280KT 2/9
BMXDDI1602H 6/6 BMXFCW501S 3/23 BMXSDI1602 4/8
BMENOP0300C 6/10 6/5
6/8 BMXSDO0802 4/8
BMENOS0300 5/5 BMXDDI1603 3/12 TSXCBY1000 2/9
BMXFCW503 3/13 BMXSRA0405 4/8
BMENOS0300C 6/10 BMXDDI1603H 6/6 6/5
BMXFCW1001 3/13 BMXXBC008K 2/9 TSXCBYACC10 2/9
BMEXBP0400 2/4 BMXDDI1604T 3/12
BMXFCW1003 3/13 6/5 6/5
BMEXBP0400H 6/4 BMXDDI3202K 3/12
5 BMEXBP0602
BMEXBP0602H
2/4
6/4
BMXDDI6402K
BMXDDM3202K
3/12
3/13
BMXFTA150
BMXFTA152
3/23
3/23
BMXXBC015K 2/9
6/5
TSXCBYK9 2/9
6/5
BMXFTA300 3/23 BMXXBC030K 2/9 TSXTLYEX 2/9
BMEXBP0800 2/4 BMXDDM16022 3/13 6/5 6/5
BMXFTA302 3/23
BMEXBP0800H 6/4 BMXDDM16022H 6/6 BMXXBC050K 2/9
BMXFTB2000 3/13 6/5
BMEXBP1002 2/4 BMXDDM16025 3/13 V
3/23
BMEXBP1002H 6/4 BMXDDM16025H 6/6 3/31 BMXXBC120K 2/9 VW3M8223R30 3/37
6
4/8 6/5
BMEXBP1200 2/4 BMXDDO1602 3/12
4/9 BMXXBE1000 2/9
BMEXBP1200H 6/4 BMXDDO1602H 6/6 6/6 BMXXBE1000H 6/4
BMXAMI0410 3/22 BMXDDO1612 3/12 6/8
6/11 BMXXBE2005 2/9
BMXAMI0410H 6/7 BMXDDO1612H 6/6
BMXFTB2010 3/13 BMXXBP0400 2/4
BMXAMI0800 3/22 BMXDDO3202K 3/12
3/23 BMXXBP0400H 6/4
BMXAMI0810 3/22 BMXDDO6402K 3/12 3/31
BMXXBP0600 2/4
9/4
www.schneider-electric.com/psx
Head Office The information provided in this documentation contains general descriptions and/or technical
35, rue Joseph Monier characteristics of the performance of the products contained herein. This documentation is
F-92500 Rueil-Malmaison not intended as a substitute for and is not to be used for determining suitability or reliability of
France these products for specific user applications. It is the duty of any such user or integrator to
perform the appropriate and complete risk analysis, evaluation and testing of the products with
respect to the relevant specific application or use thereof. Neither Schneider Electric nor any
of its affiliates or subsidiaries shall be responsible or liable for misuse of the information
contained herein.