Project Name: North Dagon Hospitsl 10/21/2020

The document provides calculations for the booster pump and pneumatic tank sizing for the North Dagon Hospital project. It calculates the total water supply flow rate needed as 656.60 wsfu (water supply fixture units) or 152.81 USgpm (US gallons per minute). It determines that 3 booster pumps with a design flow rate of 61.13 usgpm each would be required. It also sizes the pneumatic tank at 500 liters to maintain water pressure between 90-110 psi. Notes specify assumptions for public space water needs like pools and water tanks.

Uploaded by

codefinder
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
202 views2 pages

Project Name: North Dagon Hospitsl 10/21/2020

The document provides calculations for the booster pump and pneumatic tank sizing for the North Dagon Hospital project. It calculates the total water supply flow rate needed as 656.60 wsfu (water supply fixture units) or 152.81 USgpm (US gallons per minute). It determines that 3 booster pumps with a design flow rate of 61.13 usgpm each would be required. It also sizes the pneumatic tank at 500 liters to maintain water pressure between 90-110 psi. Notes specify assumptions for public space water needs like pools and water tanks.

Uploaded by

codefinder
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Project Name : NORTH DAGON HOSPITSL 10/21/2020

Booster Pump Calculation (BP-1)

Building Description Qty X wsfu = wsfu Remark


Block A Public WC 24 X 5 = 120 wsfu
Public Basin 23 X 2 = 46 wsfu
Public Shower 4 X 4 = 16 wsfu
Private WC 2 X 2.2 = 4.4 wsfu
Private Basin 2 X 0.7 = 1.4 wsfu
Private shower 2 X 1.4 = 2.8
Sink X 4 = 0
Tap 3 X 4 = 12 202.6

Block B Public WC 19 X 5 = 95 wsfu


Public Basin 26 X 2 = 52 wsfu
Public Shower 14 X 4 = 56 wsfu
Private WC 50 X 2.2 = 110
Private Basin 50 X 0.7 = 35
Private shower 50 X 1.4 = 70
Sink 6 X 4 = 24 wsfu
Tap 3 X 4 = 12 454

Total = 656.60 wsfu 152.81 usgpm


Required Flow Rate = 152.81 usgpm
Total Number of Booster Pump to be run at the same time = 3 Nos.
Maximum Flow Rate of Each Pump = 50.94 usgpm
Design Pump Flow Rate (20% SF Added) = 61.13 usgpm
= 3.86 L/s 50.90 Igpm
Design Pump Flow Rate = 4.00 L/s 52.79 Igpm
c
14.4 cu.m/hr
Pump Outlet Pressure to maintain = 82.02 ft
= 25.00 m
NPSH = 3.00 m
Suction Head = 0.60 m Above Pump
Static Head = 12.80 m
Friction Loss through pipe = 15.00 m
Total Head Required = 56.40 m
Added 10% Safety Factor = 62.04 m
Design Pump Head = 65.00 m c 213.3 Ft
c
Type = Electric 92.31773
Pump Efficiency (%) = 60%
Motor Efficiency (%) = 75%
9.81x1000xQxh = 4.25 KW
6
3.6x10 x M.E
Estimated Power Consumption (Shaft Power/ Motor Eff.) = 5.67 kW 7.60 hp
Maximum Possible simultaneous Power Consumption = 17.00 KW 22.80 hp
c

Prepared by : Santi Engineering Co. Ltd Page - 5


Project Name : NORTH DAGON HOSPITSL 10/21/2020

Pnuematic Tank Sizing


Design Flow Rate = 61.13 usgpm
Assume 4% of minium water draw from system 2.45 usgpm
for 10 minute draw out water 24.45 usgal
Max Pressure = 110.00 Psi
Min Pressure = 90.00 Psi
In order for simple and easy calculation assume minium pressure to be 90 psi and max pressure to be 110 psi
(P2-P1)/P2 = 0.160
Vd
Vt =
(P2-P1)/P2
= 152.81 usgal
= 578.47 Litters
Desing Pnuematic Tank Size = 500.00 Litters x 1 nos

NOTE :
The following assumption were made for public spaces
- Swimming pool make up water to fill within 1 hr and the flow rate required is ~ 1gpm.
- Above ground water tank to fill within 2 hr and the flow rate required is ~ 18gpm.
Water Flow Rate Value were derived from Table E 103.3(3) of International Plumbing Code based on Accmu; wsfu of Column 5.

Prepared by : Santi Engineering Co. Ltd Page - 6