1] PRODUCT PRESENTATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3] PACKAGE CONTENTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5] programmation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Starting the ATRIUM Software. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Understanding the ATRIUM Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Users . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Holidays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Schedules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Access Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
System Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Door Lock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Bells . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Tamper switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Readers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Accounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Copyright (C) 2011-2012 CDVI. All rights reserved. ATRIUM Access Control is protected by copyright law and international
treaties. Unauthorized reproduction or distribution of this product, or any portion of it, may result in severe civil and criminal
penalties, and will be prosecuted to the maximum extent possible under law.
All other brand and product names are trademarks or registered trademarks of their respective companies.
The information contained in this publication is subject to change without notice.
2 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
1] PRODUCT PRESENTATION
The ATRIUM software is an advanced and powerful access control management tool. It allows an operator to
monitor and manage the system by accessing the ATRIUM controller using a network connection. The ATRIUM
software manages the controller and its expanders. ATRIUM DVD includes the ATRIUM software and the
reference manual. The reference manuals for ATRIUM hardware components are also available on the ATRIUM
DVD.
This chapter contains important information concerning the installation and use of this software.
cdvigroup.com 3
INSTALLATION MANUAL
A10
ATRIUM Software
This section describes how to install the ATRIUM software on a computer, start the application, register your
product and add a controller.
Computer Requirements
The ATRIUM interface is designed to operate with computers running a suitable Windows operating system as
detailed in the “Operating System Requirements”.
• Pentium 4
• 1GB RAM (2GB for superior performance)
• 4GB recommended; more for larger installations
• Ethernet access either through physical 10/100 Mbps Ethernet port or WiFi
For technical support in Canada or the U.S., call 1-866-610-0102, Monday to Friday from 8:00 a.m. to 8:00 p.m.
EST. For other locations, please refer to last page of this document or visit our website: www.cdvigroup.com.
4 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
3] PACKAGE CONTENTS
• One DVD
To install the ATRIUM software on Windows, you must be logged on with an administrator account.
1. Start the ATRIUM setup either from the supplied DVD or from the hard drive when downloaded from
the web.
a) To install from DVD, insert the ATRIUM software DVD into the computer’s drive. If the auto
run feature is enabled, go to the step 2. Otherwise, use Windows Explorer to locate and start
ATRIUM-Setup.exe.
b) To install from the hard drive, first download the application from www.cdvigroup.com then use
Windows Explorer to locate and start ATRIUM-Setup.exe.
2. Select the installation language from the list then click on OK.
3. Click Next.
4. The License Agreement window will appear. To install the ATRIUM software, select “I agree to these
terms and conditions” check box and click Next.
5. If you wish to select a different folder destination for the ATRIUM software, click the Browse button,
choose the folder destination and click Install.
6. Click Finish to complete the installation. If required, restart your computer to complete the
installation.
cdvigroup.com 5
INSTALLATION MANUAL
A10
ATRIUM Software
5] programmation
3. Type the password for the selected account. The default password for all accounts is admin. If you
don’t remember the password, click on the “?” button next to the Password field to obtain a password
hint. Refer to the “Accounts” chapter for account and password management.
4. Select the language that will be used for the account; English is selected by default.
5. Click OK.
6 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Registering your ATRIUM software is mandatory. Registration gives access to future updates and new product
information.
The ATRIUM software will stop running after 30 days following installation. The registration form is automatically
displayed every time you start the application until you register successfully. If you decide to register later, you
can access the registration form as follows:
cdvigroup.com 7
INSTALLATION MANUAL
A10
ATRIUM Software
Adding a Controller
For each new account, the following screen is displayed to indicate that a controller needs to be associated with
the account. To add a controller, proceed with the following steps.
1. Click on Add Controller. The Controller Connection pop up will be displayed.
8 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
The Serial Number, IP Address and Software Port fields of the selected controller will be carried over.
3. Click OK.
4. Enter the module login ID and Password. The default login ID and password are “admin”.
5. Click Login. The application will synchronize with the controller and with the expander modules
connected to the controller.
cdvigroup.com 9
INSTALLATION MANUAL
A10
ATRIUM Software
Menu
Ribbon
Buttons
Opened Close the
Window Window
Events
Window
Alert
Window
Connection Status
Dashboard
• Credentials
- Users, refer to page 15.
- Cards, refer to page 23.
• Access Configuration
- Holidays, refer to page 27.
- Schedules, refer to page 30.
- Areas, refer to page 35.
- Access Levels, refer to page 38.
10 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
• Control
- Doors, refer to page 40.
- Relays, refer to page 47. This icon is also available from the Hardware tab.
- Inputs, refer to page 49. This icon is also available from the Hardware tab.
- Outputs, refer to page 55. This icon is also available from the Hardware tab.
• Monitoring
- Events, refer to page 57.
- Reports, refer to page 60.
• Languages:
The ATRIUM software is a multi-language application. Select the desired language from the list.
Hardware
• Hardware
- System Overview, refer to page 62.
- Inputs, refer to page 49. This icon is also available from the Dashboard tab.
- Outputs, refer to page 55. This icon is also available from the Dashboard tab.
- Door Locks, refer to page 69.
- Relays, refer to page 47. This icon is also available from the Dashboard tab.
- Bells, refer to page 71.
- Tamper Switches, refer to page 74.
- Readers, refer to page 75.
Advanced Configuration
• Programming
- Macros, refer to page 77.
• Management
- Accounts, refer to page 80.
cdvigroup.com 11
INSTALLATION MANUAL
A10
ATRIUM Software
Pop-Up
Window
Docking
arrows
Once a window has been moved as a pop-up, the docking mode is enabled meaning that each window that will
be opened will be docked as shown in the following picture.
Close the
Selected
Docked Window
Docked
Window
Select a
Docked Window
12 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Alert Windows
The Hardware Alert and Software Alert windows show event status respectively related to hardware and
software events. The following table lists examples of hardware and software events.
Examples of Events
Attempt to write a duplicate card or keyboard code failed. Module SN: 0, object ID: 1
The module 0 already has an active connection.
Module 0 information was successfully changed.
Software Cannot connect to the module 0, User right error.
Communication timeout. Module: 0, synchronizer: 1
Login error: the login ID and/or password are wrong.
etc.
Connection Status
Indicates the communication status with the ATRIUM module(s).
• Online: Connection established with the controller.
• Offline: Connection not established or lost with the controller.
• Synchronizing: Synchronizing the computer and controller data.
• Limited Connectivity: Connection established with the controller module but at least one of the
expansion modules is offline.
cdvigroup.com 13
INSTALLATION MANUAL
A10
ATRIUM Software
1. When changing the name of a system component in the ATRIUM software windows (i.e. name of a
door, user, relay, etc.), ATRIUM will immediately refresh the screen.
2. Please note that ATRIUM supports up to 16 (first and last names) or 32 (other labels) characters for
text fields and up to 1000 characters for Notes fields.
Required Fields
Fields surrounded by a red frame are either required fields or fields in error.
For example, the Display Name, Format, and Hex fields from the Card Properties window are mandatory
(required) fields.
A field in error prevents from saving changes and closing the window.
14 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Users
Programming a user allows to define the details pertaining to the user. Any individual that needs to access an
area (room) must be defined in the system as a user. Once defined, a card can be assigned to a user.
From the Dashboard tab, click on the Users icon. From this window, a user may be added, edited, or deleted.
• USER INSTALLER: This user is active by default, can program cards and has a system and
web access login. This user is usually the System Installer that configures all hardware related
configurations. The installer usually defines along with the owner the perimeters of an area that
needs to be protected by an access door and also define with the owner or system manager, the
different access levels and access schedules.
• MASTER USER: This user is active by default, can add / delete cards and users, has the
ACCESS LEVEL ALWAYS and has a system and web access login. This user is usually the system
administrator or manager, the responsible to add and delete user in the system. The MASTER USER
also defines the access levels, the access schedules, the holidays and the different access rights of
all the other users.
• PROGRAMMING USER: This user is active by default and is used to add new cards to the system.
Whenever the CARD ENROLLMENT mode is used, all the new cards programmed will inherit the
programming of the user associated to the PROGRAMMING CARD. It is also possible to define
multiple PROGRAMMING USER with different configuration and access rights. With this, it is then
possible to program different PROGRAMMING USER allowing easy USER programming with a specific
template.
cdvigroup.com 15
INSTALLATION MANUAL
A10
ATRIUM Software
Adding a User
From the Dashboard tab, click on the Users icon and click on the Add button.
General Information
• First Name: Indicates the first name of the user. A maximum of 16 characters is allowed.
• Last Name: Indicates the last name of the user. A maximum of 16 characters is allowed.
• Active: When selected, indicates that the user is active.
• Allow Extended Time: When a user is granted access to a door, the door will remain unlocked for
the period defined by the door’s Unlock Time. When Allow Extended Access is enabled, the door will
remain unlocked for the duration of the door’s Extended Time in addition to its Unlock Time. This
option is particularly useful for individuals that may require more time to access the door.
• Can Program Cards: Enables this user’s card to activate “Card Enrollment” mode when a second
card, which has the “PROGRAMMING Card” option activated, is presented to the same reader within
5 seconds.
Card enrollment mode can also be activated via the “Cards” tab in the ATRIUM software.
Cards may also be added sequentially using the on-board MODE button; refer to the AC22 2-Door
Controller instruction manual for more information.
16 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
• Activation Date: Indicates the date the user becomes valid. Enter the year, month, day and time
of the day the user becomes valid or click on the calendar icon and select the date and time. The
user will become active at selected activation date and time.
• Expiry Date: Indicates the date the user becomes invalid. This is useful for personnel on contract
which would require an access for a specific period of time. Enter the year, month, day and time of
the day the user expires or click on the calendar icon and select the date and time. The user will
expires at the selected date and time. For permanent users, do not select an expiration date (leave
the field empty).
• Language: ATRIUM supports several languages. Select the language this user will use when
accessing the ATRIUM software or web server. The user must have a system login ID and password.
cdvigroup.com 17
INSTALLATION MANUAL
A10
ATRIUM Software
Credentials Tab
The Credentials tab allows to assign cards, a keypad code and a system login to a user.
Cards
Allows to assign/unassign access card(s), a keypad code (optional) and an ATRIUM system login
(optional).
• Assign button: To assign a card to this user, click on the Assign button and select a card from the
list. The cards are listed with the following information: Active, ID, Display Name, Number, User,
Activation Date, Expiry Date, Lost, Stolen, and Programming Card. Valid and invalid cards are listed
and can be selected but a card will not be operational until its status is changed to Active.
• Unassign button: To unassign a card, select a card from the list of cards and click on the Unassign
button.
• Add button: To add a new card, click on the Add button. Refer to “Adding a Card” on page 24 for
more information.
• Edit button: To edit a card, select a card from the list of cards and click on edit. Refer to “Adding a
Card” for more information.
Keypad Code
• Assign a Code: When selected, allows to assign a code to access a door that is configured to use
keypad codes.
• Code: The code must contain five digits and must be unique. Each digit can be any numerical value
from zero to nine.
• Confirm Code: Re-enter the code for confirmation.
18 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
System Login
Allows the user to login to the ATRIUM software and/or web server.
• Assign a Login: Select this check box to enable the access to the PC and/or ATRIUM’s Web server
for this user.
• Login ID: Enter a login name that will be used to access the PC and/or ATRIUM’s Web server. Up to
32 characters are allowed.
• Password: Enter the password that will be used to access the PC and/or WATRIUM’s Web server..
Up to 32 characters are allowed.
• Confirm Password: Re-enter the password for confirmation.
• Password Hint: Enter a password hint that will help you remember your password in case you
forget the password.
• Allow PC Software Access: When selected, gives access to the PC version of the ATRIUM
software.
• Allow Web Access: When selected, gives access to the Web server.
cdvigroup.com 19
INSTALLATION MANUAL
A10
ATRIUM Software
Access Levels
• Assign: Click on the Assign button and select the access level(s) to be assigned to the user. For
information, refer to “Access Levels” on page 38. If two or more access levels are assigned to a user,
access is granted as long as one of the defined access levels is valid when the card is presented.
• Unassign: Select an access level from the list and click on the Unassign button to revoke this
access level for the user.
• Add: Allows to define a new access level. Click on the Add button to add a new access level. Refer
to “Adding an Access Level” for more information.
• Edit: Allows to edit an access level. Refer to “Adding an Access Level” on page 38 for more
information.
20 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Work Tab
The Work tab allows to enter the user’s professional contact information.
Home Tab
The Home tab allows to enter the user’s personal contact information.
Events Tab
The Events tab lists, in real-time, the selected user’s related events. Refer to “Events” on page 57 for more
information.
cdvigroup.com 21
INSTALLATION MANUAL
A10
ATRIUM Software
Notes Tab
Use the Notes text field to record any additional notes that may be required. We recommend that you keep a
log of what settings were changed and when they were changed.
Save Button
Use the save button to save changes.
Cancel Button
Use the cancel button to ignore changes.
Modifying a User
Select a user from the list and click on the Edit button. See “Adding a User” for more information.
Deleting a User
Select the user from the list and click the Delete button. A dialogue box will appear requesting confirmation.
22 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Cards
Allows to define the details pertaining to the card. The card may be associated to a user directly from the Card
Properties window while defining the card or later from either the Card Properties or User Properties windows.
From the Dashboard tab, click on the Cards icon. From this page, cards may be added, edited, or deleted.
• MASTER Card: This card is active, no expiration date, 26-bit format, and is assigned to
USER MASTER.
• PROGRAMMING Card: This card is active, no expiration date, 26-bit format, has the Programming
Card option enabled, and is assigned to USER PROGRAMMING.
cdvigroup.com 23
INSTALLATION MANUAL
A10
ATRIUM Software
Adding a Card
The card may be added either using the Add button or the “Card Enrollment mode”.
Cards may also be added sequentially using either an access card followed by a programming
card or the on-board MODE button; refer to the AC22 2-Door Controller instruction manual for
more information. The access card must be assigned to a user having the option “Can Program
Cards” selected; refer to “User General Information” on page 16. The programming card must have
Programming Card enabled; see “Options Tab” on page 25.
From the Dashboard tab, click on Cards, and click on the Add button.
General Information
• Display Name: Identifies the card throughout the ATRIUM software. We recommend using a name
that is representative of the card.
• Active: When selected, indicates that the card is active.
• User: Allows to assign this card to a user. You can leave this field empty allowing you to assign this
card to a user in the “Users” menu.
• Activation Date: Allows to enter the date the card becomes valid. Enter the year, month, day and
time of the day the card becomes valid or click on the calendar icon and select the date. The card
will become active at selected activation date and time.
• Expiry Date: Allows to enter the date the card expires. This is useful for personnel on contract
which would require an access for a specific period of time. Enter either the year, month, day and
time of the day the card expires or click on the calendar icon and select the date and time. The card
will expires at selected date and time. For permanent cards, do not select an expiration date.
24 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Number
• Format: Choices are 26-bit, 30-bit, 44-bit, and Track 2.
• Number and Hex: The card number can be found printed directly on the card or written on a
cross-reference sheet. Depending on the Format selected, the card number may contain a family
number followed by the card number. The family number is always the first part of the number and
is usually followed by a colon (e.g. 123:45678). The card number is always the second part of the
number and is usually preceded by a colon (e.g. 123:45678). If you cannot locate the card number,
you can either use the Card Enrollment option (see “Card Enrollment” on page 26) or present the
card to any reader in the system and its family and card number will appear in the Instigator
column of the real-time Events window (refer to “Events” on page 57). When you have located the
correct family and card numbers, type the family number in the first field and the card number in
the second field. Alternatively, enter the card number in hexadecimal in the Hex field. Entering the
Card Number in decimal format will affect the Card Number (HEX) field and vice versa.
Options Tab
• Lost: When selected, the card status becomes lost.
• Stolen: When selected, the card status become stolen.
When the Lost and/or Stolen check box is selected, the card’s privileges are indefinitely revoked
without having to deactivate or remove the card from the database. As soon as you click Save, the
card can no longer be used until its option status is changed.
• Programming Card: When selected, allows to use this card to add cards sequentially through a
door reader; refer to the 2-Door Controller instruction manual for the card enrollment procedure
using the MASTER and PROGRAMMING cards. Each card added will be assigned to a new user that
will have the same access levels as the user assigned to the Programming Card.
Cards may be added using the “Card Enrollment mode”, see page 26.
Cards may also be added sequentially using the on-board MODE button; refer to the 2-Door Controller
instruction manual for more information.
Notes Tab
Use the Notes text field to record any additional notes that may be required. We recommend that you keep a
log of what settings were changed and when they were changed.
Save Button
Use the save button to save changes.
Cancel Button
Use the cancel button to ignore changes.
cdvigroup.com 25
INSTALLATION MANUAL
A10
ATRIUM Software
Modifying a Card
Select a card from the list and click on the Edit button. See “Adding a Card” on page 24 for more information.
Deleting a Card
To delete an existing card, select the card from the list and click on the Delete button. A dialogue box will
appear requesting confirmation.
Card Enrollment
This option allows to add one or multiples cards sequentially through the selected door reader.
To use the card enrollment feature:
1. Select the “Listen for New Cards on Reader” check box to enable this feature.
2. Select a card reader from the list.
3. Present, one by one, the new cards to be added to the system.
4. For each card presented, a card properties window pops up.
5. For each card, set its name and configure the other parameters as required. See “Adding a Card” on
page 24 for more information. Each added card has the following settings by default:
• Enabled
• Not assigned
• No expiry date
• Card number and format automatically set
6. Click on Save to complete the addition of the card.
The card enrollment mode ends when no new card is presented for 5 minutes or when the “Listen for
New Cards on Reader” check box is cleared.
26 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Holidays
Holidays define which days in a year are considered as exception. Holidays can be included or excluded from a
schedule (refer to “Holidays Tab” on page 33). The holiday is defined by selecting both the start date and time,
then the duration. The holiday can be configured to repeat every year. The holiday can be configured to be the
same day of the week based on the week the holiday occurs (for example, the first Monday of September).
From the Dashboard tab, click on the Holidays icon. From this page, holidays may be added, edited and
deleted.
• Christmas
cdvigroup.com 27
INSTALLATION MANUAL
A10
ATRIUM Software
Adding a Holiday
From the Dashboard tab, click on the Holiday icon and click on the Add button.
General Information
• Display Name: Identifies the holiday throughout the ATRIUM software. We recommend using a
name that is representative of the holiday.
• Active: When selected, activates the usage of the holiday.
• Date: Enter the date of the holiday (yyyy:mm:dd) or select the date using the calendar icon to the
right of the date field.
• Start Time: Enter the time the holiday starts (hh:mm).
• Length (dd:hh:mm): Enter the duration of the holiday (dd:hh:mm).
• Occurs Yearly: When selected, repeats the holiday every year.
• Use Relative Day: Enable “Use Relative Day” if the holiday occurs always the same day of the
week. Select the day of the week the holiday occurs. The date entered in the Date field will be used
to automatically adjust the holiday date based on which day the holiday occurs. For example if the
holiday occurs on the third Monday of May, the date will be adjusted to respect these criteria.
Notes Tab
Use the Notes text field to record any additional notes that may be required. We recommend that you keep a
log of what settings were changed and when they were changed.
Save Button
Use the save button to save changes.
Cancel Button
Use the cancel button to ignore changes.
28 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Modifying a Holiday
Select a holiday from the list and click on the Edit button. See “Adding a Holiday” on page 28 for more
information.
Deleting a Holiday
To delete an existing holiday, select the holiday from the list and click on the Delete button. A dialogue box will
appear requesting confirmation.
cdvigroup.com 29
INSTALLATION MANUAL
A10
ATRIUM Software
Schedules
A schedule can be used to unlock doors, control access to areas, and much more. Schedules play an important
role in the operation of many ATRIUM functions and are widely used throughout the software (see “Where
Schedules Can be Used” below). A schedule is made up of time periods which determine when that schedule
will be valid. Each period in a schedule specifies the days and times the schedule will be valid.
From the Dashboard tab, click on the Schedules icon. From this page, schedules may be added, edited, and
deleted.
By default several schedules are defined. The Never and Always schedules cannot be modified or deleted.
• Always: This schedule is valid 24 hours a day, 365 days per year including any programmed
holidays.
• Never: This schedule is invalid at all times.
The other pre-defined schedules are not described here. Use the Edit button to see the parameters of
each schedule and to adapt the schedule to your own needs if required.
30 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Adding a Schedule
From the Dashboard tab, click on the Schedules icon and then on the Add button.
General Information
• Display Name: Identifies the schedule throughout the ATRIUM software. We recommend using a
name that is representative of the schedule.
• Active: When selected, activates the schedule.
• Start Date: Enter an initiating date for this schedule (yyyy:mm:dd) or select a date using the
calendar icon next to the Start Date field. The schedule starts at the date specified.
• Cycle Length (days): The schedule is repeated after the number of days specified. The Schedule
tab displays up to 7 days at once. If the schedule is based on more than 7 days, use the right/left
scrolling arrows located at the top right of the window to access the other days.
cdvigroup.com 31
INSTALLATION MANUAL
A10
ATRIUM Software
Schedule Tab
The schedule tab allows to set the time period(s) per day.
32 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Holidays Tab
Allows to include or exclude holidays to/from the schedule. A schedule with an included holiday will remain
valid. A schedule with an excluded holiday will become invalid for the duration of the holiday.
• Assign: Select the holidays that should be included/excluded in/from the current schedule and click
on Assign.
• Unassign: Select the holiday that should be removed from the list of included/excluded and click
on Unassign.
The choice of including and excluding a specific holiday must be exclusive (not both).
• Add: Allows to define and add a new holiday. Click on the Add button to add a new holiday. Refer
to “Adding a Holiday” on page 28 for more information.
• Edit: Allows to edit a holiday. Select a holiday from the list and click on Edit. Refer to “Adding a
Holiday” on page 28 for more information.
cdvigroup.com 33
INSTALLATION MANUAL
A10
ATRIUM Software
Notes Tab
Use the Notes text field to record any additional notes that may be required. We recommend that you keep a
log of what settings were changed and when they were changed.
Save Button
Use the save button to save changes.
Modifying a Schedule
Select a schedule from the list and click on the Edit button. See “Adding a Schedule” on page 31 for more
information.
Deleting a Schedule
To delete an existing schedule, select the schedule from the list and click on the Delete button. A dialogue box
will appear requesting confirmation.
34 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Areas
Programming areas determines the different access rooms that will be controlled by the ATRIUM system. Once
defined, an area can be assigned to an access level which can be assigned to one or more users/card holders.
Area are an important concept in the ATRIUM system. Instead of giving access to doors, ATRIUM gives access
to areas. Thus, if a user has access to an area, it will be possible for him to access the area using any door that
directly gives access to that area. This avoids having to configure the access for each door individually for this
user.
The ATRIUM Access Control System differs from all Example of Areas
the other access control system on the market
today. The existing access control system
determines access levels based on a door to Door 3
door basis while ATRIUM determines access
levels based on areas delimited by doors. This
new method greatly simplifies the programming Cafeteria
Door 2
of the system. Since an area (room) can consist 02 - President’s
of many doors, with ATRIUM, you only need to Office
tell the system that a group of user has access
to this room (area) or not and not which door
of this room. In some installations, some rooms
Door 4
03 - Conference Room
can have 10 or more access points (doors).
With ATRIUM, as soon as you tell the system
that a group of user (access levels) have access
Door 1
to this room, all the door leading to this room 01- Reception & Hallway
are added. This is also a great innovation when
Door 5
07 - Accounting
this door to the access level. Adding a door thus
becomes very simple and very efficient. 05 - Shipping
Door 6
cdvigroup.com 35
INSTALLATION MANUAL
A10
ATRIUM Software
Adding an Area
From the Dashboard tab, click on the Areas tab and then click on the Add button.
General Information
• Display Name: Identifies the area throughout the ATRIUM software. We recommend using a name
that is representative of the area.
Events Tab
The Events tab lists in real-time the selected area events. Refer to “Events” on page 57 for more information.
Notes Tab
Use the Notes text field to record any additional notes that may be required. We recommend that you keep a
log of what settings were changed and when they were changed.
Save Button
Use the save button to save changes.
Cancel Button
Use the cancel button to ignore changes.
36 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Modifying an Area
Select an area from the list and click on the Edit button. See “Adding an Area” on page 36 for more information.
Deleting an Area
To delete an existing area, select the area from the list and click on the Delete button. A dialogue box will
appear requesting confirmation.
cdvigroup.com 37
INSTALLATION MANUAL
A10
ATRIUM Software
Access Levels
Access levels determine which areas in the building a user will have access to and during which schedules. This
is done by enabling the access level and then assigning a schedule to each area.
In order to define access levels, you must first create Areas and Schedules.
From the Dashboard tab, click on the Access Levels icon. From this page, access levels may be added, edited,
and deleted.
38 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
General Information
• Display Name: Identifies the access level throughout the ATRIUM software. We recommend using
a name that is representative of the access level.
• Active: When selected, activates the access level.
Areas Tab
Assign a schedule to each area to determine which areas (rooms) in the system a user, having this access level,
will have access to and during which periods.
Areas (page 35) and Schedules (page 30) must be defined first.
Notes Tab
Use the Notes text field to record any additional notes that may be required. We recommend that you keep a
log of what settings were changed and when they were changed.
Save Button
Use the save button to save changes.
Cancel Button
Use the cancel button to ignore changes.
cdvigroup.com 39
INSTALLATION MANUAL
A10
ATRIUM Software
Doors
The term door refers to any access point controlled by a reader and/or keypad such as a door, turnstile, gate,
cabinet, etc. To control entry and exit through an access point (door), a reader and/or keypad can be used on
both sides of the door.
The use of door contacts on all controlled doors is highly recommended since it greatly enhances the level of
security provided by an access control system. Many of the door’s programmable options can only be used if a
door contact is installed.
Each 2-Door controller (AC22) supports two readers and up to four 2-Door Expansion Modules (AX22), which
provide an additional 2 doors each. Therefore, each controller can monitor the state of up to 10 doors.
All doors of the ATRIUM access control system including the ATRIUM controller and all door expanders
are listed. To access doors per ATRIUM controller or door expander, refer to “System Overview” on
page 62.
From the Dashboard tab, click on the Doors icon. From this page, doors may be edited and manual control
may be applied.
40 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Status Indicates that the door has been opened for too long. This state
lasts until either the door is closed, returning its status to Closed,
Pre-Alarm
or the Open Too Long alarm expires, changing the door’s status to
In Alarm/Forced.
In Alarm/Forced Indicates that the door is forced open or was left opened too long.
Locked by Operator Indicates that the door has been manually locked by the operator.
Unlocked by Operator Indicates that the door is manually unlocked by the operator.
Unlocked for Access Indicates that the door is unlocked following a valid access event.
Access Disabled Access to the door has been manually de-activated by the operator.
Access Enabled Access to the door is allowed following its programmed parameters.
cdvigroup.com 41
INSTALLATION MANUAL
A10
ATRIUM Software
Modifying a Door
From the Dashboard tab, click on the Doors icon, select/highlight a door in the list and click the Edit button.
General Information
• Display Name: Identifies the door throughout the ATRIUM software. We recommend using a name
that is representative of the door.
• Active: When selected, activates the usage of this door.
Options
• Relocks on Door Open: Select the Relocks On Door Open check box to relock the door as soon
as it opens. When the check box is cleared, the system relocks the door when the unlock time has
elapsed (see Unlock Time).
• Relocks on Door Close: Select the Relocks On Door Close check box to relock the door as soon as
the door closes.
• Can be Left Open: Select the Can be Left Open check box to allow a door to stay open without
generating a door open too long alarm.
42 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Schedule
• Unlock Schedule: Select the schedule during which the door will automatically unlock. For
example, you may want a door to remain unlocked from 9 a.m. to 5 p.m. Monday to Friday. To do
so, create the appropriate schedule and select it from the Unlock Schedule drop-down list. Refer to
“Schedules” on page 30 for more information.
• Unlocks on First Access/First Man In: Select the Unlocks on First Access/First Man In check box
to prevent the door from unlocking automatically until the first user with valid access presents his
card at the door.
Timing
• Unlock Time (seconds): Enter a value between 1 and 254 seconds (Default: 5 seconds).
Represents the amount of time the door will remain unlocked when an access granted or unlock
event is generated at the door.
• Extended Time (seconds): When a user is granted access, the controller will unlock the door
for the period defined by the Unlock Time. However, if the user has been programmed with the
extended time allowed (see Allow Extended Time on page 16), the controller will unlock the door for
the duration of the Unlock Time in addition to the value programmed in the Extended Time. In the
Extended access text field, type a value between 1 and 254 seconds (Default: 15 seconds). This
option is particularly useful for individuals that may require more time to access the door.
• Open Too long Pre-Alarm (seconds): Before generating an Open too long event, the controller
can be programmed to generate a pre-alarm as a warning of the upcoming alarm. Enter a value
between 1 and 254 seconds (Default: 45 seconds) that represents the amount of time a door can
remain open after an access granted or door unlock event before generating a door left open event.
• Open Too Long Alarm (seconds): Enter a value between 1 and 254 seconds (Default: 15
seconds) that added with the Open Too Long Pre-Alarm value represents the amount of time a door
can remain open after an Access Granted or Door Unlock event before generating a Door Open Too
Long event (see example on page 44).
cdvigroup.com 43
INSTALLATION MANUAL
A10
ATRIUM Software
Example of open too long pre-alarm and open too long alarm
Open Too Long Pre-Alarm Time Open Too Long Alarm Time
(45 seconds) (15 seconds)
Area
Select the area from the list for each side of the door. Leave the field empty if the side of the door is
outside the building.
REX
If there is a REX associated with this side of the door, select the REX from the list, otherwise leave
the field empty.
Reader
If there is a reader associated with this side of the door, select the door from the list, otherwise
leave the field empty.
Contact Input
Select the door’s contact from the list.
Lock
Select the door’s lock from the list.
44 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Unlock Options
• Card: When selected, allows to use a card to access this door. Used when a reader is installed at
the door
• ... and PIN: When selected, specifies that the user, after presenting his card, has to enter a PIN
(Personal Identification Number) on the door keypad to access this door. Refer to “Keypad Code” on
page 18 for more information. Used when both a reader and a keypad are installed for this door.
• Keypad Code: When selected, allows to use a PIN (Personal Identification Number) to access this
door. Refer to “Keypad Code” on page 18 for more information. Used when a keypad is installed.
• REX: When selected, unlocks the door when the controller receives a valid Request for Exit (the
door must be closed and locked when the option “... even if Door Open” is not selected).
• ... even if Door Open: When selected, unlocks the door regardless of its current status (i.e. Door
forced, Door open too long, etc.) when receiving a valid request for exit (REX).
• REX Schedule: Allows to select the schedule that will specify when the REX can be used.
Events Tab
The Events tab lists in real-time the events associated to this door. Refer to Events on page 57 for more
information.
Notes Tab
Use the Notes text field to record any additional notes that may be required. We recommend that you keep a
log of what settings were changed and when they were changed.
Save Button
Use the save button to save changes.
Cancel Button
Use the cancel button to ignore changes.
cdvigroup.com 45
INSTALLATION MANUAL
A10
ATRIUM Software
The following buttons allow to manually change the state of a door. These changes override the
normal scheduled state. To cancel the override command, click on the Reset button.
Reset
Cancels the operator’s override door control,
returning the door to its current scheduled
state.
Lock
Manually locks the selected door if it was
unlocked either on schedule, manually or by
an operator.
Unlock
Manually unlocks the selected door, overriding its scheduled state. The door will remain unlocked permanently.
Use the reset button to enable schedule settings.
Grant Access
Manually unlocks the selected door temporarily for the period specified by the door’s Unlock Time.
Disable Access
Manually revokes the access to this door by
disabling its readers and REX devices.
Enable Access
Manually returns the door to its programmed
parameters.
46 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Relays
Typically, relays are used to activate alarm sounders or other devices such as lighting control units and air
conditioners. Relays are controlled using macros. For example, a relay can be activated by a macro when the
trigger event occurs whithin the schedule (refer to “Macros” on page 77).
From the Dashboard tab, click on the Relays icon. From this page, relays may be edited, manual control may
be applied and live status may be displayed.
Relays are only used with macros, refer to “Macros” on page 77 for more information.
Modifying a Relay
From the Dashboard tab, click on Relays icon, select a relay from the list and click on the Edit button.
General Information
• Display Name: Identifies the relay throughout the ATRIUM software. We recommend using a name
that is representative of the usage of this relay.
• Active: When selected, enables the usage of this relay.
• Reversed Logic: When selected, reverses the logic from either normally closed (N.C.) to normally
open (N.O.) or vice-versa. Refer to Jumper Settings from the module instruction manual for more
information on N.C. and N.O.
cdvigroup.com 47
INSTALLATION MANUAL
A10
ATRIUM Software
Notes Tab
Use the Notes text field to record any additional notes that may be required. We recommend that you keep a
log of what settings were changed and when they were changed.
Save Button
Use the save button to save changes.
Cancel Button
Use the cancel button to ignore changes.
Legend
Indicates that either the module is not synchronized or the module has an older
Unknown
firmware version that is not compatible with the ATRIUM software.
Reset
Cancels the operator’s override relay control, returning the relay to its current scheduled or event state.
Activate
Manually activates the relay, overriding its current scheduled or event state.
48 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
inputs
Typically, the inputs are used to monitor the status of door contacts and request for exit devices installed on the
controlled door. Inputs can activate relays reader outputs or the bell outputs through the use of macros.
Each controller includes ten inputs which can be connected using zone doubling technology to monitor up to 20
input devices.
All inputs of the ATRIUM access control system including the ATRIUM controller and all door expanders
are listed. To access Inputs per ATRIUM controller or door expander, refer to “System Overview” on
page 62.
From the Dashboard tab, click on the Inputs tab. From this page, inputs may be edited and live status may be
displayed.
cdvigroup.com 49
INSTALLATION MANUAL
A10
ATRIUM Software
Modifying an Input
From the Dashboard tab, click on the Inputs icon, select an input from the list and click on the Edit button.
General Information
• Connection Method: Select the input connection method:
50 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
When using this method, only one device can be connected to the
input. The input must be connected using only one Contact (NO or
NC: programmable per INPUT) as described in Figure 1. This setup
will not support WIRE CUT or WIRE SHORT supervision, but will
generate an alarm condition when the state of the input is breached. Input 1
Figure 2
INPUTS
Single with WIRE SHORT Supervision
12V Z1 GND Z2 Z3 GND Z4 Z5
When using this method, only one device can be connected to the 1K
Figure 3
INPUTS
WIRE SHORT supervision: YES (Detected as INPUT SHORT)
12V Z1 GND Z2 Z3 GND Z4 Z5
WIRE CUT supervision: NO
Input 1
1K
cdvigroup.com 51
INSTALLATION MANUAL
A10
ATRIUM Software
When using this method, only one device can be connected to 12V Z1 GND Z2 Z3 GND Z4 Z5
EOL
the input. The input must be connected using only one Contact
(NO or NC: programmable per INPUT) as described in Figure 1K
5. This setup will support both WIRE CUT and WIRE SHORT Input 1
supervision and will generate an alarm condition when the
state of the input is breached.
1K Tamper Input 1
WIRE SHORT supervision: YES (Detected as INPUT SHORT)
WIRE CUT supervision: YES (Detected as INPUT CUT)
52 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Input Tab
(A second input tab will appear when using any of the zone doubling connection methods)
Options
• Display Name: Identifies the input throughout the ATRIUM software. We recommend using a name
that is representative of the input.
• Active: When selected, activates the input.
• Reversed Logic: When selected, reverses the logic from either normally closed (N.C.) to normally
open (N.O.) or N.O. to N.C. Typically normally open is used for devices (inputs) that close upon
activation such as smoke detectors and water level sensors. Typically normally closed is used for
devices (inputs) that open upon activation such as door contacts and request for exit detectors.
• Input Response Time (ms): This delay defines how quickly the controller will respond to the
trigger of an opening input. This prevents any momentary glitch from causing unnecessary alarms.
If the input remains triggered for the defined time delay, the controller will react according to its
programming. The default value is 100ms. Type a value from 0 to 3 600 000 ms (1 hour).
• Input Restore Time (ms): This delay defines how quickly the controller will respond to the trigger
of a closing input. This prevents any momentary glitch from causing unnecessary zone closure. If
the input remains closed for the defined time delay, the controller will consider the inputs as being
closed. The default value is 100ms. Type a value from 0 to 3 600 000 ms (1 hour).
Notes Tab
Use the Notes text field to record any additional notes that may be required. We recommend that
you keep a log of what settings were changed and when they were changed.
Save Button
Use the save button to save changes.
Cancel Button
Use the cancel button to ignore changes.
cdvigroup.com 53
INSTALLATION MANUAL
A10
ATRIUM Software
Legend
Trouble Indicates that the state of the input is WIRE CUT or WIRE SHORT.
Indicates that either the module is not synchronized or the module has an
Unknown
older firmware version that is not compatible with the ATRIUM application.
54 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Outputs
By default, the outputs (six per AC22 and AX22) are used to control the built-in LEDs and buzzers of card
readers and keypads. For example, a red/green indicator on the reader will inform the user that access has
been granted (changes from red to green), or the reader buzzer will inform the card user that the door has
been left open or the door has been forced open.
Each controller includes six multi-function outputs. Each controller also supports up to four 2-Door Expansion
Modules, which provide an additional 6 outputs each.
All outputs of the ATRIUM access control system, including the ATRIUM controller and all door
expanders, are listed. To access outputs per ATRIUM controller or door expander, refer to “System
Overview”.
From the dashboard tab, click on Outputs. From this page, outputs may be edited, and manual control may
be applied.
cdvigroup.com 55
INSTALLATION MANUAL
A10
ATRIUM Software
Modifying an Output
From the Dashboard tab, click on the Outputs icon, select an output from the list and click on the Edit button.
General Information
• Display Name: Identifies the input throughout the ATRIUM software. We recommend using a name
that is representative of the output.
• Active: When selected, activates the usage of the output.
• Reversed Logic: When selected, reverses the logic from either either normally closed (N.C.) to
normally open (N.O.) or N.O. to N.C.
Notes Tab
Use the Notes text field to record any additional notes that may be required. We recommend that you keep a
log of what settings were changed and when they were changed.
Save Button
Use the save button to save changes.
Cancel Button
Use the cancel button to ignore changes.
Reset
Cancel the override output control, returning the output to its current scheduled or event state.
Activate
Manually activates the output overriding the activation delay.
56 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Events
Reports each event that occurs in the system in real-time. A specific event can be programmed to perform an
action using the macros; refer to “Macros” on page 77.
The Events window lists in real-time the events or device status of the ATRIUM system.
From the Dashboard tab, click on the Events tab. From this page, it is possible to view the event’s details.
By default all events/status are displayed in real-time. Use the following toggle buttons to select/remove
specific events to be displayed.
• Access button; see 59 for more information.
• Security, button; see page 59 for more information.
• Alarms button; see page 59 for more information.
• Troubles button; see page 59 for more information.
• Others button; see page 59 for more information.
cdvigroup.com 57
INSTALLATION MANUAL
A10
ATRIUM Software
Object
Indicates the provenance of the event.
• Type: Indicates the type of device or component.
• Display Name: Indicates the name of the device or component.
• Module: Indicates which module contains the device or object.
• ID: Indicates which object the event applies to.
Event
Indicates the description of the event.
Sequence Number indicates a sequential number given to each event.
Instigator
Indicates the instigator of the event
• Type: Indicates the type of instigator.
• Display Name: Indicates the name of the instigator.
• Module: Indicates which module contains the device or object.
• ID: Indicates which object the event applies to.
58 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Access
Displays access-related events when this check box is selected.
Security
Displays security-related events when this check box is selected.
Alarms
Displays alarm-related events when this check box is selected.
Troubles
Displays trouble-related events when this check box is selected.
Others
Displays all other events when this check box is selected.
cdvigroup.com 59
INSTALLATION MANUAL
A10
ATRIUM Software
Reports
Generate reports for a specific period of time, user, door and/or area. Reports can also be printed and saved.
From the Dashboard tab, click on the Reports tab. From this page reports may be generated, viewed, printed
and saved.
Generating a Report
Parameters
Select the parameter criteria that will be used to generate the report.
• Start Time and End Time: Select the period for the report by entering the start and end date and
time using the “yyyy:mm:dd hh:mm” format or select the date and time.
• User: Select a specific user from the list or leave the field empty to include all users.
• Door: Select a specific door from the list or leave the field empty to include all doors.
• Area: Select a specific area from the list of leave the field empty to include all areas.
• Maximum Number of Results: Enter the maximum events allowed in the report. The default
setting is 1000 events.
Search
Generates the report based on the selected parameters and displays its content in the Results section.
60 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Results
Displays the generated report and allows navigating through the report, printing and saving the report results.
cdvigroup.com 61
INSTALLATION MANUAL
A10
ATRIUM Software
System Overview
The system overview displays and allows management of all ATRIUM modules within the access control system.
From the system overview it is possible to see and control the inputs, outputs, readers, doors, areas, door
locks, relays, bell and tamper switches. It also display system logs for each ATRIUM modules.
All ATRIUM controller(s) and expander(s) in the system are listed and are identified as follows:
• AC22 2-Door Controller: When selecteded, controller information is displayed like the following;
controller name, product code, serial number, MAC Address, IP Address and Firmware Version.
• AX22 2-Door Expander: When selecteded, expander information is displayed like the following;
expander name, product code, serial number and Firmware Version.
Under each controller and expander, the following information is available. Summary, status and control are
available for each device or setting.
62 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
General Information
Allows to change the display name. All other information are read only.
• Display Name: Identifies the controller/expander throughout the ATRIUM software. We
recommend using a name that is representative of the controller/expander module.
• Product Code: Indicates the module product code; AC22 for the ATRIUM 2-Door Controller, AX22
for the ATRIUM 2-Door Expander, etc.
• Serial Number: Indicates the serial number for the controller/expander module.
• Firmware Version: Indicates the current version of the module’s firmware.
cdvigroup.com 63
INSTALLATION MANUAL
A10
ATRIUM Software
• Detection Delay (seconds): Change the detection delay if required. The default setting is 300
seconds (5 minutes).
64 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
General Information
• Time Zone: Select the time zone reference based on the UTC time and offset.
cdvigroup.com 65
INSTALLATION MANUAL
A10
ATRIUM Software
Advanced Options
Monitoring
Displays the monitored system’s voltage and current values.
Primary Power
• Fail Delay (minutes): Value between 0 and 65534 minutes that represents the amount of time
before sending power failure event message.
• Restore Delay (minutes): Value between 0 and 65534 minutes that represents the amount of time
before sending power restore event message.
66 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Battery
• Options
- Current: Select the maximum current that will be used to charge the battery; 250mA (Default),
320mA, 500mA or 1A.
Deleting a Module
To delete a module, select the module from the list and click on the Delete button. Deleting a controller
automatically deletes the controller itself as well as all attached expander modules. However, the distributed
entities (users, cards, schedules, etc.) are not deleted. A dialogue box will appear requesting confirmation.
Replace
Replaces a defective and offline module that has been physically replaced. Only available for offline modules.
To replace the module:
The configuration from the old module will be transferred to the new module, including the non-distributed
entities (inputs, outputs, areas, tamper switches, etc.).
cdvigroup.com 67
INSTALLATION MANUAL
A10
ATRIUM Software
Upload Firmware
Upgrades the selected controller or expander module with a new firmware.
Locate
Allows to find a module when the serial number of the module has been removed or is not legible.
To locate a module:
1. Select the module to locate.
2. Click on the Locate button.
3. Open the door of each module’s metal box, the corresponding module’s GLOBAL -STAT LED will be
flashing rapidly. Refer to the module instruction manual for more information.
4. Click on Stop Localization to exit the locate mode.
Stop Localization
Stops the module localization. Refer to “Locate” for more information.
Reboot
Reboots the selected controller or expander module.
• Select the controller or expander module to be rebooted.
• Click on Reboot.
• Click Yes to confirm.
68 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Door Lock
Typically, the door locks are used to control the door lock devices such as door strike and electromagnetic devices.
Each controller includes two door locks and supports up to four 2-Door Expansion Modules (AX22) which
provide an additional 2 door locks each. Therefore, each controller can monitor the state of up to 10 door locks.
General Information
• Display Name: Identifies the door lock throughout the ATRIUM software. We recommend using a
name that is representative of the door lock output.
• Active: When selected, activates the usage of this door lock.
• Reversed Logic: When selected, reverses the logic from either normally closed (N.C.) to normally
open (N.O.) or vice-versa. Refer to Jumper Settings from the module instruction manual for more
information on N.C. and N.O.
Notes Tab
Use the Notes text field to record any additional notes that may be required. We recommend that you
keep a log of what settings were changed and when they were changed.
cdvigroup.com 69
INSTALLATION MANUAL
A10
ATRIUM Software
Advanced Options
Monitoring
• Refresh button: Refreshes the voltage and current values.
- Voltage (V): Indicates the voltage supplied to the door lock device.
- Current (A): Indicates the current used by the connected lock device.
Legend
Trouble Indicates that the state of the door lock supply is short circuited or overloaded.
Indicates that either the module is not synchronized or the module has an older
Unknown
firmware version that is not compatible with the ATRIUM application.
Save Button
Use the save button to save changes.
Cancel Button
Use the cancel button to ignore changes.
70 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Bells
The ATRIUM controller provides one bell output that can be used to drive one or several bells connected in
parallel. Refer to the AC22 2-Door Controller instruction manual for more information.
From the Hardware tab, click on the Bells icon.
Legend
Indicates that the state of the bell is either missing (absent), short circuited
Trouble
or overloaded
Indicates that either the module is not synchronized or the module has an
Unknown
older firmware version that is not compatible with the ATRIUM application.
cdvigroup.com 71
INSTALLATION MANUAL
A10
ATRIUM Software
General Information
• Display Name: Identifies the bell/siren throughout the ATRIUM software. We recommend using a
name that is representative of the bell/siren.
• Active: When selected, activates the usage of the bell/siren.
• Cutoff Delay (minutes): Type a value between 0 and 1000 minutes (Default: 4 minutes) that
represents the amount of time the controller will maintain the bell active.
Notes Tab
Use the Notes text field to record any additional notes that may be required. We recommend that you
keep a log of what settings were changed and when they were changed.
72 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Save Button
Use the save button to save changes.
Cancel Button
Use the cancel button to ignore changes.
Reset
Cancel the override bell control, returning the bell to its current scheduled or event state.
Activate
Manually activates the bell overriding the activation delay.
cdvigroup.com 73
INSTALLATION MANUAL
A10
ATRIUM Software
Tamper switches
Tamper switches detect when the cabinet door is opened or when the cabinet is removed from the wall.
Each AC22 controller and AX22 expander may have 2 tamper switches per cabinet, a wall and a door tamper
switch.
However, even when both are installed, only one tamper instance is monitored by the ATRIUM software per
module box since they are connected in series.
From the Hardware tab, click on the Tamper Switches icon.
General Information
• Display Name: Identifies the tamper switch throughout the ATRIUM software. We recommend
using a name that is representative of the tamper switch.
• Active: When selected, activates the usage of this tamper switch.
Notes Tab
Use the Notes text field to record any additional notes that may be required. We recommend that you
keep a log of what settings were changed and when they were changed.
Save Button
Use the save button to save changes.
Cancel Button
Use the cancel button to ignore changes.
74 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Readers
Readers such as keypad and proximity readers are used to request access to an area via a door.
Each controller includes two readers and supports up to four 2-Door Expansion Modules (AX22) which provide
two readers each. Therefore, each controller can monitor the state of up to 10 readers.
cdvigroup.com 75
INSTALLATION MANUAL
A10
ATRIUM Software
Modifying a Reader
From the Hardware tab, click on the Readers icon, select a reader from the list and click on the Edit button.
General Information
• Display Name: Identifies the reader throughout the ATRIUM software. We recommend using a
name that is representative of the reader.
• Active: When selected, activates the usage of this reader.
• Lighting Color: Identifies if the reader has a 2 or 3-color LED. Choices are Generic (Red & Green)
and CDVI (Red, Green & Blue).
• Red LED Output: If there is a red LED associated to the door reader, select the red LED’s output
name, otherwise, leave it unassigned.
• Green LED Output: If there is a green LED associated to the door reader, select the green LED’s
output name, otherwise, leave it unassigned.
• Buzzer Output: If there is a buzzer associated to the door reader, select buzzer’s output name,
otherwise, leave it unassigned.
Notes Tab
Use the Notes text field to record any additional notes that may be required. We recommend that you
keep a log of what settings were changed and when they were changed.
Save Button
Use the save button to save changes.
Cancel Button
Use the cancel button to ignore changes.
76 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Macros
Macros are used to cause an action on a device when triggering on an event. The macro instructs a device to
perform a specific actions like Activate Relay, Lock Door (Latched), etc.
The ATRIUM application allows the creation of a macro by selecting the trigger event and the resulting
command. Up to 100 macros can be created.
All macros of the ATRIUM access control system are saved on the AC22 2-Door Controller module.
Adding a Macro
From the Advanced Configuration tab, click on the Macros icon, and click on the Add button.
General Information
• Display Name: Identifies the macro throughout the ATRIUM software. We recommend using a
name that is representative of the macro.
• Active: When selected, activates the usage of this macro.
• Schedule: Select the schedule which will define when the macro can be used.
cdvigroup.com 77
INSTALLATION MANUAL
A10
ATRIUM Software
Trigger Event
Select the device type, the event and the entity that will be used as the trigger event. The entities are listed
with the format “Module Serial #: Display Name”.
Type Event
Areas Access to Areas Granted, Access to Area Denied, User Entered Area, User Exited Area
Low Battery, Battery Absent, Low Battery Restored, Battery Absent Trouble Restored, Added,
Batteries Edited, Deleted, Programming Initialized, Programming Reset
Bell Deactivates, Bell Activated, Bell Trouble, Bell Trouble Restored, Bell Shorted, Bell Absent,
Bells Bell Short Circuit Restored, Bell Detected, Added, Edited, Deleted, Programming Initialized,
Programming Reset
Door Unlocked, Door Locked, Door Opened, Door Closed, Door in Pre-Alarm, Door in Alarm,
Door Forced, Door in Trouble, Door Restored After Trouble, Door Restored After Alarm, Door
Doors Restored After Pre-Alarm, Door Restored After Being Forced, Access to Door Was Enabled,
Access to Door Was Disabled, User has Entered the System Through Door, User has Exited the
System Through Door
Door Lock Activated, Door Lock Deactivated, Door Lock Power Trouble, Door Lock Power
Door Locks Restored, Door Lock Restored by Emergency Input, Door lock Bypassed by Emergency Input,
Added, Edited, Deleted, Programming Initialized, Programming Reset
Input Opened, Input Closed, Added, Edited, Deleted, Programming Initialized, Programming
Inputs Reset
Primary Power Trouble, Primary Power Trouble Restored, Primary Power Failure, Primary
Primary Power Power Failure Restored, Added, Edited, Deleted, Programming Initialized, Programming Reset
Readers Card Read, Added, Edited, Deleted, Programming Initialized, Programming Reset
Relay Deactivated, Relay Activated, Relay Pulse Mode Activated, Added, Edited, Deleted,
Relays Programming Initialized, Programming Reset
Smart Supply Smart Supply Output Trouble, Smart Supply Output Trouble Restored, Added, Edited, Deleted,
Outputs Programming Initialized, Programming Reset
78 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Resulting Command
Select the device type and the command then select the entity on which the command will be applied. The
entities are listed with the format “Module Serial #: Display Name”.
Type Event
Bells Reset Bell, Activate Bell
Doors Unlock Door (Latched), Lock Door (Latched), Enable Access, Disable Access, Reset Door
Notes Tab
Use the Notes text field to record any additional notes that may be required. We recommend that you
keep a log of what settings were changed and when they were changed.
Save Button
Use the save button to save changes.
Cancel Button
Use the cancel button to ignore changes.
Modifying a Macro
Select a macro from the list and click on the Edit button. See “Adding a Macro” on page 77 for more information.
Deleting a Macro
Select the macro from the list and click on the Delete button. A dialogue box will appear requesting
confirmation.
cdvigroup.com 79
INSTALLATION MANUAL
A10
ATRIUM Software
Accounts
Accounts are used when a computer connects to different ATRIUM installations. Each account has two database
files; one for the configuration settings and one to store the system’s events. Typically, an installer creates a
separate account for each client site he may have.
Each account has two dedicated database files; one for the static entities (users, cards, schedules, input,
outputs, areas, tamper switches, etc.) and one for the events.
From the Advanced Configuration tab, click on the Accounts icon, and click on the Add button.
Adding an Account
From the Advanced Configuration tab, click on the Accounts icon, and click on the Add button.
• Account: Identifies the account throughout the ATRIUM software. We recommend using a name
that is representative of the account.
Deleting an Account
To delete an existing account, select the account from the list and click on the Delete button. A dialogue
box will appear requesting confirmation. Deleting an account will erase the two database files related to this
account. The Default account cannot be deleted.
80 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
Backup
Allows to backup the ATRIUM databases (entities and/or events) for the selected account.
From the Advanced Configuration tab, click on the Accounts icon, select an account from the list, and click
on the Backup button.
To back up the database(s), select the database(s) that must be saved and select the path (if required). By
default, both databases (configuration and events) for the selected account will be saved to the default path.
Click on OK to back up the configuration on the selected drive.
Restore
Allows to restore the ATRIUM databases (entities and/or events) for the selected account from a backup.
From the Advanced Configuration tab, click on the Accounts icon, select an account from the list, and click
on the Restore button.
To restore the database(s), select the database(s) that must be restored and select the path (if required). By
default both databases (configuration and events) for the selected account will be restored from the default
path. Click on OK to transfer the databases to the controller module and sub-module(s).
Change Password
Allows changing the password of the selected account. Type the new password in the Password and Confirm
Password fields. Enter a Password Hint to easily remember the password if lost.
cdvigroup.com 81
INSTALLATION MANUAL
A10
ATRIUM Software
The “limited lifetime warranty” is offered by CDVI exclusively for CDVI products featuring the logo “limited
lifetime warranty”, and supplied by authorized CDVI dealers participating in the offer. You can obtain the
address of the local authorized dealer participating in the offer by contacting CDVI or a local CDVI subsidiary.
The “limited lifetime warranty” is only applicable to hidden defects detected during the lifetime of the product,
as defined by the CDVI Group (10 years or 200 000 operations - whichever of the two expires first).
The “limited lifetime warranty” conditions shall not modify the sales conditions between CDVI and its customers.
CONDITIONS :
• Hidden defects are guaranteed for an unlimited shelf life (period of time before use).
• To be eligible for the “limited lifetime warranty”, the product must be registered at CDVI within
one month of its delivery to the end user, by completing and returning the “warranty” form by fax,
email or post to the local CDVI subsidiary. This information may also be registered on line at www.
cdvigroup.com.
• Only the issue of the “limited lifetime warranty” certificate by CDVI can confirm product
registration; CDVI may not be held responsible in the event of loss or non presentationof the form.
• The “limited lifetime warranty” only applies to products installed by a skilled and experienced
personal with the necessary trade qualifications to install according to the highest standards,
respecting the standards, instructions and guidelines defined by CDVI and according to the
maximum recommended specifications.
• To enable CDVI to determine whether a product is eligible to claim for the “limited lifetime
warranty”, after prior issue of a return of materials authorization number (RMA) by CDVI, the
customer must return the product and all of its accessories in the original packaging with a copy of
its invoice. The transport fees shall be paid by the customer and the package must be returned to
CDVI or to a CDVI authorized repair centre.
• Eligibility for the “limited lifetime warranty” cover must be confirmed by CDVI.
• The “limited lifetime warranty” only covers the replacement or repair of the parts acknowledged as
faulty by CDVI.
• CDVI reserves the right to respect its obligation by replacing the product or the parts acknowledged
as faulty by a standard part replacement or by a product or new parts, or by an updated or
improved version of the product with identical or similar functionalities.
• In respect of the applicable law, CDVI cannot be held responsible for material or immaterial
damages caused to goods or to third parties and as a direct or indirect result of the installation,
utilization, product faults or poor functioning of a device.
• The “limited lifetime warranty” is non-assignable and non-transferrable; only the person who
registered the aforementioned warranty may benefit from the warranty.
• The “limited lifetime warranty” is limited to the eligible product and is strictly limited to the
conditions in effect on the date of purchase by the customer.
82 cdvigroup.com
INSTALLATION MANUAL
A10
ATRIUM Software
NOTES:
cdvigroup.com 83
Reference : G0301FR0413V01
Extranet : EXE-CDVI_OH A10 CMYK A4 EN 01
*G0301FR0413V01*
Toutes les informations mentionnées à titre indicatif sur le présent document (photos, dessins, caractéristiques
All the information contained within this document (photos, drawing, features, specifications and dimensions)
techniques et dimensions) peuvent varier et sont susceptibles de modifications sans notification préalable.
could be perceptibly different and can be changed without prior notice.