ATS Controller Model 5560 Overview

The document describes the Model 5560 Automatic Transfer Switch and Mains Controller. It monitors utility power and automatically starts backup generators when utility power fails. It allows precise load sharing control of multiple generators and synchronizes them with returning utility power for seamless transfer back. The controller provides instrumentation displays and configurable inputs/outputs to meet complex specifications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
232 views2 pages

ATS Controller Model 5560 Overview

The document describes the Model 5560 Automatic Transfer Switch and Mains Controller. It monitors utility power and automatically starts backup generators when utility power fails. It allows precise load sharing control of multiple generators and synchronizes them with returning utility power for seamless transfer back. The controller provides instrumentation displays and configurable inputs/outputs to meet complex specifications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

5560

DEEP SEA ELECTRONICS ATS / MAINS


CONTROLLER

FEATURES DESCRIPTION Issue 1


AM 14/06/05
Automatically senses mains (utility) The Model 5560 is an Automatic
failure and starts the backup
Transfer switch and Mains
generators (controlled by DSE model
5510 controllers). controller with comprehensive
instrumentation and load control
Allows precise changes to be made features.
to the generator bus/mains supply
load share (import/export control) The module is used to monitor a mains
Can maintain a specific mains supply and automatically start and
(utility) or generator power factor. stop the system’s generating sets
(controlled by DSE 5510 load sharing
ATS and Peak lopping control for controllers). It indicates the
5510 controlled generator bus
operational status by means of an
Will synchronise multiple 5510 LCD display, and LEDs on the front SPECIFICATION
controlled gensets with the returning panel. DC Supply:
mains (utility) supply to provide no- 8V to 35V Continuous.
break changeover back to the mains The system is used to ‘manage’ the Able to survive 0V for 50mS, providing
supply. generator bus, which is fed by DSE supply was at least 10V before dropout
‘Soft transfer’ (load ramping) both to 5510 load sharing controllers. and supply recovers to 5V. This is
and from the generator supply. achieved without the need for internal
batteries.
The 5560 instructs the 5510
Can be used to load test the
synchronised generator bus without
controllers to make precise changes to Max. Operating Current:
removing power from the load. the generating set outputs which can 460mA at 12V. 245mA at 24V.
be used in many applications
Clear, backlit LCD display to show Max. Standby Current:
including: 375mA at 12V. 200mA at 24V.
the status of the load switches, and • Peak lopping. The generating sets
mains (utility) supply as well as to Generator bus Input Range:
are used to ensure the mains load
annunciate alarm conditions should 15V(L-N) to 277V(L-N) AC (+20%)
they occur. is kept below a specific,
configurable level. Generator bus Input Frequency:
Integral, configurable starting and • No-break return to mains supply. 50Hz - 60Hz at rated engine speed
stopping timers. The generator bus is voltage (Minimum: 15V AC L-N)
Configurable inputs and outputs to matched and synchronised with
Mains Sensing Input Range:
help meet complex specifications. the returned mains supply to allow 15V(L-N) to 277V(L-N) AC (+20%)
transfer back to mains with no
Integral log for viewing event history. break in supply to the load. Mains Sensing Input Frequency:
50Hz - 60Hz (Minimum: 15V AC L-N)
INSTRUMENTATION Selected operational sequences, Auxiliary Relay Outputs:
The 5560 module provides the following
timers and alarms can be altered by 5A DC at supply voltage.
instrumentation LCD displays, accessed the customer. Alterations to the
system are made using the 810 Generator bus loading Relay Output:
via the LCD PAGE and DISPLAY 8A AC 250V – normally open.
SCROLL push buttons: interface and a PC. This interface
also provides real time diagnostic Mains loading Relay Output:
Bus Volts (L1-N, L2-N, L3-N) facilities. 8A AC 250V – normally closed.
Bus Volts (L1-L2, L2-L3, L3-L1)
Bus Hz Operation of the module is via Mains (utility) C.T. Burden:
Bus kW 0.5VA
pushbutton controls (with security
Bus kVAr locking facility) mounted on the front Operating Temperature Range:
Bus phase sequence panel with STOP/RESET, AUTO, -30°C to +70°C
Mains Volts (L1-N, L2-N, L3-N)
Mains Volts (L1-L2, L2-L3, L3-L1)
TEST, MANUAL and START
Dimensions:
Mains Hz functions. The first four pushbuttons 240mm x 172mm x 57mm
Mains Amps feature LED ‘selected’ indications. (9.45” x 6.77” x 2¼”)
Mains kW Further pushbuttons provide Panel cutout:
Mains kVA MUTE/LAMP TEST, LCD PAGE, 220mm x 160mm (8.7” x 6.3”)
Mains pf DISPLAY SCROLL and LOAD
Mains kVAr SWITCHING control functions. The 5000 series modules have been
Mains kWh designed for front panel mounting. The
Mains kVAh The module features 32-Bit module is fitted into the cutout with the fixing
Mains kVArh Microprocessor control and a clips removed. These are then fitted from
Mains phase sequence comprehensive list of timers and pre- the rear. Connection is via locking plug and
Synchroscope socket connectors.
configured sequences. User
configurable expansion facilities are Deep Sea Electronics reserve the right to change
specification without prior notice.
also provided.
CASE DIMENSIONS

Panel cut-out 220mm x 160mm (8.7” x 6.3”)


TYPICAL W IRING
DIAGRAM

Deep Sea Electronics Plc. Deep Sea Electronics Inc.


Highfield House, Hunmanby Industrial Estate, 3230 Williams Avenue
North Yorkshire. YO14 0PH. ENGLAND Rockford, Illinois 61101-2668, U.S.A