EF TD Transformer differential protection
INGEPAC™ EF TD is a range of Intelligent Electronic Devices that provide all the protection and
control functionalities required for two and three winding power transformers. It also provides
instantaneous and biased differential protection, with harmonics blocking, as well as low
impedance restricted earth fault.
Its design is compliant with all the requirements of standards in the electrical sector, including
IEC 61850. INGEPAC™ EF TD provides comprehensive and detailed information, by means
of its monitoring and events recording capabilities, these being fundamental elements in an
electrical grid’s improvement process.
52 W1 W2 52
G G
81m 59N
74TC 74TC
74CC 74CC
81M
50 50
59 46 46
51 50G 50G 51
27
49 49 EF TD0
24v 50BF
50N 51G 51G 50N
Model
50BF
Software
Hz
51N 51N
24 87G 87G
All the equipment in the INGEPACTM family 59Q 5 harm
th
can be accessed using powerful software
32
tools developed by Ingeteam and which run 2nd , 2nd + 4 th & 5th HARMONIC
on Windows®. 68FF
BLOCK
The application software is specifically
67 /
designed for simple and user-friendly access 67N 87
to the equipment.
EFS Transformer protection functions 81 Monitoring units Active and reactive power
87 Instantaneous and biased 81R ROCOF Rate of Change of 68FF Fuse failure Frequency
differential protection for two and Frequency ΣkI2 per pole Power factor
three winding transformers Current functions Closing and trip circuit monitoring Maximeters
87R Restricted earth fault for 3x50/51 (67) Excessive number of trips Active and reactive energy
transformer and autotransformer, 50N/51N (67N) Open pole detector / Dead line counters, both directions
two units 50G/51G Earthing overcurrent, Breaker status logic Voltage and current THD
24 Over-excitation (5th harmonic) two units Automation Chronological historical events
24 Over-excitation (V/f) 46TOC (67Q), 46IOC (67Q) 79 Auto-reclose and fault recording
Voltage and frequency functions 49 Thermal image Data acquisition functions Breaker monitoring
27 32 Power units Phase and neutral current Oscillography
59 51V Voltage controlled overcurrent Differential and restraint current Measurements historical reports
47 / 59Q Negative sequence Cold Load Pickup Phase-phase and phase-earth
59N Zero sequence 50BF Breaker failure voltage
www.ingeteam.com
[email protected]
Overview
Insulation and Main features
electromagnetic tests
The technical data in this catalogue is subject to change without prior notice. FY00IPTT01_D/022020
∙ Dielectric withstand IEC 60255-27 ∙ Protection and control in one single device
∙ Insulation resistance measurement IEC 60255-27 ∙ Wide range current inputs allowing the same device to be connected to 1 A and 5 A CT secondary
∙ Impulse voltage IEC 60255-27 ∙ Application software specifically designed for simple and user-friendly access to the equipment
∙ Electrostatic discharge immunity IEC 61000-4-2 ∙ Graphical and textual logic programming based on IEC 61131-3
∙ Radiated radiofrequency ∙ Different hardware options allow to define the most suitable configuration for the application
electromagnetic field immunity IEC 61000-4-3
∙ Complementary functions for responding to primary element failures (breaker failure and trip/
∙ Electrical fast transient /
burst immunity IEC 61000-4-4 close circuits supervision)
∙ Surge immunity IEC 61000-4-5 ∙ Chronological events record, fault reports, load curves and oscillography
∙ Immunity to conducted ∙ Historic measurements record, including currents (demand), voltage and power
disturbances, induced by
radiofrequency fields IEC 61000-4-6
∙ Six setting groups for instantaneously adapting the settings to changes in grid configuration
∙ Power frequency magnetic
without resetting the device
field immunity IEC 61000-4-8 ∙ Circuit breakers monitoring
∙ Impulse magnetic field immunity IEC 61000-4-9 ∙ Metering: current (individual, biased and differential), voltage, power, power factor, frequency,
∙ Damped oscillatory magnetic negative sequence current, demand maximeter, THD (fundamental values and RMS)
field immunity IEC 61000-4-10
∙ Active and reactive energy counters, in both directions
∙ Ripple on dc input power port IEC 61000-4-17
∙ Trips, operation openings, energy cut off by the breaker and automatic reclosing operations
∙ Damped oscillatory wave immunity IEC 61000-4-18
totalizers
∙ Voltage dips, short interruptions
and voltage variations immunity IEC 61000-4-29 ∙ Front panel with 4.9” monochromatic graphic display, programmable function keys with 2 LED
∙ Power frequency immunity IEC 60255-22-7 each, 19 programmable LED and 1 fixed two-colour hardware status LED, numerical keypad and
∙ Withstand to radiated menu keys
electromagnetic interference from ∙ Digital inputs for control, automation and protection functions
transceivers IEEE 37.90.2
∙ Digital outputs for control/tripping and signalling
∙ Measurements of radiated and
conducted radiofrequency ∙ Ethernet communication RJ45 and USB ports on the front
disturbances EN 55022 ∙ Up to 6 serial and 2 Ethernet rear ports
∙ Communication protocols: IEC 61850 Ed.1 and 2, DNP 3.0, IEC 60870-5-103, IEC 60870-5-
Climatic
104, PROCOME
∙ Cold IEC 60068-2-1
∙ Synchronisation from communications protocols, SNTP, IEEE 1588 (PTP), demodulated IRIG-B
∙ Dry heat IEC 60068-2-2
input or PPS input
∙ Change of temperature IEC 60068-2-14
∙ Web server for monitoring and setting without needing additional software
∙ Damp heat, cyclic IEC 60068-2-30
∙ Cybersecurity features: sFTP, HTTPs, firewall, audit log, password accesing
∙ Damp heat steady IEC 60068-2-78
∙ External protection level IEC 60529
Mechanical
Options
∙ Vibrations IEC 60255-21-1
∙ Shock and bump IEC 60255-21-2
∙ Two housing types: 5U 1/2 x 19” rack and 4U 19” rack, which can contain the following modules
∙ Seismic IEC 60255-21-3
in different configurations:
11 digital inputs and 9 digital outputs
16 digital inputs and 16 digital outputs
16 digital inputs and 8 digital outputs
32 digital inputs
16 digital inputs and 8 analog inputs
16 digital inputs and 8 analog inputs (4 isolated)
8 digital inputs, 4 digital outputs and 4 high break contact outputs
8 digital inputs, 4 digital outputs and 4 high speed, high break contact outputs
8 digital inputs and 8 digital outputs
∙ Selectable rear port connectivity:
Up to 6 serial communication ports
Up to 2 Ethernet communication ports
∙ Serial ports in glass fibre optic, plastic fibre optic, RS232 or RS485
∙ Ethernet ports in glass fibre optic or RJ45
∙ HSR, PRP, and D-Link redundancy
∙ Captures analog measurements using Sampled Values (SV) protocol, through IEC 61850-9-2 or
IEC 61869-9 standards
∙ Different models for auxiliary voltages most commonly found in electrical installations
∙ Basic or extended control features
∙ IP54 lid
∙ Nine programmable graphic pages in local display
∙ RIO module (Remote Input/Output)
∙ Redundant power supply
Applications
∙ 2 or 3 windings transformer protection and control
∙ Autotransformer protection and control
∙ Grid Automation
www.ingeteam.com
[email protected]