Parameter                                      Value
Engine Serial Number                           ZAR00796
Equipment ID                                   NOT PROGRAMMED
Comments
3516B Engine - Genset #1 (ZAR00796)
Parameter                                      Value
Equipment ID                                   NOT PROGRAMMED
Engine Serial Number                           ZAR00796
ECM Serial Number                              3361B203JP
Personality Module Part Number                 3489844-00
Personality Module Release Date                MAY09
Personality Module Description                 GENSET
Logged Diagnostic Codes [Diagnostic Clock = 599 hours] - 3516B Engine - Genset #1
(ZAR00796)
Code          Description                                       Occ.    First       Last
91- 8         Throttle Position Sensor : Abnormal Frequency,    1       599         599
              Pulse Width, or Period
Logged Event Codes [Diagnostic Clock = 599 hours] - 3516B Engine - Genset #1 (ZAR00796)
Code        Description                                         Occ.    First       Last
No Logged
Event Codes
Active Diagnostic Codes - 3516B Engine - Genset #1 (ZAR00796)
Code          Description
No Active
Diagnostic
Codes
Active Event Codes - 3516B Engine - Genset #1 (ZAR00796)
Code        Description
No Active
Event Codes
Current Totals - 3516B Engine - Genset #1 (ZAR00796)
Description                    Value                            Unit
Total Time                     599                              hours
Total Fuel                       16734                             gal
Configuration - 3516B Engine - Genset #1 (ZAR00796)
Description                                    Value                                 Unit
Equipment ID                                   NOT PROGRAMMED
Engine Serial Number                           ZAR00796
ECM Serial Number                              3361B203JP
Personality Module Part Number                 3489844-00
Personality Module Release Date                MAY09
Rated Engine Speed                             1500                                  rpm
Fuel Ratio Control Offset                      0
Acceleration Delay Time                        0                                     sec
Engine Acceleration Rate                       250                                   rpm/s
Low Idle Speed                                 900                                   rpm
Cooldown Speed                                 900                                   rpm
Cooldown Duration                              0                                     min
Engine Pre-Lube Duration                       0                                     sec
Engine Pre-Lube System Configuration           Automatic
Engine Continuous Pre-Lube Interval            0                                     min
Crank Duration                                 0                                     sec
Maximum Number of Crank Cycles                 0
Crank Terminate RPM                            400                                   rpm
Engine Speed Droop                             0.0                                   %
Rated Fuel Position                            29.500                                mm
Fuel Correction Factor                         0                                     %
Governor Gain Factor #1                        26214
Governor Minimum Stability Factor #1           629
Governor Maximum Stability Factor #1           7864
FLS                                            0
FTS                                            0
Air Shutoff                                    Disabled
Air Intake Shutoff Detection Installation      Unavailable
Status
Ether Control                                  Disabled
Engine Cooling System Config                   SCAC (Separate Circuit Aftercooled)
Cold Cylinder Cutout                           Disabled
Direct Fuel Control Mode                       Disabled
Desired Speed Input Configuration              CAN Input
Throttle Air Pressure Sensor Installation      Unavailable
Status
Throttle Input Low Idle Duty Cycle Setpoint    Unavailable                           %
Throttle Input High Idle Duty Cycle Setpoint   Unavailable                           %
Secondary Desired Speed Input                  Not Installed
Configuration
Fuel Enable Input Configuration                CAN Input
Secondary Fuel Enable Input Enable             Enabled
Status
Coolant Level Sensor                           Not Installed
Aftercooler Coolant Level Sensor             Not Installed
Installation Status
Cat Data Link #2 Identifier                  Engine Control #1
Inlet Air Temperature Sensor                 Not Installed
Engine Oil Temperature Sensor Installation   Installed
Status
Total Tattletale                             3
Monitoring System - 3516B Engine - Genset #1 (ZAR00796)
Description              State                    Trip Point     Delay Time
Altitude (atmospheric
pressure)
Moderate Severity (2)    On                       11.0 psi       0 sec
Engine Overspeed
Least Severe (1)         On                       1770 rpm       0 sec
Most Severe (3)          On                       1770 rpm       0 sec
High Aftercooler
Coolant Temperature
Least Severe (1)         On                       216 Deg F      5 sec
Moderate Severity (2)    On                       225 Deg F      5 sec
Most Severe (3)          On                       225 Deg F      5 sec
High Air Filter
Restriction Pressure
Least Severe (1)         On                       28.1 " H2O     5 sec
Moderate Severity (2)    On                       28.1 " H2O     5 sec
High Boost Pressure
Least Severe (1)         Off                      58.0 psi       0 sec
Moderate Severity (2)    Off                      58.0 psi       0 sec
High Crankcase
Pressure
Least Severe (1)         On                       8.0 " H2O      3 sec
Moderate Severity (2)    On                       24.1 " H2O     10 sec
Most Severe (3)          On                       14.1 " H2O     3 sec
High Engine Coolant
Temperature
Least Severe (1)         On                       216 Deg F      5 sec
Moderate Severity (2)    On                       225 Deg F      30 sec
Most Severe (3)          On                       225 Deg F      5 sec
High Engine Oil Filter
Restriction Pressure
Least Severe (1)         On                       15 psi         5 sec
High Exhaust
Temperature
Least Severe (1)         On                       1342 Deg F     5 sec
Moderate Severity (2)    On                       1342 Deg F     5 sec
High Fuel Filter
Restriction Pressure
Least Severe (1)         On                       15 psi         5 sec
Low Aftercooler
Coolant Level
Least Severe (1)         On                       None           30 sec
Most Severe (3)        Off                     None                    30 sec
Low Coolant Level
Least Severe (1)       On                      None                    30 sec
Most Severe (3)        Off                     None                    30 sec
Low Engine Coolant
Temperature
Least Severe (1)       On                      176 Deg F               5 sec
Low Engine Oil
Pressure
Least Severe (1)       On                      None                    4 sec
Most Severe (3)        On                      None                    9 sec
Low Fuel Pressure
Most Severe (3)        On                      32 psi                  20 sec
Low System Voltage
Least Severe (1)       On                      20 Volts                10 sec
Injector Codes Calibration - 3516B Engine - Genset #1 (ZAR00796)
Injector                                       Code
Injector 1                                     2450
Injector 2                                     9825
Injector 3                                     1225
Injector 4                                     6410
Injector 5                                     3865
Injector 6                                     1576
Injector 7                                     5866
Injector 8                                     4740
Injector 9                                     7840
Injector 10                                    7827
Injector 11                                    6727
Injector 12                                    9602
Injector 13                                    6520
Injector 14                                    1990
Injector 15                                    7957
Injector 16                                    5200
EMCP 3.1
Parameter                                      Value
ECM Part Number                                3007645-03
ECM Serial Number                              3121B055UA
Software Group Part Number                     3927385-00
Software Group Release Date                    MAR2011
Software Group Description                     L0 9_0 Standard -- English, 2.2.3 Prod,
                                               14December2011
Logged Diagnostic Codes [SHM: 599] - EMCP 3.1
Code          Description               Occ.   SHM First   SHM Last    RTC First   RTC Last
No Logged
Diagnostic
Codes
Logged Event Codes [SHM: 599] - EMCP 3.1
Code          Description                  Occ.    SHM First   SHM Last    RTC First     RTC Last
110-17        Engine Coolant               31      0:28:30     598:19:30
              Temperature : Low - least
              severe (1)
167-17        Charging System              1       0:00:00     0:00:00
              Potential : Low - least
              severe (1)
168-17        Battery Potential / Power    21      0:00:00     162:13:30
              Input #1 : Low - least
              severe (1)
190- 1        Engine Speed : Low -         2       1:50:01     1:50:38
              most severe (3)
190-17        Engine Speed : Low -         2       1:50:01     1:50:38
              least severe (1)
970-31        Engine Auxiliary Engine      30      0:00:00     162:13:30
              Shutdown Switch
1664-31       Engine Automatic Start       1       0:00:00     0:00:00
              Failed
4007-31       Generator Control not in     27      0:00:00     1:40:30
              Automatic
Active Diagnostic Codes [SHM: 599] - EMCP 3.1
Code         Description                                                                      Occ.
No Active
Diagnostic
Codes
Active Event Codes [SHM: 599] - EMCP 3.1
Code        Description                                                                       Occ.
No Active
Event Codes
Current Totals - EMCP 3.1
Description                    Value                              Unit
Total Operating Hours          598.5                              hours
Configuration - EMCP 3.1
Description                                    Value                                   Unit
Engine Start Fault Protection Activation       30                                      sec
Delay Time
Crank Duration                                 10                                      sec
Crank Cycle Rest Interval                      10                                      sec
Engine Purge Cycle Time                        0                                       sec
Maximum Number of Crank Cycles                 5
Cooldown Duration                              5                                       min
Start Aid Activation Time                      0                                       sec
Crank Alert Activation Time                    0                                       sec
Crank Terminate RPM                            400                                     rpm
Engine Fuel Type Configuration                 Diesel
Fuel Shutoff Solenoid Type Configuration       Energized to Run
Engine Type Configuration                     Electronic
Engine Controller J1939 Data Link Support     Proprietary J1939 Support
Configuration
Engine Cooldown Speed Configuration           Rated Speed
Engine Operating State Input Configuration    Hardwired Input
Fuel Priming Feature Enable Status            Disabled
Engine Forced Idle Feature Enable Status      Disabled
Maximum Generator Voltage Output Bias         5                           %
Percentage
Generator Nominal Output Voltage              6000                        Volts
High Battery Voltage Warning Event            30.0                        Volts
Threshold
High Battery Voltage Warning Event            30                          sec
Notification Delay Time
High Battery Voltage Shutdown Event           32.0                        Volts
Threshold
High Battery Voltage Shutdown Event           2                           sec
Notification Delay Time
Low Battery Voltage Warning Event             18.0                        Volts
Threshold
Low Battery Voltage Warning Event             10                          sec
Notification Delay Time
Low Battery Charging System Voltage           22.0                        Volts
Warning Event Threshold
Low Battery Charging System Voltage           30                          sec
Warning Event Notification Delay Time
Low Cranking Voltage Warning Event            0.0                         Volts
Threshold
Low Cranking Voltage Warning Event            2                           sec
Notification Delay Time
Digital Input #1 Active State Configuration   High
Digital Input #2 Active State Configuration   Low
Digital Input #3 Active State Configuration   Low
Digital Input #4 Active State Configuration   Low
Digital Input #5 Active State Configuration   Low
Digital Input #6 Active State Configuration   Low
Digital Selector #1 Source Configuration      Input #2
Digital Selector #2 Source Configuration      Disabled
Digital Selector #3 Source Configuration      Disabled
Digital Selector #4 Source Configuration      Input #6
Digital Selector #5 Source Configuration      Disabled or Not Installed
Digital Selector #6 Source Configuration      Disabled or Not Installed
Digital Selector #7 Source Configuration      Disabled or Not Installed
Digital Selector #8 Source Configuration      Disabled or Not Installed
Digital Selector #9 Source Configuration      Disabled or Not Installed
Digital Selector #10 Source Configuration     Disabled or Not Installed
Engine Coolant Temperature Sensor             Data Link
Configuration
High Engine Coolant Temperature Warning       216                         Deg F
Event Threshold
High Engine Coolant Temperature Warning      2                  sec
Event Notification Delay Time
High Engine Coolant Temperature              225                Deg F
Shutdown Event Threshold
High Engine Coolant Temperature              10                 sec
Shutdown Event Notification Delay Time
Low Engine Coolant Temperature Warning       70                 Deg F
Event Threshold
Low Engine Coolant Temperature Warning       2                  sec
Event Notification Delay Time
Engine Coolant Temperature Sensor            Map #1
Configuration Code
Engine Oil Pressure Sensor Configuration     Data Link
Low Engine Oil Pressure Warning Event        35                 psi
Threshold
Low Idle Low Engine Oil Pressure Warning     15                 psi
Event Threshold
Low Engine Oil Pressure Warning Event        0                  sec
Notification Delay Time
Low Engine Oil Pressure Shutdown Event       30                 psi
Threshold
Low Idle Low Engine Oil Pressure             10                 psi
Shutdown Event Threshold
Low Engine Oil Pressure Shutdown Event       0                  sec
Notification Delay Time
Low Engine Oil Pressure Step Speed           1200               rpm
Engine Oil Pressure Sensor Configuration     Map #1
Code
Flywheel Teeth                               183
Engine Overspeed Setpoint                    1770               rpm
Engine Underspeed Warning Event              1290               rpm
Threshold
Engine Underspeed Warning Event              10.0               sec
Notification Delay Time
Engine Underspeed Shutdown Event             1230               rpm
Threshold
Engine Underspeed Shutdown Event             10.0               sec
Notification Delay Time
Engine Speed Sensor Configuration            Sensor
Event Input Function #1 Suspect              Custom Event
Parameter Number
Event Input Function #1 Failure Mode         Condition Exists
Identifier
Event Input Function #1 Event Notification   10                 sec
Delay Time
Event Input Function #1 Active State         High
Configuration
Event Input Function #2 Suspect              Custom Event
Parameter Number
Event Input Function #2 Failure Mode         Condition Exists
Identifier
Event Input Function #2 Event Notification   0                  sec
Delay Time
Event Input Function #2 Active State         High
Configuration
Event Input Function #3 Suspect              Custom Event
Parameter Number
Event Input Function #3 Failure Mode         Condition Exists
Identifier
Event Input Function #3 Event Notification   0                           sec
Delay Time
Event Input Function #3 Active State         High
Configuration
Event Input Function #4 Suspect              Battery Charger Failure
Parameter Number
Event Input Function #4 Failure Mode         Condition Exists
Identifier
Event Input Function #4 Event Notification   0                           sec
Delay Time
Event Input Function #4 Active State         High
Configuration
Event Input Function #5 Suspect              Disabled or Not Installed
Parameter Number
Event Input Function #5 Failure Mode         Disabled or Not Installed
Identifier
Event Input Function #5 Event Notification   Disabled or Not Installed   sec
Delay Time
Event Input Function #5 Active State         Disabled or Not Installed
Configuration
Event Input Function #6 Suspect              Disabled or Not Installed
Parameter Number
Event Input Function #6 Failure Mode         Disabled or Not Installed
Identifier
Event Input Function #6 Event Notification   Disabled or Not Installed   sec
Delay Time
Event Input Function #6 Active State         Disabled or Not Installed
Configuration
Event Output Function #1 Suspect             Engine Oil Pressure
Parameter Number
Event Output Function #1 Trigger Condition   **Disabled
Event Output Function #2 Suspect             Disabled or Not Installed
Parameter Number
Event Output Function #2 Trigger Condition   Disabled or Not Installed
Event Output Function #3 Suspect             Disabled or Not Installed
Parameter Number
Event Output Function #3 Trigger Condition   Disabled or Not Installed
Event Output Function #4 Suspect             Disabled or Not Installed
Parameter Number
Event Output Function #4 Trigger Condition   Disabled or Not Installed
Event Output Function #5 Suspect             Disabled or Not Installed
Parameter Number
Event Output Function #5 Trigger Condition   Disabled or Not Installed
Event Output Function #6 Suspect             Disabled or Not Installed
Parameter Number
Event Output Function #6 Trigger Condition   Disabled or Not Installed
Event Output Function #7 Suspect             Disabled or Not Installed
Parameter Number
Event Output Function #7 Trigger Condition   Disabled or Not Installed
Event Output Function #8 Suspect             Disabled or Not Installed
Parameter Number
Event Output Function #8 Trigger Condition   Disabled or Not Installed
Air Filter Differential Pressure Sensor      Activate Warning Condition
Diagnostic Response Configuration
Air Filter Differential Pressure Sensor      No
Diagnostic Audible Alert
Air Filter Differential Pressure Sensor      No
Diagnostic Breaker #1 Trip
Air Filter Differential Pressure Sensor      No
Diagnostic Breaker #2 Trip
Ambient Air Temperature Sensor               Activate Warning Condition
Diagnostic Response Configuration
Ambient Air Temperature Sensor               No
Diagnostic Audible Alert
Ambient Air Temperature Sensor               No
Diagnostic Breaker #1 Trip
Ambient Air Temperature Sensor               No
Diagnostic Breaker #2 Trip
Engine Coolant Level Sensor Diagnostic       Activate Warning Condition
Response Configuration
Engine Coolant Level Sensor Diagnostic       No
Audible Alert
Engine Coolant Level Sensor Diagnostic       No
Breaker #1 Trip
Engine Coolant Level Sensor Diagnostic       No
Breaker #2 Trip
Engine Coolant Temperature Sensor            Activate Warning Condition
Diagnostic Response Configuration
Engine Coolant Temperature Sensor            No
Diagnostic Audible Alert
Engine Coolant Temperature Sensor            No
Diagnostic Breaker #1 Trip
Engine Coolant Temperature Sensor            No
Diagnostic Breaker #2 Trip
Engine Oil Level Sensor Diagnostic           Activate Warning Condition
Response Configuration
Engine Oil Level Sensor Diagnostic Audible   No
Alert
Engine Oil Level Sensor Diagnostic           No
Breaker #1 Trip
Engine Oil Level Sensor Diagnostic           No
Breaker #2 Trip
Engine Oil Pressure Sensor Diagnostic        Activate Warning Condition
Response Configuration
Engine Oil Pressure Sensor Diagnostic        No
Audible Alert
Engine Oil Pressure Sensor Diagnostic        No
Breaker #1 Trip
Engine Oil Pressure Sensor Diagnostic        No
Breaker #2 Trip
Engine Oil Temperature Sensor Diagnostic     Activate Warning Condition
Response Configuration
Engine Oil Temperature Sensor Diagnostic    No
Audible Alert
Engine Oil Temperature Sensor Diagnostic    No
Breaker #1 Trip
Engine Oil Temperature Sensor Diagnostic    No
Breaker #2 Trip
Engine Speed Sensor Diagnostic              Activate Hard Shutdown Condition
Response Configuration
Engine Speed Sensor Diagnostic Audible      Yes
Alert
Engine Speed Sensor Diagnostic Breaker      No
#1 Trip
Engine Speed Sensor Diagnostic Breaker      No
#2 Trip
Exhaust Temperature Sensor Diagnostic       Activate Warning Condition
Response Configuration
Exhaust Temperature Sensor Diagnostic       No
Audible Alert
Exhaust Temperature Sensor Diagnostic       No
Breaker #1 Trip
Exhaust Temperature Sensor Diagnostic       No
Breaker #2 Trip
Right Exhaust Temperature Sensor            Activate Warning Condition
Diagnostic Response Configuration
Right Exhaust Temperature Sensor            No
Diagnostic Audible Alert
Right Exhaust Temperature Sensor            No
Diagnostic Breaker #1 Trip
Right Exhaust Temperature Sensor            No
Diagnostic Breaker #2 Trip
Left Exhaust Temperature Sensor             Activate Warning Condition
Diagnostic Response Configuration
Left Exhaust Temperature Sensor             No
Diagnostic Audible Alert
Left Exhaust Temperature Sensor             No
Diagnostic Breaker #1 Trip
Left Exhaust Temperature Sensor             No
Diagnostic Breaker #2 Trip
Fire Extinguisher Pressure Sensor           Activate Warning Condition
Diagnostic Response Configuration
Fire Extinguisher Pressure Sensor Audible   No
Alert
Fire Extinguisher Pressure Sensor Breaker   No
#1 Trip
Fire Extinguisher Pressure Sensor Breaker   No
#2 Trip
Fuel Filter Differential Pressure Sensor    Activate Warning Condition
Diagnostic Response Configuration
Fuel Filter Differential Pressure Sensor    No
Diagnostic Audible Alert
Fuel Filter Differential Pressure Sensor    No
Diagnostic Breaker #1 Trip
Fuel Filter Differential Pressure Sensor    No
Diagnostic Breaker #2 Trip
Fuel Level Sensor Diagnostic Response        Activate Warning Condition
Configuration
Fuel Level Sensor Diagnostic Audible Alert   No
Fuel Level Sensor Diagnostic Breaker #1      No
Trip
Fuel Level Sensor Diagnostic Breaker #2      No
Trip
External Tank Fuel Level Sensor              Activate Warning Condition
Diagnostic Response Configuration
External Tank Fuel Level Sensor              No
Diagnostic Audible Alert
External Tank Fuel Level Sensor              No
Diagnostic Breaker #1 Trip
External Tank Fuel Level Sensor              No
Diagnostic Breaker #2 Trip
Generator Bearing #1 Temperature Sensor      Activate Warning Condition
Diagnostic Response Configuration
Generator Bearing #1 Temperature Sensor      No
Diagnostic Audible Alert
Generator Bearing #1 Temperature Sensor      No
Diagnostic Breaker #1 Trip
Generator Bearing #1 Temperature Sensor      No
Diagnostic Breaker #2 Trip
Generator Output Sensing System              Activate Warning Condition
Diagnostic Response Configuration
Generator Output Sensing System              Yes
Diagnostic Audible Alert
Generator Output Sensing System              No
Diagnostic Breaker #1 Trip
Generator Output Sensing System              No
Diagnostic Breaker #2 Trip
Engine Oil Filter Differential Pressure      Activate Warning Condition
Sensor Diagnostic Response Config
Engine Oil Filter Differential Pressure      No
Sensor Diagnostic Audible Alert
Engine Oil Filter Differential Pressure      No
Sensor Diagnostic Breaker #1 Trip
Engine Oil Filter Differential Pressure      No
Sensor Diagnostic Breaker #2 Trip
Primary Data Link Diagnostic Response        Activate Warning Condition
Configuration
Primary Data Link Diagnostic Audible Alert   No
Primary Data Link Diagnostic Breaker #1      No
Trip
Primary Data Link Diagnostic Breaker #2      No
Trip
Starting Air Pressure Sensor Diagnostic      Activate Warning Condition
Response Configuration
Starting Air Pressure Sensor Diagnostic      No
Audible Alert
Starting Air Pressure Sensor Diagnostic      No
Breaker #1 Trip
Starting Air Pressure Sensor Diagnostic      No
Breaker #2 Trip
Battery Charger Failure Diagnostic             Activate Warning Condition
Response Configuration
Battery Charger Failure Diagnostic Audible     Yes
Alert
Engine Controller Not Responding               Activate Warning Condition
Diagnostic Response Configuration
Engine Controller Not Responding               No
Diagnostic Audible Alert
Engine Controller Not Responding               No
Diagnostic Breaker #1 Trip
Engine Controller Not Responding               No
Diagnostic Breaker #2 Trip
Air Damper Closed Event Response               Hard Shutdown & Active Only
Configuration                                  Condition
Air Damper Closed Event Audible Alert          Yes
High Air Filter Differential Pressure          Activate Warning Condition
Warning Event Response Configuration
High Air Filter Differential Pressure          Yes
Warning Event Audible Alert
High Air Filter Differential Pressure          No
Warning Event Breaker #1 Trip
High Air Filter Differential Pressure          No
Warning Event Breaker #2 Trip
High Air Filter Differential Pressure          Activate Hard Shutdown Condition
Shutdown Event Response Configuration
High Air Filter Differential Pressure          Yes
Shutdown Event Audible Alert
High Air Filter Differential Pressure          No
Shutdown Event Breaker #1 Trip
High Air Filter Differential Pressure          No
Shutdown Event Breaker #2 Trip
Low Air Filter Differential Pressure Warning   Activate Warning Condition
Event Response Configuration
Low Air Filter Differential Pressure Warning   Yes
Event Audible Alert
Low Air Filter Differential Pressure Warning   No
Event Breaker #1 Trip
Low Air Filter Differential Pressure Warning   No
Event Breaker #2 Trip
Low Air Filter Differential Pressure Warning   Yes
Event Fault Protection Timer
Low Air Filter Differential Pressure           Activate Hard Shutdown Condition
Shutdown Event Response Configuration
Low Air Filter Differential Pressure           Yes
Shutdown Event Audible Alert
Low Air Filter Differential Pressure           No
Shutdown Event Breaker #1 Trip
Low Air Filter Differential Pressure           No
Shutdown Event Breaker #2 Trip
Low Air Filter Differential Pressure           Yes
Shutdown Event Fault Protection Timer
Emergency Stop Activated Event                 Activate Hard Shutdown Condition
Response Configuration
Emergency Stop Activated Event Audible    Yes
Alert
Emergency Stop Activated Event Breaker    No
#1 Trip
Emergency Stop Activated Event Breaker    No
#2 Trip
High Engine Coolant Level Warning Event   Activate Warning Condition
Response Configuration
High Engine Coolant Level Warning Event   Yes
Audible Alert
High Engine Coolant Level Warning Event   No
Breaker #1 Trip
High Engine Coolant Level Warning Event   No
Breaker #2 Trip
High Engine Coolant Level Shutdown        Activate Hard Shutdown Condition
Event Response Configuration
High Engine Coolant Level Shutdown        Yes
Event Audible Alert
High Engine Coolant Level Shutdown        No
Event Breaker #1 Trip
High Engine Coolant Level Shutdown        No
Event Breaker #2 Trip
Low Engine Coolant Level Warning Event    Activate Warning Condition
Response Configuration
Low Engine Coolant Level Warning Event    Yes
Audible Alert
Low Engine Coolant Level Warning Event    No
Breaker #1 Trip
Low Engine Coolant Level Warning Event    No
Breaker #2 Trip
Low Engine Coolant Level Shutdown Event   Activate Hard Shutdown Condition
Response Configuration
Low Engine Coolant Level Shutdown Event   Yes
Audible Alert
Low Engine Coolant Level Shutdown Event   No
Breaker #1 Trip
Low Engine Coolant Level Shutdown Event   No
Breaker #2 Trip
High Engine Coolant Temperature Warning   Activate Warning Condition
Event Response Configuration
High Engine Coolant Temperature Warning   Yes
Event Audible Alert
High Engine Coolant Temperature Warning   No
Event Breaker #1 Trip
High Engine Coolant Temperature Warning   No
Event Breaker #2 Trip
High Engine Coolant Temperature Warning   Yes
Event Fault Protection Timer
High Engine Coolant Temperature           Activate Hard Shutdown Condition
Shutdown Event Response Configuration
High Engine Coolant Temperature           Yes
Shutdown Event Audible Alert
High Engine Coolant Temperature           No
Shutdown Event Breaker #1 Trip
High Engine Coolant Temperature          No
Shutdown Event Breaker #2 Trip
High Engine Coolant Temperature          Yes
Shutdown Event Fault Protection Timer
Low Engine Coolant Temperature Warning   Activate Warning Condition
Event Response Configuration
Low Engine Coolant Temperature Warning   Yes
Event Audible Alert
Low Engine Coolant Temperature Warning   No
Event Breaker #1 Trip
Low Engine Coolant Temperature Warning   No
Event Breaker #2 Trip
Low Engine Coolant Temperature Warning   No
Event Fault Protection Timer
Engine Failure To Start Shutdown Event   Activate Hard Shutdown Condition
Response Configuration
Engine Failure To Start Shutdown Event   Yes
Audible Alert
Engine Failure To Start Shutdown Event   No
Breaker #1 Trip
Engine Failure To Start Shutdown Event   No
Breaker #2 Trip
High Engine Oil Level Warning Event      Activate Warning Condition
Response Configuration
High Engine Oil Level Warning Event      Yes
Audible Alert
High Engine Oil Level Warning Event      No
Breaker #1 Trip
High Engine Oil Level Warning Event      No
Breaker #2 Trip
High Engine Oil Level Shutdown Event     Activate Hard Shutdown Condition
Response Configuration
High Engine Oil Level Shutdown Event     Yes
Audible Alert
High Engine Oil Level Shutdown Event     No
Breaker #1 Trip
High Engine Oil Level Shutdown Event     No
Breaker #2 Trip
Low Engine Oil Level Warning Event       Activate Warning Condition
Response Configuration
Low Engine Oil Level Warning Event       Yes
Audible Alert
Low Engine Oil Level Warning Event       No
Breaker #1 Trip
Low Engine Oil Level Warning Event       No
Breaker #2 Trip
Low Engine Oil Level Shutdown Event      Activate Hard Shutdown Condition
Response Configuration
Low Engine Oil Level Shutdown Event      Yes
Audible Alert
Low Engine Oil Level Shutdown Event      No
Breaker #1 Trip
Low Engine Oil Level Shutdown Event      No
Breaker #2 Trip
Low Engine Oil Pressure Warning Event    Activate Warning Condition
Response Configuration
Low Engine Oil Pressure Warning Event    Yes
Audible Alert
Low Engine Oil Pressure Warning Event    No
Breaker #1 Trip
Low Engine Oil Pressure Warning Event    No
Breaker #2 Trip
Low Engine Oil Pressure Warning Event    Yes
Fault Protection Timer
Low Engine Oil Pressure Shutdown Event   Activate Hard Shutdown Condition
Response Configuration
Low Engine Oil Pressure Shutdown Event   Yes
Audible Alert
Low Engine Oil Pressure Shutdown Event   No
Breaker #1 Trip
Low Engine Oil Pressure Shutdown Event   No
Breaker #2 Trip
Low Engine Oil Pressure Shutdown Event   Yes
Fault Protection Timer
High Engine Oil Temperature Warning      Activate Warning Condition
Event Response Configuration
High Engine Oil Temperature Warning      Yes
Event Audible Alert
High Engine Oil Temperature Warning      No
Event Breaker #1 Trip
High Engine Oil Temperature Warning      No
Event Breaker #2 Trip
High Engine Oil Temperature Warning      No
Event Fault Protection Timer
High Engine Oil Temperature Shutdown     Activate Hard Shutdown Condition
Event Response Configuration
High Engine Oil Temperature Shutdown     Yes
Event Audible Alert
High Engine Oil Temperature Shutdown     No
Event Breaker #1 Trip
High Engine Oil Temperature Shutdown     No
Event Breaker #2 Trip
High Engine Oil Temperature Shutdown     No
Event Fault Protection Timer
Low Engine Oil Temperature Warning       Activate Warning Condition
Event Response Configuration
Low Engine Oil Temperature Warning       Yes
Event Audible Alert
Low Engine Oil Temperature Warning       No
Event Breaker #1 Trip
Low Engine Oil Temperature Warning       No
Event Breaker #2 Trip
Low Engine Oil Temperature Warning       Yes
Event Fault Protection Timer
Low Engine Oil Temperature Shutdown      Disable Condition
Event Response Configuration
Low Engine Oil Temperature Shutdown      No
Event Audible Alert
Low Engine Oil Temperature Shutdown       No
Event Breaker #1 Trip
Low Engine Oil Temperature Shutdown       No
Event Breaker #2 Trip
Low Engine Oil Temperature Shutdown       No
Event Fault Protection Timer
Unexpected Engine Shutdown Event          Activate Hard Shutdown Condition
Response Configuration
Unexpected Engine Shutdown Event          Yes
Audible Alert
Unexpected Engine Shutdown Event          No
Breaker #1 Trip
Unexpected Engine Shutdown Event          No
Breaker #2 Trip
Engine Overspeed Shutdown Event           Activate Hard Shutdown Condition
Response Configuration
Engine Overspeed Shutdown Event           Yes
Audible Alert
Engine Overspeed Shutdown Event           No
Breaker #1 Trip
Engine Overspeed Shutdown Event           No
Breaker #2 Trip
Engine Underspeed Warning Event           Activate Warning Condition
Response Configuration
Engine Underspeed Warning Event Audible   Yes
Alert
Engine Underspeed Warning Event           No
Breaker #1 Trip
Engine Underspeed Warning Event           No
Breaker #2 Trip
Engine Underspeed Warning Event Fault     Yes
Protection Timer
Engine Underspeed Shutdown Event          Activate Hard Shutdown Condition
Response Configuration
Engine Underspeed Shutdown Event          Yes
Audible Alert
Engine Underspeed Shutdown Event          No
Breaker #1 Trip
Engine Underspeed Shutdown Event          No
Breaker #2 Trip
Engine Underspeed Shutdown Event Fault    Yes
Protection Timer
High Exhaust Temperature Warning Event    Activate Warning Condition
Response Configuration
High Exhaust Temperature Warning Event    Yes
Audible Alert
High Exhaust Temperature Warning Event    No
Breaker #1 Trip
High Exhaust Temperature Warning Event    No
Breaker #2 Trip
High Exhaust Temperature Warning Event    No
Fault Protection Timer
High Exhaust Temperature Shutdown         Activate Hard Shutdown Condition
Event Response Configuration
High Exhaust Temperature Shutdown         Yes
Event Audible Alert
High Exhaust Temperature Shutdown         No
Event Breaker #1 Trip
High Exhaust Temperature Shutdown         No
Event Breaker #2 Trip
High Exhaust Temperature Shutdown         No
Event Fault Protection Timer
Low Exhaust Temperature Warning Event     Activate Warning Condition
Response Configuration
Low Exhaust Temperature Warning Event     Yes
Audible Alert
Low Exhaust Temperature Warning Event     No
Breaker #1 Trip
Low Exhaust Temperature Warning Event     No
Breaker #2 Trip
Low Exhaust Temperature Warning Event     Yes
Fault Protection Timer
Low Exhaust Temperature Shutdown Event    Disable Condition
Response Configuration
Low Exhaust Temperature Shutdown Event    No
Audible Alert
Low Exhaust Temperature Shutdown Event    No
Breaker #1 Trip
Low Exhaust Temperature Shutdown Event    No
Breaker #2 Trip
Low Exhaust Temperature Shutdown Event    Yes
Fault Protection Timer
High Right Exhaust Temperature Warning    Activate Warning Condition
Event Response Configuration
High Right Exhaust Temperature Warning    Yes
Event Audible Alert
High Right Exhaust Temperature Warning    No
Event Breaker #1 Trip
High Right Exhaust Temperature Warning    No
Event Breaker #2 Trip
High Right Exhaust Temperature Warning    No
Event Fault Protection Timer
High Right Exhaust Temperature Shutdown   Activate Hard Shutdown Condition
Event Response Configuration
High Right Exhaust Temperature Shutdown   Yes
Event Audible Alert
High Right Exhaust Temperature Shutdown   No
Event Breaker #1 Trip
High Right Exhaust Temperature Shutdown   No
Event Breaker #2 Trip
High Right Exhaust Temperature Shutdown   No
Event Fault Protection Timer
Low Right Exhaust Temperature Warning     Activate Warning Condition
Event Response Configuration
Low Right Exhaust Temperature Warning     Yes
Event Audible Alert
Low Right Exhaust Temperature Warning     No
Event Breaker #1 Trip
Low Right Exhaust Temperature Warning    No
Event Breaker #2 Trip
Low Right Exhaust Temperature Warning    Yes
Event Fault Protection Timer
Low Right Exhaust Temperature Shutdown   Disable Condition
Event Response Configuration
Low Right Exhaust Temperature Shutdown   No
Event Audible Alert
Low Right Exhaust Temperature Shutdown   No
Event Breaker #1 Trip
Low Right Exhaust Temperature Shutdown   No
Event Breaker #2 Trip
Low Right Exhaust Temperature Shutdown   No
Event Fault Protection Timer
High Left Exhaust Temperature Warning    Activate Warning Condition
Event Response Configuration
High Left Exhaust Temperature Warning    Yes
Event Audible Alert
High Left Exhaust Temperature Warning    No
Event Breaker #1 Trip
High Left Exhaust Temperature Warning    No
Event Breaker #2 Trip
High Left Exhaust Temperature Warning    No
Event Fault Protection Timer
High Left Exhaust Temperature Shutdown   Activate Hard Shutdown Condition
Event Response Configuration
High Left Exhaust Temperature Shutdown   Yes
Event Audible Alert
High Left Exhaust Temperature Shutdown   No
Event Breaker #1 Trip
High Left Exhaust Temperature Shutdown   No
Event Breaker #2 Trip
High Left Exhaust Temperature Shutdown   No
Event Fault Protection Timer
Low Left Exhaust Temperature Warning     Activate Warning Condition
Event Response Configuration
Low Left Exhaust Temperature Warning     Yes
Event Audible Alert
Low Left Exhaust Temperature Warning     No
Event Breaker #1 Trip
Low Left Exhaust Temperature Warning     No
Event Breaker #2 Trip
Low Left Exhaust Temperature Warning     Yes
Event Fault Protection Timer
Low Left Exhaust Temperature Shutdown    Disable Condition
Event Response Configuration
Low Left Exhaust Temperature Shutdown    No
Event Audible Alert
Low Left Exhaust Temperature Shutdown    No
Event Breaker #1 Trip
Low Left Exhaust Temperature Shutdown    No
Event Breaker #2 Trip
Low Left Exhaust Temperature Shutdown    No
Event Fault Protection Timer
High Fuel Filter Differential Pressure     Activate Warning Condition
Warning Event Response Configuration
High Fuel Filter Differential Pressure     Yes
Warning Event Audible Alert
High Fuel Filter Differential Pressure     No
Warning Event Breaker #1 Trip
High Fuel Filter Differential Pressure     No
Warning Event Breaker #2 Trip
High Fuel Filter Differential Pressure     Activate Hard Shutdown Condition
Shutdown Event Response Config
High Fuel Filter Differential Pressure     Yes
Shutdown Event Audible Alert
High Fuel Filter Differential Pressure     No
Shutdown Event Breaker #1 Trip
High Fuel Filter Differential Pressure     No
Shutdown Event Breaker #2 Trip
Low Fuel Filter Differential Pressure      Activate Warning Condition
Warning Event Response Configuration
Low Fuel Filter Differential Pressure      Yes
Warning Event Audible Alert
Low Fuel Filter Differential Pressure      No
Warning Event Breaker #1 Trip
Low Fuel Filter Differential Pressure      No
Warning Event Breaker #2 Trip
Low Fuel Filter Differential Pressure      Yes
Warning Event Fault Protection Timer
Low Fuel Filter Differential Pressure      Activate Hard Shutdown Condition
Shutdown Event Response Configuration
Low Fuel Filter Differential Pressure      Yes
Shutdown Event Audible Alert
Low Fuel Filter Differential Pressure      No
Shutdown Event Breaker #1 Trip
Low Fuel Filter Differential Pressure      No
Shutdown Event Breaker #2 Trip
Low Fuel Filter Differential Pressure      Yes
Shutdown Event Fault Protection Timer
High Fuel Level Warning Event Response     Activate Warning Condition
Configuration
High Fuel Level Warning Event Audible      Yes
Alert
High Fuel Level Warning Event Breaker #1   No
Trip
High Fuel Level Warning Event Breaker #2   No
Trip
High Fuel Level Shutdown Event Response    Activate Hard Shutdown Condition
Configuration
High Fuel Level Shutdown Event Audible     Yes
Alert
High Fuel Level Shutdown Event Breaker     No
#1 Trip
High Fuel Level Shutdown Event Breaker     No
#2 Trip
Low Fuel Level Warning Event Response      Activate Warning Condition
Configuration
Low Fuel Level Warning Event Audible           Yes
Alert
Low Fuel Level Warning Event Breaker #1        No
Trip
Low Fuel Level Warning Event Breaker #2        No
Trip
Low Fuel Level Shutdown Event Response         Activate Hard Shutdown Condition
Configuration
Low Fuel Level Shutdown Event Audible          Yes
Alert
Low Fuel Level Shutdown Event Breaker          No
#1 Trip
Low Fuel Level Shutdown Event Breaker          No
#2 Trip
External Tank High Fuel Level Warning          Activate Warning Condition
Event Response Configuration
External Tank High Fuel Level Warning          Yes
Event Audible Alert
External Tank High Fuel Level Warning          No
Event Breaker #1 Trip
External Tank High Fuel Level Warning          No
Event Breaker #2 Trip
External Tank High Fuel Level Shutdown         Activate Hard Shutdown Condition
Event Response Configuration
External Tank High Fuel Level Shutdown         Yes
Event Audible Alert
External Tank High Fuel Level Shutdown         No
Event Breaker #1 Trip
External Tank High Fuel Level Shutdown         No
Event Breaker #2 Trip
External Tank Low Fuel Level Warning           Activate Warning Condition
Event Response Configuration
External Tank Low Fuel Level Warning           Yes
Event Audible Alert
External Tank Low Fuel Level Warning           No
Event Breaker #1 Trip
External Tank Low Fuel Level Warning           No
Event Breaker #2 Trip
External Tank Low Fuel Level Shutdown          Activate Hard Shutdown Condition
Event Response Configuration
External Tank Low Fuel Level Shutdown          Yes
Event Audible Alert
External Tank Low Fuel Level Shutdown          No
Event Breaker #1 Trip
External Tank Low Fuel Level Shutdown          No
Event Breaker #2 Trip
Fuel Leak Event Response Configuration         Activate Warning Condition
Fuel Leak Event Audible Alert                  Yes
Fuel Leak Event Breaker #1 Trip                No
Fuel Leak Event Breaker #2 Trip                No
High Engine Oil Filter Differential Pressure   Activate Warning Condition
Warning Event Response Config
High Engine Oil Filter Differential Pressure   Yes
Warning Event Audible Alert
High Engine Oil Filter Differential Pressure   No
Warning Event Breaker #1 Trip
High Engine Oil Filter Differential Pressure   No
Warning Event Breaker #2 Trip
High Engine Oil Filter Differential Pressure   Activate Hard Shutdown Condition
Shutdown Event Response Config
High Engine Oil Filter Differential Pressure   Yes
Shutdown Event Audible Alert
High Engine Oil Filter Differential Pressure   No
Shutdown Event Breaker #1 Trip
High Engine Oil Filter Differential Pressure   No
Shutdown Event Breaker #2 Trip
Low Engine Oil Filter Differential Pressure    Activate Warning Condition
Warning Event Response Config
Low Engine Oil Filter Differential Pressure    Yes
Warning Event Audible Alert
Low Engine Oil Filter Differential Pressure    No
Warning Event Breaker #1 Trip
Low Engine Oil Filter Differential Pressure    No
Warning Event Breaker #2 Trip
Low Engine Oil Filter Differential Pressure    Yes
Warning Fault Protection Timer
Low Engine Oil Filter Differential Pressure    Activate Hard Shutdown Condition
Shutdown Event Response Config
Low Engine Oil Filter Differential Pressure    Yes
Shutdown Event Audible Alert
Low Engine Oil Filter Differential Pressure    No
Shutdown Event Breaker #1 Trip
Low Engine Oil Filter Differential Pressure    No
Shutdown Event Breaker #2 Trip
Low Engine Oil Filter Differential Pressure    Yes
Shutdown Fault Protection Timer
High Starting Air Pressure Warning Event       Activate Warning Condition
Response Configuration
High Starting Air Pressure Warning Event       Yes
Audible Alert
High Starting Air Pressure Warning Event       No
Breaker #1 Trip
High Starting Air Pressure Warning Event       No
Breaker #2 Trip
High Starting Air Pressure Shutdown Event      Activate Hard Shutdown Condition
Response Configuration
High Starting Air Pressure Shutdown Event      Yes
Audible Alert
High Starting Air Pressure Shutdown Event      No
Breaker #1 Trip
High Starting Air Pressure Shutdown Event      No
Breaker #2 Trip
Low Starting Air Pressure Warning Event        Activate Warning Condition
Response Configuration
Low Starting Air Pressure Warning Event        Yes
Audible Alert
Low Starting Air Pressure Warning Event        No
Breaker #1 Trip
Low Starting Air Pressure Warning Event    No
Breaker #2 Trip
Low Starting Air Pressure Warning Event    Yes
Fault Protection Timer
Low Starting Air Pressure Shutdown Event   Activate Hard Shutdown Condition
Response Configuration
Low Starting Air Pressure Shutdown Event   Yes
Audible Alert
Low Starting Air Pressure Shutdown Event   No
Breaker #1 Trip
Low Starting Air Pressure Shutdown Event   No
Breaker #2 Trip
Low Starting Air Pressure Shutdown Event   Yes
Fault Protection Timer
High Gas Pressure Warning Event            Activate Warning Condition
Response Configuration
High Gas Pressure Warning Event Audible    Yes
Alert
High Gas Pressure Warning Event Breaker    No
#1 Trip
High Gas Pressure Warning Event Breaker    No
#2 Trip
High Gas Pressure Shutdown Event           Activate Hard Shutdown Condition
Response Configuration
High Gas Pressure Shutdown Event           Yes
Audible Alert
High Gas Pressure Shutdown Event           No
Breaker #1 Trip
High Gas Pressure Shutdown Event           No
Breaker #2 Trip
Low Gas Pressure Warning Event             Activate Warning Condition
Response Configuration
Low Gas Pressure Warning Event Audible     Yes
Alert
Low Gas Pressure Warning Event Breaker     No
#1 Trip
Low Gas Pressure Warning Event Breaker     No
#2 Trip
Low Gas Pressure Shutdown Event            Activate Hard Shutdown Condition
Response Configuration
Low Gas Pressure Shutdown Event            Yes
Audible Alert
Low Gas Pressure Shutdown Event            No
Breaker #1 Trip
Low Gas Pressure Shutdown Event            No
Breaker #2 Trip
Engine Intake Manifold Charge              Activate Hard Shutdown Condition
Combustion Event Response Configuration
Engine Intake Manifold Charge              Yes
Combustion Event Audible Alert
Engine Intake Manifold Charge              No
Combustion Event Loss of Utility
Engine Intake Manifold Charge              No
Combustion Event Breaker #1 Trip
Engine Intake Manifold Charge              No
Combustion Event Breaker #2 Trip
Engine Intake Manifold Charge              No
Combustion Event Fault Protection Timer
High Generator Bearing #1 Temperature      Activate Warning Condition
Warning Event Response Configuration
High Generator Bearing #1 Temperature      Yes
Warning Event Audible Alert
High Generator Bearing #1 Temperature      No
Warning Event Breaker #1 Trip
High Generator Bearing #1 Temperature      No
Warning Event Breaker #2 Trip
High Generator Bearing #1 Temperature      No
Warning Event Fault Protection Timer
High Generator Bearing #1 Temperature      Activate Hard Shutdown Condition
Shutdown Event Response Configuration
High Generator Bearing #1 Temperature      Yes
Shutdown Event Audible Alert
High Generator Bearing #1 Temperature      No
Shutdown Event Breaker #1 Trip
High Generator Bearing #1 Temperature      No
Shutdown Event Breaker #2 Trip
High Generator Bearing #1 Temperature      No
Shutdown Event Fault Protection Timer
Low Generator Bearing #1 Temperature       Activate Warning Condition
Warning Event Response Configuration
Low Generator Bearing #1 Temperature       Yes
Warning Event Audible Alert
Low Generator Bearing #1 Temperature       No
Warning Event Breaker #1 Trip
Low Generator Bearing #1 Temperature       No
Warning Event Breaker #2 Trip
Low Generator Bearing #1 Temperature       Yes
Warning Event Fault Protection Timer
Low Generator Bearing #1 Temperature       Disable Condition
Shutdown Event Response Configuration
Low Generator Bearing #1 Temperature       No
Shutdown Event Audible Alert
Low Generator Bearing #1 Temperature       No
Shutdown Event Breaker #1 Trip
Low Generator Bearing #1 Temperature       No
Shutdown Event Breaker #2 Trip
Low Generator Bearing #1 Temperature       No
Shutdown Event Fault Protection Timer
Earth Fault Event Response Configuration   Activate Hard Shutdown Condition
Earth Fault Event Audible Alert            Yes
Earth Fault Event Breaker #1 Trip          No
Earth Fault Event Breaker #2 Trip          No
Generator Winding #1 High Temperature      Activate Warning Condition
Warning Event Response Configuration
Generator Winding #1 High Temperature      Yes
Warning Event Audible Alert
Generator Winding #1 High Temperature      No
Warning Event Breaker #1 Trip
Generator Winding #1 High Temperature   No
Warning Event Breaker #2 Trip
Generator Winding #1 High Temperature   No
Warning Event Fault Protection Timer
Generator Winding #2 High Temperature   Activate Warning Condition
Warning Event Response Configuration
Generator Winding #2 High Temperature   Yes
Warning Event Audible Alert
Generator Winding #2 High Temperature   No
Warning Event Breaker #1 Trip
Generator Winding #2 High Temperature   No
Warning Event Breaker #2 Trip
Generator Winding #2 High Temperature   No
Warning Event Fault Protection Timer
Generator Winding #3 High Temperature   Activate Warning Condition
Warning Event Response Configuration
Generator Winding #3 High Temperature   Yes
Warning Event Audible Alert
Generator Winding #3 High Temperature   No
Warning Event Breaker #1 Trip
Generator Winding #3 High Temperature   No
Warning Event Breaker #2 Trip
Generator Winding #3 High Temperature   No
Warning Event Fault Protection Timer
Generator Winding #1 High Temperature   Activate Hard Shutdown Condition
Shutdown Event Response Configuration
Generator Winding #1 High Temperature   Yes
Shutdown Event Audible Alert
Generator Winding #1 High Temperature   No
Shutdown Event Breaker #1 Trip
Generator Winding #1 High Temperature   No
Shutdown Event Breaker #2 Trip
Generator Winding #1 High Temperature   No
Shutdown Event Fault Protection Timer
Generator Winding #2 High Temperature   Activate Hard Shutdown Condition
Shutdown Event Response Configuration
Generator Winding #2 High Temperature   Yes
Shutdown Event Audible Alert
Generator Winding #2 High Temperature   No
Shutdown Event Breaker #1 Trip
Generator Winding #2 High Temperature   No
Shutdown Event Breaker #2 Trip
Generator Winding #2 High Temperature   No
Shutdown Event Fault Protection Timer
Generator Winding #3 High Temperature   Activate Hard Shutdown Condition
Shutdown Event Response Configuration
Generator Winding #3 High Temperature   Yes
Shutdown Event Audible Alert
Generator Winding #3 High Temperature   No
Shutdown Event Breaker #1 Trip
Generator Winding #3 High Temperature   No
Shutdown Event Breaker #2 Trip
Generator Winding #3 High Temperature   No
Shutdown Event Fault Protection Timer
Generator High Power Warning Event       Activate Warning Condition
Response Configuration
Generator High Power Warning Event       Yes
Audible Alert
Generator High Power Warning Event       No
Breaker #1 Trip
Generator High Power Warning Event       No
Breaker #2 Trip
High Ambient Air Temperature Warning     Activate Warning Condition
Event Response Configuration
High Ambient Air Temperature Warning     Yes
Event Audible Alert
High Ambient Air Temperature Warning     No
Event Breaker #1 Trip
High Ambient Air Temperature Warning     No
Event Breaker #2 Trip
High Ambient Air Temperature Warning     No
Event Fault Protection Timer
High Ambient Air Temperature Shutdown    Activate Hard Shutdown Condition
Event Response Configuration
High Ambient Air Temperature Shutdown    Yes
Event Audible Alert
High Ambient Air Temperature Shutdown    No
Event Breaker #1 Trip
High Ambient Air Temperature Shutdown    No
Event Breaker #2 Trip
High Ambient Air Temperature Shutdown    No
Event Fault Protection Timer
Low Ambient Air Temperature Warning      Activate Warning Condition
Event Response Configuration
Low Ambient Air Temperature Warning      Yes
Event Audible Alert
Low Ambient Air Temperature Warning      No
Event Breaker #1 Trip
Low Ambient Air Temperature Warning      No
Event Breaker #2 Trip
Low Ambient Air Temperature Shutdown     Disable Condition
Event Response Configuration
Low Ambient Air Temperature Shutdown     No
Event Audible Alert
Low Ambient Air Temperature Shutdown     No
Event Breaker #1 Trip
Low Ambient Air Temperature Shutdown     No
Event Breaker #2 Trip
Automatic Transfer Switch In Normal      Active Only Condition
Position Event Response Configuration
Automatic Transfer Switch In Normal      No
Position Event Audible Alert
Automatic Transfer Switch In Emergency   Active Only Condition
Position Event Response Config
Automatic Transfer Switch In Emergency   No
Position Event Audible Alert
High Battery Voltage Warning Event       Activate Warning Condition
Response Configuration
High Battery Voltage Warning Event        Yes
Audible Alert
High Battery Voltage Warning Event        No
Breaker #1 Trip
High Battery Voltage Warning Event        No
Breaker #2 Trip
High Battery Voltage Shutdown Event       Activate Soft Shutdown Condition
Response Configuration
High Battery Voltage Shutdown Event       Yes
Audible Alert
High Battery Voltage Shutdown Event       No
Breaker #1 Trip
High Battery Voltage Shutdown Event       No
Breaker #2 Trip
Low Battery Voltage Warning Event         Disable Condition
Response Configuration
Low Battery Voltage Warning Event         Yes
Audible Alert
Low Battery Voltage Warning Event         No
Breaker #1 Trip
Low Battery Voltage Warning Event         No
Breaker #2 Trip
Low Battery Voltage Warning Event Fault   No
Protection Timer
Low Battery Charging System Voltage       Disable Condition
Warning Event Response Configuration
Low Battery Charging System Voltage       No
Warning Event Audible Alert
Low Battery Charging System Voltage       No
Warning Event Breaker #1 Trip
Low Battery Charging System Voltage       No
Warning Event Breaker #2 Trip
Low Battery Charging System Voltage       No
Warning Event Fault Protection Timer
Engine In Cooldown Event Response         Active Only Condition
Configuration
Engine In Cooldown Event Audible Alert    No
Engine Speed-Generator Output Freq        Activate Warning Condition
Mismatch Warning Event Response Config
Engine Speed-Generator Output Freq        Yes
Mismatch Warning Event Audible Alert
Engine Speed-Generator Output Freq        No
Mismatch Warning Event Breaker #1 Trip
Engine Speed-Generator Output Freq        No
Mismatch Warning Event Breaker #2 Trip
High Fire Extinguisher Pressure Warning   Activate Warning Condition
Event Response Configuration
High Fire Extinguisher Pressure Warning   Yes
Event Audible Alert
High Fire Extinguisher Pressure Warning   No
Event Breaker #1 Trip
High Fire Extinguisher Pressure Warning   No
Event Breaker #2 Trip
High Fire Extinguisher Pressure Shutdown   Activate Hard Shutdown Condition
Event Response Configuration
High Fire Extinguisher Pressure Shutdown   Yes
Event Audible Alert
High Fire Extinguisher Pressure Shutdown   No
Event Breaker #1 Trip
High Fire Extinguisher Pressure Shutdown   No
Event Breaker #2 Trip
Low Fire Extinguisher Pressure Warning     Activate Warning Condition
Event Response Configuration
Low Fire Extinguisher Pressure Warning     Yes
Event Audible Alert
Low Fire Extinguisher Pressure Warning     No
Event Breaker #1 Trip
Low Fire Extinguisher Pressure Warning     No
Event Breaker #2 Trip
Low Fire Extinguisher Pressure Warning     No
Event Fault Protection Timer
Low Fire Extinguisher Pressure Shutdown    Activate Hard Shutdown Condition
Event Response Configuration
Low Fire Extinguisher Pressure Shutdown    Yes
Event Audible Alert
Low Fire Extinguisher Pressure Shutdown    No
Event Breaker #1 Trip
Low Fire Extinguisher Pressure Shutdown    No
Event Breaker #2 Trip
Low Fire Extinguisher Pressure Shutdown    No
Event Fault Protection Timer
Generator Control Not in Automatic         Disable Condition
Warning Event Response Configuration
Generator Control Not in Automatic         No
Warning Event Audible Alert
Generator Breaker Locked Out Warning       Warning & Active Only Condition
Event Response Configuration
Generator Breaker Locked Out Warning       Yes
Event Audible Alert
Generator Breaker Locked Out Warning       No
Event Breaker #1 Trip
Generator Breaker Locked Out Warning       No
Event Breaker #2 Trip
Utility Breaker Locked Out Warning Event   Warning & Active Only Condition
Response Configuration
Utility Breaker Locked Out Warning Event   Yes
Audible Alert
Utility Breaker Locked Out Warning Event   No
Breaker #1 Trip
Utility Breaker Locked Out Warning Event   No
Breaker #2 Trip
Earth Leakage Event Response               Activate Hard Shutdown Condition
Configuration
Earth Leakage Event Audible Alert          Yes
Earth Leakage Event Breaker #1 Trip        No
Earth Leakage Event Breaker #2 Trip        No
Emergency Power System Supplying Load     Warning & Active Only Condition
Event Response Configuration
Emergency Power System Supplying Load     No
Event Audible Alert
Low Cranking Voltage Warning Event        Disable Condition
Response Configuration
Low Cranking Voltage Warning Event        No
Audible Alert
Low Cranking Voltage Warning Event        No
Breaker #1 Trip
Low Cranking Voltage Warning Event        No
Breaker #2 Trip
Custom Event #1 High Warning Event        Activate Warning Condition
Response Configuration
Custom Event #1 High Warning Event        Yes
Audible Alert
Custom Event #1 High Warning Event        No
Breaker #1 Trip
Custom Event #1 High Warning Event        No
Breaker #2 Trip
Custom Event #1 High Warning Event        No
Fault Protection Timer
Custom Event #1 High Shutdown Event       Activate Hard Shutdown Condition
Response Configuration
Custom Event #1 High Shutdown Event       Yes
Audible Alert
Custom Event #1 High Shutdown Event       No
Breaker #1 Trip
Custom Event #1 High Shutdown Event       No
Breaker #2 Trip
Custom Event #1 High Shutdown Event       No
Fault Protection Timer
Custom Event #1 Low Warning Event         Activate Warning Condition
Response Configuration
Custom Event #1 Low Warning Event         Yes
Audible Alert
Custom Event #1 Low Warning Event         No
Breaker #1 Trip
Custom Event #1 Low Warning Event         No
Breaker #2 Trip
Custom Event #1 Low Warning Event Fault   No
Protection Timer
Custom Event #1 Low Shutdown Event        Activate Hard Shutdown Condition
Response Configuration
Custom Event #1 Low Shutdown Event        Yes
Audible Alert
Custom Event #1 Low Shutdown Event        No
Breaker #1 Trip
Custom Event #1 Low Shutdown Event        No
Breaker #2 Trip
Custom Event #1 Low Shutdown Event        No
Fault Protection Timer
Custom Event #1 Condition Exists Event    Active Only Condition
Response Configuration
Custom Event #1 Condition Exists Event   No
Audible Alert
Custom Event #1 Condition Exists Event   No
Loss of Utility
Custom Event #1 Condition Exists Event   No
Breaker #1 Trip
Custom Event #1 Condition Exists Event   No
Breaker #2 Trip
Custom Event #1 Condition Exists Event   No
Fault Protection Timer
Custom Event #2 High Warning Event       Activate Warning Condition
Response Configuration
Custom Event #2 High Warning Event       Yes
Audible Alert
Custom Event #2 High Warning Event       No
Breaker #1 Trip
Custom Event #2 High Warning Event       No
Breaker #2 Trip
Custom Event #2 High Warning Event       No
Fault Protection Timer
Custom Event #2 High Shutdown Event      Activate Hard Shutdown Condition
Response Configuration
Custom Event #2 High Shutdown Audible    Yes
Alert
Custom Event #2 High Shutdown Breaker    No
#1 Trip
Custom Event #2 High Shutdown Breaker    No
#2 Trip
Custom Event #2 High Shutdown Fault      No
Protection Timer
Custom Event #2 Low Warning Event        Activate Warning Condition
Response Configuration
Custom Event #2 Low Warning Audible      Yes
Alert
Custom Event #2 Low Warning Breaker #1   No
Trip
Custom Event #2 Low Warning Breaker #2   No
Trip
Custom Event #2 Low Warning Fault        No
Protection Timer
Custom Event #2 Low Shutdown Event       Activate Hard Shutdown Condition
Response Configuration
Custom Event #2 Low Shutdown Event       Yes
Audible Alert
Custom Event #2 Low Shutdown Event       No
Breaker #1 Trip
Custom Event #2 Low Shutdown Event       No
Breaker #2 Trip
Custom Event #2 Low Shutdown Event       No
Fault Protection Timer
Custom Event #2 Condition Exists Event   Active Only Condition
Response Configuration
Custom Event #2 Condition Exists Event   No
Audible Alert
Custom Event #2 Condition Exists Event    No
Loss of Utility
Custom Event #2 Condition Exists Event    No
Breaker #1 Trip
Custom Event #2 Condition Exists Event    No
Breaker #2 Trip
Custom Event #2 Condition Exists Event    No
Fault Protection Timer
Custom Event #3 High Warning Event        Activate Warning Condition
Response Configuration
Custom Event #3 High Warning Event        Yes
Audible Alert
Custom Event #3 High Warning Event        No
Breaker #1 Trip
Custom Event #3 High Warning Event        No
Breaker #2 Trip
Custom Event #3 High Warning Event        No
Fault Protection Timer
Custom Event #3 High Shutdown Event       Activate Hard Shutdown Condition
Response Configuration
Custom Event #3 High Shutdown Event       Yes
Audible Alert
Custom Event #3 High Shutdown Event       No
Breaker #1 Trip
Custom Event #3 High Shutdown Event       No
Breaker #2 Trip
Custom Event #3 High Shutdown Event       No
Fault Protection Timer
Custom Event #3 Low Warning Event         Activate Warning Condition
Response Configuration
Custom Event #3 Low Warning Event         Yes
Audible Alert
Custom Event #3 Low Warning Event         No
Breaker #1 Trip
Custom Event #3 Low Warning Event         No
Breaker #2 Trip
Custom Event #3 Low Warning Event Fault   No
Protection Timer
Custom Event #3 Low Shutdown Event        Activate Hard Shutdown Condition
Response Configuration
Custom Event #3 Low Shutdown Event        Yes
Audible Alert
Custom Event #3 Low Shutdown Event        No
Breaker #1 Trip
Custom Event #3 Low Shutdown Event        No
Breaker #2 Trip
Custom Event #3 Low Shutdown Event        No
Fault Protection Timer
Custom Event #3 Condition Exists Event    Active Only Condition
Response Configuration
Custom Event #3 Condition Exists Event    No
Audible Alert
Custom Event #3 Condition Exists Event    No
Loss of Utility
Custom Event #3 Condition Exists Event    No
Breaker #1 Trip
Custom Event #3 Condition Exists Event    No
Breaker #2 Trip
Custom Event #3 Condition Exists Event    No
Fault Protection Timer
Custom Event #4 High Warning Event        Activate Warning Condition
Response Configuration
Custom Event #4 High Warning Event        Yes
Audible Alert
Custom Event #4 High Warning Event        No
Breaker #1 Trip
Custom Event #4 High Warning Event        No
Breaker #2 Trip
Custom Event #4 High Warning Event        No
Fault Protection Timer
Custom Event #4 High Shutdown Event       Activate Hard Shutdown Condition
Response Configuration
Custom Event #4 High Shutdown Event       Yes
Audible Alert
Custom Event #4 High Shutdown Event       No
Breaker #1 Trip
Custom Event #4 High Shutdown Event       No
Breaker #2 Trip
Custom Event #4 High Shutdown Event       No
Fault Protection Timer
Custom Event #4 Low Warning Event         Activate Warning Condition
Response Configuration
Custom Event #4 Low Warning Event         Yes
Audible Alert
Custom Event #4 Low Warning Event         No
Breaker #1 Trip
Custom Event #4 Low Warning Event         No
Breaker #2 Trip
Custom Event #4 Low Warning Event Fault   No
Protection Timer
Custom Event #4 Low Shutdown Event        Activate Hard Shutdown Condition
Response Configuration
Custom Event #4 Low Shutdown Event        Yes
Audible Alert
Custom Event #4 Low Shutdown Event        No
Breaker #1 Trip
Custom Event #4 Low Shutdown Event        No
Breaker #2 Trip
Custom Event #4 Low Shutdown Event        No
Fault Protection Timer
Custom Event #4 Condition Exists Event    Active Only Condition
Response Configuration
Custom Event #4 Condition Exists Event    No
Audible Alert
Custom Event #4 Condition Exists Event    No
Loss of Utility
Custom Event #4 Condition Exists Event    No
Breaker #1 Trip
Custom Event #4 Condition Exists Event    No
Breaker #2 Trip
Custom Event #4 Condition Exists Event    No
Fault Protection Timer
Custom Event #5 High Warning Event        Activate Warning Condition
Response Configuration
Custom Event #5 High Warning Event        Yes
Audible Alert
Custom Event #5 High Warning Event        No
Breaker #1 Trip
Custom Event #5 High Warning Event        No
Breaker #2 Trip
Custom Event #5 High Warning Event        No
Fault Protection Timer
Custom Event #5 High Shutdown Event       Activate Hard Shutdown Condition
Response Configuration
Custom Event #5 High Shutdown Event       Yes
Audible Alert
Custom Event #5 High Shutdown Event       No
Breaker #1 Trip
Custom Event #5 High Shutdown Event       No
Breaker #2 Trip
Custom Event #5 High Shutdown Event       No
Fault Protection Timer
Custom Event #5 Low Warning Event         Activate Warning Condition
Response Configuration
Custom Event #5 Low Warning Event         Yes
Audible Alert
Custom Event #5 Low Warning Event         No
Breaker #1 Trip
Custom Event #5 Low Warning Event         No
Breaker #2 Trip
Custom Event #5 Low Warning Event Fault   No
Protection Timer
Custom Event #5 Low Shutdown Event        Activate Hard Shutdown Condition
Response Configuration
Custom Event #5 Low Shutdown Event        Yes
Audible Alert
Custom Event #5 Low Shutdown Event        No
Breaker #1 Trip
Custom Event #5 Low Shutdown Event        No
Breaker #2 Trip
Custom Event #5 Low Shutdown Event        No
Fault Protection Timer
Custom Event #5 Condition Exists Event    Active Only Condition
Response Configuration
Custom Event #5 Condition Exists Event    No
Audible Alert
Custom Event #5 Condition Exists Event    No
Loss of Utility
Custom Event #5 Condition Exists Event    No
Breaker #1 Trip
Custom Event #5 Condition Exists Event    No
Breaker #2 Trip
Custom Event #5 Condition Exists Event    No
Fault Protection Timer
Custom Event #6 High Warning Event        Activate Warning Condition
Response Configuration
Custom Event #6 High Warning Event        Yes
Audible Alert
Custom Event #6 High Warning Event        No
Breaker #1 Trip
Custom Event #6 High Warning Event        No
Breaker #2 Trip
Custom Event #6 High Warning Event        No
Fault Protection Timer
Custom Event #6 High Shutdown Event       Activate Hard Shutdown Condition
Response Configuration
Custom Event #6 High Shutdown Event       Yes
Audible Alert
Custom Event #6 High Shutdown Event       No
Breaker #1 Trip
Custom Event #6 High Shutdown Event       No
Breaker #2 Trip
Custom Event #6 High Shutdown Event       No
Fault Protection Timer
Custom Event #6 Low Warning Event         Activate Warning Condition
Response Configuration
Custom Event #6 Low Warning Event         Yes
Audible Alert
Custom Event #6 Low Warning Event         No
Breaker #1 Trip
Custom Event #6 Low Warning Event         No
Breaker #2 Trip
Custom Event #6 Low Warning Event Fault   No
Protection Timer
Custom Event #6 Low Shutdown Event        Activate Hard Shutdown Condition
Response Configuration
Custom Event #6 Low Shutdown Event        Yes
Audible Alert
Custom Event #6 Low Shutdown Event        No
Breaker #1 Trip
Custom Event #6 Low Shutdown Event        No
Breaker #2 Trip
Custom Event #6 Low Shutdown Event        No
Fault Protection Timer
Custom Event #6 Condition Exists Event    Active Only Condition
Response Configuration
Custom Event #6 Condition Exists Event    No
Audible Alert
Custom Event #6 Condition Exists Event    No
Loss of Utility
Custom Event #6 Condition Exists Event    No
Breaker #1 Trip
Custom Event #6 Condition Exists Event    No
Breaker #2 Trip
Custom Event #6 Condition Exists Event    No
Fault Protection Timer
Custom Event #7 High Warning Event        Activate Warning Condition
Response Configuration
Custom Event #7 High Warning Event        Yes
Audible Alert
Custom Event #7 High Warning Event        No
Breaker #1 Trip
Custom Event #7 High Warning Event        No
Breaker #2 Trip
Custom Event #7 High Warning Event        No
Fault Protection Timer
Custom Event #7 High Shutdown Event       Activate Hard Shutdown Condition
Response Configuration
Custom Event #7 High Shutdown Event       Yes
Audible Alert
Custom Event #7 High Shutdown Event       No
Breaker #1 Trip
Custom Event #7 High Shutdown Event       No
Breaker #2 Trip
Custom Event #7 High Shutdown Event       No
Fault Protection Timer
Custom Event #7 Low Warning Event         Activate Warning Condition
Response Configuration
Custom Event #7 Low Warning Event         Yes
Audible Alert
Custom Event #7 Low Warning Event         No
Breaker #1 Trip
Custom Event #7 Low Warning Event         No
Breaker #2 Trip
Custom Event #7 Low Warning Event Fault   No
Protection Timer
Custom Event #7 Low Shutdown Event        Activate Hard Shutdown Condition
Response Configuration
Custom Event #7 Low Shutdown Event        Yes
Audible Alert
Custom Event #7 Low Shutdown Event        No
Breaker #1 Trip
Custom Event #7 Low Shutdown Event        No
Breaker #2 Trip
Custom Event #7 Low Shutdown Event        No
Fault Protection Timer
Custom Event #7 Condition Exists Event    Active Only Condition
Response Configuration
Custom Event #7 Condition Exists Event    No
Audible Alert
Custom Event #7 Condition Exists Event    No
Loss of Utility
Custom Event #7 Condition Exists Event    No
Breaker #1 Trip
Custom Event #7 Condition Exists Event    No
Breaker #2 Trip
Custom Event #7 Condition Exists Event    No
Fault Protection Timer
Custom Event #8 High Warning Event        Activate Warning Condition
Response Configuration
Custom Event #8 High Warning Event        Yes
Audible Alert
Custom Event #8 High Warning Event        No
Breaker #1 Trip
Custom Event #8 High Warning Event        No
Breaker #2 Trip
Custom Event #8 High Warning Event        No
Fault Protection Timer
Custom Event #8 High Shutdown Event       Activate Hard Shutdown Condition
Response Configuration
Custom Event #8 High Shutdown Event       Yes
Audible Alert
Custom Event #8 High Shutdown Event       No
Breaker #1 Trip
Custom Event #8 High Shutdown Event       No
Breaker #2 Trip
Custom Event #8 High Shutdown Event       No
Fault Protection Timer
Custom Event #8 Low Warning Event         Activate Warning Condition
Response Configuration
Custom Event #8 Low Warning Event         Yes
Audible Alert
Custom Event #8 Low Warning Event         No
Breaker #1 Trip
Custom Event #8 Low Warning Event         No
Breaker #2 Trip
Custom Event #8 Low Warning Event Fault   No
Protection Timer
Custom Event #8 Low Shutdown Event        Activate Hard Shutdown Condition
Response Configuration
Custom Event #8 Low Shutdown Event        Yes
Audible Alert
Custom Event #8 Low Shutdown Event        No
Breaker #1 Trip
Custom Event #8 Low Shutdown Event        No
Breaker #2 Trip
Custom Event #8 Low Shutdown Event        No
Fault Protection Timer
Custom Event #8 Condition Exists Event    Active Only Condition
Response Configuration
Custom Event #8 Condition Exists Event    No
Audible Alert
Custom Event #8 Condition Exists Event    No
Loss of Utility
Custom Event #8 Condition Exists Event    No
Breaker #1 Trip
Custom Event #8 Condition Exists Event    No
Breaker #2 Trip
Custom Event #8 Condition Exists Event    No
Fault Protection Timer
Event Warning Condition Response Auto     Enabled
Reset Enable Status
Event Audible Alert Response Auto Reset   Enabled
Enable Status
Event Loss Of Utility Response Auto Reset    Enabled
Enable Status
Event Breaker #1 Trip Response Auto          Enabled
Reset Enable Status
Event Breaker #2 Trip Response Auto          Enabled
Reset Enable Status
Generator Connection Configuration           Wye (or Star) Connection
Generator Potential Transformer Primary      7200                        Volts
Winding Rating
Generator Potential Transformer              240                         Volts
Secondary Winding Rating
Generator Current Transformer Primary        300                         Amps
Winding Rating
Generator Current Transformer Secondary      5                           Amps
Winding Rating
Number of Generator Poles                    4                           Poles
Generator Rated Frequency                    50 Hz
Generator Rated Voltage                      6000                        Volts
Generator Rated Power                        1820                        kW
Generator Rated Apparent Power               2275                        kVA
Maximum Engine Speed Bias                    400                         rpm
Generator Nominal Output Frequency           50.0                        Hz
Electronic Control Module Reduced Power      Disabled
Mode Enable Status
Electronic Control Module Reduced Power      30                          min
Mode Delay Time
Relay Output #1 Active State Configuration   High
Relay Output #2 Active State Configuration   High
Relay Output #3 Active State Configuration   High
Relay Output #4 Active State Configuration   High
Relay Output #5 Active State Configuration   High
Relay Output #6 Active State Configuration   High
Programmable Trip Point Function #1          Disabled or Not Installed
Trigger Condition
Programmable Trip Point Function #1          Disabled or Not Installed   %
Percentage Threshold
Programmable Trip Point Function #1          Disabled or Not Installed   %
Hysteresis Percentage
Programmable Trip Point Function #1 Trip     Disabled or Not Installed   sec
Activation Delay Time
Programmable Trip Point Function #1 Trip     Disabled or Not Installed   sec
Deactivation Delay Time
Programmable Trip Point Function #2          Disabled or Not Installed
Trigger Condition
Programmable Trip Point Function #2          Disabled or Not Installed   %
Percentage Threshold
Programmable Trip Point Function #2          Disabled or Not Installed   %
Hysteresis Percentage
Programmable Trip Point Function #2 Trip     Disabled or Not Installed   sec
Activation Delay Time
Programmable Trip Point Function #2 Trip     Disabled or Not Installed   sec
Deactivation Delay Time
Programmable Trip Point Function #3        Disabled or Not Installed
Trigger Condition
Programmable Trip Point Function #3        Disabled or Not Installed                %
Percentage Threshold
Programmable Trip Point Function #3        Disabled or Not Installed                %
Hysteresis Percentage
Programmable Trip Point Function #3 Trip   Disabled or Not Installed                sec
Activation Delay Time
Programmable Trip Point Function #3 Trip   Disabled or Not Installed                sec
Deactivation Delay Time
Programmable Trip Point Function #4        Disabled or Not Installed
Trigger Condition
Programmable Trip Point Function #4        Disabled or Not Installed                %
Percentage Threshold
Programmable Trip Point Function #4        Disabled or Not Installed                %
Hysteresis Percentage
Programmable Trip Point Function #4 Trip   Disabled or Not Installed                sec
Activation Delay Time
Programmable Trip Point Function #4 Trip   Disabled or Not Installed                sec
Deactivation Delay Time
Engine Serial Number                       Not Programmed
Display Pressure Units Configuration       psi
Display Temperature Units Configuration    Degrees Centigrade (Celsius)
Display Volume Units Configuration         liters
Digital Voltage Regulator
Parameter                                       Value
ECM Part Number                                 3147755-00
ECM Serial Number                               34816053GD
Software Group Part Number                      3184763-01
Software Group Release Date                     NOV2007
Software Group Description                      Regulator Software
Logged Diagnostic Codes [SHM: 599] - Digital Voltage Regulator
Code           Description               Occ.   SHM First   SHM Last    RTC First       RTC Last
No Logged
Diagnostic
Codes
Logged Event Codes [SHM: 599] - Digital Voltage Regulator
Code           Description              Occ.    SHM First   SHM Last    RTC First       RTC Last
611- 0         System Diagnostic Code 24        1:24:00     2:00:00     1/1/2000        1/1/2000
               #1 : High - most severe                                  12:00:19        12:00:09
               (3)                                                      AM              AM
2456-17        Generator Total Reactive 99      57:15:00    435:36:00   1/1/2000        1/12/2000
               Power : Low - least                                      12:50:49        9:20:25 AM
               severe (1)                                               AM
Active Diagnostic Codes [SHM: 599] - Digital Voltage Regulator
Code          Description                                                                   Occ.
No Active
Diagnostic
Codes
Active Event Codes [SHM: 599] - Digital Voltage Regulator
Code        Description                                                          Occ.
No Active
Event Codes
Configuration - Digital Voltage Regulator
Description                                 Value                        Unit
Voltage Regulator Power Input Frequency     200                          Hz
Configuration
Potential Transformer Primary Winding       6000                         Volts
Rating
Potential Transformer Secondary Winding     400                          Volts
Rating
Current Transformer Primary Winding         300                          Amps
Rating
Current Transformer Secondary Winding       5                            Amps
Rating
Generator Connection Configuration          Three Phase
Generator Rated Frequency                   50 Hz
Generator Rated Voltage                     6000                         Volts
Generator Rated Current                     208                          Amps
Voltage Regulator Loss of Sensing           2.0                          sec
Shutdown Event Notification Delay Time
Generator Rotating Diode Monitor            2.0                          Amps
Shutdown Event Current Threshold
Generator Reverse VAr Shutdown Event        10                           %
Percentage Threshold
Generator Reverse VAr Shutdown Event        3.0                          sec
Notification Delay Time
Generator Reverse VAr Shutdown Event        Activate Warning Condition
Response Configuration
Generator Over Voltage Shutdown Event       135                          %
Percentage Threshold
Generator Over Voltage Shutdown Event       2                            sec
Notification Delay Time
Generator Over Voltage Shutdown Event       Activate Warning Condition
Response Configuration
Generator Under Voltage Shutdown Event      60                           %
Percentage Threshold
Generator Under Voltage Shutdown Event      30                           sec
Notification Delay Time
Generator Under Voltage Shutdown Event      Activate Warning Condition
Response Configuration
Voltage Regulator Over Excitation           12.0                         Amps
Shutdown Event Threshold
Voltage Regulator Over Excitation           10.0                         sec
Shutdown Event Notification Delay Time
Voltage Regulator Over Excitation           Definite Time
Shutdown Event Notification Delay Type
Voltage Regulator Fault Reset Switch        Activate Warning Condition
Diagnostic Response Configuration
Generator Nominal Output Voltage            6000                         Volts
Voltage Regulator Corner (Knee)              49.8             Hz
Frequency
Voltage Regulator Deviation From Corner      5.0              Hz
(Knee) Frequency
Voltage Regulator Volts/Hz Slope 1           2.0              V/Hz
Voltage Regulator Volts/Hz Slope 2           2.0              V/Hz
Voltage Regulator Minimum Voltage            50.0             %
Setpoint Percentage
Voltage Regulator Minimum Frequency          33.0             Hz
Threshold
Voltage Regulator Maximum Droop              0.0              %
Percentage
Voltage Regulator Voltage (IR)               0.0              %
Compensation Percentage
Voltage Regulator Starting Time              5.0              sec
Voltage Regulator Starting Voltage Percent   10.0             %
Voltage Regulator Noise Filter Time          0.00             sec
Constant
Voltage Regulation Proportional Gain         20.00            %
Percentage
Voltage Regulation Integral Gain             60.00            %
Percentage
Voltage Regulation Derivative Gain           3.00             %
Percentage
Voltage Regulator Gain Setting Selection     7
Number
Voltage Regulator Gain Setting Type          User Defined
Configuration
Voltage Regulator Loop Gain Percentage       5.00             %
Maximum Generator Voltage Output Bias        15               %
Percentage Setpoint
Desired Voltage Input Configuration          Invalid Data
Generator Nominal Output Power Factor        1.00
Voltage Regulator Nominal Reactive Power     0.0              %
Percentage
Generator Power Factor Controller Loop       0.30             %
Gain Percentage
Generator Power Factor Controller Integral   0.50             %
Gain Percentage
Voltage Regulator Load Compensation          Off
Type Configuration
Voltage Regulator Power Factor/VAr           Reactive Power
Controller Mode Selection
Voltage Regulator Desired Power Factor       Lagging
Configuration
Generator VAr Controller Loop Gain           0.25             %
Percentage
Generator VAr Controller Integral Gain       0.50             %
Percentage
VAr / Power Factor Control Input             Invalid Data
Configuration