Solis-80K-5G, Solis-100K-HV-5G
Solis-110K-BHV-5G
Solis Three Phase Inverters
360 degree
Features:
▶▶ Over 99% Max. effciency
▶▶ Wide voltage range and low startup voltage
▶▶ 9/10 MPPT design with precise MPPT algorithm
▶▶ THDi<3%, low harmonic distortion against grid
▶▶ Anti-resonance, supporting over 6MW parallelled in one transformer
▶▶ Perfect commercial site monitoring solution
▶▶ Intelligent redundant fan-cooling
567mm
▶▶ Strings intelligent monitoring, Smart I-V Curve Diagnosis
supported
▶▶ Fuse free design to avoid fire hazard
▶▶ Type II surge arrester for both DC and AC, type I surge arrestor optional 1050mm 314.5mm
▶▶ Leakage current repression technology
▶▶ Volt-watt work mode integrated Model:
▶▶ DC input reverse alarm 400V: Solis-80K-5G
▶▶ Optional anti-PID function integrated 480V: Solis-100K-HV-5G
▶▶ Integrated DC switches, AC switch optional 540V: Solis-110K-BHV-5G
Datasheet
Model Name Solis-80K-5G Solis-100K-HV-5G Solis-110K-BHV-5G
Input DC
Max. input voltage 1100V
Rated voltage 600V
Start-up voltage 195V
MPPT voltage range 180-1000V
Max. input current 9*26A 10*26A
Max. short circuit current 9*40A 10*40A
MPPT number/Max. input strings number 9/18 10/20
Output AC
Rated output power 80kW 100kW 110kW
Max. apparent output power 88kVA 110kVA 121kVA
Max. output power 88kW 110kW 121kW
Rated grid voltage 3/N/PE, 220/380V, 230/400V 3/PE, 480V 3/PE, 540V
Rated grid frequency 50/60Hz
Rated grid output current 121.6A 120.3A 117.6A
Max. output current 133.7A 132.3A 129.4A
Power Factor >0.99 (0.8 leading - 0.8 lagging)
THDi <3%
Efficiency
Max. efficiency 98.7% 99.0%
EU efficiency 98.3% 98.5%
Protection
DC reverse-polarity protection Yes
Short circuit protection Yes
Output over current protection Yes
Surge protection DC Type II / AC Type II (AC Type I optional)
Grid monitoring Yes
Anti-islanding protection Yes
Strings monitoring Yes
I/V Curve scanning Yes
Anti-PID function Optional
Integrated AFCI (DC arc-fault circuit protection) Optional
Integrated DC switch Yes
Integrated AC switch Optional
General Data
Dimensions (W*H*D) 1050*567*314.5 mm (with AC switch)
Weight 82kg
Topology Transformerless
Self consumption <2W (night)
Operating ambient temperature range -25 ~ +60°C
Relative humidity 0-100%
Ingress protection IP66
Cooling concept Intelligent redundant fan-cooling
Max. operation altitude 4000m
VDE-AR-N 4105, VDE V 0124, VDE V 0126-1-1, UTE C15-712-1, NRS 097-1-2, G98, G99,
Grid connection standard
EN 50549-1/-2, RD 1699, UNE 206006, UNE 206007-1, IEC 61727, DEWA
Safety/EMC standard IEC 62109-1/-2, IEC 62116, EN 61000-6-2/-4
Features
DC connection MC4 connector
AC connection OT terminal (max. 185 mm²)
Display LCD, 2×20 Z
Communication RS485, Optional: Wi-Fi, GPRS, PLC
Sold in India by: Loop Solar | Ph: 9971136369 | E: [email protected] | W: www.loopsolar.com