Iocl City Gas Distribution Project For GA

This document provides a 3-page datasheet for a 5KVA UPS system with model MF1106L16 from Oval Projects Engineering Pvt. Ltd. The UPS has a 5kVA/4kW power rating and uses an online double conversion design with DSP controlled PWM technology. It can provide backup power for a minimum of 4 hours under a 2x5KVA parallel redundant configuration. The UPS has monitoring and communication capabilities.

Uploaded by

subudhiprasanna
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
233 views4 pages

Iocl City Gas Distribution Project For GA

This document provides a 3-page datasheet for a 5KVA UPS system with model MF1106L16 from Oval Projects Engineering Pvt. Ltd. The UPS has a 5kVA/4kW power rating and uses an online double conversion design with DSP controlled PWM technology. It can provide backup power for a minimum of 4 hours under a 2x5KVA parallel redundant configuration. The UPS has monitoring and communication capabilities.

Uploaded by

subudhiprasanna
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

OVAL PROJECTS ENGINEERING PVT. LTD.

Milan Chakra,Badharghat
Agartala,799003
9650243616
[email protected]

PROJECT
IOCL CITY GAS DISTRIBUTION PROJECT FOR BOKARO GA
TITLE:

DOCUMENT
UPS DATA SHEET
TITLE:
DOCUMENT Rev. No. 0
OVAL/CGS/BOKARO/029
NO.:
DATA SHEET Pages 3
MF1106L16-5KVA-31
No.

OWNER: INDIAN OIL CORPORATION LTD

CONSULTANT: TRACTEBEL ENGINEERING PVT. LTD

CONTRACTOR: OVAL PROJECTS ENGINEERING PVT. LTD.

BEST POWER HIMANGS


0 13.10.2020 Issued for Approval PANKAJ
EQUIPMENTS HU

Rev Prepared Checked Reviewed Approved


Date Description Vendor Name
No. By By By By
GUARANTEED TECHNICAL PARTICULARS
Product Datasheet: 3-Phase Input &
1-Phase Output 5KVA UPS
GENERAL INFORMATION

Power Rating kVA/kW 5 / 4


Model MF1106L16
On-Line Double Conversion using DSP
Technology controlled PWM
Bypass Static& Static & Manual Bypass as inbuilt
Manual
Cold Start Available Starting of UPS on DC mode without
mains mode & vice versa
Auto-start Capability of getting ON after mains
Available resuming under complete shutdown
on battery mode
Generator Compatibility Available DG Set Power supply as input under
raw mains failure
P Parallel Redundancy Capability Project Specific: 2Nos
Design Specific: 4Nos
Operating temperature °C 0 ~ 45
Storage temperature °C -10 ~ +70
Relative humidity (non-condensing) % < 95
Altitude m <1000m above MSL No Derating
Cooling / Ventilation Forced
Audible noise level (according EN 50091) dB < 60dB
Protection degree IP42 (Project Specific)
IP20 (Default Design Specific) )
Colour Texture RAL 9005 / RAL7032
Accessibility (Service) Front & Rear
Cable Entry Rear Bottom
MS Sheet Thickness Cover & Door 1.2mm ; Base structure 1.5mm
Dimension with IP42 Enclosure( Approx.) mm W=600 D =650 H =950
Communication Interface RS-232 with power
management software &
MODBUS
Design Standard General & Safety : IEC/EN 62040-1
EMC Requirements: IEC/EN62040-2
Test & Performance: IEC/EN 62040-3
Manufacturing Standard QMS: ISO9001:2015
EMS: ISO14001:2015
OHSAS: 18001:2007

MF1106-5K DATASHEET

1
BLOCK DIAGRAM

UPS INPUT: RECTIFIER / CHARGER


Input 3-Phase+N
Nominal input Vac
380, 400, 415 (+ 25%, -25%)
voltage Range %

Nominal Frequency Hz 50
Frequency Range 45-55Hz ( Auto sensing)
Input power factor ≥ 0.80
DC output voltage accuracy % ±1%
Walk-in time duration s 5~60
DC output voltage ripple % rms ≤1%
AC-DC converter type IGBT Based
Input protection Breaker
Rectifier Efficiency % 98%

BATTERY

Type standard 2V Cell Sealed Maintenance Free


±108VDC
Nominal VDC Volt Also Configurable ±96VDC & ±120VDC
Floating voltage Volt 2.25VDC/cell
Minimum discharge voltage Volt 1.75VDC/cell
Charging Current Amp 10A Max

2
MF1106-5K DATASHEET
Typical Recharge Time 6-8Hrs to 90% full capacity
Over/under voltage, EOD, Boost
Battery protection
charge overtime
Min 4Hrs under 2 x 5KVA Parallel
Back up time
Redundant Configuration i.e 2Hrs
with each individual UPS
80AH/2V x 108 Nos with Each
Battery Bank
Individual UPS
Battery Make Exide

UPS OUTPUT: INVERTER


Nominal output voltage (selectable) V 220V / 230V / 240VAC, 1P +N
Power Factor 0.8
Voltage Regulation % ± 1%
Frequency Mains Mode: Autosensing with input
Hz
Battery Mode: 50Hz± 0.1Hz
THDv % < 5% @ 100% linear load
Overload Capability % ≤125% for 10Mins
≤ 150% for 1Min
Efficiency % >90%

Short circuit characteristic UPS Shutdown Output

Output waveform Sinusoidal

MONITORING
LOCAL ON FRONT PANEL
 LCD Display for measuring parameters : Input Voltage & Frequency, Output Voltage &
Frequency, Bypass Voltage & Frequency, Load % / KVA/KW, Battery
Voltage ,Charging / Discharging
 LED indications for Mains Mode, Battery Mode, Bypass Mode & Fault Conditions
 Keypad ON/OFF, UP/DN

PARAMETER SETTINGS

Mode Setting, O/P Voltage & Frequency Setting, Battery Capacity & Numbers Setting, Buzzer
Mute Setting, Parallel ID/Qty/Redundancy Setting

ALARMS & PROTECTIONS


Short Circuit, Input Under/Over Voltage, Over Current, Over Load, DC BUS Under / Over
Voltage and Battery low

MF1106-5K DATASHEET 3