Voltage Stability Conditions Considering Cwuzacteristics Pal, Senior Member Public Service Electric and Gas Company Newark, N.J
Voltage Stability Conditions Considering Cwuzacteristics Pal, Senior Member Public Service Electric and Gas Company Newark, N.J
Abstract: It is shown that when the characteristic of as follows: Assuming that an equilibrium, satisfying
the composite load of a typical utility system is taken the operating constraints, i.e. a viable power flow
into account, large disturbance voltage stability is solution exists, the equilibrium state is steady-state
assured by the existence of the stable equilibrium (small signal) stable if all the eigenvalues of the
state of the post-disturbance system, as determined system, linearized around the operating point, have
from the standard power flow model. When the load negative real parts. Large disturbance stability is
contains static components, stability limits extend assured if the system state at the end of the disturb-
considerably. The exact limit for such loads can also ance lies within the region of attraction of the stable
be determined from a power flow model, properly equilibrium point of the post-disturbance system.
modified to reflect the static component of the load. Voltage instability is primarily a small signal
In specific situations, when the bulk of the load is phenomenon. In the brief period following a large
composed of fast response loads, a correct assessment disturbance most loads behave as static loads, e.g.
of voltage stability would require comprehensive constant impedance or, at worst, constant current. It
analyses, employing detailed dynamic models of all has been recognized that for such loads voltage insta-
system components. The use of the conventional power bility cannot occur. By the time the load dynamics
flow model may lead to considerable error. start having any impact on the system response, the
disturbance would have reached the small signal status,
Kewords: Voltage Stability, Voltage Collapse, Load provided of course, synchronous stability has been
Characteristics. maintained. This would be particularly true for compo-
site loads in a large utility system. Therefore, it is
INTRODUCTION only necessary to assure small signal stability of the
final post-disturbance system. A rigorous justification
The existing and continuing trend toward heavier supporting this view will be provided in this paper.
line loadings has resulted in an increased need for
reactive power management, and raised the possibilities Voltage instability is largely determined by load
of voltage instability and collapse. Concerns for characteristics and the available means of voltage
voltage instability and collapse are prompting control. For true voltage instability, at least a part
utilities to better understand the phenomenon so as to of the total load must be of self-restoring (constant
devise effective, efficient and economic solutions to MVA) type. By the same token, voltage stability prob-
the problem. The problem of reactive power and voltage lems become less severe as static or voltage sensitive
control, i.e. maintaining an acceptable system voltage loads constitute a portion of the total load. The
profile by providing adequate reactive supports at precise determination of the stability limit for such
appropriate locations so as to meet system reactive loads is demonstrated in the paper.
need efficiently, is well U erstood and reported
extensively in the literature'-' It is not, however, SYSTEM AND LOAD MODEL
well appreciated that maintaining a good voltage pro-
file does not automatically guarantee voltage stabili- We will adopt the prevailing view that voltage col-
tr, and that voltage instability need not be associated lapse is a relatively slow process and, therefore, it
with low voltages, although frequently it is. can be (although it need not be) studied in isolation,
i.e. by separating it from the angle (synchronous)
Traditional methods of voltage stability investiga- stability aspects. We will concentrate only on the
tion, for example, 1 3 ) - [ 7 ] , have relied on static ana- dynamics that are likely to have appreciable impacts on
lyses using the conventional power flow model. Defini- voltage stability. The dynamics that affect voltage
tions and tests for voltage instability have been pro- stability are the dynamics of the load and the dynamics
posed accordingly. Such analyses will, however, deter- of the voltage control devices, especially those of the
mine the power limit, which may or may not be indicat- generator excitation controls.
ive of voltage stability limit. We note that only a
dynamic system can experience instability. Voltage Important insights into the mechanisms of voltage
instability is load driven. In a voltage stability instability and collapse can be obtained through the
analysis it is, therefore, imperative that a dynamic use of a simplified model, incorporating only the
system formulation, including the pertinent load dyna- elements that are dominant in controlling these mecha-
mics, be employed. We will follow the well established nisms. The conclusions drawn from the simplified
procedures for assessing stability of dynamic systems. analysis can then be verified by detailed simulations.
In simple terms the stability conditions may be stated The power system we will analyze is shown in Figure 1.
A single generator is supplying a load over a trans-
mission line. For simplicity, all resistances and line
91 SM 490-3 PWRS A paper recommended and approved chargings have been neglected. However, any reactive
by the IEEE Power System Engineering Committee of support that might be present at the load end of the
the IEEE Power Engineering Society for presentation transmission ljne has been included.
at the IEEE/PES 1991 Summer Meeting, San Diego,
California, July 28 - August 1, 1991. Manuscript It has been recognized that the most stringent load
submitted February 1, 1991; made available for from the viewpoint of voltage stability is the load
printing May 29, 1991. that maintains a constant MVA characteristic, either
due to the nature of the load itself or due to the
action of control mechanisms that are intended to main-
tain constant voltage at the load supply point, such as
LTC's, distribution voltage regulators, etc., thereby
rendering any load constant MVA. (Note that even with-
0885-8950/92$03.oOo1992IEEE
244
an unstable equilibrium point. This may be verified by
linearizing equation (1) around the equilibrium points,
and applying the condition for stability.
vs I!? jx j B 1 VL
T VL(l-BX) VL pI
“Lo
1.0 -
tn
Fig.1 A power system with constant source voltage c,
rl C
supplying a load through a transmission s!
line. The phasor diagram applies to a unity
power factor load.
0.5 -
out voltage control action, certain apparently static
loads, such as thermostatically controlled heating
loads, due to their constant energy consumptions, tend 0.5 Po 1.0
to behave as constant MVA loads in the longer term.) Power
We will, therefore, concentrate primarily on constant
MVA loads, and show the effect on voltage stability
when parts of the load possess characteristics other Fig.2 Power-Voltagecurve Of shown in Fig.1.
than constant MVA, such as constant impedance.
It will be shown that if the state reached at the
In a voltage stability analysis, it is important to end of the disturbance lies anywhere on the portion
model the relevant dynamics of the load. Employing a V ACB of the P-V curve, the post-disturbance system
static model for constant MVA loads can lead to errone- w h be stable, i.e. the operating point will settle
ous and, often, misleading results. A constant MVA load at the stable equilibrium point A. The region V ACB,
is not a static load. This means, it cannot jump
instantaneously from one demand level to another as the
i.e. the region of the P-V curve to the right the 3
unstable equilibrium point is the region of attraction
demand changes. Following a change in the demand, the of the stable equilibrium point of the post-disturbance
load will at first change according to its instantane- system.
ous characteristic such as, constant impedance or
current. It will then adjust the current drawn from
the system until the load supplied by the system satis- From the phasor diagram (Fig.1)’
fies the demand at the final system voltage. Similarly,
when there is a sudden change in the system voltage, 2 VS2
such as, following a disturbance, the load will change
momentarily. It will then adjust the current (or imped- vL - (1-BX)’ + G2X2
ance) and draw, from the system, whatever current is
necessary in order to satisfy the demand. The process Equation therefore, be expressed as
is not instantaneous. A definite time lag is involved.
A load model, in order to be suitable for voltage d PoX2(G-Glo)(G-G20)
stabtlity analysis, must recognize this basic fact. T-G-
Ldt (1-BX)2 + G2X2
For our purpose, the dynamic behavior of constant
MVA load may be represented by a simple first order where,
delay model. Several forms of this model are given in
2
[ 8 ] - [ 9 ] . For simplicity, we will assume a unity power Vs 5 JVs4 - 4P02X2(l-BX)2
factor load, whose dynamics may be represented by
Glo,20 2P0X2
d
T - G
Ldt
- Po - VLLG (1) The two values of G correspond to the two voltage
solutions for the given power P . In Figure 2, these
where two solutions correspond to the“ equilibrium points B
V is the load voltage and A, respectively. The two voltage solutions are:
PL is the power set point
Go is the load conductance which is adjusted to
maintain constant power Vs 2 +_ 4VS4 - 4P02X2(l-BX)2
T is the load time constant
L v-2
L
- 2 (1-BX)
REGION OF ATTRACTION
The higher value of G corresponds to the low
Before a discussion of the results of the paper can voltage solution, and vice versa. This is verified by
be presented, it will be necessary to examine the noting that
region of attraction of the stable equilibrium point in
2
the context of the system power voltage (P-V) curves.
Consider the simplified radial power system with
vL1 G20 - vL22Glo -
constant sending-end voltage shown in Figure 1. Assum- Equation (2) shows that if the initial state is to
ing, for simplicity, a unity power factor load, the the left of the point A on the P-V curve (G less than
power-voltage curve of the post-disturbance system is G ) , dG/dt is positive, and therefore, the operating
shown in Figure 2. For a constant power load P , the p8Pnt will move to A, at which point dG/dt = 0.
load characteristic, as shown by the vertical ‘line, Similarly, if the initial state is anywhere on the
would intersect the system P-V curve at two points, A portion ACB (G <G<G ) , dG/dt is negative and, there-
and B, corresponding to the two possible equilibrium fore, the ope&?ing E i n t moves to A. If the initial
points. Point A, on the upper portion of the system state is to the left of B, dG/dt is positive and the
P-V curve (the high voltage solution), is a stable operating point moves further away from B. The region
equilibrium point, whereas point B, on the lower to the right of B is, therefore, the region of attrac-
portion of the P-V curve (the low voltage solution), is tion of the stable equilibrium point A.
245
G cos28 + GL > 0, which yields The above result can be readily extended to large
2 networks if we first relate the stability limit, as
cos28 > - VL GL/Po (7) determined above, to the system Jacobian, modified to
where
load.
-
Po ,G:V is the constant power part of the
reflect the static part of the load.
For the simple example considered above, the incre-
mental power flow equations cam be written as:
Voltage stability limit is reached when - (VsVL/X)cos8 2VLGL-(VS/X)sin8
cos28 = - vL~G~/P~ (8)
(VSVL/X)sine
In order to illustrate this further, consider the is at A, the intersection of the pre-disturbance steady
case when about 50% of the load is resistive. The state P-V curve, the transient P-V curve and the
system P-V curves and the steady-state load character- steady-state load characteristic, which is a vertical
istics for this case are shown in Figure 5, in solid line at P for the constant power load assumed.
lines. For a total load P1, A is the initial, pre-
disturbance operating point. The equilibrium points
following the disturbance are shown on the post- I pre-dist. Pre-dist.
disturbance P-V curve at B and B'. (Recall that when
/
a part of the load is static, both equilibrium points P) 1.0
P
may be on the lower portion of the system P-V curve.)
c,
rl
9
I Pre-disturbance a , 1 0.5
1.0
m
n
c,
rl
I I -1.u_
I I
9 0.5
PO
0.5 Power
zi
system will be stable. The approximate path of the ,steady
operating point from initial to final state is marked 1.
by arrows as shown. P
Post-dist. 3
transient
Note that if the initial total load is P2, an c,
4