14 M Steel Beam Bridge -Design
LARSEN & TOUBRO LIMITED
ECC DIVISION
400/220/66kV GIS Substation Project Wangtoo, Himachal Pradesh 110/100 MVA
PROJECT:
Transformer Transportation across River Sutlej
STRUCTURE: 14 M Steel Beam Bridge -Floor Plate Capacity Check
Design Data
Thickness of Top plate t = 7 mm
Depth of Stiffener plate Ds = 120 mm
Thickness of Stiffener plate ts = 10 mm
Weld thickness b/w Stiffener plate tw = 8 mm
Weld thickness b/w Stiffener plate to top plate tw = 6 mm
Spacing b/w Stiffeners a = 300 mm
Yield Strength of plate fy = 250 N/mm2
Check for Top Plate
Boundary Condition of plate = All Edge Fixed
7 mm
300 mm
300 mm
Length of Skid Pad = 300 mm
Breath of Skid Pad = 250 mm
Area of Skid Pad = 75000 mm2
Load on Skid Pad = 3.75 MT
Pressure Below Skid Pad p = 0.5 N/mm2
Bending Stress at Centre of Plate 0.1386x pxa2/t2 = 127.3 N/mm2
Refer Roark's Formula < 165 N/mm2
Hence ok
14 M Steel Beam Bridge -Design
Check for Stiffener Plate
Flange width of stringer beam/Cross Beam = 125 mm
Bearing area below load transfer = 5000 mm2
Bearing stress = 7.5 N/mm2
< 200 N/mm2
Check for Bending Hence ok
Distance b/w Cross Beam = 1500 mm
300
36 Ixx = 7761600 mm4
x x 120 x10 Zxx = 215600 mm3
3.75 MT
250 1250
Max moment due to skid load = 7812500 N-mm
Bending Compressive Stress = 36 N/mm2
< 165 N/mm2
Hence ok