Gas Detection and
VESDA Sensepoint XCL – Large Bore Environmental Monitoring
Features
• Wide range of gases to support most
application needs:
-- Carbon Monoxide (ppm)
-- Flammable gases (% LEL)
-- Oxygen (% v/v)
-- Carbon Dioxide (% v/v, ppm)
• Aspirated gas sampling technology:
-- Capable of remote sampling – no
VESDA Sensepoint XCL – Large Bore is a gas detection solution that utilizes the ASD need to enter detection zone
pipe network to deliver superior gas detection via multiple hole (multi-point) sampling.
-- Centralized maintenance & service
The combined solution provides reliable detection of gases for occupant protection and
– saves time & money
process monitoring whilst simultaneously ensuring protection against fire threats.
-- Detector protected against the
The VESDA Sensepoint XCL – Large Bore portfolio has a range of gas sensors that
harshness of the environment –
addresses a wide range of applications and through its Bluetooth interface can be
reliable long term performance
paired with a smart device for commissioning and maintenance. The smart device
application (Sensepoint App) provides quick access to detector diagnostic information • Multi-point gas sampling:
and simplifies detector configuration, calibration and bump testing. -- Greater coverage area
-- Increased design flexibility
How it works
-- Reliable detection in high airflows
VESDA Sensepoint XCL – Large Bore is designed to be easily incorporated to existing • Integral alarm status LEDs
or new ASD pipe networks without major construction or electrical cabling / conduit and
utilizes the flow in the pipe for the continuous delivery of air samples to the gas sensor • Field replaceable gas sensor
for analysis. cartridges
It is capable of remote sampling which means the detector can be placed outside • Smart device application (Sensepoint
the detection zone at a convenient location for maintenance & service where free App) enables faster detector
business operation, restricted access and safety of personnel is important. Air drawn commissioning, maintenance and
to the detector can be conditioned to remove contaminates which ensures the detector service
maintains reliable long-term performance in a wide range of environments. • Bluetooth Wireless Interface
A single VESDA Sensepoint XCL – Large Bore detector delivers multi-point gas (compatible smart device iOS10 /
sampling capability giving it the advantage of providing larger coverage, increased Android 4.3 or above)
design flexibility and reliable detection in high airflow areas compared to fixed point gas • Multiple output options (configurable
detectors. relays, 4-20 mA or Modbus RTU)
Approvals
Applications include
• Energy storage systems (batteries) • Electrical safety
• Utility / service tunnels -- EN/UL/IEC 61010-1
• Heating plant rooms -- CSA-C22.2 No. 61010-1-12
• Manufacturing / Petroleum industries • CE - EMC
• Parking garages / Loading bays
-- EN 50270
• Power generation
• Refrigerated storage • RADIO
• Waste handling facilities -- RED, FCC, BT SIG
• Agriculture • OTHERS
• Water treatment / sewerage plants -- UL2075 (CO and CH4), AS 1668.2
• Health care / Hospitals
• Food / beverage industry
Flexible Output Options
VESDA Sensepoint XCL – Large Bore is available with either 4-20 mA analog or
Modbus RTU output, both versions being equipped with relays. The result is a flexible
solution that can be integrated to BMS, fire alarm panels, PLCs, HVAC, etc.
Gas Detection and
VESDA Sensepoint XCL – Large Bore Environmental Monitoring
Installation Specifications
The VESDA Sensepoint XCL – Large Bore detector is designed to be inserted in-line to Supply Voltage
the pipe network and is supplied with 60° elbows in the box: 24 VDC nominal
11 to 32V DC (Analog 4-20 mA)
9 to 32V DC (Modbus)
24V AC 50/60Hz Nominal (20 to 27 VAC)
20 to 27V AC (all versions)
Maximum Power Consumption
4-20 mA: < 1.2 W (toxic), < 1.7W (CAT, CO2)
Modbus: < 0.7 W (toxic), < 1.2W (CAT, CO2)
Relay: additional 0.6W total
VESDA Sensepoint XCL Ordering Information Maximum Inrush Current: 850 mA
Dimensions (WxHxD)
The VESDA Sensepoint XCL – Large Bore detector comes complete with the main 113 x 113 x 59 mm (4.4 x 4.4 x 2.3 in)
detector unit (pre-installed with sensor cartridge), flow cap and elbows.
Weight
500 g (1.1 lb)
Casing Material
Polycarbonate
Ingress Protection Rating
IP65, Type 4 (NEMA 250)
Operating Conditions
Operating Temperature:
−20 to +50 °C (−4 to +122 °F)
Storage Temperature:
0 to +30 °C (+32 to +86 °F)
Humidity:
0 to 99% (non-condensing)
CAT versions: 10 to 90% RH. Operating the detector outside
this range may result in increased drift and a reduction in
detector accuracy.
Atmospheric pressure:
90 to 110 kPa
Wire/Terminal size
Ordering Codes Connects to ASD pipe networks 25mm
Gas Type / Range 4-20mA Analogue, Relay Modbus RTU, Relay (0.98”), 27mm (1.06”) OD
Flammable (CAT) 20-100% LEL XCL-LB-CH4-RA XCL-LB-CH4-RM Output
Oxygen 25.0% v/v (Fixed) XCL-LB-O2-RA XCL-LB-O2-RM Analog: 0 to 22 mA
Carbon Monoxide 50 to 1000 ppm XCL-LB-CO-RA XCL-LB-CO-RM Digital: Modbus RTU
Carbon Dioxide 1000 to 5000 ppm XCL-LB-CO2PP-RA XCL-LB-CO2PP-RM 2 Relays (24V DC / 240V AC, 5A)
Carbon Dioxide 1.0 to 5.0% v/v XCL-LB-CO2VV-RA XCL-LB-CO2VV-RM
Spare Parts
Replacement Gas Sensor Part Number
Flammable (CAT) XCL-SC-CH4
Oxygen XCL-SC-O2
Carbon Monoxide XCL-XRL-SC-CO
Carbon Dioxide (ppm) XCL-SC-CO2PP
Carbon Dioxide (% v/v) XCL-SC-CO2VV
Spare Parts / Consumables Part Number
Flow Cap XCL-LB-CAP
60° Elbows – pack of 4 XCL-LB-ELB
Cable Glands – pack of 10 XCL-M20-CG
Filter CAT, NH3, CO2 – pack of 10 XCL-LB-FLT-1
Filter CO, O2, H2S, NO2, H2– pack of 10 XCL-LB-FLT-2
Sensor Cover CAT, NH3, CO2 XCL-LB-COV-1
Sensor Cover CO, O2, H2S, NO2, H2 XCL-LB-COV-2
www.xtralis.com
UK and Europe +44 1442 242 330 The Americas +1 800 229 4434
Middle East +962 6 588 5622 Asia +86 10 56697101 Australia and New Zealand +61 3 9936 7000
The contents of this document are provided on an “as is” basis. No representation or warranty (either express or implied) is made as to the completeness,
accuracy or reliability of the contents of this document. The manufacturer reserves the right to change designs or specifications without obligation
and without further notice. Except as otherwise provided, all warranties, express or implied, including without limitation any implied warranties of
merchantability and fitness for a particular purpose are expressly excluded.
Xtralis, the Xtralis logo, The Sooner You Know, VESDA-E, VESDA, ICAM, ECO, OSID, and Sensepoint are trademarks and/or registered trademarks of
Xtralis and/or its subsidiaries in the United States and/or other countries. Other brand names mentioned herein are for identification purposes only and
may be trademarks of their respective holder(s). Your use of this document does not constitute or create a licence or any other right to use the name and/
or trademark and/or label.
This document is subject to copyright owned by Xtralis. You agree not to copy, communicate to the public, adapt, distribute, transfer, sell, modify or
publish any contents of this document without the express prior written consent of Xtralis.
Doc. no. 35553_01, December 2019 Part: 30929