Estimated Daily Load per
Load Usage day
Items Description
(kW) (hr) (kWh)
A B AxB
1 Mechanical Ventilation System
a. Supply Carpark Ventilation Fans at Basement VSD Controller 180 4 720
b. Exhaust Carpark Ventilation Fans at Basement VSD Controller 180 4 720
c. Exhaust Carpark Ventilation Fans at 1st storey VSD Controller 30 4 120
d. Mini Jet Fans at Basement 8.25 4 33
e. Mini Jet Fans at 1st Storey 1.65 4 6.6
f. SSL MV at basement 6 24 144
g. Staircase MV leading to basement 4 24 96
h. PWCS Exhaust MV 15 12 180
i. PWCS Supply MV 15 12 180
j. PWCS Exhaust MV - Control Room 1.5 12 18
k. PWCS Supply MV - Control Room 1.5 12 18
l. Toilet MV for shops at BLK 432B 2.8 12 33.6
m. Fresh Air Fan at Ejector Pit 0.75 24 18
n. Exhaust Air Fan at Ejector Pit 0.75 24 18
o. Fresh Air Fan at Sprinkler Pump Room 0.75 4 3
p. Exhaust Air Fan at Sprinkler Pump Room 0.75 4 3
q. Exhaust Air Fan at Eating House HCP Toilet 0.4 12 4.8
r. Exhaust Air Fan at Eating House Female Toilet 0.4 12 4.8
s. Exhaust Air Fan at CCC HCP Toilet 0.4 12 4.8
t. Exhaust Air Fan at MSCP - Utility Center 0.4 12 4.8
u. Fresh Air Fan at MSCP - Utility Center 0.4 12 4.8
v. Exhaust Air Fan at MSCP - Toilet & Store 0.4 12 4.8
2 Type of Pu
a. Sump Pump at Basement Ejector Pit 2.8 3 8.4
b. Ejector Pump at Basement Ejector Pit 5.6 3 16.8
c. Domestic Water Transfer Pumps at basement 120 3 360
d. Domestic Water Booster Pumps at roof 12 3 36
e. Rainwater Sump Pumps at Basement 18 3 54
Stormwater Pump Basement 8.8 3 26.4
3 Lifts
a. Lifts 203.4 2 406.8
4 Lighting
a. Lift lobby lightings (7pm-7am) 7.67 12 92.0568
b. Staircase lightings (7pm-7am) 7.11 12 85.3776
c. Carpark lightings (24hours) 14.97 24 359.2248
d. Corridor lightings (7pm-7am) 22.35 12 268.1844
e. Roof garden lightings (7pm-12am) 2.30 5 11.517
Total 4064.761
Items Formula
Total kWh per day ∑ (A x B) 4064.761
Total energy comsumption per year for common areas ∑ (A x B) x 1483638
Gross Floor area C 1100000
∑ (A x B)
EEI for Common facilities (kWh/m2/yr) EEI-common x 365
C 1.348761