The document summarizes the estimated daily electrical load and usage of various mechanical ventilation systems, pumps, lifts, and lighting for common areas of a building with a gross floor area of 1,100,000 square meters. It calculates the total estimated daily load as 4,064.761 kWh. It then estimates the total annual energy consumption for common areas as 1,483,638 kWh and calculates the energy efficiency index for common facilities as 1.348761 kWh/m2/yr.

Uploaded by

Cheah Chen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
22 views1 page

EEI Calculation (19.11.2020) PDF

The document summarizes the estimated daily electrical load and usage of various mechanical ventilation systems, pumps, lifts, and lighting for common areas of a building with a gross floor area of 1,100,000 square meters. It calculates the total estimated daily load as 4,064.761 kWh. It then estimates the total annual energy consumption for common areas as 1,483,638 kWh and calculates the energy efficiency index for common facilities as 1.348761 kWh/m2/yr.

Uploaded by

Cheah Chen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Estimated Daily Load per

Load Usage day


Items Description
(kW) (hr) (kWh)
A B AxB
1 Mechanical Ventilation System
a. Supply Carpark Ventilation Fans at Basement VSD Controller 180 4 720
b. Exhaust Carpark Ventilation Fans at Basement VSD Controller 180 4 720
c. Exhaust Carpark Ventilation Fans at 1st storey VSD Controller 30 4 120
d. Mini Jet Fans at Basement 8.25 4 33
e. Mini Jet Fans at 1st Storey 1.65 4 6.6
f. SSL MV at basement 6 24 144
g. Staircase MV leading to basement 4 24 96
h. PWCS Exhaust MV 15 12 180
i. PWCS Supply MV 15 12 180
j. PWCS Exhaust MV - Control Room 1.5 12 18
k. PWCS Supply MV - Control Room 1.5 12 18
l. Toilet MV for shops at BLK 432B 2.8 12 33.6
m. Fresh Air Fan at Ejector Pit 0.75 24 18
n. Exhaust Air Fan at Ejector Pit 0.75 24 18
o. Fresh Air Fan at Sprinkler Pump Room 0.75 4 3
p. Exhaust Air Fan at Sprinkler Pump Room 0.75 4 3
q. Exhaust Air Fan at Eating House HCP Toilet 0.4 12 4.8
r. Exhaust Air Fan at Eating House Female Toilet 0.4 12 4.8
s. Exhaust Air Fan at CCC HCP Toilet 0.4 12 4.8
t. Exhaust Air Fan at MSCP - Utility Center 0.4 12 4.8
u. Fresh Air Fan at MSCP - Utility Center 0.4 12 4.8
v. Exhaust Air Fan at MSCP - Toilet & Store 0.4 12 4.8

2 Type of Pu
a. Sump Pump at Basement Ejector Pit 2.8 3 8.4
b. Ejector Pump at Basement Ejector Pit 5.6 3 16.8
c. Domestic Water Transfer Pumps at basement 120 3 360
d. Domestic Water Booster Pumps at roof 12 3 36
e. Rainwater Sump Pumps at Basement 18 3 54
Stormwater Pump Basement 8.8 3 26.4

3 Lifts
a. Lifts 203.4 2 406.8

4 Lighting
a. Lift lobby lightings (7pm-7am) 7.67 12 92.0568
b. Staircase lightings (7pm-7am) 7.11 12 85.3776
c. Carpark lightings (24hours) 14.97 24 359.2248
d. Corridor lightings (7pm-7am) 22.35 12 268.1844
e. Roof garden lightings (7pm-12am) 2.30 5 11.517

Total 4064.761

Items Formula
Total kWh per day ∑ (A x B) 4064.761
Total energy comsumption per year for common areas ∑ (A x B) x 1483638
Gross Floor area C 1100000
∑ (A x B)
EEI for Common facilities (kWh/m2/yr) EEI-common x 365
C 1.348761