Determination of Hot-Spot
Determination of Hot-Spot
DETERMINATION OF HOT-SPOT
TEMPERATURE FOR ONAN DISTRIBUTION
TRANSFORMERS WITH DYNAMIC THERMAL MODELLING
M.Sc. THESIS
Oluş SÖNMEZ
JUNE 2012
ISTANBUL TECHNICAL UNIVERSITY GRADUATE SCHOOL OF SCIENCE
ENGINEERING AND TECHNOLOGY
DETERMINATION OF HOT-SPOT
TEMPERATURE FOR ONAN DISTRIBUTION
TRANSFORMERS WITH DYNAMIC THERMAL MODELLING
M.Sc. THESIS
Oluş SÖNMEZ
(504081042)
JUNE 2012
ĠSTANBUL TEKNĠK ÜNĠVERSĠTESĠ FEN BĠLĠMLERĠ ENSTĠTÜSÜ
Oluş SÖNMEZ
(504081042)
HAZĠRAN 2012
Oluş Sönmez, a M.Sc.student of ITU Graduate School of Science Engineering
and Technology student ID 504081042, successfully defended the thesisentitled
“Determination of Hot-spot Temperature For ONAN Distribitution Transformers
with Dynamic Thermal Modelling ”, which he prepared after fulfilling the
requirements specified in the associated legislations, before the jury whose signatures
are below.
v
vi
To my grandfather; Mr. Süreyya Sönmez,
vii
viii
FOREWORD
I would like to thank to my supervisor Ass. Prof. Dr. Güven Kömürgöz for showing
such confidence on my abilities. I am very grateful for her continuous support,
encouragement and guidance.
I am also grateful to Dr. Bora Alboyacı, for all his contributions to my academic
career.
I want to thank to my mother, father and brother for their continuous support to me
especially to my father Mr. Ümit Sönmez.Thank you for the wisdom and experiences
you shared with me, without which this document would not have been.
Finally, I would like to thank to my grandfather Mr. Süreyya Sönmez for directing
me to transformer engineering.
ix
x
TABLE OF CONTENTS
Page
FOREWORD ............................................................................................................. ix
TABLE OF CONTENTS .......................................................................................... xi
ABBREVIATIONS AND SYMBOLS ................................................................... xiii
LIST OF TABLES ................................................................................................. xvii
LIST OF FIGURES ................................................................................................ xix
SUMMARY ............................................................................................................. xxi
ÖZET...................................................................................................................... xxiii
1. INTRODUCTION .................................................................................................. 1
2. THERMAL MODELLING OF DISTRIBUTION TRANSFORMERS ........... 5
2.1 IEEE Standard C57.91-1995 Model................................................................... 5
2.1.1 Top-oil temperature rise over ambient ........................................................ 6
2.1.2 Oil time constant ......................................................................................... 7
2.1.3 Winding hot-spot temperature rise over top-oil rise ................................... 7
2.2 IEC Standard 60076-7 Model ............................................................................ 8
2.2.1 Top-oil temperature rise over ambient ........................................................ 8
2.2.2 Hot-spot temperature rise over top-oil temperature .................................. 11
2.2.3 Winding time constant .............................................................................. 12
2.3 D. Susa’s Thermal Model................................................................................. 12
2.3.1 Thermal electrical analogy ........................................................................ 12
2.3.2 Top oil temperature rise over ambient model ........................................... 16
2.3.3 Hot-spot temperature rise over oil temperature model ............................. 18
3. EXPERIMENTAL STUDY................................................................................. 21
3.1 Measurements From Temperature Rise Tests .................................................. 21
3.1.1 Tested unit design parameters ................................................................... 22
3.1.2 Location of thermocouples........................................................................ 26
3.1.3 Applied temperature rise tests ................................................................... 30
3.1.4 Results of tests ......................................................................................... 34
3.1.4.1 Top-oil temperature............................................................................ 34
3.1.4.2 Bottom-oil temperature ...................................................................... 36
3.1.4.3 Hot-spot to top-oil temperature rise ................................................... 38
3.1.4.4 Average temperature rises .................................................................. 41
3.2 Results Obtained With Thermal Models .......................................................... 46
3.3 Comparison Of Measured Values With Results Of Thermal Models .............. 49
4. CONCLUSIONS .................................................................................................. 53
REFERENCES ......................................................................................................... 55
APPENDICES .......................................................................................................... 59
CURRICULUM VITAE .......................................................................................... 69
xi
xii
ABBREVIATIONS AND SYMBOLS
xiii
PDC,pu : DC losses ( I2R losses ) in per unit
Peddy : Eddy losses
Peddy,pu : Eddy losses in per unit
Pfe : No-load losses
Pl : Total load losses
P(θhs)pu : Load loss varies on temperature change in per unit
Pstray : Stray losses
pu : Per unit
q : Generated heat
qfe : Generated heat by no-load losses
qcu : Generated heat by load losses
qtot : Generated heat by total losses
R : Ratio of load losses at rated power to the no-load losses
Ri : Cold resistance (initial measured value)
Rel : Electrical resistance
Rhv : High voltage winding resistance
Rlv : Low voltage winding resistance
Rth : Thermal resistance
Rth-oil : Non-linear oil to air thermal resistance
Ru : Calculated resistance (ultimate measured value)
sec : Second
t : Time
Temp. : Temperature
T1 : Thermometer pocket location
T2 : Top of the cooling fins thermocouple location
T3 : Outlet of the winding cooling channel (duct ) thermocouple location
u : Electrical voltage
W : Watt
x : An oil thermal constant
y : A thermal constant
z : Vector varies with thermal time constant
μ : Viscosity of oil
μpu : Viscosity of oil in per unit
θ : Temperature
θamb : Ambient Temperature
θbo : Bottom oil temperature
θbo,i : Initial bottom oil temperature
θhs : Hot-spot temperature
θhs,hv : Hot-spot temperature for high voltage winding
θhs,i : Initial hot-spot temperature
θhs,lv : Hot-spot temperature for low voltage winding
θoil : Top-oil temperature
θoil,average : Average oil temperature
θoil,i : Initial top-oil temperature
θoil,bottom-surfece : Oil temperature at the bottom of tank
θoil,top-surfece : Oil temperature at the top of tank
θi : Cold temperature (calculated temperature)
θk : Temperature factor for calculation
θu : Calculated temperature (ultimate temperature)
θw,average : Average winding temperature
xiv
Δθbo,rated : Rated bottom-oil temperature rise at rated power
Δθhs : Hot-spot temperature rise over top-oil temperature
Δθhs,I : Initial winding temperature rise over top-oil temperature
Δθhs,rated : Rated hot-spot temperature rise over top-oil temperature at rated load
Δθhs,U : Ultimate winding temperature rise over top-oil temperature
Δθoil,I : Initial top oil temperature rise over ambient
Δθoil,rated : Rated bottom-oil temperature rise at rated power
Δθoil,U : Ultimate top oil temperature rise over ambient
Δθw/A,R : Average winding temperature rise over ambient at rated load
τoil : Oil time constant
τoil,rated : Rated oil time at rated load
τw : Winding time constant
xv
xvi
LIST OF TABLES
Page
Table 2.1 : Recommended constants for ONAN cooled distribution transformers .... 9
Table 2.2 : Parameters for Thermal and Electrical Analogy . ................................... 13
Table 2.3 :Viscosity calculation constants ................................................................ 15
Table 3.1 : Nameplate data of tested transformer. .................................................... 22
Table 3.2 :Load steps of the second test ................................................................... 32
Table 3.3 : Measured highest top-oil temperatures . ................................................. 36
Table 3.4 : Measured highest bottom-oil temperatures ............................................. 38
Table 3.5 :Hot-spot temperature rises to top oil temperature rises ......................... 40
Table 3.6 : Measured warm resistances. ................................................................... 42
Table 3.7 :Calculated resistance and average winding temperatures ........................ 44
Table 3.8 :Average winding – average oil temperature rise according to IEC. ........ 44
Table 3.9 : Average winding – average oil temperature rise according to IEEE. ..... 45
Table 3.10 :Average winding – average oil temperature rise according to D. Susa 46
Table 3.11 :Data which is used in thermal models ................................................... 47
Table A.1 :Technical datasheet for temperature monitoring and recording devices 61
Table A.2 :Technical datasheet of temperature monitoring device .......................... 62
Table A.3 :CPC 100 Winding resistance measurement test device datasheet .......... 64
xvii
xviii
LIST OF FIGURES
Page
xix
Figure A.6 : Tested transformer view from test laboratory during test .................... 67
xx
DETERMINATION OF HOT-SPOT TEMPERATURE FOR ONAN
DISTRIBUTION TRANSFORMERS WITH DYNAMIC THERMAL
MODELLING
SUMMARY
Transformers are one of the largest capital investment part of distribution networks.
Transformers’ reliability is very important for electrical networks considering cost
impact of power outages.
High temperature rise problem, one of the most serious problems for transformers.
Loading cycles and ambient conditions of transformers can be different than design
conditions. Transformer top-oil temperature and winding hot spot temperatures are
most critical parameters for transformer because it causes aging and therefore affects
life time of transformer. It is very important to determine hot-spot temperature and
oil temperature accurately which depends on ambient conditions and loading
conditions to avoid loss of life on transformer.
One solution to determine top-oil temperature and winding hot-spot temperature is
to use on-line monitoring devices like fiber optical measurement devices. Other
solution is to use dynamic thermal models to define top-oil temperature and winding
hot-spot temperatures. Considering that fiber optical measurement solutions are very
costly for distribution transformers, generally thermal models are mandatory to
define critical temperatures of distribution transformers.
IEEE C57.91-1995 and IEC 60076-7 standards present thermal models for defining
critical temperatures in transformers. These models are widely used in industry. On
the other hand these methods are solved with exponential equations and they do not
take into account the affects of change on oil temperature. Dynamic thermal model
which is proposed by D. Susa, requires similar input parameters with IEEE C57.91-
1995 model and IEC 60076-7 model, in addition to this, this thermal model takes
into account the effects of change on oil temperature.
Scope of this study is to verify three differenttemperature rise models for distribution
transformers to allow optimum loading of natural oil cooled transformers by using
the data which could be obtained from manufacturer.
In this study, on a 1000 kVA 33/0.4 kV ONAN cooled distribution transformer, two
temperature rise tests are realized. In first test, total losses are injected and necessary
data to determine transformers specific parameters for thermal models obtained. In
the second test, a varying load test is realized. Three different thermal models are
used for same varying loading characteristic and results are compared with
measurement results.
Significant advantage of this study is, necessary parameters for all thermal models
are determined with proper measurements of tested unit, therefore all three models
are compared under same conditions.
xxi
xxii
ONAN SOĞUTMALI DAĞITIM TRANSFORMATÖRLERĠNĠN EN-SICAK
NOKTA SICAKLIĞININ DĠNAMĠK ISIL MODELLEME ĠLE
BELĠRLENMESĠ
ÖZET
xxiii
prensipler arasındaki benzerliği kullanarak, transformatörlerin ısıl analizi için direnç
ve kapasite içeren bir devre sunar. Bu devrede, direnç, yağ sıcaklığına bağlı olarak
değişkendir. Bu devrenin çözümü ile bir diferansiyel denklem elde edilir. Sonuç
olarak karmaşık ısıl problem, bir elektrik devresine benzetilerek, diferansiyel
denklem ile çözülür. Bu yöntemde, standartlarda önerilen yöntemden farklı olarak,
yağ sıcaklığı değişiminin yükte kayıplara ve yağ viskozitesine etkisi dikkate
alınmıştır.
Bu çalışmanın kapsamı, yukarıda belirtilen üç farklı ısıl modelin, üreticiden
alınabilecek veriler kullanılarak, doğal soğutmalı dağıtım transformatörlerinin
optimum olarak yüklenebilmesinin sağlanması amacı ile doğrulanmasıdır.
Bu çalışmada, 1000 kVA gücünde 33/0.4 kV değiştirme oranına sahip, ONAN
soğutmalı (doğal yağ soğutmalı) bir dağıtım transformatörü kullanılmıştır.
Transformatör ülkemizde yaygın olarak kullanılan aynı güçteki transformatörlere
eşdeğer nitelikte seçilmiştir. Söz konusu transformatörün dışında ve içinde sıcaklık
ölçümü için ısı sensörleri monte edilmiştir. Transformatör içindeki sensörler, her bir
sargının alçak gerilim ve yüksek gerilim kısımlarına konulmuştur. Sargı içindeki
sensörlerin yerlerinin seçiminde, daha önce yapılan çalışmalar ve tecrübeler dikkate
alınarak en sıcak noktaların oluşması beklenen bölgeler seçilmiştir. Özellikle en
sıcak noktanın beklendiği sargılara, ilave olarak ikişer sensör daha konulmuştur.
Sargı içindeki ısı sensörlerine ek olarak, çeşitli noktalardaki yağ sıcaklıklarını
ölçebilmek için, transformatör kapak ve kazanına da ısı sensörleri yerleştirilmiştir.
Bu sensörler ile tepe yağ sıcaklığı üç farklı noktadan ölçülebilmiştir. Dip yağ
sıcaklığı ise iki farklı noktadan sensörlerin yardımı ile ölçülmüştür. Toplamda on beş
sensör kullanılmıştır. Bu sensörler, görüntüleme ve kaydetme cihazlarına
bağlanmıştır. Ölçümler sırasında sürekli olarak ortam sıcaklığı da ölçülerek
kaydedilmiştir. Ortam sıcaklığının değişimi etkisi, transformatörün kritik
sıcaklıklarını doğrudan etkileyeceği için bütün modellerde, ortam sıcaklığı etkisi
dikkate alınmıştır. Testler sırasında ısıl kamera kullanılarak, ısı dağılımı
gözlenmiştir. Isıl kamera ile transformatörün kazanın içinde yağın etkisi ile beklenen
dengeli sıcaklık dağılımı doğrulanmıştır.
Transformatör üzerinde iki farklı sıcaklık artış deneyi uygulanmıştır. Birinci
deneyde, toplam kayıplar transformatör üzerinden geçirilmiştir ve söz konusu
transformatörün ısıl modelleri için gerekli değişkenler ve sabitler elde edilmiştir.
Transformatörün ısıl özelliklerinin belirlenmesi için bu test kullanılmıştır. Sensörler
yardımı ile yapılan ölçümlere ek olarak, transformatörün alçak gerilim ve yüksek
gerilim sargılarının doğru akım dirençleri soğuk ve sıcak durumlarda ölçülerek
ortalama sargı sıcaklık artış değerleri belirlenmiştir.
İkinci test sırasında ise farklı akımlar transformatöre uygulanarak değişken yük
durumu deneyi gerçekleştirilmiştir. Bu test sırasında transformatör üç saat boyunca
anma gücü ile yüklenmiştir ardından 105 dakika boyunca iki katı yük ile
yüklenmiştir.Ardındam transformatör iki katı yüklenmesi kesilerek, son yarım saat
transformatör yüksüz durumda bırakılarak ölçümlere devam edilmiştir.Testler
transformatörün sekonder tarafı kısa devre edilmek sureti ile primerden akım
uygulanması şeklinde gerçekleştirilmiştir. İkinci test sonucunda elde edilen tepe yağ
sıcaklığı ve alçak gerilim ve yüksek gerilim sargıları için en sıcak nokta sıcaklıkları,
matematiksel model ile elde edilen sonuçlarla karşılaştırılmıştır.
Bu çalışmada, üç farklı matematiksel model kullanılmıştır.Bunlardan ilki IEEE
C58.91 standardında belirtilen modeldir, ikincisi IEC 60076-7 standardında belirtilen
xxiv
modeldir. Bu iki modele ek olarak, D. Susa tarafından geliştirilen model
kullanılmıştır. Bu modelde ısıl devre ile elektrik devreleri arasındaki benzerlik
kullanılmıştır. Bu benzerliğe göre ısı kaynağı, akım kaynağı olarak; sıcaklık, gerilim
olarak; ısıl direnç, elektriksel direnç olarak ve ısıl kapasite; elektriksel kapasite
olarak modellenmiştir. Bu şekilde karmaşık ısıl problem, basit bir R-C elektrik
devresine indirgenmiştir. Bu devre, devre analizi yöntemleri ile çözülerek
diferansiyel denklemler elde edilmiştir. Tepe yağ sıcaklığı ve en sıcak nokta
sıcaklıkları ise bu diferansiyel denklemler çözüşerek elde edilmiştir. Bu modelde,
standartlarda verilen modellerden farklı olarak sıcaklıkla, yağın fiziksel
özelliklerindeki değişim de dikkate alınmıştır. Yağın fiziksel değerlerindeki en etkin
değişim viskozite değerinde olduğu için, modelde viskozitenin sıcaklık ile değişim
etkisi kullanılmıştır. Buna ek olarak, transformatör kayıplarının da sıcaklık ile
değişimi modelde dikkate alınmıştır. Standartlarda verilen modeller kullanılırken,
gerekli olan değişkenler, deneyler ile elde edilen veriler ve optimizasyon yöntemleri
kullanılarak belirlenmiştir.
Testte uygulanan ile aynı değişken yük durumu, söz konusu üç ısıl modelde
gerçeklenmiştir. Modeller ile hem tepe yağ sıcaklığı hem de alçak gerilim ve yüksek
gerilim sargıları için sıcak nokta sıcaklıkları hesaplanmıştır. Elde edilen sonuçlar,
ölçüm sonucu ile elde edilen sonuçlar ile karşılaştırılmıştır.
Bu çalışmanın önemli bir üstünlüğü, uygulanacak ısıl modeller için değişkenler,
gerçekleştirilen test sayesinde, doğru bir şekilde elde edilmiştir. Isıl modellerin
karşılaştırılması için gerekli olan ölçümler yapılmıştır. Bu nedenle her üç model de
aynı şartlar altında karşılaştırılabilmiştir.
xxv
xxvi
1. INTRODUCTION
Transformer history starts from the early 1880s. It is based on induction principle
which is discovered by Faraday in 1831 [1]. Modern transformers are widely used in
transmission, distribution systems and also industrial systems. Transformers are one
of the most expensive equipments of electrical systems. Efficiency of transformers
are relatively high compared to different electrical machines. Except no load and
load losses, output power is approximately equal to input power. On the other hand,
these losses causetemperature rises on transformers.
High temperature rise problem , one of the most serious problems for all kind of
transformers[4]. Loading cycles and ambient conditions of transformers can be
different than design conditions. Transformer top-oil temperature and winding hot
spot temperatures are most critical parameters for transformer because it causes
aging and therefore affects life time of transformer. In oil filled distribution
transformers A class insulation which of system temperature is 105 C is commonly
used [5]. A class insulation contains mainly cellulosic based materials. For cellulosic
insulation materials rate of aging will rapidly increase above 110 C, this affects aging
rate of distribution transformer directly. In Figure 1.1, aging acceleration rate
changes with hot-spot temperature change is plotted according to equations given in
IEEE standard C57.91-1995 [6,7].
1
1000
Aging acceleration factor, pu
100
10
0,1
0,01
0,001
60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
Winding hot-spot temperature, ̊C
Many on-line and off-line monitoring systems have been developed [8-12]. However
on-line monitoring by direct measurement of winding temperature by using fiber
optic probes, is a very costly method for distribution transformers. Therefore,
thermal models should be used for distribution transformers to define loading
capability.
These thermal models are based on conventional heat transfer theory [13],
transformer thermal tests [14-27], application for the lumped capacitance method,
thermal electrical analogy [27] .In previous studies, it has been noticed that hot-spot
temperature rise over top-oil temperature for load changes is a function which
depends on time [24,27]. Present IEC and IEEE standards recommends thermal
models to determine top-oil temperature and hot-spot temperatures [6-7,28 ]. These
models are widely used in industry to determine temperatures. In addition to this, an
2
investigation performed on a 2500 kVA transformer without external cooling showed
accurate results [24]. Author was highly motivated to make a study to verify this
method with measured values of a smaller distribution transformer and compare
results with IEC and IEEE standards which are very widely used in market [6,28].
Scope of this study is to verify different thermal models for distribution transformers
to allow optimum loading of natural oil cooled transformers by using the data which
could be obtained from manufacturer.In this thesis, two different temperature rise
tests are realized on a 1000 kVA ONAN cooled distribution transformer, installed
with measurement thermocouples. First temperature rise test is constant load test.
From the data obtained from the first test, parameters required for thermal modelsare
determined by using optimization methods.In the second temperature rise test,
varying step loads are applied as given in Table 3.2. Temperature values for top-oil
and hot-spots are determined by three different thermal models for same loading
condition which is realized during Test 2. Results obtained from variable load tests
for tested distribution transformer is compared with calculated temperature values.
For calculations of hot-spot and oil temperatures, three different models are used and
results are compared.
Primary aim of this thesis is to verify different models which could be applied for
distribution transformers by using input data which could be obtained by
manufacturer.Therefore various thermal models are compared with measured values
for a standard ONAN cooled distribution transformer which means without external
cooling.
Three models which will be used in this study is explained in Chapter 2 with details.
Two of the methods are given in generally accepted standards and other method is
developed by D. Susa [24,26]. Experimental study which realized with a 1000 kVA
33/0.4 kV ONAN cooled distribution transformer is explained with details in Chapter
3. In this chapter, measured values and calculated values are plotted and compared.
Conclusions and comments obtained from this study are given in Chapter 4.
3
4
2. THERMAL MODELLING OF DISTRIBUTION TRANSFORMERS
In this section, three different method for thermal modeling is described. Definition
of methods are as following;
IEEE standard C57.91-1995 provides two different methods for predicting thermal
behavior of transformers. One of them is explained in Clause 7 of related standard
and other method is given in Annex G of this standard. The Annex G method,
provides a non-linear model, however it requires, more input data for model, and for
distribution transformers required data for Annex G method could not be easily
found in the market for all distribution transformers[6,30]. Special temperature rise
tests like bottom temperature rise measurement required to obtain requested input
5
data to model. Considering that this study is mainly targeting distribution
transformers, only Clause 7 model is used in this study. Normally, according to
Clause 7 model, variable ambient temperature affects are not considered, however in
this study, affects of ambient changes applied in model to obtain more accurate
results.
According to this thermal model, first top-oil temperature over ambient is calculated.
For this calculations, oil time constant should be defined. Following, winding hot-
spot rise over top-oil rise is calculated.
In standard, top-oil temperature rise at a time after a step load change is given with
following equation [28];
t
τoil
Δθ oil (Δ oil,U Δθ oil,I )(1 exp ) Δθ oil,I (2.1)
Where;
In case of multi step loading cycles, equation 2.1 is used for each load step and in
each step top-oil rise calculated for the previous load step is used as initial top-oil
rise of next step.
Ultimate top oil temperature rise over ambient is calculated with following equation;
n IEEE
K 2R 1
oil, U oil, rated (2.2)
R 1
6
2.1.2 Oil time constant
In IEEE C57.91 standard, rated oil time constant is given with an equation which
uses thermal capacity value, rated temperature rise value and total losses. Formula
is given in equation 2.3.
Where; MAP is the weight of active part (core and coil assembly) (in kg) , Mtank is
the weight of tank and other steel parts which have direct contact to oil (in kg) and
Moil is weight of oil (in kg).
Top oil time constant for each interval calculated with following equation;
oil, U oil, I
( ) ( )
oil, rated oil, rated
oil oil, rated 1 1 (2.5)
oil, U n IEEE oil, I n IEEE
( ) ( )
oil, rated oil, rated
where
nIEEE is constant exponential defined 0.8 for ONAN cooled transformers [6].
Winding hottest-spot temperature over top-oil rise for each step load cycle is given
by following equation;
where;
7
Δθhs,U ultimate winding temperature rise over top-oil temperature ( in K )
Ultimate winding temperature rise over top-oil temperature calculated with following
equation;
WhereΔθhs,ratedis rated winding temperature rise over top oil temperature ( in K) and
m is the exponential constant which is 0.8 for ONAN cooled transformers.
IEC standard provides two thermal models. One of them is given as an exponential
equation solution, this method is more suitable for load cycles which are changing
with steps [28,31]. The other method which is given as a differential equation
solution, is suitable for randomly changing load cycles. Second method is mainly
applicable for on-line monitoring [31]. In this study, exponential equation solution
model is used.
In this model, primarily, top oil temperature rise over ambient is calculated by
defining necessary variables and constants. Afterwards, hot-spot temperature rise
over top-oil temperature rise is calculated by defining necessary variable and
constants.
According to IEC 60076-7 standard, oil temperature rise over ambient temperature is
given with an equation depends on a function. This function includes exponential
constants. IEC 60076-7 has recommended some values for constants [28].
Equation given in 2.8 is applied at load increase. Equation which is given in 2.9 is
applied at load decrease.
8
oil ( oil, I oil, U )f 3 ( t ) oil, U (2.9)
x
K 2R 1
oil, U oil, rated (2.10)
R 1
where;x is the oil exponent, f1(t) indicates the relative increase of the top-oil
temperature rise in per-unit value. f3(t) indicates the relative decrease of the top-oil
temperature rise value in per-unit value.f1(t) and f3(t) fuctions are solved with
following equations which are given in equation 2.11 and equation 2.12;
t
k11
f 1 ( t ) (1 exp oil , rated
) (2.11)
t
k11
f 3 ( t ) exp oil , rated (2.12)
9
However more accurate results had been obtained by estimating this constant from
top-oil temperature rise curve which is plotted by realizing temperature rise test
according to IEC 60076-2 standard [32].
Measured relative increase of the top-oil temperature rise of the steady state value is
calculated as per unit value with following equation [31]
k oilj k ambj
kf 1j (2.13)
oil, rated
where
k measured variable
f1j relative increase of oil temperature rise over ambient for related step
(2.14)
where;
k measured variable
Recommended k11 value in IEC 60076-7 which is given in Table 2.1 is used for
initial value of minimization [28].
10
2.2.2 Hot-spot temperature rise over top-oil temperature
hs hs, U (2.16)
Ultimate winding temperature rise over top-oil temperature rise is calculated with
following equation.
f2(t) indicates the relative increase of the hot-spot temperature rise to top-oil
temperature rise value in per-unit value.Equations is shown in Equation 2.18.
t
t oil , rated
k 22 x k 22
f 2 (t) k 21x (1 exp w
) (k 21 1)(1 exp ) (2.18)
Where; k21 is thermal model time constant, k22 is the thermal model time constant
and τw is the winding time constant ( min.).
It is recommended to use defined values for thermal constants by IEC Standard [28].
These values are given inthe related standard. k21 is given as 1.0 for ONAN cooled
distribution transformers. k22is given as 2.0 for ONAN cooled distribution
11
transformers as shown in Table 2.1. For y value it is recommended to use 1.6 for
ONAN cooled distribution transformers.
According to IEC standard, the winding time constant value which is used in
equation 2.18 is calculated with equation 2.19 which is given below [28].
M w cg r
w
60Pl (2.19)
Where
One of the most used heat transfer law; Fourier theory’s equation form is with the
same form of Ohm’s law which is one of the most-well known electrcal law.
Therefore mathematical solution of a thermal system is usually similar to
12
mathematical soluation of an electrical system. By using this similarity, an equivalent
electrical circuit can be obtained to solve a thermal problem [20]. In Figure 2.1, a
basic electrical RC circuit is given.
u R
i C
It will be noticed that thermal analogy could be replaced as in Table 2.2 into
electrical analogy parameters based on basic heat transfer principles [13,20,25,27].
Thermal Electrical
Accordingly, new RC circuit is defined for thermal analogy which is given in Figure
2.2;
13
R th q amb
q
Cth
q
The change of viscosity with oil temperature change is significantly higher than the
change on other parameters [15,22,27]. This is shown in Figure 2.3 by plotting all
major oil physical parameter changes, which depends on temperature. Therefore,
only viscosity value of oil is variable in the model and other parameters are constant.
Oil physical parameters’ equations are taken from [15,27].
14
18
16
The viscosity of oil is dependent on oil temperature and formula is given in Equation
2.20.
D and Gparameters are constants related with transformer oil characteristic and they
are given in IEEE standard which is shown in Table 2.3. In the Table 2.3, viscosity
constants for two different insulation fluids are given[6].
Insulation Fluid D G
Mineral Oil 0.0013573 2797.3
Silicone Fluid 0.12127 1782.3
15
2.3.2 Top oil temperature rise over ambient model
From basic RC circuit which is given in Figure 2.2, thermal circuit is defined for top-
oil temperature as shown in Figure 2.4;[17, 24]. In this model, no-load losses and
load losses are defined as current sources in circuit diagram [25,26]. No-load losses
are constant and load losses are dependent on load factor.Because load losses varies
with load factor.For top oil temperature rise model, both no load and load losses are
heat sources since oil temperature is affected from heat of both losses. Capacitance
of oil is indicated as constant and calculation equation is given in Equation 2.4.
Thermal resistance value is variable of the circuit and depends on oil viscosity
change with temperature. Ambient temperature is indicated as voltage source, since it
is constant and added on top-oil temperature rise value to determine top-oil
temperature.
q tot R th-oil
q oil
q fe qcu C th-oil
q amb
Where; qtotis total heat generated with affect of losses (in W), qfeis heat generated
with affect of only no load losses (in W), qcuis heat generated with affect of load
losses (DC losses, eddy and stray losses ) (in W) and Rth-oilis non-linear oil to air
thermal resistance.
This circuit is solved with circuit analysis theory and differential equation which is
given Equation 2.21 is found [6,7,27-28].
1 R
pu oil, rated pu oil, rated
dt n Susa (2.21)
oil, rated
16
Where,
K load factor
In Susa’s method, rated oil time constant is calculated according to IEEE Std.
C57.91-1995(Cor.2002)[7]. It is noticed that in IEEE method constant is used in
hours, however in Susa’s method it is used in minutes.
Oil viscosity is calculated from Equation 2.20 for each oil temperature value,
however in model it is used in per unit.
Pl
R (2.22)
Pfe
I
K (2.23)
I rated
where;
17
In this model, different than other two models, which are described in the previous
sections, both thermal resistance and oil time constants are affected from change of
oil viscosity [27].
R th-hs-oil
q hs
q tot R th-oil
q oil
q fe qcu C th-oil
q amb
Figure 2.5 : Hot-spot temperature circuit model together with top-oil model circuit.
Where, qcuis heat generated with affect of load losses (DC losses, eddy and stray
losses) ( W ) , Rth-hs-oil isnon-linear hot-spot to oil thermal resistance, θhsis hot-spot
temperature ( C ).
Model for hot-spot temperature rise over oil temperature is based on thermal model
which is using thermal electrical analogy similar to oil temperature rise model [13].
18
RC circuit which is developed for hot-spot temperature is given in Figure 2.5. In
developed thermal model, different than oil temperature rise model, only load losses
are taken into account. Load losses are given as a current source which varies with
load factor since it is heat source. Thermal capacitance of winding is given as
constant. Thermal resistance of winding is a variable value which depends on oil
viscosity. Top oil temperature is given as voltage source and value of top oil
temperature is taken from top-oil temperature model which equation is given in
Equation 2.21.
This circuit is solved with similar way with top-oil model with circuit analysis theory
and differential equation which is given Equation 2.24 is found [6-7, 29].
where
hs k hs , rated k
P( )
hs pu PDC, pu ( ) Peddy , pu ( ) (2.25)
hs , rated k hs k
θk temperature factor for calculation, equal to 225 for aluminum and 235
for copper;
19
Differential equations which are obtained in Equation 2.21 and 2.24 are solved with a
numerical analysis method to determine the temperature for both oil and hot-spot for
windings.
20
3. EXPERIMENTAL STUDY
Unit, which tests have been performed is a distribution transformer without external
cooling (ONAN cooled). Fifteen Thermocouples has been installed during
manufacturing of transformer. Location of thermocouples have been determined
according to past experiment results to measure hottest points [23-24].
Thermocouples installed to same locations in all three coils to compare temperature
differences between each coil.Measurement devices and thermocouples data is given
in Appendix A. Considering tolerance of thermocouple and monitoring device, total
accuracy of measurements expected ±2%.In this section, experimental study is
explained with three subsections.In first part, realized test unit and realized tests are
explained. In the second part, calculations, which are realized with thermal models,
are given. In the third subsection, measured and calculated values are compared.
Two different tests are realized with 1000 kVA distribution transformer. Results of
tests are plotted and necessary parameters for thermal models are determined from
this test. Tested unit details, realized tests and results of tests are given in following
subsections.
21
3.1.1 Tested unit design parameters
Table 3.1 shows the nameplate data of the tested transformer. These values are taken
from test report of manufacturer.
In Figure 3.1 , basic transformer active part schema is given . There are fifteen
Aluminum foil windings in the secondary winding (LV winding). There are two
cooling channels between the layers, one of them is located between layer five and
22
layer six and the other channel is located between layer ten and layer eleven. The
distance between secondaryconductor to the core yoke is 58 mm from top. It is also
the same for the bottom of winding. 45 mm of this space is pressboard insulation
material.
Primary winding has 14 layers, and total number of turns are 2142.Enameled isolated
aluminum conductor is used as primary winding conductor. There are three cooling
channels in primary winding. First cooling channel is located immediately after
secondary winding and before the start of the primary winding. Second cooling
channel is located between layer 4 and layer 5 and third cooling channel is located
between layer 8 and layer 9. The distance between primary conductor to the core
yoke is 58 mm from top. It is same for bottom. 45 mm of this space is pressboard
insulation material. Internal view of transformer is given in Figure 3.2 and Figure
3.3. In figure 3.3, thermocouples inside of tank are shown.
23
Figure 3.3 : Internal view of tested transformer with thermocouples.
Transformer tank is corrugated wall design which consists from total of 112 cooling
fins. 25 of this fins are located in each short side of transformer tank and 31 of fins
are located in each long side of transformer. Figure 3.4 and Figure 3.5 shows the
transformer’s exterior view.Quantities of cooling fins and locations are shown in
Figure 3.7.
In Figure 3.5, thermocouples which are coming inside of tank to outside of tank is
shown. In same figure, monitoring devices for temperature is also shown. During
tests, these monitoring devices are not installed on transformers fins, they are
installed in a separate area.
24
Figure 3.4 : Exterior view of tested transformer from HV side.
25
3.1.2 Location of thermocouples
Four thermocouples are installed in primary (high voltage) windings. In each coil,
one thermocouple is installed. All thermocouples are installed approximately 5 mm
depth from aluminum conductor material, since it was expected to get hottest
temperature at this location [24]. In addition to this, one thermocouple is installed to
outlet of cooling channel.
Transformers top view drawing is given in Figure 3.7. Location of bushings and
thermometer pocket can be seen in that figure. In addition cooling fins of transformer
tank is shown on the drawing which is given in Figure 3.7.
Two thermocouples are installed in the bottom part of the tank. One of them is
located in the bottom part of phase insulation pressboard to measure the mixed
bottom oil temperature and other thermocouple is installed in the lowest part of the
bottom of the tank. Locations of thermocouples are shown in Figure 3.9.
26
Figure 3.6 : Positions of thermocouples on phase B winding.
27
Figure 3.8 : Thermocouple in thermometer pocket.
28
Figure 3.10 : Location of thermocouples in windings.
29
To measure the ambient temperature during the tests, two opposite side located
thermocouples are installed in the test room with a distance of 1 m from transformer.
During the tests, six of the thermocouples which are installed outtterpary of the tank
are connected to a data logger, which records temperature readings continuously with
15 second intervals. Details of data logger, which designed for measurement and
recording of temperatures are given in Appendix A.
In addition, thermal images of transformer during tests has been taken with thermal
camera which is data is given in Appendix A. However, thermal photos are only
taken to observe distribution of temperature on transformer tank , these data is not
used neither in calculation nor plotting..
Two different temperature rise tests applied to the transformer. In the first test,
constant nominal load applied. This test realized according to total loss injection
method which is givenin standard IEC 60076-2[32]. According to this method, rated
current and rated voltage is not applied to transformer simultaneously, total losses
30
which are written on routine test report of transformer is injected. Injection method is
to short-circuit transformers secondary side and apply necessary current from
primary side to inject total losses to transformer. This test has two steps. In first step,
total losses ( both no-load and load losses ) are injected to transformer till rate of
change of top oil temperature rise has fallen below 1 K per hour. After this period, in
the second step, only nominal current is applied to transformer from primary side
while secondary is short-circuit condition for 1 hour. At the end of the hour,
connections are removed in shortest time possible and DC resistance measurement
for windings is done. Average winding temperature rise for both high voltage and
low voltage side is determined by using DC resistance measurements after test and
before test in cold condition [32]. Temperature difference is defined by comparing
change on the DC resistance values. DC resistance values are measured with
specially designed test device for this application which applies high currents to
obtain resistance measurement in short time and accurately. Detail of device is given
in Appendix A. In figure 3.13, transformer is shown during first test. As described,
transformer’s secondary is in short-circuit condition and current is applied from
primary side as seen in Figure 3.13.
31
In the second test, varying load test is realized. First nominal current (1.00 pu) is
applied for three hours, and following double current ( 2.00 pu) is applied for 1.45
hours. Load steps are given in Table 3.2. this load steps arechosenrandomly by
aiming to obtain a sudden change on loading., and extreme overloading conditions is
applied to transformer during double current step.
All assembled thermocouple’s measurements have been recorded for both tests.
Both tests are realized in main tap position which is 4th tap with 33000 V rating.
Total fifteen unit thermocouples are used during tests. These thermocouples are three
wire type Pt100 resistance temperature detectors (RTD).Six of these thermocouples
are connected to a continuous data monitoring and recording device and rest of the
thermocouples are connected to three separate Pt100 monitoring device.
thermocouples. Considering tolerance of thermocouple and monitoring device, total
accuracy of measurements expected ±2%. Details of measurement devices are given
in Appendix A.
Continuous data monitoring and recording device has recorded temperature values
for six thermocouples continuously with 15 second intervals. For the other
thermocouples only monitoring devices are used and values are recorded
manually.Taken thermal images during tests are given in Figure 3.14 and Figure
3.15. In Figure 3.14, narrow side of transformer cooling fins are shown during test.
In Figure 3.15, longer side of transformer cooling fins are shown.
32
Figure 3.14 : Thermal camera view from narrow side.
33
3.1.4 Results of tests
Measurements recorded during both tests are analyzed. Top oil temperatures and
bottom oil temperatures which are measured from different locations are compared.
Hot-spot temperatures for both high voltage and low voltage side is determined.
Measured values for both top-oil temperature and winding hot spot temperatures are
plotted. Average winding temperature rise is calculated according to data which is
obtained from temperature rise test. Average oil over ambient temperature rise values
are defined according to different methods which are explained in IEC 60076-2
standard, IEEE C57.12.90 standard and D. Susa’s study [2,24,32]. Results are
compared. Gradients are calculated according to different methods. Results
calculated for gradients are compared.
Top oil temperaturesare measured and recorded from three different locations. Most
common measurement method is thermometer pocket measurement since most of the
transformers in market has thermometer pocket and thermometers installed on
existing transformers are assembled in thermometer pockets. In addition to this,
measurements are recorded from thermocouples assembled on top radiator and oil
cooling channel outlet in tank.
Measured values in constant load test (Test 1) are plotted in Figure 3.16. Measured
values in varying load test (Test 2) are plotted in Figure 3.17.For both tests,
measurement results from different top oil temperature locations are given in Figures
3.16 and Figures 3.17. According to measurements, highest top oil temperature is
obtained from the thermocouple, located on outlet of cooling channel.Although
highest top oil temperature is obtained from outlet of cooling channel, these values
are not used in calculations and models. In industry usually no thermocouples are
located inside of distribution transformers’ tank therefore measurement of top oil at
the outlet of cooling channel is not common [24].
34
80
70
Top-oil Temperatures, ̊C
60
50
40
30
20
10
0
0 100 200 300 400 500 600
Time, minutes
Figure 3.16 : Measured top-oil temperatures at three different locations in first test.
140
120
Top-oil Temperatures, ̊C
100
80
60
40
20
0
0 50 100 150 200 250 300 350
Time, minutes
35
In Table 3.3, highest measured values in different locations are given for both test 1
and test 2. As also shown in Figure 3.16 and Figure 3.17,hightest top oil temperature
is obtained from thermocouple, which is located in the outlet of winding,’s cooling
channel. In Table 3.3 T1, T2 and T3 locations are indicating thermocouples at
following locations; T1 is thermometer pocket, T2 is top of the cooling fins and T3
is outlet of the winding cooling channel (duct).
Bottom oil temperatures are measured and recorded from two different locations.
One of them is installed inside of the tank to measure mixed bottom oil temperature
and other thermocouple was installed on the lowest bottom part of transformer tank.
36
60
50
Bottom-oil Temperatures, ̊C
40
30
20
10
0
0 100 200 300 400 500 600
Time, minutes
100
90
Bottom-oil Temperatures, ̊C
80
70
60
50
40
30
20
10
0
0 50 100 150 200 250 300 350
Time, minutes
37
The Figure 3.18 shows the bottom oil temperatures measured from different
locations in first test. Figure 3.19 shows the top oil temperatures measured from
different locations in test 2.
Hottest spot temperatures are defined by comparing the hottest measurement values.
For both primary (high voltage) and secondary (low voltage) windings, highest
temperature measured in phase B which is the mid located phase. This result is
reasonable since mid located phase windings are affected from both other two
38
windings temperature raises. On the other hand, the difference is not
significant.Measured values in constant load test are plotted in Figure 3.20. In figure
3.21, varying load test results for hot-spot temperatures are given. It also noted that
low voltage winding hot spot temperatures are higher than high voltage winding’s
hot spot temperatures. This result is as expected since low voltage winding is internal
located between magnetic core and primary windings, therefore oil circulation and
heat transfer is expected less than high voltage windings.Location of thermocouples
which measured the hottest points are shown in Figure 3.10.
100
90
80
Hot spot Temperatures, ̊C
70
60
50
40
30
20
10
0
0 100 200 300 400 500 600
Time, minutes
Figure 3.20 : Winding hot spot temperatures in the first test (constant load test)
39
250
200
Hot spot Temperatures, ̊C
150
100
50
0
0 50 100 150 200 250 300 350
Time, minutes
Figure 3.21 : Winding hot spot temperatures in the second test (varying load test)
Hottest spot rise above top oil temperature is calculated for both high voltage and
low voltage winding. During this calculation top oil temperature has been taken from
different locations and results are compared in Table 3.5.
In this study rated hot-spot to top oil temperature rise is take by using oil temperature
in thermometer pocket. Reason of this is, oil thermometer pocket is most common
measurement location for top oil temperature in industry as already explained in
40
Section 3.1.4.1. Hottest spot rise over top oil pocket temperature is plotted in
Figure3.22. It had been observed that the hot-spot temperature rise over top-oil
temperature had not experienced with overshoot. This were expected since it had
been verified in the past studies that in transformers without external cooling , a
function with overshootshould not be observed [23,28].
30
Hot spot to top oil Temperature rises, K
25
20
15
10
0
0 50 100 150 200 250
Time, minutes
As a part of constant load test, resistance values are measured immediately after tests
as per related IEC standard [32]. Measured values and cold resistance values are
given Table 3.6 and Table 3.7.
Ru
u ( i k ) k (3.1)
Ri
41
Where;θu is calculated temperature(in C);θiiscold temperature (initial measured
value) (in C) ;θkis temperature factor for calculation, equal to 225 for aluminum; 235
for copper;Riis the cold resistance (initial measured value) (in ohm) and Ru is
thecalculated resistance (in ohm).
Before starting temperature rise test, during transformer is in cold condition, initial
resistance values are measured and recorded. These values are given in Table 3.7.
After completing test, during transformer in warm condition, resistance measurement
test of same winding is repeated. Measured values are given in Table 3.6. Since
transformer winding is cooling down during measurement, more than ten measured
resistance values are recorded. It is shown in Table 3.6 that resistance values are
continuously reducing.Measurement is realized with a sensitive resistance
measurement device which is data is given in Appendix A. Considering that, an
amount of time is lose during removing connections of test and connecting test
device for resistance measurement, resistance at the end of the test is determined
with an extrapolation. This extrapolation is realized by plotting measured values and
finding equation of this function from graph.
42
14
RHV = -3E-07t3 + 0,0001t2 - 0,02t + 12,364
12
Warm Resistance values, ohm
10
0
0 50 100 150 200 250
Time, sec.
1320
LV Warm Resistance Values, μohm
1300
RLV = -1E-05t3 + 0,0054t2 - 0,9166t + 1293
1280
1260
1240
1220
1200
1180
1160
1140
1120
0 50 100 150 200 250
Time, sec.
According to extrapolation, values from plotted graphs which are given in Figure
3.23 for high voltage winding and given in Figure 3.24 for low voltage winding,
warm resistance values were defined. From warm resistance values, average winding
temperatures are calculated by using Equoation 3.1. Calculated values are given in
Table 3.7.
43
Table 3.7 : Calculated resistance and average winding temperatures
Warm
Cold Resistances θw,average, C Resistances θw,average, C
HV LV HV LV HV LV HV LV
9.92 1028 12.364 1293
17 17
ohm μohm ohm μohm 76.62 79.38
In this study, average oil temperature rises are defined with different methods and
results are compared.
According to IEC standard, average oil temperature is calculated only using top oil
temperature. Equation is given in Equation 3.2 [32].
Table 3.8 : Average winding – average oil temperature rise according to IEC method
According to IEC 60076-2
θoil, average , gr, K H, pu
Location
C LV HV LV HV
T1 58.66 20.72 17.96 1.17 1.17
44
hs
H (3.3)
gr
θw,averageis calculated from resistance measurements with Equation 3.1 and results are
shown inTable 3.7.
From this equation, calculated average oil temperature values are given in Table 3.9.
Table 3.9 : Average winding- average oil temperature rise according to IEEE
According to IEEE
θoil, average , gr, K H, pu
Location
C LV HV LV HV
T1 50.35 29.03 26.27 0.84 0.80
Considering that , measured top oil temperature and bottom oil temperatures are for
mixed oil temperatures, average mixed oil temperature is calculated with following
equotaiton [24];
oil bo
oil,average (3.6)
2
Top oil temperature is taken 69 C from first test ( constant load test) results which is
shown Table 3.3. Bottom oil temperature is taken 48.6 C from Table 3.4.
45
Average winding to average oil tempeatureis calculated with Equation 3.6.H is the
hot spot factor and it is calculated from equoation 3.3.
Table 3.10 : Average winding – average oil temperature rise according to D. Susa
According to D. Susa Method
θoil, average , gr, K H, pu
Location
C LV HV LV HV
T1 58.80 20.58 17.82 1.18 1.18
It is observed that the difference between average winding to average oil temperature
rise values calculated according to IEC standard and calculated according to bottom
oil temperature measurements in tank (D.Susa Method) gives similar results. On the
other hand, values had been calculated according to IEEE method, are notably higher
than the calculated values according to bottom oil temperature measurements in tank.
Top oil temperature and hot-spot winding temperatures for both high voltage and low
voltage windings are calculated with three different methods which are explained in
Section 3. Data required for these models are obtained from test 1 which is constant
load test as explained in previous part of study. Optimization is done for defining
some parameters which are required in thermal models. Data which are used for
calculation of thermal models are given in Table 3.11. Average oil temperature rises
and average winding temperature rises are determined according to different methods
which are given in IEC, IEEE standards and Susa’s study [6,7,24,28]. Results are
compared between each other and between measured values during test 2 which is
varying load test.
46
Table 3.11 : Data which is used in thermal models
Windings
Quantity Unit
LV HV
kVA Base 1000 1000 kVA
Temp. Base 75 75 C
PDC 9550 W
Peddy+ Pstray 627 W
Pfe 100 W
pu Base 1000 1000 kVA
Δθw/A,R 62.08 59.32 K
Δθhs,rated 24.3 21 K
Δθoil,rated 51.7 K
Δθbo,rated 31.3 K
H 1.181 1.178
gr 20.58 17.82 K
τoil,rated 199.04 min
τw (IEEE) 5 5 min
τw (IEC) 8.2 8.6 min
k11 0.822
k21 1.0
k22 2.0
x 0.8
y 1.6
nIEEE 0.8
m 0.8
nSusa 0.25
Map 1810 kg
Mfe 1205 kg
Mw 114 192 kg
Mtank 550 kg
Moil 930 kg
θhs,i 24 25 K
θoil,i 20.8 K
θbo,i 15.1 K
47
For all models; power rating base is taken as 1000 kVA since transformer rated
power is 1000 kVA, temperature base is taken as 75 C. Temperature base is
important to define load losses correctly since load losses depends on temperature
changes. It is very important especially in D. Susa method, since affect of
temperature change on losses are considered, base temperature value is very
important.
No-load losses are taken reduced since Test 2 ( varying load test ) is realized with
short-circuit method which is already explained in Section 3.1.3. Other loss values
are obtained from manufacturer’s test report. It is confirmed that, given load losses
on test report are with the same temperature base which is 75 C as given in Table
3.11.
Δθw/A,R which indicated rated average winding temperature increase over ambient is
calculated by using average winding temperature rise values which are given in
Table 3.7 and ambient temperature during test.
Top-oil temperature rise over ambient which is taken from Table 3.3 by using
ambient temperature which is explained in previous paragraph.Δθhs,ratedis taken from
Table 3.5 by using oil temperature in thermometer pocket ( T1 ).
Top oil temperature rise over ambient temperature which is shown with Δθoil,rated in
Table 3.11 is calculated by using top oil temperature value in Table 3.3 and ambient
temperature. Similarly bottom oil temperature rise over ambient (Δθ bo,rated ) is
calculated from Table 3.4 by using ambient temperature.
Hot spot factor ( H ) is calculated from Equation 3.3 by using rated hot-spot
temperature rise over top oil temperature which is given in Table 3.5 and gradient
which is calculated according to in Table 3.10.
Rated oil temperature time constant (τoil,rated) is calculated from Equation 2.3.
Winding time constants for both high voltage and low voltage windings for IEEE
model, are taken as 5 minutes as per recommendation of the standard [6]. Winding
48
time constants for IEC and Susa’s models arecalculated according to equation which
is given in section 2.2.3 , Equation 2.19.
Constants required for IEC thermal model is indicated as k11, k12, k22, x and y as
already explained in Section 2.2. k11 value is determined by realizing optimization
as described in Equation 2.13 and 2.14. Optimization is realized by minimizing
function which is given in Equation 2.14. Other constants are taken from IEC 60076-
7 recommendations which are given in Table 2.1.
Constants for IEEE C57.91-1995 method which are shown as nIEEE and m in Table
3.11 are taken from recomandations of this standard[6].
Weight data of transformer’s various parts are obtained from manufacturer. These
data is indicated as Map, Mwdn, Mtankand Moil in Table 3.11 .
Initial temperatures for top oil (θoil,i), bottom oil (θbo,i) and hot spot temperatures for
both high voltage and low voltage windings (θhs,i)are taken from measurement
records of Test 2 which is varying load test. Initial temperatures of hottest spots and
top oil were not same with ambient temperature. These temperatures were slightly
higher because of the, effect of previous temperature rise test.
All thermal models, are solved for same load cycle which is applied during Test 2
which is given in Table 3.2.
Exponential equations for IEC and IEEE method which are given and explained in
Section 2.1 and Section 2.2 are solved for each interval and results are plotted in
Figure 3.25 , Figure 3.26 and Figure 3.27.
Differential equations in D. Susa’s method which are given and explainedin Section
2.3, are solved with fourth order Runge-Kutta method. Obtained results are plotted
on Figure 3.25 , Figure 3.26 and Figure 3.27.
Results obtained by thermal models in Section 3.2 are compared in this part. Both
top-oil temperatures and hot-spot temperatures for high voltage and low voltage
windings are determined with thermal models. These calculated values are plotted
49
and compared with measured values.Identificaiton of methods on graphs are as
following:
In Figure 3.25, top oil temperature values which are measured and calculated with
thermal models are given. It is observed that IEEE method give slightly higher
results, IEC method give slightly lower results and D.Susa thermal model give more
accurate results compared to measured values.
140,0
120,0
100,0
Top oil temperature, ̊C
80,0
60,0
40,0
20,0
0,0
0 50 100 150 200 250 300 350
Time, minutes
Measurement IEEE Method
IEC Method TM
In Figure 3.26, hot-spot temperatures for low voltage winding’s are plotted. In
Figure 3.26, both measured and calculated with thermal models are given. It is
observed that IEEE method give significantly higher results, IEC method give
slightly lower results and D. Susa thermal model gives more accurate results
50
compared to measured values. On the other hand D. Susa method, does not give
accurate results in first minutes of load step change which shows winding time
constant is not defined correctly.
200,0
LV hottest spot temperature, ̊C
150,0
100,0
50,0
0,0
0 50 100 150 200 250 300 350
Time, minutes
200,0
HV hottest spot temperature, ̊C
160,0
120,0
80,0
40,0
0,0
0 50 100 150 200 250 300 350
Time, minutes
Measurement IEEE Method
IEC Method TM
Ambient Temperature
51
In Figure 3.27, hot spot temperature values for high voltage winding which are
measured and calculated with thermal models are given. It is observed that
differences between measured values and calculated values are very similar to
differences for low voltage winding which is shown in Figure 3.26. It is noticed that
IEEE method give significantly higher results and IEC method gives slightly lower
results. D. Susa method gives accurate results especially for the hottest temperature.
52
4. CONCLUSIONS
In the industry two basic thermal models are widely used which are proposed by IEC
and IEEE. These two models uses exponentials formulas and neglects the affect of
viscosity change with oil temperature change. Thermal model which is developed by
Dejan Susa, takes into account the oil viscosity changes and loss variations with
temperature changes. In addition to oil viscosity and loss variations, it also takes into
account the change on time constants.
In this study, average winding to average oil gradients which are calculated
according to different methods were compared with each other. It is observed that ,
IEC method gives very similar results with well established calculations methods.
On the other hand, IEEE method, gives significantly higher values compared to well-
established calculation methods.
For top oil temperature, three different models’ results are compared with measured
values. In all models, proper rated oil time temperature rise values are used which
were obtained during temperature rise tests with well-established methods. Also
affects of ambient temperature changes are adapted on all thermal models. Therefore
it is noticed that, all three methods supplied similar results to measured values.
Thermal model which is developed by D. Susa, gave the best result for all load
cycles except slight difference on cooling down condition. It is observed that values
calculated according to IEEE method , are considerably higher from measured values
and for IEC method , it is just the opposite and calculated values are considerably
lower than measured values.
53
For hot-spot temperature, three different models’ results are compared with the
measured values for both high voltage and low voltage windings. As in top oil
model, in hot-spot model also, proper rated winding hot-spot temperature rise values
are used. It is observed that the values obtained from IEEE method are slightly
higher than the measured values and the values obtained from IEC method are
slightly lower than measured values. According to results obtained from thermal
model which developed by D. Susa, highest hottest-spot temperature is calculated
very accurately compared to measured data. On the other hand, a significant
difference is noticed during first minutes of step load change. This has shown that
winding time constant for this transformer is not defined properly.
It is observed that, results are very dependent on accurate input data for defined rated
load parameters like rated temperature rise values and rated top-oil time constants.
Considering the difficulty of defining, winding time constant with temperature rise
tests, further research and development is needed to improved defining the winding
time constant for distribution transformers.
54
REFERENCES
[1] Del Vecchio, R. M., Poulin, B., Feghali, P.T., Shah, D.M. and Ahuja, R.
(2002).Transformer Design Principles: With Applications to Core
Form Transformers.CRC Press 2001.
[2] IEEE (2006). IEEE Std C57.12.90-2006 : IEEE Standard Test Code for Liquid-
Immersed Distribution,Power and Regulating Transformers, IEEE.
[3] IEC (2011).IEC 60076-1 ed3.0Power transformers – Part 1: General, IEC.
[4]Kömürgöz, G. (2002). Kendi kendine soğuyan kuru tip güç transformatörlerinde
sargı ısınma hesabına katkılar, PhD Thesis, ITU.
[5] IEC (2007). IEC 60085-1 ed4.0Electrical insulation – Thermal evaluation and
designation, IEC.
[6] IEEE (1995). IEEE Std C57.91-1995 IEEE Guide for Loading Mineral-Oil-
Immersed Transformers, IEEE.
[7] IEEE (2002). IEEE Std C57.91-1995/Cor 1-2002 IEEE Guide for Loading
Mineral-Oil-Immersed Transformers Corrigendum 1, IEEE.
[8]Betta, G., Pietrosanto, A., and Scaglione, A. R. (2000).An enhanced fiber optic
temperature sensor system for power transformer monitoring,
Instrumentation and Measurement Technology Conference, IMTC
2000, Proceedings of the 17th IEEE, Vol.1, 1-4 May 2000.
[9]Feng, J.Q., Sun, P., Tang, W.H., Buse, D.P., Wu, Q.H., Richardson, Z. and
Fitch, J. (2002). Implementation of a power transformer temperature
monitoring system, International Conference on Power System
Technology, ProocedingsPowerCon 2002., Volume 3, 13-17 October
2002, p. 466-473.
[10]Lachman, M.F., Griffin, P.J., Walter, W. and Wilson, A. (2003). Real-time
dynamic loading and thermal diagnostic of power transformers, IEEE
Transactions on Power Delivery, Volume 18, Issue 1, January 2003, p.
142-148.
[11] Swift, G.W., Zocholl, E.S., Bajpai, M., Burger, J.F., Castro, C.H., Chano,
S.R., Cobelo, F.S.P., Fennell, E.C., Gilbert, J.G., Grier, S.E., Haas,
R.W., Hartmann, W.G., Hedding, R.A., Kerrigan, P., Mazumdar,
S., Miller, D.H., Mysore, P.G., Nagpal, M., Rebbapragada, R.V.,
Thaden, M.V.,Uchiyama, J.T., Usman, S.M., Wardlow, J.D. and
Yalla M. (2001) Adaptive transformer thermal overload protection,
IEEE Transactions on Power Delivery, Volume 16, Issue 4, October
2001, p. 516-520.
[12]Lesieutre, B.C., Hagman, W.H., Kirtley and J.L.Jr. (1997).An improved
transformer top oil temperature model for us in an on-line monitoring
55
and diagnostic system, IEEE Transactions on Power Delivery,
Volume 12, Issue 1, January 1997, p. 249-256.
[13]Bergman, L. T., Incropera, F.P., Lavine, A.S. and Dewitt, D.P. (2011).
Fundamentals of Heat and Mass Transfer, Seventh Edition, John
Wiley & Sons, Inc.
[14]Aubin, J.R., Bergeron, R. and Morin, R. (1990). Distribution Transformer
Overloading Capability Under Cold-Load Pickup Conditions, IEEE
Transactions on Power Delivery, Volume 5, Issue 4, October 1990
1997, p. 1883-1891.
[15]Blume, L. F., Boyajian, A., Camilli, G., Lennox, T.C., Minecci, S. and
Montsinger V.M. (1951). Transformer Engineering, 2nd edition,
John Wiley & Sons, Inc.
[16] Grubb, R.L., Hudis, M. and Traut, A.R. (1981). A Transformer Thermal Duct
Study of Various Insulating Fluids, IEEE Transactions on Power
Apparatus and Systems, Volume PAS-100, No. 2, February 1981, p.
466-473.
[17]Karsai, K., Kerenyi, D. and Kiss L. (1987). Large Power Transformers,
Elsevier Science Publishers.
[18]Nordman, H., Hironniemi, E. and Pesonen, A.J. (1990). Determination of hot-
spot temperature rise at rated load and at overload, CIGRE Paper 12-
103.
[19]Nordman, H., Rafsback, N., and Susa D. (2003). Temperature responses to
step changes in the load current of power transformers, IEEE
Transactions on Power Delivery, Volume 18, Issue 4, October 2003,
p. 1110-1117.
[20] Tang, W.H., Wu, Q.H., and Richardson Z.J. (2002). Equivalent heat circuit
based power transformer thermal model, Electric Power Applications,
IEE Proceedings, Volume 149, Issue 2, March 2002, p. 87-92.
[21]Tang, W.H., Wu, Q.H., and Richardson Z.J. (2004). A simplified transformer
thermal model based on thermal-electric analogy, IEEE Transactions
on Power Delivery, Volume 19, Issue 3, July 2004, p. 1112-1119.
[22]Pierce, L.W. (1992). An investigation of the thermal performance of an oil filled
transformer winding, IEEE Transactions on Power Delivery, Volume
7, Issue 3, July 1992, p. 1347-1358.
[23]Radakovic, Z., Feser, K., (2003). A new method for the calculation of the hot-
spot temperature in power transformers with ONAN cooling, IEEE
Transactions on Power Delivery, Volume 18, Issue 4, October 2003,
p. 1284-1292.
[24]Susa, D., Lehtonen, M. andNordman, H. (2005). Dynamic Thermal Modelling
of Distribution Transformers, IEEE Transactions on Power Delivery,
Volume 20, Issue 3, July 2005, p. 1919-1929.
[25] Swift, G., Molinski, T.S., and Lehn, W. (2001). A fundamental approach to
transformer thermal modeling-I, Theory and equivalent circuit, IEEE
Transactions on Power Delivery, Volume 16, Issue 2, April 2001, p.
171-175.
56
[26] Swift, G., Molinski, T.S., Bray, R. and Menzies, R. (2001). A fundamental
approach to transformer thermal modeling-II, Field Verification, IEEE
Transactions on Power Delivery, Volume 16, Issue 2, April 2001, p.
176-180.
[27]Susa, D. (2005). Dynamic Thermal Modelling of Power Transformers , Doctoral
Dissertation, Helsinki University of Technology.
[28] IEC (2005).IEC 60076-7 ed1.0Power transformers – Part 7: Loading guide for
oil-immersed power transformers, IEC.
[29]Susa, D., Lehtonen, M. andNordman, H. (2005). Dynamic Thermal Modelling
of Power Transformers, IEEE Transactions on Power Delivery,
Volume 20, Issue 1, January 2005, p. 197-204.
[30]Rivera, L.J., Tylavsky, D.J. (2007). Dynamic Thermal Modelling of Power
Transformers, Power Systems Engineering Research Center,
November 2007 .
[31] Susa, D. and Nordman, H. (2012). IEC 60076-7 loading guide thermal model
constants estimation, European Transactions on Electrical Power 2012
, DOI: 10.1002/etep.1631.
[32] IEC (2011). IEC 60076-2 ed3.0Power transformers – Part 2: Temperature rise
for liquid-immersed transformers, IEC.
[33]Radakovic, Z., Kalic, D., (1997). Results of a novel algorithm for the
calculation of the characteristic temperatures in power oil
transformers, Electrical Engineering 80, p. 205-214.
57
58
APPENDICES
59
APPENDIX A
In this appendix part, data of measurement devices are given. During this study,
mainly following devices are used; thermocouples, temperature monitoring and
recording devices, winding resistance measurement device. In this section datasheets
for temperature monitoring and recording devices are given in Figure A.1, Figure
A.3, and Figure A.4. In addition to this, in Figure A.2, Figure A.5, Figure A.6 ,
Figure A.7, Figure A.8 and Figure A.9, photos of the test devices which are used in
this study are shown.
60
Table A.1 : Technical datasheet for temperature monitoring and recording devices
61
Table A.2 : Technical datasheet of temperature monitoring device
62
Figure A.2 : Temperature monitoring and recording devices in varying load test.
63
Figure A.3 : Thermal camera
Table A.3 : CPC 100 winding resistance measurement test device datasheet
64
Figure A.4 : CPC 100 winding resistance measurement test device view.
65
Figure A.5 : Test room while recording temperature reading during test 1
66
Figure A.6 : Tested transformer view from test laboratory during test
67
68
CURRICULUM VITAE
E-Mail: [email protected]
69