Multi Panel Meter MT4Y/MT4W Series
Multi Panel Meter MT4Y/MT4W Series
Ordering information
Temp.
controller
Refer to the 4th Autonics catalogue for the
MT 4 W DV 4 N before version. (I)
SSR/
N Indicator(Without output function) Power
controller
0 Relay contact output
1 NPN open collector output (J)
Y Type Counter
L-35
MT4Y/MT4W Series
Specifications
MT4Y-DV-4 MT4Y-AV-4 MT4W-DV-4 MT4W-AV-4 MT4W-DV-1 MT4W-AV-1
Series
MT4Y-DA-4 MT4Y-AA-4 MT4W-DA-4 MT4W-AA-4 MT4W-DA-1 MT4W-AA-1
AC voltage, AC voltage, AC voltage,
DC voltage, DC voltage, DC voltage,
Measurement input ampere, ampere, ampere,
ampere ampere ampere
Frequency Frequency Frequency
100-240VAC 50/60Hz 12-24VDC
Power supply
(Allowable voltage range: 90 to 110%) (Allowable voltage range: 90 to 110%)
Power consumption 5VA 5W
Display method 7Segment LED display(red)(Character height: 14.2mm)
• 23℃±5℃ - DC Type: F.S. ±0.1% rdg±2digit / AC Type: F.S. ±0.3% rdg±3digit
Display accuracy DC/AC Type F.S +0.3% rdg +3digit max. only for 5A terminal.
• -10℃ to 50℃ - DC/AC Type: F.S.±0.5% rdg±3digit
Max. allowable input 110% F.S for each measured input range
A/D conversion method Practical oversampling using successive approximation ADC
Sampling cycle DC type: 50ms, AC type: 16.6ms
Max. indication range -1999 to 9999(4digit)
• Relay output - Contact capacity: 250VAC 3A, 30VDC 3A / Contact composition: N.O(1a)
Preset output
• NPN/PNP Open collector output - 12-24VDC ±2V 50mA Max. (Resistive load)
• RS485 communication output - Baud rate: 1200/2400/4800/9600, Communication method: 2-wire half duplex,
Sub output Synchronous method: Asynchronous method, Protocol: Modbus type
(Transmission output) • Serial/BCD output - NPN Open collector output: 12-24VDC Max. 50mA(Resistive load)
• DC4-20mA output - Resolution: 12,000 division(Load resistance max. 600Ω)
※
AC measuring function 1 Selectable RMS or AVG
※1
Frequency measurement function Measurement range : 0.100 to 9999Hz(Variable by decimal point position)
※2
Hold function Includes(External hold function)
Insulation resistance Min. 100MΩ(at 500VDC megger) between external terminal and case
Dielectric stength 2,000VAC for 1minute between external terminal and case
Noise stength ±2kV the square wave noise(pulse width : 1㎲) by the noise simulator
Mechanical 0.75mm amplitude at frequency of 10 to 55Hz(for 1 min.) in each of X, Y, Z directions for 2hours
Vibration
Malfunction 0.5mm amplitude at frequency of 10 to 55Hz(for 1 min.) in each of X, Y, Z directions for 10minutes
Mechanical 100m/s²(approx. 10G) in each of X, Y, Z directions for 3 times
Shock
Malfunction 300m/s²(approx. 30G) in each of X, Y, Z directions for 3 times
Relay Malfunction Min. 20,000,000 operations
life cycle Mechanical Min. 100,000 operations(250VAC 3A Load current)
Environ Ambient temperature -10 to 50℃, storage: -20 to 60℃
-ment Ambient humidity 35 to 85%RH, storage: 35 to 85%RH
Double insulation or reinfored insulation
Insulation type
(Mark: , dielectric strength between the measuring input part and the power part: 1kV)
Approval
Unit weight Approx. 134g Approx. 211g
※1: AC measuring function, and frequency measuring function are only for AC measuring input type.
If only frequency input the AC type(display method of measuring input) which option is in MT4W, MT4W will operate the only indicating type.
※2: MT4Y- -4N model has no hold function.
※Environment resistance is rated at no freezing or condensation.
4 5
4 5
1. HI : High output indication of preset 4. MODE key : Mode Key
2. GO : GO output indication of preset 5. : Moves digit, enters parameter mode, : changes SV
3. LO : Low output indication of preset
6. Unit label part
L-36
Multi Panel Meter
Connections (A)
Photo
electric
Measuring input connection of MT4Y Series sensor
(B)
● MT4Y-DV-4 ● MT4Y-AV-4 Fiber
optic
sensor
1 2 3 4 5 6 7 1 2 3 4 5 6 7
(C)
250mV 2V/1V Door/Area
/50mV sensor
5V/1V SOURCE 20V/10V SOURCE
100-240VAC 110V/50V 100-240VAC
50V/10V (D)
50/60Hz 5VA 50/60Hz 5VA
500V/250V Proximity
500V/100V
sensor
● MT4Y-DA-4 ● MT4Y-AA-4
(E)
Pressure
1 2 3 4 5 6 7 1 2 3 4 5 6 7 sensor
5mA 100mA
/2mA (F)
/50mA
Rotary
50mA/ SOURCE 500mA SOURCE encoder
4-20mA 100-240VAC /250mA 100-240VAC
500mA/200mA 50/60Hz 5VA 1A 50/60Hz 5VA
(G)
5A/2A 5A/2.5A Connector/
Socket
1 2 3 4 5 6 7 (J)
Hold/Zero Hold/Zero Counter
HI GO LO COM HI GO LO COM
●MT4Y- -42 ●MT4Y- -43 ●MT4Y- -44 (K)
(Triple PNP O.C output) (Relay output+Transmission output) (Relay+RS485 communication output) Timer
8 9 10 11 12 13 8 9 10 11 12 13 8 9 10 11 12 13 (L)
+ - Panel
B(-) A(+) meter
Hold/Zero
2 4 6 8 10 12 14 CLOCK DATA LATCH POL COM (O)
※POL : When a display value is "-", the signal Sensor
controller
1 3 5 7 9 11 13 of "-" will be outputted.
(P)
COM B D D1 D3 POL ※Hirose connector pin header model of the unit : HIF3BA-14PA-2.54DS Switching
※Contact Hirose Electric to purchase socket and wires of Hirose connector. mode power
supply
[Socket : HIF3BA-14D-2.54R]
(Q)
Stepper
Measuring input connection of MT4W Series motor&
Driver&Controller
250mV (S)
2V/1V
/50mV Field
+ - + - network
5V/1V Hold/Zero 20V/10V Hold/Zero device
50V/10V
SOURCE 110V/50V SOURCE
12-24VDC 12-24VDC
500V/100V 500V/250V (T)
100-240VAC 100-240VAC Software
50/60Hz 5VA 50/60Hz 5VA
● MT4W-DA- ● MT4W-AA-
(U)
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 Other
5mA 100mA
/2mA /50mA
+ - + -
50mA/ Hold/Zero 500mA
Hold/Zero
4-20mA SOURCE /250mA SOURCE
500mA/200mA 12-24VDC 1A 12-24VDC
100-240VAC 5A/2.5A 100-240VAC
5A/2A 50/60Hz 5VA 50/60Hz 5VA
L-37
MT4Y/MT4W Series
Output terminal connection of MT4W Series
● MT4W- - 0(Triple relay contact output ● MT4W- - 1 (Triple relay contact output)
+Transmission output)
MAIN OUT MAIN OUT
CONTACT OUT CONTACT OUT
: 250VAC 3A 1a RESISTIVE LOAD : 250VAC 3A 1a RESISTIVE LOAD
10 11 12 13 14 15 10 11 12 13 14 15
+ -
DC4-20mA
HI GO LO
Load 600Ω Max.
HI GO LO COM
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9
PCB
● MT4W- - 6/ MT4W- - 7 (Triple NPN/PNP open collector output+Low speed serial output)
+24VDC ※POL: When a display value is "-", the signal of "-" will be +24VDC
GO 30mA Max. outputted. GO 30mA Max.
2 4 6 8 10 12 14 16 18 20 2 4 6 8
MAIN OUT :
MAIN OUT :
PNP OPEN COLLECTOR
NPN OPEN COLLECTOR
1 3 5 7 9 11 13 15 17 19 12-24VDC Max. 50mA 1 3 5 7
12-24VDC Max. 50mA
COM2 DATA
COM1 HI LO 0V COM1 HI LO 0V
SERIAL OUT :
NPN OPEN COLLECTOR
12-24VDC Max. 50mA
COM1 HI LO COM1 HI LO 0V
0V A(+)
RS485
L-38
Multi Panel Meter
(C)
● Panel cut-out Door/Area
sensor
Min. 91
36
30
(D)
Proximity
31.5 + 00.5 sensor
Min. 40
<MT4Y- -4N, 40 to 44, 46>
68
+ 0.7
(F)
Rotary
6 77 10 Pin Hirose connector encoder
(HIF3BD-10PA-2.54DS)
(G)
● MT4Y- -40, 41, 42 Connector/
Socket
30
(H)
Temp.
<MT4Y- -45> controller
(I)
SSR/
Power
controller
● MT4W- - N (Indicator)
(J)
Counter
109 106 ● Panel cut-out
96 6 89.5 Relay contact
Min. 116
output terminal (K)
Timer
45 + 00.6
Min. 52
(L)
44.8
Panel
48
92 + 00.8 meter
(M)
Tacho/
※There is no Relay contact output terminal Speed/ Pulse
meter
block in indication type.
(N)
< MT4W- - N, MT4W- - 0, 1> Display
● MT4W- - 0 to 9 unit
110.4
(O)
6 89.5 Sensor
20 Pin Hirose connector controller
(HIF3BA-20PA-2.54DS)
(P)
Switching
mode power
44.8
supply
(Q)
Stepper
motor&
Driver&Controller
< MT4W- - 2 to 9>
(R)
Graphic/
Logic
Parameter setting panel
(S)
Field
RUN network
※Press key in RUN status, it will advance to [ ](Parameter 0) group. device
Press Key Press Key Press ※Press key for 2 sec. in RUN mode, [ ] is displayed. (T)
Key
for 3sec.
※ Press key for 4 sec. in RUN mode, [ ] is displayed after [ ]. Software
L-39
MT4Y/MT4W Series
Parameter 1 group
RUN
Press key for 3sec.
PA1
● Measuring input chart by model
Display of factory Select measuring input specification by
IN-R default for
measuring input
. Item Range of measuring input
- Refer to " Specification of MT4Y/W-DV 500V 100V 50V 10V 5V 1V 0.25V 50ㅡMV 500V
measuring input and range".
MT4Y/W-DA 5A 2A )5A )2A 50MV 4-20MV 5MV 2MV 5A
MT4Y/W-AV 500V 250V 110P(☆) 50V 20V 10V 2V 1V 500V
Select the display method of measuring input. MT4Y/W-AA 5A 2.5A 1A )5A )25A )1A 50mA 5A
D1SP STND ※(☆) Standard specification. (110P is 440VAC/110VAC P.T)
Select STND SCAL FREQ
- Refer to measuring input specification and range chart.
(FREQ mode is only for AC measuring type.)
Max. display Decimal point Select decimal point position. Decimal point Set frequency measuring
STND value DOT position 0 0.0 0.00 0.000
DOT position range, it is decided as
the decimal point position.
※When selecting the decimal point ( Change the
position, "H-SC ", L-SC " have deci- decimal point position)
It shows Max. display mal point position.
value of standard 0 1 to 9999Hz
specification.
Set display value against 0.0 0.1 to 999.9Hz
Display value is fixed. Max. display
H-SC value max. measuring input. 0.00 0.10 to 99.99Hz
( : Shift the digit 0.000 0.100 to 9.999Hz
: Change setting value) ※In case of selecting frequency display, no
output will be provided even if it is output
support models (Main output, Sub output
and RS485 output).
Set display value against
Min. display
L-SC value
min. measuring input.
※After setting each mode, press MODE key for 2 sec. to return to RUN.
※If any key is untouched for 60sec. after advance to Parameter, it will return to RUN.
Factory defaults
Parameter MT4Y/W-DV MT4Y/W-DA MT4Y/W-AV MT4Y/W-AA Parameter MT4Y/W-DV MT4Y/W-DA MT4Y/W-AV MT4Y/W-AA
L-40
Multi Panel Meter
(B)
Press key for 5sec. Fiber
optic
PA1 sensor
(D)
In MT4Y-□-□3,□4, "OFF, LST" are only displayed. Proximity
Set preset hysteresis. Within 10% of F.S. sensor
HYS HYS But, it is not displayed when OVtT mode is OFF.
(E)
Pressure
sensor
Set startup compensation time.
STaT 0)0 ( :Shift the digit, : Change setting value)
Setting range : 0.0 to 99.9sec. (F)
Rotary
encoder
Set monitoring delay time.
PEkT 00 5 ( :Shift the digit, : Change setting value)
(G)
Setting range : 00 to 30sec. Connector/
Socket
Set a display cycle. ( :Shift the digit, : Change setting value)
D1sT )2 5 Setting range : 0.1 to 5.0sec.
(H)
Temp.
controller
Select zero function with operation at front. (Set with key)
ZERO NO When + Key key are pressed for 3 sec. to set ㅛㄷㄴYES, it will be zero function and the deviation (I)
SSR/
value is saved automatically at ㅛ INbL mode. Power
controller
Select input with 6, 7(MT4W)[12, 13(MT4Y)] terminal or zero function for external signal.
EV1N HOLD (Set with , Key) (J)
HOLD : Holding display value, ZERO : Zero function using Hold/Zero terminal Counter
Set the high limit value, output point of current output 20mA.
FS-H 50)0 ( :Shift the digit, : Change setting value) (K)
Timer
(When changing measuring input and prescale mode, it is changed automatically
as maximum value of input range.)
Set the low limit value, output point of current output 4mA. (L)
FS-L 00)0 ( :Shift the digit, : Change setting value) Panel
meter
(When changing measuring input and prescale mode, it is changed automatically
as minimum value of input range.)
(M)
Set the address of RS485 communication output. Tacho/
ADRS 01 ( :Shift the digit, : Change setting value)
Speed/ Pulse
meter
Setting range : 01~ 99
(N)
Select Baud rate of RS485 communication output. Display
BPS 9600 Setting range : 9600 4800 2400 1200
unit
(O)
Sensor
Set parity bit of RS485 communication.
PRTY NONE Set range: NONE/EVEN/ODD
controller
(P)
Switching
Set stop bit of RS485 communication. mode power
STP 2 Set range: 1 / 2
supply
(Q)
Stepper
motor&
Set response wait time of RS485 communication.
RSmT 5 Set range: 5 to 99
OFF Disable to lock keys
Driver&Controller
(R)
Graphic/
LOC1 Lock Parameter 1 Logic
Set key lock function and select from 4 types. panel
LOC2 Lock Parameter 1, 2
LOC OFF ㅐㄹOFF LOC1 LOC2 LOC3 ㅐㄹOFF LOC3 Lock Parameter 0, 1 and 2 (S)
Field
network
※The dotted mode is only displayed for output type. device
※After setting each mode, press MODE key for 2 sec. to return to RUN mode. (T)
※If any key is untouched for 60sec. after advance to PARAMETER, it will return to RUN mode. Software
Factory defaults
(U)
Parameter MT4Y/W-DV MT4Y/W-DA MT4Y/W-AV MT4Y/W-AA Parameter MT4Y/W-DV MT4Y/W-DA MT4Y/W-AV MT4Y/W-AA Other
OUtT OFF OFF OFF OFF EV1N HOLD HOLD HOLD HOLD
HYS 001 001 001 001 FS-H 50)0 %000 50)0 %000
STAT 0)0 0)0 0)0 0)0 FS-L 00)0 )000 00)0 )000
PEkT 00 5 00 5 00 5 00 5 ARDS 01 01 01 01
DIsT )2 5 )2 5 )2 5 )2 5 BPS 9600 9600 9600 9600
ZERO NO NO NO NO LOC OFF OFF OFF OFF
L-41
MT4Y/MT4W Series
Parameter 0 group
RUN
Press key
※If any key is untouched for 60sec. after advance to Parameter, it will return to RUN mode.
Factory defaults
Parameter MT4Y/W-DV MT4Y/W-DA MT4Y/W-AV MT4Y/W-AA Parameter MT4Y/W-DV MT4Y/W-DA MT4Y/W-AV MT4Y/W-AA
hSET 50)0 %000 50)0 %000 hPEK )0 )000 )0 )000
lSET 00)0 )000 00)0 )000 lPEK )0 )000 )0 )000
L-42
Multi Panel Meter
upper gradient at [PA 1: INbH]and [PA 1 : INbE]. In order Setting range : 00.0 to 99.9(unit: sec.)
to measure frequency normally, input signal, over 10% F.S. Factory default : 00.0 (D)
Proximity
of the measured range, should be supplied. Please select Error display function sensor
with 3 ways as below. When zero point adjustment with range, it returns to RUN mode.
front key and Hold terminal is finished normally, zero point (K)
Press both
Short-circuit external 'b' and particular values are 'A' and 'B', it will display a=A,
(M)
PA 1: Direct Hold terminal no.11,12 b=B as below graphs. Tacho/
, keys for
input correction [no. 6, 7(MT4W)]over Speed/ Pulse
Description 3 sec. at the meter
value method at min. 50m. Display B B B
measuring Display Display
INbL mode. ※It is enable to use value (N)
mode. A value A value
in option mode. a
Display
b unit
a b a b A
※Refer to " Error correction function", " Error display Input value Input value
Input value
function" and " Parameter 2" for function and error. (O)
Display A a b A
Sensor
Current output(DC4-20mA) scale function value
Display A a b
controller
value Display
[PA2 group: / ] B
value
(P)
Switching
It sets current output for the display value at the output a b B B mode power
Input value Input value Input value supply
current DC 4-20mA.
It sets display value for 4mA at FS-L and 20mA at FS-H Gradient correction function
(Q)
Stepper
and the range between FS-H and FS-L should be 10% motor&
Min. αY
12.000
Display value
L-43
MT4Y/MT4W Series
① Select 0-1VDC for measuring input in Parameter1. Preset output Mode
② Standard specification in input : 0-1VDC and 1.000 [PA 2 group : mode]
therefore it has to be 15.000 (H-SC) for 1VDC(input) in
Mode Output operation Operation
order to display 3.000 for DC200mV(input). But it is dis-
able due to setting range is 9.999 H
H:Hysteresis
③ In this case, please check below chart.
Please set as INbH× H-SC=15.000 OFF No output
Setting H-SC L-SC INbH Other If it is equal or smaller than low
GO setting value, LO output will be ON.
lST
① Disable 0.000 1.000 - LO H If it is bigger than low setting value,
GO output will be ON.
② 7.500 0.000 2.000
If it is equal or bigger than high
③ 5.000 0.000 3.000 It will be the same HI H setting value, HI output will be ON.
hST
④ 3.750 0.000 4.000 display value. GO If it is equal or smaller than high
setting value, GO output will be ON.
⑤ 3.000 0.000 5.000
If it is equal or smaller than low
HI H setting value and equal or bigger
than high setting value, the output
Error correction function LhST GO will be ON. If it is bigger than Low
LO setting value and smaller than high
[PA 1 group : INbH / INbL] H
setting value, GO output will be ON.
It corrects display value error of measured input. If it is equal or bigger than low set
HI H and equal or bigger than high set
INbL : ±99 (Adjust deviation of low value) value, output will be ON. If it is
HhST GO smaller than low setting value and
INbH : 5.000 to 0.100 [Correct gradient(%) of high value] high setting value, GO output will
LO H
Display value=(Measured value × INbH) + INbL be ON.
Ex)Low value correction If it is equal or smaller than low
HI H setting value, LO output will be ON.
When there is an application where there is a residual If it is equal or smaller than high
LlST GO setting value, HI output will be ON.
voltage of 1.2V, but a 0V display is desired, then it If it is bigger than low setting value
LO H
is possible by adjusting the INbL parameter setting and High setting value, GO output
will be ON.
to 12(offset correcting value or equal to 1.2V without This operation is the same as lST
decimal) that the desired display value of 0 can be GO But it doesn't operate at initial low
LdST LO set value, it will operate at next low
achieved. H set value. If this is higher than low
Ex)High value correction set value, Go output will be ON.
When there is an application where the high actual ※"H" means hysteresis and able to set 1 to 99 at "HYS" mode
value of display is 501 and exceeds the 500V display in para-meter 2 among above comparison output chart.
range, then it is possible by adjusting the INbH ※In MT4Y-☐-☐3, ☐4, lST modes are only available to use.
parameter setting to 0.998(calculated by desired value
of 500/actual value of 501), that the desired value can
Sub output(Transmission function)
be achieved. ● RS485 communication output
※The offset correction range of INbL is within -99 to 99 It is able to set address(01 to 99)
for D-0, D-1 digit regardless of decimal point. It is able to transmit by selecting modulation speed
(Transmitted number of signal per 1sec.) of serial trans
Display cycle delay function -mission. (Selectable 1200, 2400, 4800, 9600bps)
[PA 2 group: D1sT] ● Low-speed serial output
In some applications the measured input may fluctuate It outputs current display value as Low-frequency(50Hz)
which in turn causes the display to fluctuate. By adjusting type.
the display cycle delay function time in the D1sT mode in ● Current output(DC4-20mA)
parameter 2, the operator can adjust the display time within It outputs DC4-20mA against High/Low-limit scale.
a range of 0.1 sec to 5 sec. For example, if the operator (Resolution: 12000 division)
sets the display cycle time to 4.0 sec., the display value ● BCD output
displayed will be the average input value over 4 sec. and It outputs display value as BCD Code..
also will show any changes if any every 4 sec. ※Only one sub-output is selectable.
(More than one sub-output is not allowed.)
Monitoring peak display value function
[PA 0 group: hPEK/lPEK, PA 2 group: PEkT ]
It monitors max./min. value of display value based on the
current displays value and then displays the data at hPEK,
lPEK of parameter 0. Set the delay time(0 to 30 sec.)
at PEkT of parameter 2 in order to prevent malfunction
caused by initial overcurrent or overvoltage, when monitor-
ing the peak value. Delay time is 0 to 30 sec. and it starts
to monitor the peak value after the set time. When pressing
any one of keys at hPEK, lPEK of parameter 0,
the monitored data is initialized.
※Monitoring function is not indicate when the delay time is
set as "00 5"at PEkT of parameter 2.
L-44
Multi Panel Meter
Time chart of BCD output and Serial output (A)
Photo
● BCD output(Negative logic) electric
sensor
(B)
t Fiber
t : 7.8ms optic
ta tw tb ta : 0.5ms sensor
tw : 5ms
Digit signal (C)
tb : 2.3ms Door/Area
sensor
D2 (F)
Digit Rotary
D1 encoder
D0
(G)
A H L H L H Connector/
Socket
B H L L H H (H)
Temp.
controller
Data C H H H H H
(I)
SSR/
D H H H H H Power
controller
dot H H L H H
(J)
Display Counter
tw t : 20ms (L)
ta : 0.05ms Panel
tw : 5ms meter
Latch tb : 4.95ms
t ta tb (M)
Tacho/
Speed/ Pulse
meter
Clock Cn-1 Cn C1
(N)
Display
Data Dn-1 Dn D1 unit
Input (O)
ordering 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 1 Sensor
controller
DP D C B A DP D C B A DP D C B A DP D C B A DP
Clock (P)
Switching
Data H H L H H H H H L L L H H L H H H H H L mode power
supply
*tw
*ta *tb
(Q)
Stepper
motor&
Latch Driver&Controller
Display (R)
Graphic/
Logic
panel
(S)
Field
network
device
(T)
Software
(U)
Other