Multi Panel Meter MT4Y/MT4W Series

The document summarizes an MT4Y/MT4W series multi panel meter that features various output options and functions. It has a max measuring input specification of 500VDC, 500VAC, 5ADC, 5ACA. It offers functions like monitoring max and min display values, display cycle delay, zero function, and high display correction. The power supply ranges from 12-24VDC to 100-240VAC.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
251 views11 pages

Multi Panel Meter MT4Y/MT4W Series

The document summarizes an MT4Y/MT4W series multi panel meter that features various output options and functions. It has a max measuring input specification of 500VDC, 500VAC, 5ADC, 5ACA. It offers functions like monitoring max and min display values, display cycle delay, zero function, and high display correction. The power supply ranges from 12-24VDC to 100-240VAC.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

MT4Y/MT4W Series Multi Panel Meter

DIN W72×H36mm, W96×H48mm, digital multi panel meter (A)


Photo
electric
Features sensor

● Super version of panel meter (B)


Fiber
● Various output options(Default : Indicator) optic
sensor
RS485 Communication output, Low speed serial output,
Current(4-20mA), BCD output, NPN/PNP open collector (C)
Door/Area
output, Relay output sensor

● Max. measuring input specification (D)


: 500VDC, 500VAC, 5ADC, 5ACA Proximity
sensor
● Max. display range : -1999 to 9999
● High/Low scale function (E)
● AC frequency measurement function : 0.1 to 9999Hz Pressure
sensor
● Various functions : Monitoring function for max. and
min. display value function, display cycle delay function, (F)
Rotary
Zero function, High display correction function, encoder

Current output scale function


(G)
● Wide range of power supply : 12-24VDC, 100-240VAC Connector/
Socket
Please read “Caution for your safety” in operation
manual before using.
※Upgraded version is released on April of 2006. (H)

Ordering information
Temp.
controller
Refer to the 4th Autonics catalogue for the
MT 4 W DV 4 N before version. (I)
SSR/
N Indicator(Without output function) Power
controller
0 Relay contact output
1 NPN open collector output (J)
Y Type Counter

2 PNP open collector output


※1
3 Relay contact output+Transmission output(DC4-20mA) (K)
Timer
※1
4 Relay contact output+RS485 communication output
5 BCD dynamic output (L)
Panel
6 Low speed serial output meter
Output ※Output(0 to 6) : Option
(M)
※1: Relay contact output of 3, 4 is able only to Low out. Tacho/
Speed/ Pulse
meter
N Indication type(No output function)
0 Relay contact output+Transmission output(DC4-20mA) (N)
Display
1 Relay contact output unit

2 NPN open collector output+BCD dynamic output


(O)
Sensor
3 PNP open collector output+BCD dynamic output controller
W Type
4 NPN open collector output+Transmission output(DC4-20mA)
(P)
Switching
5 PNP open collector output+Transmission output(DC4-20mA) mode power
supply
6 NPN open collector output+Low speed serial output
(Q)
7 PNP open collector output+Low speed serial output Stepper
motor&
8 NPN open collector output+RS485 output Driver&Controller

9 PNP open collector output+RS485 output (R)


Graphic/
※Output(0 to 9) : Option Logic
panel
Power supply 1 12-24VDC
(S)
4 100-240VAC Field
network
device
DV DC Voltage
Input DA DC Ampere (T)
Software
AV AC Voltage
AA AC Ampere
(U)
Other
Size Y DIN W72×H36mm
W DIN W96×H48mm
Digit
4 9999(4digit)
Item
MT Multi meter
※To measure the current over DC 5A, please select DV type because the shunt should be used.
※In case of selecting frequency display, no output will be provided even if it is output support models. (Main output, Sub output and RS485 output)

L-35
MT4Y/MT4W Series

Specifications
MT4Y-DV-4 MT4Y-AV-4 MT4W-DV-4 MT4W-AV-4 MT4W-DV-1 MT4W-AV-1
Series
MT4Y-DA-4 MT4Y-AA-4 MT4W-DA-4 MT4W-AA-4 MT4W-DA-1 MT4W-AA-1
AC voltage, AC voltage, AC voltage,
DC voltage, DC voltage, DC voltage,
Measurement input ampere, ampere, ampere,
ampere ampere ampere
Frequency Frequency Frequency
100-240VAC 50/60Hz 12-24VDC
Power supply
(Allowable voltage range: 90 to 110%) (Allowable voltage range: 90 to 110%)
Power consumption 5VA 5W
Display method 7Segment LED display(red)(Character height: 14.2mm)
• 23℃±5℃ - DC Type: F.S. ±0.1% rdg±2digit / AC Type: F.S. ±0.3% rdg±3digit
Display accuracy DC/AC Type F.S +0.3% rdg +3digit max. only for 5A terminal.
• -10℃ to 50℃ - DC/AC Type: F.S.±0.5% rdg±3digit
Max. allowable input 110% F.S for each measured input range
A/D conversion method Practical oversampling using successive approximation ADC
Sampling cycle DC type: 50ms, AC type: 16.6ms
Max. indication range -1999 to 9999(4digit)
• Relay output - Contact capacity: 250VAC 3A, 30VDC 3A / Contact composition: N.O(1a)
Preset output
• NPN/PNP Open collector output - 12-24VDC ±2V 50mA Max. (Resistive load)

• RS485 communication output - Baud rate: 1200/2400/4800/9600, Communication method: 2-wire half duplex,
Sub output Synchronous method: Asynchronous method, Protocol: Modbus type
(Transmission output) • Serial/BCD output - NPN Open collector output: 12-24VDC Max. 50mA(Resistive load)
• DC4-20mA output - Resolution: 12,000 division(Load resistance max. 600Ω)

AC measuring function 1 Selectable RMS or AVG
※1
Frequency measurement function Measurement range : 0.100 to 9999Hz(Variable by decimal point position)
※2
Hold function Includes(External hold function)
Insulation resistance Min. 100MΩ(at 500VDC megger) between external terminal and case
Dielectric stength 2,000VAC for 1minute between external terminal and case
Noise stength ±2kV the square wave noise(pulse width : 1㎲) by the noise simulator
Mechanical 0.75mm amplitude at frequency of 10 to 55Hz(for 1 min.) in each of X, Y, Z directions for 2hours
Vibration
Malfunction 0.5mm amplitude at frequency of 10 to 55Hz(for 1 min.) in each of X, Y, Z directions for 10minutes
Mechanical 100m/s²(approx. 10G) in each of X, Y, Z directions for 3 times
Shock
Malfunction 300m/s²(approx. 30G) in each of X, Y, Z directions for 3 times
Relay Malfunction Min. 20,000,000 operations
life cycle Mechanical Min. 100,000 operations(250VAC 3A Load current)
Environ Ambient temperature -10 to 50℃, storage: -20 to 60℃
-ment Ambient humidity 35 to 85%RH, storage: 35 to 85%RH
Double insulation or reinfored insulation
Insulation type
(Mark: , dielectric strength between the measuring input part and the power part: 1kV)
Approval
Unit weight Approx. 134g Approx. 211g
※1: AC measuring function, and frequency measuring function are only for AC measuring input type.
If only frequency input the AC type(display method of measuring input) which option is in MT4W, MT4W will operate the only indicating type.
※2: MT4Y- -4N model has no hold function.
※Environment resistance is rated at no freezing or condensation.

Front panel identification


● MT4Y Series ● MT4W Series
1 1
2 6 2 6
3
3

4 5
4 5
1. HI : High output indication of preset 4. MODE key : Mode Key
2. GO : GO output indication of preset 5. : Moves digit, enters parameter mode, : changes SV
3. LO : Low output indication of preset
6. Unit label part

※There is no 1, 2, 3 on a display panel of MT4Y- -4N, 45, 46 and MT4W- -4N.


※In MT4Y- - 3, 4, OUT is used for Go output display and there is no 1, 3 in display panel.

L-36
Multi Panel Meter

Connections (A)
Photo
electric
Measuring input connection of MT4Y Series sensor

(B)
● MT4Y-DV-4 ● MT4Y-AV-4 Fiber
optic
sensor
1 2 3 4 5 6 7 1 2 3 4 5 6 7
(C)
250mV 2V/1V Door/Area
/50mV sensor
5V/1V SOURCE 20V/10V SOURCE
100-240VAC 110V/50V 100-240VAC
50V/10V (D)
50/60Hz 5VA 50/60Hz 5VA
500V/250V Proximity
500V/100V
sensor

● MT4Y-DA-4 ● MT4Y-AA-4
(E)
Pressure
1 2 3 4 5 6 7 1 2 3 4 5 6 7 sensor

5mA 100mA
/2mA (F)
/50mA
Rotary
50mA/ SOURCE 500mA SOURCE encoder
4-20mA 100-240VAC /250mA 100-240VAC
500mA/200mA 50/60Hz 5VA 1A 50/60Hz 5VA
(G)
5A/2A 5A/2.5A Connector/
Socket

Output terminal of connection of MT4Y Series (H)


Temp.

●MT4Y- -4N (Indicator) ●MT4Y- -40 ●MT4Y- -41 controller

(Triple relay contact output) (Triple NPN O.C output) (I)


SSR/
8 9 10 11 12 13 8 9 10 11 12 13 Power
controller

1 2 3 4 5 6 7 (J)
Hold/Zero Hold/Zero Counter
HI GO LO COM HI GO LO COM
●MT4Y- -42 ●MT4Y- -43 ●MT4Y- -44 (K)
(Triple PNP O.C output) (Relay output+Transmission output) (Relay+RS485 communication output) Timer

8 9 10 11 12 13 8 9 10 11 12 13 8 9 10 11 12 13 (L)
+ - Panel
B(-) A(+) meter

Hold/Zero DC4-20mALoad OUT OUT


600Ω max. Hold/Zero RS485 Hold/Zero
HI GO LO COM (M)
Tacho/
Speed/ Pulse
●MT4Y- -45 ●MT4Y- -46(Low speed serial output) meter

(BCD Dynamic output) 8 9 10 11 12 13


Hold/Zero PCB (N)
Display
A C D0 D2 Dot unit

Hold/Zero
2 4 6 8 10 12 14 CLOCK DATA LATCH POL COM (O)
※POL : When a display value is "-", the signal Sensor
controller
1 3 5 7 9 11 13 of "-" will be outputted.
(P)
COM B D D1 D3 POL ※Hirose connector pin header model of the unit : HIF3BA-14PA-2.54DS Switching
※Contact Hirose Electric to purchase socket and wires of Hirose connector. mode power
supply
[Socket : HIF3BA-14D-2.54R]
(Q)
Stepper
Measuring input connection of MT4W Series motor&
Driver&Controller

● MT4W-DV- ● MT4W-AV- (R)


Graphic/
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 Logic
panel

250mV (S)
2V/1V
/50mV Field
+ - + - network
5V/1V Hold/Zero 20V/10V Hold/Zero device
50V/10V
SOURCE 110V/50V SOURCE
12-24VDC 12-24VDC
500V/100V 500V/250V (T)
100-240VAC 100-240VAC Software
50/60Hz 5VA 50/60Hz 5VA
● MT4W-DA- ● MT4W-AA-
(U)
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 Other

5mA 100mA
/2mA /50mA
+ - + -
50mA/ Hold/Zero 500mA
Hold/Zero
4-20mA SOURCE /250mA SOURCE
500mA/200mA 12-24VDC 1A 12-24VDC
100-240VAC 5A/2.5A 100-240VAC
5A/2A 50/60Hz 5VA 50/60Hz 5VA

L-37
MT4Y/MT4W Series
Output terminal connection of MT4W Series
● MT4W- - 0(Triple relay contact output ● MT4W- - 1 (Triple relay contact output)
+Transmission output)
MAIN OUT MAIN OUT
CONTACT OUT CONTACT OUT
: 250VAC 3A 1a RESISTIVE LOAD : 250VAC 3A 1a RESISTIVE LOAD

10 11 12 13 14 15 10 11 12 13 14 15
+ -
DC4-20mA
HI GO LO
Load 600Ω Max.
HI GO LO COM

1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9

PCB

1 2 3 4 5 6 7 8 9 ※Hirose connector pin header model of the unit : HIF3BA-20PA-2.54DS


※Contact Hirose Electric to purchase socket and wires of Hirose connec-
tor. [Socket: HIF3BA-20D-2.54R]
● MT4W- - 2 / MT4W- - 3 (Triple NPN/PNP open collector output+BCD output)
+24VDC +24VDC
30mA Max. 30mA Max.
GO B D D1 D3 DOT COM2 GO

MAIN OUT : 2 4 6 8 10 12 14 16 18 20 MAIN OUT : 2 4 6 8


NPN OPEN COLLECTOR PNP OPEN COLLECTOR
12-24VDC Max. 50mA 12-24VDC Max. 50mA
1 3 5 7 9 11 13 15 17 19 1 3 5 7
A C D0 D2 POL
COM1 HI LO 0V COM1 HI LO 0V
BCD OUT :
NPN OPEN COLLECTOR ※POL: When a display value is "-", the signal of "-" will be
12-24VDC Max. 50mA outputted.

● MT4W- - 4/ MT4W- - 5 (Triple NPN/PNP open collector output+Transmission output)


+24VDC +24VDC
GO 30mA Max. GO 30mA Max.
(-)

MAIN OUT : 2 4 6 8 10 12 14 16 18 20 MAIN OUT : 2 4 6 8


NPN OPEN COLLECTOR PNP OPEN COLLECTOR
12-24VDC Max. 50mA 12-24VDC Max. 50mA
1 3 5 7 9 11 13 15 17 19 1 3 5 7
(+)
COM1 HI LO 0V COM1 HI LO 0V
Current:
DC4-20mA LOAD 600Ω Max.

● MT4W- - 6/ MT4W- - 7 (Triple NPN/PNP open collector output+Low speed serial output)
+24VDC ※POL: When a display value is "-", the signal of "-" will be +24VDC
GO 30mA Max. outputted. GO 30mA Max.

2 4 6 8 10 12 14 16 18 20 2 4 6 8
MAIN OUT :
MAIN OUT :
PNP OPEN COLLECTOR
NPN OPEN COLLECTOR
1 3 5 7 9 11 13 15 17 19 12-24VDC Max. 50mA 1 3 5 7
12-24VDC Max. 50mA
COM2 DATA
COM1 HI LO 0V COM1 HI LO 0V
SERIAL OUT :
NPN OPEN COLLECTOR
12-24VDC Max. 50mA

● MT4W- - 8/ MT4W- - 9 (Triple NPN/PNP open collector output+RS485 output)


+24VDC +24VDC
30mA RS485
GO 30mA Max.
GO Max. B(-)
MAIN OUT : MAIN OUT : 2 4 6 8
NPN OPEN COLLECTOR 2 4 6 8 10 12 14 16 18 20 PNP OPEN COLLECTOR
12-24VDC Max. 50mA 12-24VDC Max. 50mA
1 3 5 7
1 3 5 7 9 11 13 15 17 19

COM1 HI LO COM1 HI LO 0V
0V A(+)
RS485

L-38
Multi Panel Meter

Dimensions (unit: mm)


(A)
Photo
electric
sensor
● MT4Y- -4N, 45, 46
(B)
85 Fiber
optic
72 6 77 sensor

(C)
● Panel cut-out Door/Area
sensor
Min. 91
36

30
(D)
Proximity
31.5 + 00.5 sensor

Min. 40
<MT4Y- -4N, 40 to 44, 46>
68
+ 0.7

● MT4Y- -43, 44 0 (E)


Pressure
sensor

(F)
Rotary
6 77 10 Pin Hirose connector encoder

(HIF3BD-10PA-2.54DS)
(G)
● MT4Y- -40, 41, 42 Connector/
Socket

30
(H)
Temp.
<MT4Y- -45> controller

(I)
SSR/
Power
controller

● MT4W- - N (Indicator)
(J)
Counter
109 106 ● Panel cut-out
96 6 89.5 Relay contact
Min. 116
output terminal (K)
Timer

45 + 00.6
Min. 52
(L)
44.8

Panel
48

92 + 00.8 meter

(M)
Tacho/
※There is no Relay contact output terminal Speed/ Pulse
meter
block in indication type.
(N)
< MT4W- - N, MT4W- - 0, 1> Display

● MT4W- - 0 to 9 unit

110.4
(O)
6 89.5 Sensor
20 Pin Hirose connector controller

(HIF3BA-20PA-2.54DS)
(P)
Switching
mode power
44.8

supply

(Q)
Stepper
motor&
Driver&Controller
< MT4W- - 2 to 9>
(R)
Graphic/
Logic
Parameter setting panel

(S)
Field
RUN network
※Press key in RUN status, it will advance to [ ](Parameter 0) group. device

Press Key Press Key Press ※Press key for 2 sec. in RUN mode, [ ] is displayed. (T)
Key
for 3sec.
※ Press key for 4 sec. in RUN mode, [ ] is displayed after [ ]. Software

When pressing key continually, it stops displaying at [ ].


PA0 PA1 ※It is advanced to current display parameter releasing key at [ ] or [ ]. (U)
Other
Press Key Press Key
※ Press key for 3 sec., it is returned to RUN at any position.
for 2sec. ※If any key is not touched for 60 sec. in each parameter, it returns to RUN mode.
※ After return to RUN mode, press key within 2 sec., it returns to previous pa-
PA2 rameter.(Refer to the below descriptions for set parameter.)
※It cannot advance to[ ] when preset output operation mode of [ ] is [ ].
Press Key
for 3sec.

L-39
MT4Y/MT4W Series

Parameter 1 group
RUN
Press key for 3sec.

PA1
● Measuring input chart by model
Display of factory Select measuring input specification by
IN-R default for
measuring input
. Item Range of measuring input
- Refer to " Specification of MT4Y/W-DV 500V 100V 50V 10V 5V 1V 0.25V 50ㅡMV 500V
measuring input and range".
MT4Y/W-DA 5A 2A )5A )2A 50MV 4-20MV 5MV 2MV 5A
MT4Y/W-AV 500V 250V 110P(☆) 50V 20V 10V 2V 1V 500V
Select the display method of measuring input. MT4Y/W-AA 5A 2.5A 1A )5A )25A )1A 50mA 5A
D1SP STND ※(☆) Standard specification. (110P is 440VAC/110VAC P.T)
Select STND SCAL FREQ
- Refer to measuring input specification and range chart.
(FREQ mode is only for AC measuring type.)

Select measuring method for AC.


IN-T AVG
Select AVG RM5 (Average: AVG/Root mean square: RMS)
(This parameter will be displayed only for AC measuring models. In case
of selecting frequency display, it will not be displayed.)

When DISP is SCAL W h e n DISP is FREQ


When DISP is STND
(It is only displayed for AC measuring type.)

Max. display Decimal point Select decimal point position. Decimal point Set frequency measuring
STND value DOT position 0 0.0 0.00 0.000
DOT position range, it is decided as
the decimal point position.
※When selecting the decimal point ( Change the
position, "H-SC ", L-SC " have deci- decimal point position)
It shows Max. display mal point position.
value of standard 0 1 to 9999Hz
specification.
Set display value against 0.0 0.1 to 999.9Hz
Display value is fixed. Max. display
H-SC value max. measuring input. 0.00 0.10 to 99.99Hz
( : Shift the digit 0.000 0.100 to 9.999Hz
: Change setting value) ※In case of selecting frequency display, no
output will be provided even if it is output
support models (Main output, Sub output
and RS485 output).
Set display value against
Min. display
L-SC value
min. measuring input.

( : Shift the digit


: Change setting value)
It corrects a gradient of
It corrects a gradient of High-limit display value against max. input. display value against max.
INbH !000 The setting range is 0.100 to 5.000(%). INbH !000 input.
( : Change setting value, : Shift the digit) Setting range:0.001 to 9.999
( : Shift the digit
: Change setting
value)
It corrects deviation of Low-limit display value against Min. input. Set
INbL 00 Setting range is -99 to 99.(Refer to zero point function) INbE 10-0 Setting range : 10-2 to 101
( : Set a deviation value, : Shift the digit) ( : Shift the digit
: Change setting
value)

※After setting each mode, press MODE key for 2 sec. to return to RUN.
※If any key is untouched for 60sec. after advance to Parameter, it will return to RUN.

Factory defaults
Parameter MT4Y/W-DV MT4Y/W-DA MT4Y/W-AV MT4Y/W-AA Parameter MT4Y/W-DV MT4Y/W-DA MT4Y/W-AV MT4Y/W-AA

1N-R 500V SA 500V SA 1NbH !000 !000 !000 !000


D1SP STND STND STND STND INbL 00 00 00 00
1N-T - - AVG AVG DOT )0 )000 )0 )000
STND 50)0 %000 50)0 %000 1NbE - - 10-0 10-0

L-40
Multi Panel Meter

Parameter 2 group (A)


Photo
electric
RUN sensor

(B)
Press key for 5sec. Fiber
optic

PA1 sensor

Move after 1sec. (C)


Door/Area
Select Preset output mode. Selectable:
OUtT OFF OFF lST hST LhST HhST LlST LdST
sensor

(D)
In MT4Y-□-□3,□4, "OFF, LST" are only displayed. Proximity
Set preset hysteresis. Within 10% of F.S. sensor
HYS HYS But, it is not displayed when OVtT mode is OFF.
(E)
Pressure
sensor
Set startup compensation time.
STaT 0)0 ( :Shift the digit, : Change setting value)
Setting range : 0.0 to 99.9sec. (F)
Rotary
encoder
Set monitoring delay time.
PEkT 00 5 ( :Shift the digit, : Change setting value)
(G)
Setting range : 00 to 30sec. Connector/
Socket
Set a display cycle. ( :Shift the digit, : Change setting value)
D1sT )2 5 Setting range : 0.1 to 5.0sec.
(H)
Temp.
controller
Select zero function with operation at front. (Set with key)
ZERO NO When + Key key are pressed for 3 sec. to set ㅛㄷㄴYES, it will be zero function and the deviation (I)
SSR/
value is saved automatically at ㅛ INbL mode. Power
controller
Select input with 6, 7(MT4W)[12, 13(MT4Y)] terminal or zero function for external signal.
EV1N HOLD (Set with , Key) (J)
HOLD : Holding display value, ZERO : Zero function using Hold/Zero terminal Counter

Set the high limit value, output point of current output 20mA.
FS-H 50)0 ( :Shift the digit, : Change setting value) (K)
Timer
(When changing measuring input and prescale mode, it is changed automatically
as maximum value of input range.)
Set the low limit value, output point of current output 4mA. (L)
FS-L 00)0 ( :Shift the digit, : Change setting value) Panel
meter
(When changing measuring input and prescale mode, it is changed automatically
as minimum value of input range.)
(M)
Set the address of RS485 communication output. Tacho/
ADRS 01 ( :Shift the digit, : Change setting value)
Speed/ Pulse
meter
Setting range : 01~ 99
(N)
Select Baud rate of RS485 communication output. Display
BPS 9600 Setting range : 9600 4800 2400 1200
unit

(O)
Sensor
Set parity bit of RS485 communication.
PRTY NONE Set range: NONE/EVEN/ODD
controller

(P)
Switching
Set stop bit of RS485 communication. mode power
STP 2 Set range: 1 / 2
supply

(Q)
Stepper
motor&
Set response wait time of RS485 communication.
RSmT 5 Set range: 5 to 99
OFF Disable to lock keys
Driver&Controller

(R)
Graphic/
LOC1 Lock Parameter 1 Logic
Set key lock function and select from 4 types. panel
LOC2 Lock Parameter 1, 2
LOC OFF ㅐㄹOFF LOC1 LOC2 LOC3 ㅐㄹOFF LOC3 Lock Parameter 0, 1 and 2 (S)
Field
network
※The dotted mode is only displayed for output type. device

※After setting each mode, press MODE key for 2 sec. to return to RUN mode. (T)
※If any key is untouched for 60sec. after advance to PARAMETER, it will return to RUN mode. Software

Factory defaults
(U)
Parameter MT4Y/W-DV MT4Y/W-DA MT4Y/W-AV MT4Y/W-AA Parameter MT4Y/W-DV MT4Y/W-DA MT4Y/W-AV MT4Y/W-AA Other

OUtT OFF OFF OFF OFF EV1N HOLD HOLD HOLD HOLD
HYS 001 001 001 001 FS-H 50)0 %000 50)0 %000
STAT 0)0 0)0 0)0 0)0 FS-L 00)0 )000 00)0 )000
PEkT 00 5 00 5 00 5 00 5 ARDS 01 01 01 01
DIsT )2 5 )2 5 )2 5 )2 5 BPS 9600 9600 9600 9600
ZERO NO NO NO NO LOC OFF OFF OFF OFF

L-41
MT4Y/MT4W Series

Parameter 0 group
RUN
Press key

Set preset High-limit value. (Set with , , key)


hSET 50)0 ※It is displayed when set the preset only.
When set OFF in OUtT mod e i f P A - 2 , t h e p a r a m e t e r i s n o t d i s p l a y e d .

Set preset Low-limit value. (Set with , , key)


lSET 00)0 ※It is displayed when set the preset only.
When set OFF in OUtT mode if PA-2, the parameter is not displayed.

It shows High-limit monitoring value while it is in RUN mode.


hPEK )0 It will be reset by pressing , , key.

It shows Low-limit monitoring value while it is in RUN mode.


lPEK )0 It will be reset by pressing , , key.
※If "00" is set in PEKT mode of PA-2, hPEK and lPEK modes will not be displayed.

※If any key is untouched for 60sec. after advance to Parameter, it will return to RUN mode.

Factory defaults
Parameter MT4Y/W-DV MT4Y/W-DA MT4Y/W-AV MT4Y/W-AA Parameter MT4Y/W-DV MT4Y/W-DA MT4Y/W-AV MT4Y/W-AA
hSET 50)0 %000 50)0 %000 hPEK )0 )000 )0 )000
lSET 00)0 )000 00)0 )000 lPEK )0 )000 )0 )000

Measuring input and range


Type Measuring input and range Input impedance Display range [STND] Prescale display range [SCAL]

0-500V [500V] 4.33MΩ 0.0 to 500.0


0-100V [100V] 4.33MΩ 0.0 to 100.0
0-50V [50V] 433.15kΩ 0.00 to 50.00
0-10V [10V] 433.15kΩ 0.00 to 10.00
DC Volt
0-5V [5V] 43.15kΩ 0.000 to 5.000
0-1V [1V] 43.15kΩ 0.000 to 1.000
0-250mV [0.25V] 2.15kΩ 0.0 to 250.0 DOT Display range
0-50mV [50MV] 2.15kΩ 0.00 to 50.00 0 -1999 to 9999
0-5A [5A] 0.01Ω 0.000 to 5.000 )0 -199.9 to 999.9
0-2A [2A] 0.01Ω 0.000 to 2.000 -19.99 to 99.99
)00
0-500mA [0.5A] 0.1Ω 0.0 to 500.0
)00 -1.999 to 9.999
0-200mA [0.2A] 0.1Ω 0.0 to 200.0
DC Ampere (The display range is changed
0-50mA [50MA] 1.0Ω 0.00 to 50.00
according to the decimal point
4-20mA [4-20] 1.0Ω 4.00 to 20.00 position.)
0-5mA [5MA] 10.0Ω 0.000 to 5.000
0-2mA [2MA] 10.0Ω 0.000 to 2.000 ※Please connect proper terminal its
0-500V [500V] 4.98MΩ 0.0 to 500.0 max. input voltage is within 30 to
100% of input terminal.
0-250V [250V] 4.98MΩ 0.0 to 250.0 When it is higher than input
0-110V [110P] 1.08MΩ 0.0 to 440.0 voltage, it may cause a breakdown
0-50V [50V] 1.08MΩ 0.00 to 50.00 of terminal and over display range
AC Volt and the accuracy is decreased
0-20V [20V] 200kΩ 0.00 to 20.00
when it is connected to the
0-10V [10V] 200kΩ 0.00 to 10.00
terminal under 30%.
0-2V [2V] 20kΩ 0.000 to 2.000
0-1V [1V] 20kΩ 0.000 to 1.000 ※110P is standard specification
0-5A [5A] 0.01Ω 0.000 to 5.000 440V/110VAC P.T.
0-2.5A [2.5A] 0.01Ω 0.000 to 2.500
0-1A [1A] 0.05Ω 0.000 to 1.000
AC Ampere 0-500mA [0.5A] 0.1Ω 0.0 to 500.0
0-250mA [0.25A] 0.1Ω 0.0 to 250.0
0-100mA [0.1A] 0.5Ω 0.0 to 100.0
0-50mA [50MA] 0.5Ω 0.00 to 50.00

L-42
Multi Panel Meter

Functions change NO→ YES. (A)


Photo

AC frequency measurement function Startup compensation time function


electric
sensor

[PA 1 group: DISP] [PA 2 group : STAT] (B)


Fiber
It measures input signal frequency when it is AC input. This time function limits the operation of an output until the optic
sensor
It uses fixed decimal point[PA1: DOT], measured range measured input(overvoltage or inrush current) is stable
can be changed by setting and measured range of decimal at moment of power on. All outputs are off during startup (C)
Door/Area
point position is as below chart. It is available to adjust the compensation time setting after power is applied. sensor

upper gradient at [PA 1: INbH]and [PA 1 : INbE]. In order Setting range : 00.0 to 99.9(unit: sec.)
to measure frequency normally, input signal, over 10% F.S. Factory default : 00.0 (D)
Proximity
of the measured range, should be supplied. Please select Error display function sensor

the proper point of


Display Description
① Measuring range (E)
Pressure
Flashing when measuring input is exceeded the max. sensor
Decimal point HHHH
0.000 0.00 0.0 0 allowable input(110%)
position Flashing when measuring input is exceeded the minx. (F)
Measurement 0.100 to 0.10 to 0.1 to 1 to LLLL Rotary
allowable input(-10%) encoder
range 9.999Hz 99.99Hz 999.9Hz 9999Hz Lights when display input is exceeded the max. display
D-HH
※Accuracy of frequency measurement : range(9999) or H-SC setting value (G)
Below 1kHz, F.S. ±0.1rdg ±2digit. D-LL
Lights when display input is exceeded the min. display Connector/
Socket
From 1kHz to 10kHz, F.S. ±0.3rdg ±2digit. range (-1999) or L-SC setting value
② INbH : 0.100 to 9.999 [Gradient adjustment of high value] Flashes when measuring frequency is exceeded themax. (H)
F-HH
-2 -1 0 1
③ INbE : 10 , 10 , 10 , 10 [Index adjustment of INbH] measuring rvalue (9999) Temp.
controller
OVER Flashes when it exceeds zero adjustment range(±99)
Zero adjustment function (I)
(Deviation correction function of low limit ※Error display is released automatically when it is in the SSR/
Power
measured and display range.
display value)
controller

※"LLLL" is displayed when the measuring input is


It adjusts the display value of the optional configured input 4-20mA. (J)
value as zero by force, zero point error can be adjusted ※ After flashing " OVER" 2 times when it exceeds the zero
Counter

with 3 ways as below. When zero point adjustment with range, it returns to RUN mode.
front key and Hold terminal is finished normally, zero point (K)

of measurement terminal is displayed and the adjusted


Display scale function[PA 1 group: H-SC/L-SC] Timer

value at saved in INbL automatically. This function is to display setting(-1999 to 9999) of


particular High/Low-limit value in order to display High/Low- (L)
Panel
Operation Input correction value Front panel key External input signal limit value of measured input. If measured inputs are 'a' and meter

Press both
Short-circuit external 'b' and particular values are 'A' and 'B', it will display a=A,
(M)
PA 1: Direct Hold terminal no.11,12 b=B as below graphs. Tacho/
, keys for
input correction [no. 6, 7(MT4W)]over Speed/ Pulse
Description 3 sec. at the meter
value method at min. 50m. Display B B B
measuring Display Display
INbL mode. ※It is enable to use value (N)
mode. A value A value
in option mode. a
Display
b unit
a b a b A
※Refer to " Error correction function", " Error display Input value Input value
Input value
function" and " Parameter 2" for function and error. (O)
Display A a b A
Sensor
Current output(DC4-20mA) scale function value
Display A a b
controller

value Display
[PA2 group: / ] B
value
(P)
Switching
It sets current output for the display value at the output a b B B mode power
Input value Input value Input value supply
current DC 4-20mA.
It sets display value for 4mA at FS-L and 20mA at FS-H Gradient correction function
(Q)
Stepper
and the range between FS-H and FS-L should be 10% motor&

※When min. set interval between FS-H and FS-L is


[PA 1 group: INbH] Driver&Controller

This function is to correct a gradient of prescale value and (R)


set as under 10% F.S., it changed as over 10% F.S. Graphic/
display value. (Fig.1)Display value Y can be used as α, β Logic
automatically.) panel
※Preset display value is fixed to output as 4mA at under times against X input value by correction function[INbH].
And also can be used as correction function of max. display (S)
FS-L and 20mA at over FS-H. Field

Output value(H-SC). Adjustment range is 0.100 to 5.000 and network


device
20mA multiply current gradient.
Ex)Input : DC200mV, Display : 3.000 for MT4W-DV (T)
Software
15.000
Display value

Min. αY
12.000
Display value

4mA setting range α time (U)


Other
9.000
F.S. 10% Y Display
Display value βtime 6.000
FS-L FS-H value for
βY
Initialization function 3.000 measuring
1.000 input
It initializes as the factory default status. If press , , Input
0 X Input
keys together for 2sec. in RUN mode, INlT mode and the (Fig. 1) value 0.2 0.4 0.6 0.8 1V value
setting value (NO) is displayed every 0.5 sec. and it will be (Setting the gradient correction value)
initialized as the factory default when press MODE key after

L-43
MT4Y/MT4W Series
① Select 0-1VDC for measuring input in Parameter1. Preset output Mode
② Standard specification in input : 0-1VDC and 1.000 [PA 2 group : mode]
therefore it has to be 15.000 (H-SC) for 1VDC(input) in
Mode Output operation Operation
order to display 3.000 for DC200mV(input). But it is dis-
able due to setting range is 9.999 H
H:Hysteresis
③ In this case, please check below chart.
Please set as INbH× H-SC=15.000 OFF No output
Setting H-SC L-SC INbH Other If it is equal or smaller than low
GO setting value, LO output will be ON.
lST
① Disable 0.000 1.000 - LO H If it is bigger than low setting value,
GO output will be ON.
② 7.500 0.000 2.000
If it is equal or bigger than high
③ 5.000 0.000 3.000 It will be the same HI H setting value, HI output will be ON.
hST
④ 3.750 0.000 4.000 display value. GO If it is equal or smaller than high
setting value, GO output will be ON.
⑤ 3.000 0.000 5.000
If it is equal or smaller than low
HI H setting value and equal or bigger
than high setting value, the output
Error correction function LhST GO will be ON. If it is bigger than Low
LO setting value and smaller than high
[PA 1 group : INbH / INbL] H
setting value, GO output will be ON.
It corrects display value error of measured input. If it is equal or bigger than low set
HI H and equal or bigger than high set
INbL : ±99 (Adjust deviation of low value) value, output will be ON. If it is
HhST GO smaller than low setting value and
INbH : 5.000 to 0.100 [Correct gradient(%) of high value] high setting value, GO output will
LO H
Display value=(Measured value × INbH) + INbL be ON.
Ex)Low value correction If it is equal or smaller than low
HI H setting value, LO output will be ON.
When there is an application where there is a residual If it is equal or smaller than high
LlST GO setting value, HI output will be ON.
voltage of 1.2V, but a 0V display is desired, then it If it is bigger than low setting value
LO H
is possible by adjusting the INbL parameter setting and High setting value, GO output
will be ON.
to 12(offset correcting value or equal to 1.2V without This operation is the same as lST
decimal) that the desired display value of 0 can be GO But it doesn't operate at initial low
LdST LO set value, it will operate at next low
achieved. H set value. If this is higher than low
Ex)High value correction set value, Go output will be ON.
When there is an application where the high actual ※"H" means hysteresis and able to set 1 to 99 at "HYS" mode
value of display is 501 and exceeds the 500V display in para-meter 2 among above comparison output chart.
range, then it is possible by adjusting the INbH ※In MT4Y-☐-☐3, ☐4, lST modes are only available to use.
parameter setting to 0.998(calculated by desired value
of 500/actual value of 501), that the desired value can
Sub output(Transmission function)
be achieved. ● RS485 communication output
※The offset correction range of INbL is within -99 to 99 It is able to set address(01 to 99)
for D-0, D-1 digit regardless of decimal point. It is able to transmit by selecting modulation speed
(Transmitted number of signal per 1sec.) of serial trans
Display cycle delay function -mission. (Selectable 1200, 2400, 4800, 9600bps)
[PA 2 group: D1sT] ● Low-speed serial output
In some applications the measured input may fluctuate It outputs current display value as Low-frequency(50Hz)
which in turn causes the display to fluctuate. By adjusting type.
the display cycle delay function time in the D1sT mode in ● Current output(DC4-20mA)
parameter 2, the operator can adjust the display time within It outputs DC4-20mA against High/Low-limit scale.
a range of 0.1 sec to 5 sec. For example, if the operator (Resolution: 12000 division)
sets the display cycle time to 4.0 sec., the display value ● BCD output
displayed will be the average input value over 4 sec. and It outputs display value as BCD Code..
also will show any changes if any every 4 sec. ※Only one sub-output is selectable.
(More than one sub-output is not allowed.)
Monitoring peak display value function
[PA 0 group: hPEK/lPEK, PA 2 group: PEkT ]
It monitors max./min. value of display value based on the
current displays value and then displays the data at hPEK,
lPEK of parameter 0. Set the delay time(0 to 30 sec.)
at PEkT of parameter 2 in order to prevent malfunction
caused by initial overcurrent or overvoltage, when monitor-
ing the peak value. Delay time is 0 to 30 sec. and it starts
to monitor the peak value after the set time. When pressing
any one of keys at hPEK, lPEK of parameter 0,
the monitored data is initialized.
※Monitoring function is not indicate when the delay time is
set as "00 5"at PEkT of parameter 2.

L-44
Multi Panel Meter
Time chart of BCD output and Serial output (A)
Photo
● BCD output(Negative logic) electric
sensor

(B)
t Fiber
t : 7.8ms optic
ta tw tb ta : 0.5ms sensor

tw : 5ms
Digit signal (C)
tb : 2.3ms Door/Area
sensor

Input Data Data (D)


Proximity
sensor
31.2ms
(E)
Pressure
D3 sensor

D2 (F)
Digit Rotary
D1 encoder

D0
(G)
A H L H L H Connector/
Socket

B H L L H H (H)
Temp.
controller
Data C H H H H H
(I)
SSR/
D H H H H H Power
controller

dot H H L H H
(J)
Display Counter

● Serial output(Negative logic)-Clock frequency:50Hz (K)


Timer

tw t : 20ms (L)
ta : 0.05ms Panel
tw : 5ms meter

Latch tb : 4.95ms
t ta tb (M)
Tacho/
Speed/ Pulse
meter
Clock Cn-1 Cn C1
(N)
Display
Data Dn-1 Dn D1 unit

Input (O)
ordering 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 1 Sensor
controller
DP D C B A DP D C B A DP D C B A DP D C B A DP
Clock (P)
Switching
Data H H L H H H H H L L L H H L H H H H H L mode power
supply
*tw
*ta *tb
(Q)
Stepper
motor&
Latch Driver&Controller

Display (R)
Graphic/
Logic
panel

(S)
Field
network
device

(T)
Software

(U)
Other

L-45