The document summarizes a configurable wall cladding system called METAL W-H 1100. It is a hook-on wall cladding solution that uses a concealed grid system. The system uses galvanized steel panels that are square edged and come in four types - A, B, C, and D - with varying length, width, and maximum size dimensions. It can be ordered with plain, micro-perforated, or standard perforated surfaces and includes a black acoustic fleece inlay as well as perimeter shadow gaps between panels.

Uploaded by

gabibotez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
155 views11 pages

METAL W-H 1100: Configurable Wall Cladding System

The document summarizes a configurable wall cladding system called METAL W-H 1100. It is a hook-on wall cladding solution that uses a concealed grid system. The system uses galvanized steel panels that are square edged and come in four types - A, B, C, and D - with varying length, width, and maximum size dimensions. It can be ordered with plain, micro-perforated, or standard perforated surfaces and includes a black acoustic fleece inlay as well as perimeter shadow gaps between panels.

Uploaded by

gabibotez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

METAL W-H 1100

CONFIGURABLE WALL CLADDING SYSTEM


HOOK-ON SOLUTION WITH CONCEALED GRID

ELEVATION VIEW PANEL MATERIAL GALVANISED STEEL 1.0 mm


EDGE DETAIL SQUARE EDGED
GAP DETAIL 5 mm GAP, WITH 5 mm GASKET AND SPACERS ON ONE LONG AND ONE SHORT SIDE
DIMENSIONS PANEL TYPE A LENGTH (A): 600 - 1300 mm / WIDTH (B): 250-1000 mm / MAX. PANEL SIZE: 1.3 m²

MODULE
DIMENSIONS PANEL TYPE B LENGTH (A): 1301 - 2500 mm / WIDTH (B): 250-1000 mm / MAX. PANEL SIZE: 2.5 m²
DIMENSIONS PANEL TYPE C LENGTH (A): 2501 - 3000 mm / WIDTH (B): 250-1000 mm / MAX. PANEL SIZE: 3.0 m²
DIMENSIONS PANEL TYPE D LENGTH (A): 600 - 2000 mm / WIDTH (B): 250-1000 mm / MAX. PANEL SIZE: 2.0 m²
PERFORATION PLAIN, Rd 1522, Rg 2516
ACOUSTIC INLAY BLACK ACOUSTIC FLEECE, FURTHER INLAYS ON REQUEST
GRID SYSTEM U-WALL PROFILE FIXED TO WALL

5
PERIMETER SHADOW GAP, NO CUT PANELS
APPLICATION AREA ROOMS WITHOUT IMPACT RESISTANCE REQUIREMENT

DETAIL A Rd 1522 Rg 2516


MICRO PERFORATION STANDARD PERFORATION
22% OPEN AREA 16% OPEN AREA

PANEL LENGTH (A)


BPM315627
STANDARD PLAIN BORDER STANDARD PLAIN BORDER
BPM315628

MODULE
4x BPM311191
PLASTIC SPACER

5.5
5

4
BLACK GASKET Ø1.5 4 Ø2.5 5.5

BPM315624 FURTHER PERFORATIONS ON REQUEST


21

BPM315623

A DETAIL B

MODULE
BPM315624
BPM315627

60 +17
4x BPM311191

-8
B

20
60 +17
-8

5
BPM315623 BPM315628
PANEL WIDTH (B) BLACK GASKET
5
PLASTIC SPACER
MODULE MODULE MODULE

THESE DRAWINGS SHOW TYPICAL CONDITIONS WHICH THE ARMSTRONG PRODUCTS DEPICTED ARE INSTALLED. THEY ARE NOT SUBSTITUTE FOR AN ARCHITECT'S OR ENGINEER'S PLAN AND DO NOT REFLECT THE UNIQUE REQUIREMENTS OF LOCAL BUILDING CODES, LAWS, STATUES, ORDINANCES RULES AND REGULATIONS (LEGAL REQUIREMENTS) THAT MAY BE APPLICABLE FOR A PARTICULAR INSTALLATION. ARMSTRONG DOES NOT WARRANT, AND ASSUMES NO LIABILITY
FOR THE ACCURACY OR COMPLETENESS OF THE DRAWING FOR A PARTICULAR INSTALLATION OR THEIR FITNESS FOR A PARTICULAR PURPOSE. THE USER IS ADVICE TO CONSULT WITH A DULY LICENSED ARCHITECT OR ENGINEER IN THE PARTICULAR LOCALE OF THE INSTALLATION TO ASSURE COMPLIANCE WITH ALL LEGAL REQUIREMENTS. ARMSTRONG IS NOT LICENSED TO PROVIDE PROFESSIONAL ARCHITECTURE OR ENGINEERING DESIGN SERVICES. 08.08.2017 www.armstrongceilings.eu
METAL W-H 1100
CONFIGURABLE WALL CLADDING SYSTEM
HOOK-ON SOLUTION WITH CONCEALED GRID

PANEL TYPE OPTIONS UPRIGHT PANELS WITH 8 SUSPENSION POINTS


STANDARD PANEL
FOR DETAILED INFORMATION SEE SEPARATE DATASHEET
(B) = 250-1000 (B) = 250-1000
PERIMETER PANEL
WITH VISIBLE EDGES

UPRIGHT PANELS WITH 6 SUSPENSION POINTS


A SAME PANEL CAN BE USED ON
(B) = 250-1000 (B) = 250-1000 180° THE OPPOSITE END.
THE GASKET POSITION NEEDS TO
BE CHANGED (GASKET DELIVERED
C04 C03 C05 C08 A SEPARATELY AND FIXED ON SITE).
THIS WORKS NOT FOR ALL
PERFORATIONS!

B04 B03 B05 B08 SPECIAL SHAPES ON REQUEST

(A) = 2501-3000
UPRIGHT PANELS WITH 4 SUSPENSION POINTS
(A) = 1301-2500

C02 C01 C02 C09


(B) = 250-1000 (B) = 250-1000
RECLINED PANELS WITH 4 SUSPENSION POINTS
B02 B01 B02 B09
(A) = 600-2000 (A) = 600-2000
A04 A03 A05 A08
(A) = 600-1300

D04 D03 D05 D08

(B) = 250-1000
A02 A01 A02 A09
C05 C03 C04 C08 D02 D01 D02 D09
B05 B03 B04 B08

A05 A03 A04 A08


D05 D03 D04 D08

38 mm VISIBLE EDGE ALL AROUND

UPRIGHT PANELS WITH 8 SUSPENSION POINTS


UPRIGHT PANELS WITH 6 SUSPENSION POINTS (B) = 250-1000 (B) = 250-1000

(B) = 250-1000 (B) = 250-1000

UPRIGHT PANELS WITH 4 SUSPENSION POINTS


(A) = 2501-3000
(A) = 1301-2500

RECLINED PANELS WITH 4 SUSPENSION POINTS


(B) = 250-1000 (B) = 250-1000
C06 C07 C06 C10 (A) = 600-2000 (A) = 600-2000
(A) = 600-1300

(B) = 250-1000

B06 B07 B06 B10 SINGLE


SINGLE PANEL
PANEL
A06 A07 A06 A10
SINGLE D06 D07 D06 D10
PANEL SINGLE PANEL

THESE DRAWINGS SHOW TYPICAL CONDITIONS WHICH THE ARMSTRONG PRODUCTS DEPICTED ARE INSTALLED. THEY ARE NOT SUBSTITUTE FOR AN ARCHITECT'S OR ENGINEER'S PLAN AND DO NOT REFLECT THE UNIQUE REQUIREMENTS OF LOCAL BUILDING CODES, LAWS, STATUES, ORDINANCES RULES AND REGULATIONS (LEGAL REQUIREMENTS) THAT MAY BE APPLICABLE FOR A PARTICULAR INSTALLATION. ARMSTRONG DOES NOT WARRANT, AND ASSUMES NO LIABILITY
FOR THE ACCURACY OR COMPLETENESS OF THE DRAWING FOR A PARTICULAR INSTALLATION OR THEIR FITNESS FOR A PARTICULAR PURPOSE. THE USER IS ADVICE TO CONSULT WITH A DULY LICENSED ARCHITECT OR ENGINEER IN THE PARTICULAR LOCALE OF THE INSTALLATION TO ASSURE COMPLIANCE WITH ALL LEGAL REQUIREMENTS. ARMSTRONG IS NOT LICENSED TO PROVIDE PROFESSIONAL ARCHITECTURE OR ENGINEERING DESIGN SERVICES. 08.08.2017 www.armstrongceilings.eu
METAL W-H 1100
CONFIGURABLE WALL CLADDING SYSTEM
HOOK-ON SOLUTION WITH CONCEALED GRID

PANEL TYPE A01 STANDARD UPRIGHT PANEL WITH 4 SUSPENSION POINTS PANEL TYPE B01 STANDARD UPRIGHT PANEL WITH 6 SUSPENSION POINTS
10 10 10 10
30

30

30

30
PANEL LENGTH (A) = 600 -1300 POST-COATED PANEL LENGTH (A) = 1301 - 2500 POST-COATED

30 27.5 60 x 60 27.5 30 27.5 60 x 60 x 60 27.5


8

8
CA CA
PANEL WIDTH (B) = 250 - 1000

PANEL WIDTH (B) = 250 - 1000


E2 F2 E2 F2

1 1
DA DA
8

8
30 30

PANEL TYPE C01 STANDARD UPRIGHT PANEL WITH 8 SUSPENSION POINTS PANEL TYPE D01 STANDARD RECLINED PANEL WITH 4 SUSPENSION POINTS
10 10 8 8

1
30

30

30

30
PANEL LENGTH (A) = 2501 - 3000 POST-COATED 30 PANEL LENGTH (A) = 600 - 2000 POST-COATED

30 27.5 60 x 60 x 60 x 60 27.5

10

27.5
CA
8

PANEL WIDTH (B) = 250 - 1000


CA
PANEL WIDTH (B) = 250 - 1000

60
E2 F2

x
E2 F2

60

1
27.5

DA DA
10
8

30
30

THESE DRAWINGS SHOW TYPICAL CONDITIONS WHICH THE ARMSTRONG PRODUCTS DEPICTED ARE INSTALLED. THEY ARE NOT SUBSTITUTE FOR AN ARCHITECT'S OR ENGINEER'S PLAN AND DO NOT REFLECT THE UNIQUE REQUIREMENTS OF LOCAL BUILDING CODES, LAWS, STATUES, ORDINANCES RULES AND REGULATIONS (LEGAL REQUIREMENTS) THAT MAY BE APPLICABLE FOR A PARTICULAR INSTALLATION. ARMSTRONG DOES NOT WARRANT, AND ASSUMES NO LIABILITY
FOR THE ACCURACY OR COMPLETENESS OF THE DRAWING FOR A PARTICULAR INSTALLATION OR THEIR FITNESS FOR A PARTICULAR PURPOSE. THE USER IS ADVICE TO CONSULT WITH A DULY LICENSED ARCHITECT OR ENGINEER IN THE PARTICULAR LOCALE OF THE INSTALLATION TO ASSURE COMPLIANCE WITH ALL LEGAL REQUIREMENTS. ARMSTRONG IS NOT LICENSED TO PROVIDE PROFESSIONAL ARCHITECTURE OR ENGINEERING DESIGN SERVICES. 08.08.2017 www.armstrongceilings.eu
METAL W-H 1100
CONFIGURABLE WALL CLADDING SYSTEM
HOOK-ON SOLUTION WITH CONCEALED GRID

PANEL INSERTION PANEL EXTRACTION


1 2 3 1 2 3

MIN.12

MIN.10
MIN.12

MIN.10
THESE DRAWINGS SHOW TYPICAL CONDITIONS WHICH THE ARMSTRONG PRODUCTS DEPICTED ARE INSTALLED. THEY ARE NOT SUBSTITUTE FOR AN ARCHITECT'S OR ENGINEER'S PLAN AND DO NOT REFLECT THE UNIQUE REQUIREMENTS OF LOCAL BUILDING CODES, LAWS, STATUES, ORDINANCES RULES AND REGULATIONS (LEGAL REQUIREMENTS) THAT MAY BE APPLICABLE FOR A PARTICULAR INSTALLATION. ARMSTRONG DOES NOT WARRANT, AND ASSUMES NO LIABILITY
FOR THE ACCURACY OR COMPLETENESS OF THE DRAWING FOR A PARTICULAR INSTALLATION OR THEIR FITNESS FOR A PARTICULAR PURPOSE. THE USER IS ADVICE TO CONSULT WITH A DULY LICENSED ARCHITECT OR ENGINEER IN THE PARTICULAR LOCALE OF THE INSTALLATION TO ASSURE COMPLIANCE WITH ALL LEGAL REQUIREMENTS. ARMSTRONG IS NOT LICENSED TO PROVIDE PROFESSIONAL ARCHITECTURE OR ENGINEERING DESIGN SERVICES. 08.08.2017 www.armstrongceilings.eu
METAL W-H 1100
CONFIGURABLE WALL CLADDING SYSTEM
HOOK-ON SOLUTION WITH CONCEALED GRID

WALL FIXING MIN. 1 kN


DETAIL C WALL ANCHOR (BY OTHERS) DETAIL E CONNECTOR FOR U-WALL PROFILE TYPICAL GRID LAYOUT
ADJUSTABLE ±7

a3
BPM315623
FRONT VIEW 7

BPM315626

8x BPM311191

a0
16 24 8 24 33 24
CENTRE LINE
40 20 32 20 57 20
STANDARD 60 MIN.52 MAX.77 BPM315626
VAR.

TOP VIEW
BPM315624
8x BPM311191
24

BPM315623

BPM315623 4x BPM311191
DETAIL F SUSPENSION ELEMENT

BPM315623
DETAIL D CORNER WALL ANCHOR TO CUT, IF NEEDED WALL FIXING MIN. 1 kN

a3
(BY OTHERS)
FRONT VIEW ADJUSTABLE ±7 BPM315628
7

60
BPM315627 a2

a0 PITCH DISTANCE OF WALL FIXING POINTS


4x BPM311191 PANEL TYPE A, B, C = MAX. 750 mm / TYPE D = MAX. 500 mm
BPM315623
a2 DISTANCE BETWEEN U-WALL PROFILES
BPM315627
PANEL TYPE A, B, C = MAX. 1000 mm / TYPE D = MAX. 2000 mm
BPM315628
16 24 8 24 33 24 a3 DISTANCE FROM LAST WALL FIXING POINT TO U-WALL PROFILE END
CENTRE LINE
= MAX. 100 mm
40 20 32 20 57 20
STANDARD 60 MIN.52 MAX.77
DETAIL G
VAR.

U-WALL PROFILE 24

1.5

50
BPM315625
24

3000
TOP VIEW 4x BPM311191

THESE DRAWINGS SHOW TYPICAL CONDITIONS WHICH THE ARMSTRONG PRODUCTS DEPICTED ARE INSTALLED. THEY ARE NOT SUBSTITUTE FOR AN ARCHITECT'S OR ENGINEER'S PLAN AND DO NOT REFLECT THE UNIQUE REQUIREMENTS OF LOCAL BUILDING CODES, LAWS, STATUES, ORDINANCES RULES AND REGULATIONS (LEGAL REQUIREMENTS) THAT MAY BE APPLICABLE FOR A PARTICULAR INSTALLATION. ARMSTRONG DOES NOT WARRANT, AND ASSUMES NO LIABILITY
FOR THE ACCURACY OR COMPLETENESS OF THE DRAWING FOR A PARTICULAR INSTALLATION OR THEIR FITNESS FOR A PARTICULAR PURPOSE. THE USER IS ADVICE TO CONSULT WITH A DULY LICENSED ARCHITECT OR ENGINEER IN THE PARTICULAR LOCALE OF THE INSTALLATION TO ASSURE COMPLIANCE WITH ALL LEGAL REQUIREMENTS. ARMSTRONG IS NOT LICENSED TO PROVIDE PROFESSIONAL ARCHITECTURE OR ENGINEERING DESIGN SERVICES. 08.08.2017 www.armstrongceilings.eu
METAL W-H 1100
CONFIGURABLE WALL CLADDING SYSTEM
HOOK-ON SOLUTION WITH CONCEALED GRID

HORIZONTAL SECTIONS - LATERAL DETAILS


DETAIL F1 CLOSED GAP TO WALL DETAIL F2 OPEN SHADOW GAP TO WALL DETAIL F3 VISIBLE END WITH OPTIONAL COVER PROFILE DETAIL F4 VISIBLE END WITH SPECIAL PANEL

SHIM
(BY OTHERS)

VAR.
VAR.
BPM315627 BPM315627 BPM315627 BPM315627

60 +17
-8
60 +17

60 +17

60 +17
-8

-8

-8

50
19
5 BPM315625 MIN.5 BPM315625 BPM315625 BPM315625
4x BPM311191 4x BPM311191 4x BPM311191 SPECIAL END PANEL* 4x BPM311191
BPM315623 BPM315623 BPM315623 WITH WELDED PROFILE BPM315623
BPM315628 BPM315628 BPM315628 (PROJECT SPECIFIC) BPM315628
PERIMETER PANEL PERIMETER PANEL PERIMETER PANEL
OPTIONAL COVER PROFILE
(PROJECT SPECIFIC)

DETAIL F5 END DETAIL WITH COVER SHEET DETAIL F6 END DETAIL TO DOOR FRAME DETAIL F7 END DETAIL TO DOOR FRAME
SHIM MIN.50
MIN.50 (BY OTHERS)

BPM315627
BPM315627

60 +17
-8
60 +17
-8

min.15

5 MIN.50
DOOR LEAF BPM315625
5

50 - 200
BPM315625 (BY OTHERS) 4x BPM311191
4x BPM311191 BPM315623
BPM315623 DOOR FRAME BPM315628
BPM315628 (BY OTHERS) PERIMETER PANEL
PERIMETER PANEL BPM315627

60 +17
-8
SPECIAL END COVER
(PROJECT SPECIFIC)

BPM315625
SPECIAL END PANEL* 4x BPM311191
WITH WELDED PROFILE BPM315623
(PROJECT SPECIFIC) BPM315628

* A POSITIONING ANGLE IS NEEDED ON THE OPPOSITE SIDE OF THE PANEL, TO KEEP THE POSITION AND PREVENT THE PANEL FROM FALLING DOWN.

THESE DRAWINGS SHOW TYPICAL CONDITIONS WHICH THE ARMSTRONG PRODUCTS DEPICTED ARE INSTALLED. THEY ARE NOT SUBSTITUTE FOR AN ARCHITECT'S OR ENGINEER'S PLAN AND DO NOT REFLECT THE UNIQUE REQUIREMENTS OF LOCAL BUILDING CODES, LAWS, STATUES, ORDINANCES RULES AND REGULATIONS (LEGAL REQUIREMENTS) THAT MAY BE APPLICABLE FOR A PARTICULAR INSTALLATION. ARMSTRONG DOES NOT WARRANT, AND ASSUMES NO LIABILITY
FOR THE ACCURACY OR COMPLETENESS OF THE DRAWING FOR A PARTICULAR INSTALLATION OR THEIR FITNESS FOR A PARTICULAR PURPOSE. THE USER IS ADVICE TO CONSULT WITH A DULY LICENSED ARCHITECT OR ENGINEER IN THE PARTICULAR LOCALE OF THE INSTALLATION TO ASSURE COMPLIANCE WITH ALL LEGAL REQUIREMENTS. ARMSTRONG IS NOT LICENSED TO PROVIDE PROFESSIONAL ARCHITECTURE OR ENGINEERING DESIGN SERVICES. 08.08.2017 www.armstrongceilings.eu
METAL W-H 1100
CONFIGURABLE WALL CLADDING SYSTEM
HOOK-ON SOLUTION WITH CONCEALED GRID

HORIZONTAL SECTIONS - CORNER DETAILS


DETAIL G1 CLOSED CORNER GAP DETAIL G2 OPEN CORNER GAP DETAIL G3 INSIDE CORNER PANEL

BPM315624
BPM315627 BPM315627 BPM315627
4x BPM311191

60 +17
60 +17

60 +17

-8
-8

-8

°
5 BPM315625 BPM315625

90
VAR. 5 BPM315628
4x BPM311191 4x BPM311191
SPECIAL CORNER PANEL, STANDARD PANEL
BPM315623 BPM315623
BPM315628 BPM315628 REINFORCED AT THE CORNER,
PERIMETER PANEL PERIMETER PANEL VARIOUS ANGLES POSSIBLE,
OPTIONS AND DIMENSIONS ON REQUEST
(PROJECT SPECIFIC)

DETAIL G6 OUTSIDE CORNER PANEL


DETAIL G4 OUTSIDE CORNER DETAIL DETAIL G5 OUTSIDE CORNER DETAIL
60 +17
-8 60 +17
-8 BPM315623 STANDARD PANEL

STANDARD PANEL STANDARD PANEL

5
STANDARD
BPM315624
PANEL
4x BPM311191
BPM315625 BPM315625 BPM315628
MIN.50

4x BPM311191 4x BPM311191

5
BPM315628 BPM315628
BPM315627
5

BPM315623
BPM315627 BPM315627
BPM315623 BPM315623
MAX.70
°
90

MIN.50
70 - 100

°
90

SPECIAL CORNER PANEL, VARIOUS ANGLES POSSIBLE,


MIN.50 °
OPTIONS AND DIMENSIONS ON REQUEST 90 SPECIAL CORNER PANEL,
60 +17
-8

(PROJECT SPECIFIC) VARIOUS ANGLES POSSIBLE,


OPTIONS AND DIMENSIONS
SPECIAL CORNER PANEL, VARIOUS ANGLES POSSIBLE,
ON REQUEST
OPTIONS AND DIMENSIONS ON REQUEST (PROJECT SPECIFIC)
(PROJECT SPECIFIC)

* A POSITIONING ANGLE IS NEEDED ON THE OPPOSITE SIDE OF THE PANEL, TO KEEP THE POSITION AND PREVENT THE PANEL FROM FALLING DOWN.
5

THESE DRAWINGS SHOW TYPICAL CONDITIONS WHICH THE ARMSTRONG PRODUCTS DEPICTED ARE INSTALLED. THEY ARE NOT SUBSTITUTE FOR AN ARCHITECT'S OR ENGINEER'S PLAN AND DO NOT REFLECT THE UNIQUE REQUIREMENTS OF LOCAL BUILDING CODES, LAWS, STATUES, ORDINANCES RULES AND REGULATIONS (LEGAL REQUIREMENTS) THAT MAY BE APPLICABLE FOR A PARTICULAR INSTALLATION. ARMSTRONG DOES NOT WARRANT, AND ASSUMES NO LIABILITY
FOR THE ACCURACY OR COMPLETENESS OF THE DRAWING FOR A PARTICULAR INSTALLATION OR THEIR FITNESS FOR A PARTICULAR PURPOSE. THE USER IS ADVICE TO CONSULT WITH A DULY LICENSED ARCHITECT OR ENGINEER IN THE PARTICULAR LOCALE OF THE INSTALLATION TO ASSURE COMPLIANCE WITH ALL LEGAL REQUIREMENTS. ARMSTRONG IS NOT LICENSED TO PROVIDE PROFESSIONAL ARCHITECTURE OR ENGINEERING DESIGN SERVICES. 08.08.2017 www.armstrongceilings.eu
METAL W-H 1100
CONFIGURABLE WALL CLADDING SYSTEM
HOOK-ON SOLUTION WITH CONCEALED GRID

VERTICAL SECTIONS - TOP END DETAILS


DETAIL H1 NON-VISIBLE END DETAIL H2 STANDARD VISIBLE END DETAIL H3 SPECIAL VISIBLE END DETAIL H4 WITH COVER PROFILE
VAR. 30 VAR. 38 VAR. 50

MIN.12
OPTIONAL COVER PROFILE
(PROJECT SPECIFIC)

BPM315628 BPM315628 BPM315628

4x BPM311191 4x BPM311191 4x BPM311191


MIN.12
BPM315627 BPM315627 BPM315627
4x BPM311191
PERIMETER PANEL PERIMETER PANEL
BPM315627
PERIMETER PANEL
BPM315628
4x BPM311191 4x BPM311191 4x BPM311191

BPM315624 BPM315624 BPM315624


4x BPM311191
BPM315623 BPM315623 BPM315623 BPM315624
STANDARD PANEL
+17 +17 +17
60 -8 60 -8 60 -8

BPM315623
+17
60 -8

DETAIL H4 TO WINDOW SILL DETAIL H5 TRANSITION TO METAL CEILING DETAIL H6 OPEN GAP DETAIL H7 CLOSED GAP
VAR. 30

WINDOW SILL COVER ANGLE

MIN.12
(BY OTHERS)

MIN.12
(PROJECT SPECIFIC)

MIN.12
MIN.12

METAL CEILING 4x BPM311191


4x BPM311191 BPM315627
BPM315627 4x BPM311191
4x BPM311191
BPM315628 BPM315628
BPM315627 4x BPM311191 BPM315627
STANDARD PANEL
BPM315628 BPM315628
BPM315624 4x BPM311191
BPM315624
BPM315623 STANDARD PANEL
4x BPM311191 +17
4x BPM311191
BPM315624 60 -8
BPM315623 BPM315624
STANDARD PANEL STANDARD PANEL
60 +17
-8

BPM315623 BPM315623
+17
60 +17
-8 60 -8

THESE DRAWINGS SHOW TYPICAL CONDITIONS WHICH THE ARMSTRONG PRODUCTS DEPICTED ARE INSTALLED. THEY ARE NOT SUBSTITUTE FOR AN ARCHITECT'S OR ENGINEER'S PLAN AND DO NOT REFLECT THE UNIQUE REQUIREMENTS OF LOCAL BUILDING CODES, LAWS, STATUES, ORDINANCES RULES AND REGULATIONS (LEGAL REQUIREMENTS) THAT MAY BE APPLICABLE FOR A PARTICULAR INSTALLATION. ARMSTRONG DOES NOT WARRANT, AND ASSUMES NO LIABILITY
FOR THE ACCURACY OR COMPLETENESS OF THE DRAWING FOR A PARTICULAR INSTALLATION OR THEIR FITNESS FOR A PARTICULAR PURPOSE. THE USER IS ADVICE TO CONSULT WITH A DULY LICENSED ARCHITECT OR ENGINEER IN THE PARTICULAR LOCALE OF THE INSTALLATION TO ASSURE COMPLIANCE WITH ALL LEGAL REQUIREMENTS. ARMSTRONG IS NOT LICENSED TO PROVIDE PROFESSIONAL ARCHITECTURE OR ENGINEERING DESIGN SERVICES. 08.08.2017 www.armstrongceilings.eu
METAL W-H 1100
CONFIGURABLE WALL CLADDING SYSTEM
HOOK-ON SOLUTION WITH CONCEALED GRID

VERTICAL SECTIONS - BOTTOM END DETAILS


DETAIL I1 NON-VISIBLE END DETAIL I2 STANDARD VISIBLE END DETAIL I3 SPECIAL VISIBLE END DETAIL I4 DETAIL WITH COVER SHEET
60 +17
-8 60 +17
-8

BPM315623 BPM315623
BPM315628 BPM315623 BPM315628
BPM315623
4x BPM311191 BPM315628 BPM315628 4x BPM311191

BPM315627 4x BPM311191 4x BPM311191 BPM315627


BPM315624 BPM315627 BPM315624
BPM315627 4x BPM311191
4x BPM311191 4x BPM311191
BPM315624
STANDARD PANEL 4x BPM311191 BPM315624 STANDARD PANEL

PERIMETER PANEL PERIMETER PANEL

MIN.50

5
60 +17
-8

VAR. 38 VAR. 50

SPECIAL END COVER


(PROJECT SPECIFIC)

DETAIL I5 DETAIL TO DOOR FRAME DETAIL I6 OPEN GAP DETAIL I7 CLOSED GAP DETAIL I8 TRANSITION TO METAL CEILING
60 +17
-8 60 +17
-8 60 +17
-8 60 +17
-8

BPM315623 BPM315623 BPM315623 BPM315623


BPM315628 BPM315628 BPM315628 BPM315628

4x BPM311191 4x BPM311191 4x BPM311191 4x BPM311191

BPM315627 BPM315627 BPM315627 BPM315627


BPM315624 BPM315624 BPM315624 BPM315624
4x BPM311191 4x BPM311191 4x BPM311191 4x BPM311191
STANDARD PANEL STANDARD PANEL
STANDARD PANEL STRUCTURE
MIN.5

(BY OTHERS) SPECIAL PANEL


5

SKIRTING

VAR.
(PROJECT SPECIFIC)
DOOR FRAME
(BY OTHERS)

VAR. 30 - 100
METAL CEILING
DOOR LEAF
(BY OTHERS)

THESE DRAWINGS SHOW TYPICAL CONDITIONS WHICH THE ARMSTRONG PRODUCTS DEPICTED ARE INSTALLED. THEY ARE NOT SUBSTITUTE FOR AN ARCHITECT'S OR ENGINEER'S PLAN AND DO NOT REFLECT THE UNIQUE REQUIREMENTS OF LOCAL BUILDING CODES, LAWS, STATUES, ORDINANCES RULES AND REGULATIONS (LEGAL REQUIREMENTS) THAT MAY BE APPLICABLE FOR A PARTICULAR INSTALLATION. ARMSTRONG DOES NOT WARRANT, AND ASSUMES NO LIABILITY
FOR THE ACCURACY OR COMPLETENESS OF THE DRAWING FOR A PARTICULAR INSTALLATION OR THEIR FITNESS FOR A PARTICULAR PURPOSE. THE USER IS ADVICE TO CONSULT WITH A DULY LICENSED ARCHITECT OR ENGINEER IN THE PARTICULAR LOCALE OF THE INSTALLATION TO ASSURE COMPLIANCE WITH ALL LEGAL REQUIREMENTS. ARMSTRONG IS NOT LICENSED TO PROVIDE PROFESSIONAL ARCHITECTURE OR ENGINEERING DESIGN SERVICES. 08.08.2017 www.armstrongceilings.eu
METAL W-H 1100
CONFIGURABLE WALL CLADDING SYSTEM
HOOK-ON SOLUTION WITH CONCEALED GRID

DETAIL K ADDITIONAL U-WALL PROFILE AGAINST IMPACT, FOR PANEL TYPE D

60 +17
-8
PANEL LENGTH (A) 5
MODULE MODULE MODULE

PROJECT SPECIFIC SOLUTIONS HORIZONTAL SECTIONS

DETAIL L1 COLUMN CLADDING DETAIL L2 COLUMN CLADDING DETAIL L3 CURVED PANELS

THESE DRAWINGS SHOW TYPICAL CONDITIONS WHICH THE ARMSTRONG PRODUCTS DEPICTED ARE INSTALLED. THEY ARE NOT SUBSTITUTE FOR AN ARCHITECT'S OR ENGINEER'S PLAN AND DO NOT REFLECT THE UNIQUE REQUIREMENTS OF LOCAL BUILDING CODES, LAWS, STATUES, ORDINANCES RULES AND REGULATIONS (LEGAL REQUIREMENTS) THAT MAY BE APPLICABLE FOR A PARTICULAR INSTALLATION. ARMSTRONG DOES NOT WARRANT, AND ASSUMES NO LIABILITY
FOR THE ACCURACY OR COMPLETENESS OF THE DRAWING FOR A PARTICULAR INSTALLATION OR THEIR FITNESS FOR A PARTICULAR PURPOSE. THE USER IS ADVICE TO CONSULT WITH A DULY LICENSED ARCHITECT OR ENGINEER IN THE PARTICULAR LOCALE OF THE INSTALLATION TO ASSURE COMPLIANCE WITH ALL LEGAL REQUIREMENTS. ARMSTRONG IS NOT LICENSED TO PROVIDE PROFESSIONAL ARCHITECTURE OR ENGINEERING DESIGN SERVICES. 08.08.2017 www.armstrongceilings.eu
W­H 1100