Data sheet 6AG2515-2RM00-4AB0
SIPLUS S7-1500 CPU 1515R-2 PN TX Rail -40...+70 °C TX with 85
°C for 10 minutes With conformal coating Based on 6ES7515-
2RM00-0AB0 . Central processing unit with work memory 500 KB for
program and 3 MB for data, 1st interface: PROFINET With 2-port
switch 2nd interface: PROFINET RT, SIMATIC Memory Card
required ****************************** Special sales release required
General information
Product type designation CPU 1515R-2 PN
Control elements
Mode selector switch 1
Supply voltage
Type of supply voltage 24 V DC
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Mains buffering
● Mains/voltage failure stored energy time 5 ms
Input current
Current consumption (rated value) 0.8 A
Inrush current, max. 2.4 A
I²t 0.02 A²·s
Power loss
6AG2515-2RM00-4AB0 Subject to change without notice
Page 1/9 11/27/2020 © Copyright Siemens
Power loss, typ. 6.3 W
Memory
Number of slots for SIMATIC memory card 1
SIMATIC memory card required Yes
Work memory
● integrated (for program) 500 kbyte
● integrated (for data) 3 Mbyte
Load memory
● Plug-in (SIMATIC Memory Card), max. 32 Gbyte
Backup
● maintenance-free Yes
CPU processing times
for bit operations, typ. 60 ns
for word operations, typ. 72 ns
for fixed point arithmetic, typ. 96 ns
for floating point arithmetic, typ. 384 ns
CPU-blocks
Number of elements (total) 6 000; Blocks (OB, FB, FC, DB) and UDTs
DB
● Number range Number range: 1 to 59 999
● Size, max. 3 Mbyte; For non-optimized block accesses, the max. size of the
DB is 64 KB
FB
● Number range 0 ... 65 535
● Size, max. 500 kbyte
FC
● Number range 0 ... 65 535
● Size, max. 500 kbyte
OB
● Size, max. 500 kbyte
● Number of free cycle OBs 100
● Number of time alarm OBs 20
● Number of delay alarm OBs 20
● Number of cyclic interrupt OBs 20
● Number of process alarm OBs 50
● Number of startup OBs 100
● Number of asynchronous error OBs 4
● Number of synchronous error OBs 2
● Number of diagnostic alarm OBs 1
Nesting depth
● per priority class 24
6AG2515-2RM00-4AB0 Subject to change without notice
Page 2/9 11/27/2020 © Copyright Siemens
Counters, timers and their retentivity
S7 counter
● Number 2 048
Retentivity
— adjustable Yes
IEC counter
● Number Any (only limited by the main memory)
Retentivity
— adjustable Yes
S7 times
● Number 2 048
Retentivity
— adjustable Yes
IEC timer
● Number Any (only limited by the main memory)
Retentivity
— adjustable Yes
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), 512 kbyte
max.
Flag
● Number, max. 16 kbyte
● Number of clock memories 8; 8 clock memory bit, grouped into one clock memory byte
Data blocks
● Retentivity adjustable Yes
● Retentivity preset No
Local data
● per priority class, max. 64 kbyte; max. 16 KB per block
Address area
Number of IO modules 4 096; max. number of modules / submodules
I/O address area
● Inputs 32 kbyte; All inputs are in the process image
● Outputs 32 kbyte; All outputs are in the process image
per integrated IO subsystem
— Inputs (volume) 8 kbyte
— Outputs (volume) 8 kbyte
Subprocess images
● Number of subprocess images, max. 32
Hardware configuration
Number of IO Controllers
● integrated 1
6AG2515-2RM00-4AB0 Subject to change without notice
Page 3/9 11/27/2020 © Copyright Siemens
Time of day
Clock
● Backup time 6 wk; At 40 °C ambient temperature, typically
● Deviation per day, max. 10 s; Typ.: 2 s
Operating hours counter
● Number 16
Clock synchronization
● supported Yes
● in AS, master No
● in AS, slave No
● on Ethernet via NTP Yes
Interfaces
Number of PROFINET interfaces 1
1. Interface
Interface types
● RJ 45 (Ethernet) Yes; X1
● Number of ports 2
● integrated switch Yes
Protocols
● IP protocol Yes; IPv4
● PROFINET IO Controller Yes
● PROFINET IO Device No
● SIMATIC communication Yes; Only Server
● Open IE communication Yes
● Web server No
● Media redundancy Yes
PROFINET IO Controller
Services
— PG/OP communication Yes
— Isochronous mode No
— IRT No
— MRP Yes; Only Manager Auto, max. 50 nodes; only 16 are
recommended, however
— MRPD No
— PROFIenergy Yes
— Number of connectable IO Devices, max. 64
— Updating times The minimum value of the update time also depends on
communication share set for PROFINET IO, on the number of IO
devices, and on the quantity of configured user data
Update time for RT
— for send cycle of 1 ms 1 ms to 512 ms
6AG2515-2RM00-4AB0 Subject to change without notice
Page 4/9 11/27/2020 © Copyright Siemens
2. Interface
Interface types
● RJ 45 (Ethernet) Yes; X2
● Number of ports 1
● integrated switch No
Protocols
● IP protocol Yes; IPv4
● PROFINET IO Controller No
● PROFINET IO Device No
● SIMATIC communication Yes; Only Server
● Open IE communication Yes
● Web server No
● Media redundancy No
Interface types
RJ 45 (Ethernet)
● 100 Mbps Yes
● Autonegotiation Yes
● Autocrossing Yes
● Industrial Ethernet status LED Yes
Protocols
Number of connections
● Number of connections, max. 108
● Number of connections reserved for 10
ES/HMI/web
Redundancy mode
Media redundancy
— MRP Yes; Manager Auto is permanently set in TIA. Max. 50 nodes are
possible, 16 are recommended
— MRPD No
— Switchover time on line break, typ. 200 ms; PROFINET MRP
— Number of stations in the ring, max. 50; Only 16 are recommended, however
SIMATIC communication
● S7 routing No
● S7 communication, as server Yes
● S7 communication, as client No
Open IE communication
● TCP/IP Yes
— Data length, max. 64 kbyte
— several passive connections per port, Yes
supported
● ISO-on-TCP (RFC1006) Yes
6AG2515-2RM00-4AB0 Subject to change without notice
Page 5/9 11/27/2020 © Copyright Siemens
— Data length, max. 64 kbyte
● UDP Yes
— Data length, max. 2 kbyte; 1 472 bytes for UDP broadcast
— UDP multicast Yes; Max. 5 multicast circuits
● DHCP No
● SNMP Yes
● DCP Yes
● LLDP Yes
Web server
● HTTP No
● HTTPS No
OPC UA
● OPC UA Client No
● OPC UA Server No
Further protocols
● MODBUS Yes; MODBUS TCP
S7 message functions
Program alarms No
Test commissioning functions
Joint commission (Team Engineering) No
Status block Yes; up to 8 simultaneously
Single step No
Status/control
● Status/control variable Yes
● Variables Inputs/outputs, memory bits, DBs, distributed I/Os, timers,
counters
● Number of variables, max.
— of which status variables, max. 200; per job
— of which control variables, max. 200; per job
Forcing
● Forcing, variables Peripheral inputs/outputs
● Number of variables, max. 200
Diagnostic buffer
● present Yes
● Number of entries, max. 3 200
— of which powerfail-proof 500
Traces
● Number of configurable Traces 4
● Memory size per trace, max. 512 kbyte
Interrupts/diagnostics/status information
Diagnostics indication LED
6AG2515-2RM00-4AB0 Subject to change without notice
Page 6/9 11/27/2020 © Copyright Siemens
● RUN/STOP LED Yes
● ERROR LED Yes
● MAINT LED Yes
● Connection display LINK TX/RX Yes
Supported technology objects
Motion Control No
Controller
● PID_Compact No
● PID_3Step No
● PID-Temp No
Counting and measuring
● High-speed counter No
Isolation
Isolation tested with 707 V DC (type test) and according to EN 50155 (routine test)
Standards, approvals, certificates
Railway application
● EN 50121-3-2 Yes; EMC for rail vehicles
● EN 50121-4 Yes; EMC for signal and telecommunications systems
● EN 50124-1 Yes; Railway applications - overvoltage category OV2; pollution
degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC
● EN 50125-1 Yes; Rail vehicles - see ambient conditions
● EN 50125-2 Yes; Stationary electrical equipment - see ambient conditions
● EN 50125-3 Yes; Signal and telecommunications systems - see ambient
conditions; vibrations and shocks: Application point outside of
tracks (1 m to 3 m away from track)
● EN 50155 Yes; Rail vehicles - temperature class Tx, horizontal mounting
position, salt spray Class ST2
● EN 61373 Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B
● Fire protection acc. to EN 45545-2 Yes; Rail vehicles - verification on request
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -40 °C; = Tmin (incl. condensation/frost)
● horizontal installation, max. 70 °C; = Tmax; +85 °C for 10 min (Tx acc. to EN 50155)
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Altitude during operation relating to sea level
● Ambient air temperature-barometric pressure- Tmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m)
altitude
Relative humidity
6AG2515-2RM00-4AB0 Subject to change without notice
Page 7/9 11/27/2020 © Copyright Siemens
● With condensation, tested in accordance with 100 %; RH incl. condensation / frost (no commissioning in
IEC 60068-2-38, max. bedewed state), horizontal installation
Resistance
Coolants and lubricants
— Resistant to commercially available Yes; Incl. diesel and oil droplets in the air
coolants and lubricants
Use in stationary industrial systems
— to biologically active substances according Yes; Class 3B2 mold, fungus and dry rot spores (with the
to EN 60721-3-3 exception of fauna); Class 3B3 on request
— to chemically active substances according Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-
to EN 60721-3-3 52 (severity degree 3); *
— to mechanically active substances Yes; Class 3S4 incl. sand, dust, *
according to EN 60721-3-3
Use on land craft, rail vehicles and special-purpose vehicles
— to biologically active substances according Yes; Class 5B2 mold, fungus and dry rot spores (with the
to EN 60721-3-5 exception of fauna); Class 5B3 on request
— to chemically active substances according Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 50155
to EN 60721-3-5 (ST2); *
— to mechanically active substances Yes; Class 5S3 incl. sand, dust; *
according to EN 60721-3-5
Usage in industrial process technology
— Against chemically active substances acc. Yes; Class 3 (excluding trichlorethylene)
to EN 60654-4
— Environmental conditions for process, Yes; Level GX group A/B (excluding trichlorethylene; harmful gas
measuring and control systems acc. to concentrations up to the limits of EN 60721-3-3 class 3C4
ANSI/ISA-71.04 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of * The supplied plug covers must remain in place over the unused
environmental conditions acc. to EN 60721, interfaces during operation!
EN 60654-4 and ANSI/ISA-71.04
Conformal coating
● Coatings for printed circuit board assemblies Yes; Class 2 for high reliability
acc. to EN 61086
● Protection against fouling acc. to EN 60664-3 Yes; Type 1 protection
● Electronic equipment on rolling stock acc. to Yes; Class PC2 protective coating acc. to EN 50155:2017
EN 50155
● Military testing according to MIL-I-46058C, Yes; Discoloration of coating possible during service life
Amendment 7
● Qualification and Performance of Electrical Yes; Conformal coating, Class A
Insulating Compound for Printed Board
Assemblies according to IPC-CC-830A
Configuration
Programming
Programming language
6AG2515-2RM00-4AB0 Subject to change without notice
Page 8/9 11/27/2020 © Copyright Siemens
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes
— CFC No
— GRAPH No
Know-how protection
● User program protection/password protection Yes
● Copy protection No
● Block protection Yes
Access protection
● Protection level: Write protection Yes
● Protection level: Read/write protection Yes
● Protection level: Complete protection Yes
Dimensions
Width 105 mm
Height 147 mm
Depth 129 mm
Weights
Weight, approx. 1 100 g
Other
Note: for use in railway applications, also observe the product
information "SIPLUS extreme RAIL" A5E37661960A, Online
Support article 109736776
last modified: 11/25/2020
6AG2515-2RM00-4AB0 Subject to change without notice
Page 9/9 11/27/2020 © Copyright Siemens