0% found this document useful (0 votes)
83 views28 pages

Serial #: Installation and Operating Instructions

The document provides instructions for safely installing and operating a wood burning fireplace. It outlines safety notices and covers maintenance procedures like cleaning the chimney and glass. It also provides instructions for operation, installation, clearances to combustibles, and replacement parts.

Uploaded by

celsohernando
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
83 views28 pages

Serial #: Installation and Operating Instructions

The document provides instructions for safely installing and operating a wood burning fireplace. It outlines safety notices and covers maintenance procedures like cleaning the chimney and glass. It also provides instructions for operation, installation, clearances to combustibles, and replacement parts.

Uploaded by

celsohernando
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 28

IMPORTANT:

THESE INSTRUCTIONS ARE TO


REMAIN WITH THE HOMEOWNER.
PLEASE SAVE THESE INSTRUCTIONS.

SERIAL #

SAFETY NOTICE
INSTALLATION
If this stove is not properly installed, a
house fire may result. For your safety,
AND OPERATING
follow the installation instructions. Contact INSTRUCTIONS
local building or fire officials about
restrictions and installation inspection
requirements in your area.

TESTED and LISTED to CAN/ULC


S610-M87 AND UL 127
Meets the Environmental Protection
Agency's July 1990 Particulate Emission
Standards

MODEL: PACIFIC FP30

ZERO CLEARANCE WOOD


FIREPLACE
060514-28 PACIFIC FP30 5055.5152
Contents
Safety and Maintenance .............................................................. 3
Maintenance Checks ................................................................... 4
Creosote ....................................................................................... 5
Formation and Need for Removal .......................................................... 5
Chimney Fires........................................................................................ 5
In the event of a Chimney Fire ............................................................... 5
Avoiding a Chimney Fire ........................................................................ 5
NOTE: Operation...................................................................................... 6
WE STRONGLY Wood Selection...................................................................................... 6
How to Test Your Wood .......................................................................... 6
R E C O M M E N D T H AT Lighting for the First Time ...................................................................... 6
SMOKE DETECTORS BE Lighting a Fire ........................................................................................ 6
INSTALLED. Normal Operation .................................................................................. 6
Restarting After Extended or Overnight Burns....................................... 6
If smoke detectors have been previ-
Over Firing ............................................................................................. 7
ously installed, you may notice that
Heat Output Calculation ........................................................................ 7
they are operating more frequently.
Proper Draft ........................................................................................... 7
This may be due to curing of stove
Ash Removal ......................................................................................... 7
paint or fumes caused by accidentally
Disposal of Ashes .................................................................................. 7
leaving the fire door open. Do not
Blower Operation ................................................................................... 7
disconnect the detectors. If neces-
Baffle Removal ............................................................................. 7
Removal................................................................................................. 7
sary, relocate them to reduce their
Secondary Air Box Cleaning .................................................................. 7
sensitivity.
Glass Cleaning ...................................................................................... 7
SAFETY NOTICE:
Blower Replacement ................................................................... 8
Firebrick Installation.................................................................... 9
If this stove is not Fireplace Installation ................................................................. 10
Crate Removal ......................................................................................10
properly installed, a Locating The FP30 Fireplace ................................................................10
house fire may result. Clearances ...........................................................................................11
Procedure:.............................................................................................11
For your safety, fol- Dimensions .................................................................................11
low the installation Minimum Framing Dimensions................................................. 12
Framing Kit Assembly ............................................................... 13
instructions. Contact Minimum Clearances to Combustibles .................................... 14
Listed Chimney and Chimney Connector .............................................16
local building or fire Chase Enclosure ..................................................................................16
officials about restric- Offsets ........................................................................................ 17
Combustion Air .......................................................................... 18
tions and installation Outside Combustion Air Adapter...........................................................18
Floor Protector ........................................................................... 19
inspection require- Safety Strip ...........................................................................................19
ments in your area. Blower Wiring ........................................................................................19
Remote Heat Duct Installation .................................................. 20
Please read this entire manual before Facing and Air Inlet ................................................................... 22
you install and use your new room Cement Board Installation ................................................................... 22
heater. Failure to follow instructions
Mantel Clearances ..................................................................... 23
may result in property damage, bodily
Appendix A ................................................................................. 24
Troubleshooting ................................................................................... 24
injury, or even death.
Understanding & Operating Your Pacific Energy Stove........................ 25
Replacement Parts .............................................................................. 26
Label Location ..................................................................................... 27
Label .................................................................................................... 27

2 PACIFIC FP30 060514-28


WARNING: DO NOT SUBSTITUTE GLASS WITH ANY
Safety and OTHER TYPE MATERIAL OTHER THAN CERAMIC
GLASS

Maintenance WARNING: DO NOT SLAM LOADING DOOR OR


OTHERWISE IMPACT GLASS. WHEN CLOSING DOOR,
MAKE SURE THAT NO LOGS PROTRUDE TO IMPACT
1. Burn only, dry and well seasoned cord wood. The
THE GLASS. IF THE GLASS GETS CRACKED OR
denser or heavier the wood when dry, the greater its heat
BROKEN, IT MUST BE REPLACED BEFORE USING
value. This is why hardwoods are generally preferred.
Green or wet wood should not be used, it will reduce THE STOVE.
heat output, as well as, contribute significantly to creosote
buildup. WARNING: OVER FIRING THE APPLIANCE WILL
SHORTEN THE LIFE OF THE PRODUCT. FAILURE
WARNING: NEVER USE CHEMICALS OR ANY OTHER TO RECTIFY AN OVER FIRING CONDITION CAN BE
VOLATILE LIQUID TO START A FIRE. DO NOT BURN HAZARDOUS AND MAY VOID THE MANUFACTURER'S
GARBAGE OR FLAMMABLE FLUIDS SUCH AS WARRANTY.
GASOLINE, NAPHTHA, OR ENGINE OIL. WE STRONGLY
RECOMMEND THAT SMOKE DETECTORS BE To remove broken glass,remove the door gasket and clean out
INSTALLED. the screw heads. Remove the screws that hold the retainers
and remove the retainers, noting position for re-assembly.
2. Remove ashes frequently. Embers can roll out the door Remove all particles of glass . Be careful as they are very
and create a fire hazard. Maintain a 1"(25mm) minimum sharp. Install new glass complete with gasket. Replace
ash base. retainers, screws and gasket.

3. The area where boost combustion air enters the firebox CAUTION:
must be kept clear of excessive ash buildup which will - DO NOT OVERTIGHTEN, TIGHTEN SCREWS HAND
block air flow. This area is at the front of the firebox. TIGHT
- DO NOT CLEAN GLASS WHEN HOT
4. If glass becomes darkened through slow burning or poor - DO NOT USE ABRASIVE CLEANERS ON GLASS
wood, it can be cleaned with fireplace glass cleaner when
the stove is cold. Never scrape with an object that might 8. Do not store wood within heater installation clearances, or
scratch the glass. The type and amount of deposit on the within the space required for fuel loading and ash removal.
glass is a good indication of the flue pipe and chimney Keep the area around the heater clean and free of loose
buildup. A light brown dusty deposit that is easily wiped off combustibles, furniture, newspapers, etc.
usually indicates good combustion and dry, well-seasoned
wood and therefore relatively clean pipes and chimney. 9. Be aware that the hotter the fire, the less creosote is
On the other hand, a black greasy deposit that is difficult deposited. Weekly cleaning may be necessary in mild
to remove is a result of wet and green wood and too slow weather, even though monthly cleaning is usually enough
a burning rate. This heavy deposit is building up as quickly in the coldest months when burning rates are higher.
in the chimney.
10. Instruct all members of your family on the safe operation
of the heater. Ensure they have enough knowledge of the
5. Establish a routine for the fuel, wood burning and firing entire system if they are expected to operate it. Stress the
technique. Check daily for creosote buildup until experi- section on chimney fires and the importance of following
ence shows how often you need to clean to be safe. the steps outlined "In the event of Chimney Fire" Page 5.
WARNING: ONLY USE MATERIALS AND COMPONENTS 11. Inspect and clean your chimney system at the beginning
SUPPLIED OR SPECIFIED BY MANUFACTURER WHEN of the burning season before your first fire and at least
DOING MAINTENANCE OR REPLACEMENTS. DO NOT every two months during the burning season. Inspect
USE A FIREPLACE INSERT OR OTHER PRODUCTS NOT the interior and exterior of the pipe for defects and/or
SPECIFIED FOR USE WITH THIS FIREPLACE. damage. Remove and inspect the rain cap. Refer to the
chimney system manufacturer's installation instructions
6. DOOR GASKETS - The gasket used by Pacific Energy for the procedure to remove and or replace any necessary
(7/8"(22mm) medium density fibreglass rope) requires components to the chimney system.
only light pressure to seal. This will prolong seal life. It is
important that the door seal be maintained in good condi- 12. Maintain a distance of 30"(762mm) to all combustible
tion. Periodically inspect seals and replace if necessary. materials in the room.
(see Floor Protector section on page 19 for Floor Protec-
7. DOOR GLASS - Replacement glass can be obtained from tion dimensions)
your dealer. Use 11 3/8"9289mm) x 21 5/8"(549mm) x 5
mm ceramic glass only.

PACIFIC FP30 060514-28 3


Maintenance Checks
Check the following parts for damage such as cracks, excessive corrosion, burned out sections and
excessive warping: (See website for descriptions and more detail)

Weekly:

- Firebrick - Visual, for cracking.


- Door Gasket - sagging, placement, damage.

Monthly

- Brick rail tabs and brick rails.


- Air riser tube in the back of the firebox.
- Back side of airwash chamber.
- Baffle locking pin.
- Boost tube cover.

When Cleaning the


Chimney System:

- Top baffle board/blanket.


- Baffle.
- Top heat shield and mounting bolt.
- Baffle Gasket.
- Brick Rails.
- Manifold.

Blower:

- The blower should be cleaned out a minimum annually by using a vacumn on the intakes on the side
of the blower to remove any dust and debris. The blower is accessed through the access cover
located in the bottom of the firebox.

- Some warping of the baffle is normal(up to 1/4” or .65cm).


- Replace if the baffle has permanent warping greater than this or has cracking or breakage.
- Please contact your Dealer if you experience any of the damage listed above. Continuing to operate
your stove with broken parts may accelerate damage to other parts and may void your warranty

4 PACIFIC FP30 060514-28


2. Close air inlet on stove.
Creosote 3. Call local fire department. Have a fire extinguisher handy.
Contact your local municipal or provincial fire authority for
Formation and Need for Removal further information on how to handle a chimney fire. It is
most important that you have a clearly understood plan
When wood is burned slowly, it produces tar and other or- on how to handle a chimney fire.
ganic vapours, which combine with expelled moisture to form
creosote. The creosote vapours condense in the relatively 4. After the chimney fire is out, the chimney must be cleaned
cool chimney flue of a slow burning fire. As a result, creosote and checked for stress and cracks before starting another
residue accumulates on the flue lining. When ignited, this fire. Also check combustibles around the chimney and
creosote makes an extremely hot fire. The chimney connector the roof.
and chimney should be inspected periodically (at least once
every two months) during the heating season to determine if - The services of a competent or certified installer, (certified
a creosote buildup has occurred. If creosote has accumulated by the Wood Energy Technical Training program (WETT) - in
(3 mm. or more), it should be removed to reduce the risk of Canada, Hearth Education Foundation (HEARTH) - in U.S.A.,)
a chimney fire. are strongly recommended.
1. Highest smoke densities occur when a large amount of Avoiding a Chimney Fire
wood is added to a bed of hot coals and the air inlet is
closed. The heated wood generates smoke, but without There are two ways to avoid chimney fires:
ample air, the smoke cannot burn. Smoke-free, clean 1. Do not let creosote build up to a point where a chimney
burning requires small fuel loads, two or three logs at fire is possible.
a time or 1/4 to 1/2 of fuel load and leaving the air inlet
2. Do not have fires in the heater that may ignite chimney
relatively wide open, especially during the first 10 to 30 fires. These are very hot fires, such as when burning
minutes after each loading, when most of the smoke household trash, cardboard, Christmas tree limbs, or even
generating reactions are occurring. After 30 minutes or ordinary fuel wood; (e.g.. with a full load on a hot bed of
so, the air inlet can be turned down substantially without coals and with the air inlet excessively open.)
excessive smoke generation. Wood coals create very
little creosote-producing smoke.

2. The cooler the surface over which the wood smoke is pass-
ing, the more creosote will be condensed. Wet or green
wood contributes significantly to creosote formation as the
excess moisture that is boiled off cools the fire, making
it difficult for the tars and gases to ignite, thus creating
dense smoke and poor combustion. This moisture-laden
smoke cools the chimney, compounding the problem by
offering the smoke the ideal place to condense.
In summary, a certain amount of creosote is inevitable
and must be lived with. Regular inspection and cleaning is
the solution. The use of dry, seasoned wood and ample
combustion air will help to minimize the buildup.
Chimney Fires
The result of excessive creosote buildup is a chimney fire.
Chimney fires are dangerous. Temperatures inside the chim-
ney can exceed 2000° F(1093˚C). This causes much higher
than normal temperatures on its exterior surfaces. Thus
ignition of nearby or touching combustible material is more
likely during a chimney fire. Proper clearances are critical
during such a fire.
Chimney fires are easy to detect; they usually involve one or
more of the following:
-Flames and sparks shooting out of the top of the chimney
-A roaring sound
-Vibration of the chimney

In the event of a Chimney Fire


1. Prepare to evacuate to ensure everyone's safety. Have
a well understood plan of action for evacuation. Have a
place outside where everyone is to meet.

PACIFIC FP30 060514-28 5


1. Adjust air control to all the way to the left(High) and open
Operation door.
2. Place crumpled newspaper in the centre of the heater
and crisscross with several pieces of dry kindling. Add a
CAUTION: HOT WHILE IN OPERATION. KEEP few small pieces of dry wood on top.
CHILDREN, CLOTHING AND FURNITURE AWAY. 3. Ignite the paper and close the door. (Depending on length
CONTACT WILL CAUSE SKIN BURNS. of chimney installation, you may need to leave door open
approximately 1/2"(13mm) until kindling is fully ignited.)
WARNING: OVER FIRING THE APPLIANCE WILL SHORT- DO NOT LEAVE STOVE UNATTENDED WHILE DOOR
EN THE LIFE OF THE PRODUCT. FAILURE TO RECTIFY IS OPEN.
AN OVER FIRING CONDITION CAN BE HAZARDOUS AND 4. After the fire has established itself, open the door and add
MAY VOID THE MANUFACTURER'S WARRANTY. a few small logs. Close door.
5. Begin normal operation after a good coal base exists and
CAUTION: Never use gasoline, gasoline type lantern fuel, wood has charred.
kerosene, charcoal lighter fluid or similar liquids to start or
"freshen up" a fire in this heater. Keep all such liquids well Normal Operation
away from the heater while it is in use.
1. Set air control to a desired setting. If smoke pours down
DO NOT BURN : across the glass (waterfall effect) this indicates you have
-Salt water wood * -Treated wood shut the control down too soon or you are using too low
-Wet or green wood -Coal charcoal a setting. The wide range control makes finding the de-
sired setting for your application easy. As every home's
-Garbage/Plastic * -Solvents heating needs vary, (ie. insulation, windows, climate, etc.)
* These materials contain chlorides which will rapidly the proper setting can only be found by trial and error and
destroy metal surfaces and void warranty. should be noted for future burns.
2. To refuel, adjust air control all the way to the left(High),
Your PACIFIC ENERGY heater is designed for maximum and give the fire time to brighten. Open the door slowly,
overall efficiency at a moderate firing rate. Over firing is this will prevent back puffing.
hazardous and a waste of fuel. Too slow a burn contributes 3. Use wood of different shape, diameter and length (up to
to creosote buildup and lowers combustion efficiency. 20"(508mm)). Load your wood and try to place the logs
so that the air can flow between them. Always use dry
NOTE: Left and Right as referred to in this manual are consid- wood.
ered your left and right when facing the front of the woodstove. 4. Do not load fuel to a height or in such a manner that would
be hazardous when opening the door.
Wood Selection 5. For extended or overnight burns, unsplit logs are preferred.
Remember to char the wood completely on maximum
This heater is designed to burn natural wood only. Higher ef- setting before adjusting air control for overnight burn.
ficiency and lower emissions generally result when burning
air-dried seasoned hardwoods, as compared to softwoods WARNING: Always keep loading door closed when burn-
or to green or freshly cut hardwoods. ing. This heater is not designed for open door burning. If
unit is operated with the door open, gas and flame may
Wood should be properly air dried (seasoned) for six months be drawn out of the fireplace opening creating risks of
or more. Wet or undried wood will cause the fire to smoulder both fire and smoke.
and produce large amounts of creosote. Wet wood also pro-
duces very little heat and tends to go out often. WARNING: No alteration or modification of the combus-
tion air control assembly is permitted. Any tampering
Do not burn anything but wood. Other fuels, eg. charcoal, will void warranty and could be very hazardous.
can produce large amounts of carbon monoxide, a tasteless,
odourless gas that can kill. Under no circumstances should WARNING: Do not use grates or andirons to elevate the
you attempt to barbecue in this heater. fuel. Burn directly on the fire bricks. Replace broken or
missing bricks. Failure to do so may create a hazardous
How to Test Your Wood condition.
Add a large piece of wood to the stove when it has a good
large bed of coals. It is dry if it is burning on more than one Restarting After Extended or Overnight
side within one minute. It is damp if it turns black and lights Burns
within three minutes. If it sizzles, hisses and blackens without
igniting in five minutes it is soaked and should not be burnt. 1. Open door and rake hot embers towards the front of the
heater. Add a couple of dry, split logs on top of embers,
Lighting for the First Time close door.
2. Adjust air control all the way to the left(High) and in just
Curing of the Paint Finish/Insulation a few minutes, logs should begin burning.
To achieve the best finish, the paint on your stove must be 3. After wood has charred, reset air control to desired setting.
baked on. When burning your stove for the first 2-3 times it
is very important that the room be well ventilated. Open all 4. To achieve maximum firing rate, set control to high. Do
windows and doors. Smoke and fumes caused by the curing not use this setting other than for starting or preheating
process may cause discomfort to some individuals. fresh fuel loads.
DO NOT OVER FIRE THIS HEATER: ATTEMPTS TO
Lighting a Fire ACHIEVE HEAT OUTPUT RATES THAT EXCEED HEATER
DESIGN SPECIFICATIONS CAN RESULT IN PERMANENT
WARNING: Never use chemicals or any other volatile DAMAGE TO THE HEATER AND CHIMNEY AND MAY VOID
liquid to start a fire. MANUFACTURERS WARRANTY.
6 PACIFIC FP30 060514-28
Over Firing
Over firing can be caused by operating the unit with the door
open, damage to door gaskets allowing excess air to enter
Baffle Removal
the firebox, the use of kiln dried lumber, mill ends or paper The baffle should only be removed when chimney is being
waste and prolonged or continual use on a high burn setting. cleaned.

Heat Output Calculation DO NOT OPERATE WITH BAFFLE ASSEMBLY OR


INSULATION REMOVED.
Seasoned wood has approximately 7500 BTU's per pound.
Removal
The calculation is as follows:
Remove retaining pin at the rear inside top of the firebox, just
Amount of wood in lbs. X 7500BTU’s under the baffle. Lift baffle up and pull forward to disconnect
X .8(80% Avg. Efficiency) from the supply tube. Tilt baffle sideways to drop down and
Burn rate in Hrs. remove from firebox. Inspect gasket between baffle and sup-
ply tube. If necessary, replace with gasket #SUMB.31396
Experience will give you the right settings for proper com- available from your Pacific Energy dealer. Re-install baffle
bustion and efficient burning. Remember the correct air inlet assembly in reverse order. Ensure that the two side pieces
setting is affected by variables such as type of wood, outside of insulation are set inside the side rails and tight against the
temperature, chimney size and weather conditions. With baffle. If the insulation is damaged during removal, it should
practice, you will become proficient in operating your heater be replaced.
and will obtain the performance for which it was designed.
NOTE: AFTER YOU REMOVE THE BAFFLE, ALWAYS
Proper Draft COVER THE BAFFLE AIR TUBE THAT PROVIDES AIR
TO THE BAFFLE. THIS PREVENTS DEBRIS FALLING
1. Draft is the force which moves air from the appliance up DOWN THE TUBE.
through the chimney. The amount of draft in your chimney
depends on the length of the chimney, local geography,
Secondary Air Box Cleaning
nearby obstructions and other factors. 1. The secondary air box is located on the bottom rear of
2. Too much draft may cause excessive temperatures in the the woodstove and can be accessed by removing the
appliance. An uncontrollable burn or a glowing red stove access panel on the bottom of the firebox. Remove the
part or chimney indicates excessive draft. bricks to expose the access panel, then remove the 8
3. Inadequate draft may cause back puffing into the room screws holding the access panel.
and plugging of the chimney. Smoke leaking into the room 2. Remove the two screws securing the cover plate on the
through appliance and chimney connector joints indicates side face of the secondary air box and using a vacuum,
inadequate draft. suck out any debris.
3. Replace the cover plate.
Ash Removal * MAKE SURE THE GASKET IS IN GOOD SHAPE AND
Caution: Ashes are to be removed only when the heater is POSITIONED CORRECTLY. IF IT IS DAMAGED THEN
cold. Whenever ashes get 3(76mm) to 4(102mm) inches deep IT MUST BE REPLACED.
in your firebox, and when fire has burned down and cooled,
remove excess ashes. Leave an ash bed approximately 1" Glass Cleaning
(25 mm) deep on the firebox bottom to help maintain a hot
charcoal bed. If glass becomes darkened through slow burning or poor wood,
it can readily be cleaned with fireplace glass cleaner when the
Disposal of Ashes stove is cold. Never scrape with an object that might scratch
the glass. The type and amount of deposit on the glass is a
Ashes should be placed in a metal container with a tight fitting good indication of the flue pipe and chimney buildup. A light
lid. The closed container of ashes should be placed outside brown dusty deposit that is easily wiped off usually indicates
on a non-combustible floor or on the ground, well away from good combustion and dry, well-seasoned wood and therefore
all combustible materials, pending final disposal. If the ashes relatively clean pipes and chimney. On the other hand, a black
are disposed of by burial in soil or otherwise locally dispersed, greasy deposit that is difficult to remove is a result of wet and
they should be retained in closed container until all cinders green wood and too slow a burning rate. This heavy deposit
have thoroughly cooled. Other waste should not be placed
in this container. is building up as quickly in the chimney.

Blower Operation
The blower is wired with a thermo switch that will turn on
the blower automatically once the fireplace has reached an
appropriate operating temperature.

It is also recommended that the blower be wired to a wall


switch or dimmer switch for manual control. If the blower
should ever need to be replaced, power to the blower can
be shut off at the switch during replacement.

PACIFIC FP30 060514-28 7


FIG. #2

Blower
Replacement
1. The blower is located in the bottom rear compartment
of the woodstove and can be accessed by removing the
access panel on the bottom of the firebox. Remove the
bricks to expose the access panel, then remove the 8 bolts
holding the access panel using a 7/16" (12mm)socket or
wrench(Fig. #1).
2. Loosen the hose clamp on the 3"(76mm) flex vent at the 3"(76mm) FLEX
air box towards the front of the woodstove and disconnect
the flex vent. Gently push the flex vent clear of the access TUBE
opening(Fig. #2 & #3).
3. Disconnect the wire lead of the blower from the electri- FIG. #3
cal terminal block and the male/female connection to the
Thermo Switch .
4. Remove the two wingnuts securing the blower mounting
bracket(Fig. #4).
5. Gently lift the bracket and slide the blower towards the
front of the woodstove.
6. Lift the blower up and out of the woodstove through he
access opening.
7. Remove the nuts attaching the blower to the bracket and
replace blower(Fig. #5).
8. Reverse the process to re-install blower. Make sure the 3"(76mm)FLEX
TUBE
gasket is in good condition. Replace if needed.
FIG. #4
FIG. #1

BOLTS
WINGNUTS

FIG. #5 NUTS
Electrical Rating : 115 V, 60 Hz, 1.1A
Thermo Blower
Switch

TO SWITCH OR
SPEED
TERMINAL CONTROLLER
MALE/FEMALE BLOCK 110VAC SWITCHED
CONNECTION 110VAC COMMON
GROUND
USE ONLY COPPER CONDUCTORS
040612 5050.7434

8 PACIFIC FP30 060514-28


Firebrick Installation

This package contains 19 full-size firebricks, as well as 3 various cut-size bricks.

With the woodstove in the upright position, install firebricks as follows:

1) Place the firebricks on the bottom of the unit first. Use a total of 9 full-size (A)
and 1 cut brick (C).

2) Next install the rear firebricks, 4 full-size (A) bricks as shown.

3) Finally install 3 full-size bricks (A) and 1 cut firebrick (B) on each side as
shown.

A C

ITEM SIZE PART NUMBER

A 9” X 4 1/2” X 1 1/4” (230 mm x 115 mm x 32 mm) 5096.99


B 9” X 3 1/2” X 1 1/4” (102 mm x 115 mm x 32 mm) 3245.501
C 7 1/4” X 4 1/2” X 1 1/4” (184 mm x 115 mm x 32 mm) 245.001

PACIFIC FP30 060514-28 9


Fireplace Installation
Crate Removal
1) Carefully remove wood top and supports.
2) Remove the screws securing the fireplace to the pallet(4).
3) Remove from pallet bottom.

Warning: Under no circumstances is this heater to be installed


in a makeshift or "temporary" manner. It may be fired only
after the following conditions have been met.

- DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE


SERVING ANOTHER APPLIANCE.

- DO NOT INSTALL IN A SLEEPING ROOM.

- The services of a competent or certified installer, (certified


by the Wood Energy Technical Training program (WETT) - in
Canada, Hearth Education Foundation (HEARTH) - in U.S.A.,)
are strongly recommended.

Locating The FP30 Fireplace


The best location to install your fireplace is determined by
considering the location of windows, doors, and the traffic flow
in the room where the FP30 Fireplace is located, allowing space
in front of the unit for the hearth extension and the mantel, and
taking into consideration the location of the chimney. Ideally, you
should choose a location where the chimney will pass through
the house without cutting floor or roof joists.
Check the adequacy of the floor by first estimating the weight of
the fireplace system(approx. 650lbs(295Kg)). Next measure the
area the fireplace will occupy. Note the floor construction and
consult your local building code to determine if any additional
support is needed. In most cases, no additional floor support is
needed for the FP30 fireplace.

The FP30 fireplace may be installed directly on a non-combusti-


ble- floor or on a raised base. A minimum of 84" measured from
Series A
the base of the appliance to the ceiling is required.

The FP30 fireplace may not be installed in a factory built fireplace


unless tested with the fireplace.

Wind direction and magnitude can play a factor in the chimney


performance. Therefore the chimney outlet position is important
when locating the fireplace.

The chimney should:

• Penetrate the highest part of the roof.


• Be installed as far as possible from roof offsets, trees or any
other obstructions that may cause wind turbulence or back
drafts in the chimney.
• The least amount of offsets (elbows) possible.

Clearances

10 PACIFIC FP30 060514-28


FIG. #6
Clearances to combustible surfaces and materials are shown
on pages 14,Fig.#10 & page 17 Table #1.
Clearances may be reduced with various heat insulating
materials. Consult local, National fire codes and authorities
for approval.

Procedure:
Note: See "Combustion Air" section on page 18.

MAINTAIN CLEARANCES TO COMBUSTIBLES AS


SPECIFIED IN THE INSTALLATION INSTRUCTIONS

CAUTION: THE STRUCTURAL INTEGRITY OF THE


FLOOR, WALL AND CEILING/ROOF MUST BE MAIN-
TAINED. Rear
Standoffs
THE SPACE HEATER MUST BE CONNECTED TO A
FACTORY-BUILT CHIMNEY CONFORMING TO CAN/ULC-
S629 AND UL 103HT STANDARDS FOR 650C FACTORY-
BUILT CHIMNEYS.

1. Position stove and floor protection in accordance with the


clearances as stated on the label and in these installation
instructions.
2. Mark the position for the hole for the chimney in the ceil-
ing and roof by using a string and plumb-bob.
3. Check that the intended location will not interfere with floor
joists, ceiling joists or rafters before proceeding further. NOTE: Combustible materials cannot be used in the space
Follow the chimney manufacturer's instructions. directly above the fireplace. No material can be used or
4 Assemble the framing kit as per instructions on page 13. placed in the space above the unit with the exception of
Secure the framing kit to the top of the unit with three approved framing materials.
#8X1/2"(13mm) sheet metal screws (Fig.#6) or use The fireplace must not be in contact with any insulation
steel studs for the entire vertical section. The framing kit or loose filling material. Cover the insulation with drywall
should be flush with the front of the fireplace. Frame in panels around the fireplace.
the fireplace in accordance with the framing clearances
stated on page 12. Anchor the Framing kit to the wood
framing on the sides and top.
5. Remove the rear standoffs from the firebox and attach to
the unit with the 45 degree cut facing to wards the rear
SERIES A
of the unit as shown in Fig. #6

Dimensions 29 1/2"
FIG. #7
749mm
FP30 25"
30 3/4"
635mm
781mm

45"
1.14m 28 1/8"
33 3/8" 714mm
848mm 21 7/8"
8" 556mm
203mm 11 1/4"
286mm

44"
1.12m

PACIFIC FP30 060514-28 11


Minimum Framing Dimensions
FIG. #8 61" NOTE: THE FRAMING
1.55m DIMENSIONS AROUND THE
FIREPLACE INCLUDE THE
INNER DRYWALL BOARD.
26 1/2"
673mm

50 5/8"
1.29m
77 3/8"
1.97m
27 3/8"
695mm

6 3/8"
162mm

77 3/8"
1.97m 38 3/4"
50 5/8"
984mm
1.29m
109 1/2" Series A
2.78m

61 3/4"
1.57m

50 5/8"
1 29m
12 PACIFIC FP30 060514-28
Framing Kit Assembly
Each Kit Contains: Item Part # Description Qty.

1 5049.9912 SCREW, TEKS Pkg


1 #8 x 1/2”(13mm) 40

2 7746 STUD, TOP/BOTTOM


50 1/2”(1.28m)L 2

3 9093.22 STUD, CNTR SUPPORT


2 SIDES, 15”(381mm)L 5

4 7747 FRAMING KIT LEG


3 1/2"(89mm)L 3
3

4 Assembly

• Lay out top/bottom studs (2) and center studs (5) on a large
flat surface. (Fig #9)

• Using the screws provided (1), attach the framing kit legs(4) to
the bottom stud (2).
Series A • Next, attach each center support(3) to the bottom stud(2) and
then attach the top stud(2) to the center supports(3).

FIG. #9

PACIFIC FP30 060514-28 13


Minimum Clearances to
Combustibles
FIG. #10 1” 30”
25mm 762mm

10” 27 3/8” 6 3/8”


254mm 695mm 162mm
38 3/4”
984mm

9”
229mm

6 3/8”
162mm

Series A

14 PACIFIC FP30 060514-28


FIG. #11
Series A
The chimney may incorporate
an offset. To do this safely, all
sections of listed connector, Spark arrestor
offset elbows and chimney rain cap
section must be screwed
together by at least three
sheet metal screws per joint.
The chimney must be suitably
Storm collar
supported by the chimney
manufacturer's listed offset
Roof flashing
support. NOTE: Maximum
unsupported chimney height
Radiation shield
is 25 feet(7.62m)

Chimney Support

Minimum 7' (2.1m)


Ceiling Height

Chimney

50 3/4" (1.29m)

39" (991mm)
Minimum distance
from unit to ceiling

Non-combustible
floor protector

There are two 4"(102mm) diameter combustion outside air


inlet. One on either side of unit. The combustion air inlets
can be relocated to draw air from the rear of the unit if
desired. See page 18. Only one is required to be hooked
up for to outside combustion air if desired.

PACIFIC FP30 060514-28 15


FACTURER'S FIREPLACE ANCHOR PLATE..
Chimney 4. Assemble chimney sections so the finished length is rest-
ing on the manufacturer's adapter and protruding through
the roof. Avoid having joints between ceiling and roof. It
Installation is required to secure connections with three (3) ½" (12
mm) metal screws.
5. Install radiation shields, firestops and all pieces necessary
Listed Chimney and Chimney Connector to prevent contact with combustible materials whenever
passing through floors ceilings or attic spaces.
This appliance must be installed with a 6" chimney system 6. Install the roof support then assemble flashing and storm
approved under the following standards: CAN-ULC S629(IN collar and be sure to maintain the vapour barrier at this
CANADA) AND UL 103HT(IN U.S.). point. (Seal securely.)
7. Attach rain cap and check flashing for leaks.
YOU MUST FOLLOW THE CHIMNEY MANUFACTURER'S 8. If the chimney extends more than 5' above the point of
INSTALLATION INSTRUCTIONS FOR INSTALLATION OF contact with the roof, then it must be secured using roof
ALL CHIMNEY COMPONENTS. braces.
MAINTAIN CLEARANCES TO COMBUSTIBLES AS SPECI- Chase Enclosure
FIED INTHE CHIMNEY MANUFACTURERS INSTALLATION
INSTRUCTIONS NOTE:THE CHASE ENCLOSURE MUST HAVE A 30in2 I(194
cm2) AIR INLET. (IN U.S.A. AND CANADA) OTHERWISE,
USE APPROPRIATE SUPPORTS, CAPS, FLASHING AND SERIOUS OVERHEATING OF THE CHASE MAY RESULT.
SHIELDS IN ACCORDANCE WITH THE CHIMNEY MANU-
FACTURERS INSTALLATION INSTRUCTIONS. NOTE: THIS IS NOT A REMOTE GRAVITY HEAT DUCT IN-
TAKE. THIS IS REQUIRED SOLELY TO COOL THE CHASE
THE FOLLOWING INSTRUCTIONS ARE GENERAL SURROUNDING THE FIREPLACE. DO NOT DIRECTLY
GUIDELINES ONLY. CONNECT THE CHASE INLET TO THE 6"(150M) ADAPTER
ON THE LEFT SIDE OF THE UNIT.SEE PAGES 20 & 21 FOR
CAUTION:THE STRUCTURAL INTEGRITY OF THE FLOOR, GRAVITY HEAT DUCT INSTALLATION AND AIR SUPPLY.
WALL AND CEILING/ROOF MUST BE MAINTAINED.
The Chase inlet is to be located a minimum 1-1/2 inch above
NOTE: The FP30 can be installed with a minimum 15ft of the floor at suggested locations as depicted in Fig 23.
chimney with or without offsets.
If the chimney runs up the outside of the residence, we recom-
NOTE: Longer chimney lengths and different pitch flashings mend it be enclosed in a chase structure. The chase should
may be used. All other parts shown can be installed (see be constructed in such a way that it is an extension of the
Figure 11, Page 15). Install all components to the chimney home. It should be well insulated between the footings and
manufacturer's installation requirements. Consult your chim- the floor of the home to prevent heat loss. We also recom-
ney supplier for installation advice. mend to insulate the ceiling of the chase just as if it were in
the attic space. This will prevent cold air from dropping down
1. After locating the desired location and framing in the through the chase and into the room where the fireplace is
fireplace, cut and frame square holes in all floors, ceil- installed. Some local codes require that the walls be insulated,
ings, and roof that the chimney will pass through as per vapor sealed and sheathed with a fire rated gypsum board.
chimney manufacturer's instructions. Use a plumb bob to We strongly recommend this procedure for all installations to
line up the holes. The chimney support is mounted to the prevent cold drafts from originating in the fireplace enclosure.
framing. If you follow this procedure, we recommend that you do not
2. Maintain a minimum 2" clearance between the chimney insulate the wall above the front of the fireplace.
and any combustible materials. Do not fill the space with
insulation or any other combustible material. NOTE: Check local codes concerning installation requirements
3. Install the pipe manufacturers, Fireplace anchor plate and restrictions in your area.
by inserting it into the flue collar. Secure with stainless
steel screws. We recommend sealing the joint with stove NOTE: Combustible materials cannot be used in the space
cement. (If using ICC chimney pipe and anchor plate, directly above the fireplace. Do not fill the space above the
you will need to install an Anchor Plate spacer. Part fireplace with any material. (except the wood framing)
#FP30.7757)
The fireplace must not be in contact with any insulation or
NOTE: FOR ALL CHIMNEYS, YOU MUST USE THE MANU- loose filling material. Cover the insulation with drywall panels
It is not required to install a chase outlet but doing so can
provide extra heat into the room as well as ensure better
cooling of the chase.

NOTE: Chase inlet and optional outlet are intended to be in


the same room as the fireplace.

Series A

16 PACIFIC FP30 060514-28


Offsets
around the fireplace.
FIG. #12
The chimney for the FP30 can be installed with a maximum
of four 45° elbows(in Canada) and four 30° elbows(in
U.S.A.) as shown in Fig. #12.

Installation:
1. Install the first elbow; turn it in the required direction. It
is required to secure connections with three (3) #8 x ½"
(12 mm) metal screws.

2. Install the necessary chimney lengths to achieve the 15'


required offset. Lock the chimney lengths together ac- 30° or 45°
cording to the chimney manufacturer’s instructions. It is ELBOWS
required to use three (3) #8 x ½" (12 mm) metal screws
at every connection of the chimney. If the offset length is
made of two (2) chimney lengths or more, many chimney
manufacturers require that you use an offset or roof sup-
port halfway up the offset. If penetrating a wall, install a
wall radiation shield supplied by the chimney manufacturer
and install according to the manufacturers installation
instructions.

3. Use another elbow to turn the chimney vertically, Secure


the elbow.

4. Use a plumb bob to line up the centre of the hole. Cut a


hole for the chimney in the ceiling/floor. Frame the hole as
described on page 16 and as per chimney manufacturer's
instructions.

5. From below, install a firestop supplied by the chimney


manufacturer.

Series A

Fireplace Clearances and Dimensions


Distance of combustible material from side, back standoffs and framing kit.
Minimum distance of adjacent wall to side of fireplace door. 30” (737mm)
Ceiling clearance: from the base of the fireplace to the
7’ (2.13m)
ceiling.
Minimum chimney height: minimum total chimney height from fireplace top to
15’ (4.57m)
below the chimney rain cap.
Recommended maximum chimney height (at sea level) from top of fireplace
35’ (10.7m)
to rain cap.
Maximum chimney height supported by fireplace. 25’ (7.62m)
Minimum depth of non-combustible hearth extension: from the front of the 18” (457mm)
fireplace.
Minimum width of floor protection from side of door opening(in U.S.A.) and
from side of unit(in Canada).

PACIFIC FP30 060514-28 17


Combustion Air FIG. #13
Intake or combustion air can be supplied to the stove in one of
two ways. Consult your local building code or CAN/CSA-
B365, Installation Code for Solid-Fuel-Burning Appliances
and Equipment before proceeding.

1. Outside combustion air supply - Outside air may be


drawn from either side of the stove.

To draw outside combustion air, remove the cover plate


on the side you wish to draw the air from and connect the
outside combustion air adapter provided (Fig. #13).

Outside Combustion Air Adapter


The adapter is only required if outside combustion air is
used.

Installation:

Remove cover plate from the side of the unit closest to the
exterior wall in which you will be connecting the outside
air inlet. To change from side to rear inlets, remove the
screws holding the corner plate to the air jacket. Gently pull
corner plate from the unit and disconnect the flex vent, flip
over the corner plate and reattach the flex vent. Reattach
the corner plate to the air jacket. Place the adapter over
the 4" round hole with the collar facing out and attach with
screws previously removed with the cover plate.
Outside Air
Cut or drill a 4" diameter hole in the closest exterior wall Adapter
or in the floor anywhere inside the chase. Cover the hole
with a 4" x 4" (100 mm x 100 mm), 20GA wire mesh
with minimum1/4"(6mm) X 1/4"(6mm) spacing, rodent
screen and staple/nail in place. Provide water protection
FIG. #14
as required. Attach 4"(102mm) venting (not supplied) to
adapter

WARNING: This hole must get its air from the outdoors and
be finished with an approved vent cap. The use of outside
combustion air for residential installation requires the unit
to be secured to the structure to prevent dislodging of
the air duct. Check local building codes for instruction on
sealing the vent cap at the penetration point of the build-
ing. The combustion air inlet ducts can not terminate in
an attic space or garage.

2. Room air supply - Remove the cover plate from the front
of the unit underneath the ashlip. The stove will now draw
its air from the room through this opening and into the
firebox intake. You must ensure the room has adequate
replacement air to operate the unit.

WARNING: This unit is not designed to be operated with


the firing door open. In addition to the obvious hazard of
sparks landing on combustibles, an open fire door will WARNING: THE COMBUSTION AIR INLET
cause the heater to draw excess air from the living space
and possibly cause suffocation. MUST BE AT LEAST 5ft BELOW CHIMNEY
FLUE AND MUST NEVER TERMINATE IN
CAUTION: The living space around the heater must be well ATTIC SPACES OR GARAGES.
ventilated with good air circulation. Anything that may
cause a negative pressure can cause gases or fumes
to be pulled into the living area. During extremely cold
weather, and especially when burning at very slow rates,
the upper parts of the exposed chimney may ice up,
partially blocking the flue gases. If blockage occurs, flue
gases may enter living space.

A typical outside air connection is shown in Fig. #14.


18 PACIFIC FP30 060514-28
6. A support must be used on the first 15' section (4.6m). Safety Strip
Floor Protector The floor between the fireplace and the hearth extension/
ember protection must be protected with a 2"(51mm) deep
safety metal strip equal to the width of the unit.
The stove may be installed on a combustible floor provided
non-combustible ember protection, such as tile, metal, brick, One half of the metal strip must be under the fireplace front
etc., is used in front of the unit as per Fig. #15 & #16. and the other half must extend onto the floor and under the
This protection must extend as follows: hearth extension/ember protection as shown in Fig. #17.
In Canada: 18"(457 mm) on the firing side and 8"(203mm)
to the sides. See Figure #15, below. FIG. #17
Fireplace front

Safety metal strip The space between


FIG. #15 Canada Only the fireplace and the
hearth extension must
Minimum Width - 58"(1.47m) be sealed with a
Minimum Overall Depth - 18"(457mm) non-combustible
Hearth extension material such as
non-combustible sand-cement grout.
finish material

2”
Floor 51mm

18" [457mm]
Blower Wiring
8" [203mm] 8" [203mm] The FP30 must be connected 120 VAC house hold electrical
system.
Non-combustible
floor protector
It is recommended to also connect the unit to a wall switch
or fan speed controller.
58" [1.47m]
Insert the Romex 14/2 wire, or equivalent, into the unit
through the strain relief located on the right hand side of the
fireplace casing.
In U.S.A: 18"(457 mm) to the front and 8"(203mm) to the
sides of the fuel loading door opening. See Figure #16, below. Connect the wiring as shown in the wiring diagram below to
the terminal block located in the bottom of the unit. See section
FIG. #16 (Blower Replacement) on Page 8. All electrical connections
U.S.A. Only should be performed by a certified/licensed electrician.

Minimum Width - 38.5"(978mm) Electrical Rating : 115 V, 60 Hz, 1.1A


Minimum Overall Depth - 19 1/8"(485mm) Thermo Blower
Switch

TO SWITCH OR
SPEED
TERMINAL CONTROLLER
MALE/FEMALE BLOCK 110VAC SWITCHED
CONNECTION 110VAC COMMON
GROUND
19 1/8"
8" [203mm] 8" [203mm] [486mm] 120412 5050.7434
18" [457mm]
Non-combustible
floor protector

38 1/2" [978mm]

PACIFIC FP30 060514-28 19


Remote Gravity Heat Duct
Installation
FIG. #18

70” min TO CENTER


1.78m OF OUTLET
60 1/2”min
1.54m

GRAVITY VENT AIR INLET

IN U.S.A., A MINIMUM OF ONE REMOTE GRAVITY HEAT


DUCT KIT MUST BE INSTALLED WITH THE FP30. FIG. #19
PART# FP30.GVKIT Heat Duct
Adapters
NOTE: FOR A SINGLE GRAVITY VENT AND WHEN THE
FACING MATERIAL IS LESS THEN 3/4"THICK, THE UNIT
WILL DRAW SUFFICIENT AIR THROUGH THE OPENING
BENEATH THE ASHLIP.

CONTENTS:

1 - OUTLET ADAPTER Heat Duct


1 - HEAT DUCT ADAPTER openings
1 - 14"(356mm) X 10"(254mm) OUTLET GRILL
1 - 8"(203mm) X 8"(203mm) INLET GRILL
1 - 6"(150mm) ROUND TO 6"(150mm) SQUARE INLET BOOT
1 - 5ft(1.5m) LONG, 6"(150mm) DIAMETER TYPE "B" FLEX
VENT
1 - INSTRUCTIONS PACK WITH SCREWS

If passing through a wall to an another room or space you will


need a firestop (not included with the FP30.GVKIT).
Part #5095.75

If you require more than 5ft(1.5m) of the Type ”B” flexible


venting order Part #5095.7.

INSTALLATION:

1. Using a pair of tin snips, cut away the square section


blocking the heat duct openings and cut out and remove
insulation(Fig.#19).

2. Attach the heat duct adapter/s with the screws provided


in the FP30.GVKIT (Fig. #19).

20 PACIFIC FP30 060514-28


3. Locate and cut a 11 1/4”(286mm) X 9 3/4”(248mm) open-
ing in the wall or facing material being sure to maintain FIG. #21
structural integrity. CEILING
4. The centerline of the outlet must be a minimum 70”(1.78m)
off the floor, 16"(406mm) from any adjacent wall and a
minimum 12”(305mm) from the ceiling.

5. Bend the securing tabs on the outlet adapter inwards and 12” min
insert the 6"(150mm) flexible Type "B" venting provided
approximately 1/2”(13mm) into the opening in the wall 305mm
outlet. Secure to the outlet with two #8 X 1/2"(13mm) Tek
screws from the outside.

6. Insert the vent pipe through the opening in the wall and
position the pre-assembled wall outlet in the hole being
careful not to damage the insulation. Cover outlet adapter
with outlet screen provided or one of equal outlet area.

7. A maximum 20'(6.1m) total run including 2 - 90° bends


are allowed. The venting should only run horizontally or
up, never in a downward direction.

8. Maintain clearances to combustibles as described in the


venting manufacturer's specifications and use a firestop
if passing through a floor or wall. SECURING
9. Connect the vent pipe to the heat duct adapter on the top TABS
of the unit and secure with three #8 X 1/2’(13mm) Tek 70” min
screws.
1.78m
NOTE: FOR A SINGLE GRAVITY VENT AND WHEN THE
FACING MATERIAL IS LESS THEN 3/4"THICK, THE UNIT
WILL DRAW SUFFICIENT AIR THROUGH THE OPENING
BENEATH THE ASHLIP.

10. If running two gravity vents and/or if your facing material FLOOR
is more than 3/4”(19mm) thick(Max. 4"(102mm)), connect
an additional room air inlet to the 6"(150mm) Gravity Vent
inlet adapter on the left side of the fireplace casing(Fig.
#22).

FIG. #22
FIG. #20

WALL
OUTLET
11 1/4”
286mm

9 3/4”
248mm

GRAVITY HEAT DUCT AIR INLET. used only when


two gravity vents and/or your facing material is more than
3/4”(19mm) thick(Max. 4"(102mm)), NOT RELATED TO
CHASE AIR INLET
PACIFIC FP30 060514-28 21
Facing and Air Inlet
Cement Board Installation FIG. #23

The front facing area of the FP30 must be covered with non-
combustible cement board as shown in Fig.#23 and #24 prior
to applying any finishing material.

The cement board can be attached to the framing and to the


front of the unit outside of the dimensioned area shown by
the dotted line in Fig.#23. FACING FLANGES

Use the manufactures suggested fasteners to attach the ce-


ment board and install as recommended.

Finish the joints as per the board manufacturers recom-


mendations.
1 1/2”
38mm

1”
25mm

1”
25mm

3/4” 30in2 (194cm2)


19mm CHASE AIR INLET

FACING FLANGES

FIG. #24

NON-COMBUSTIBLE CEMENT BOARD


29” MIN REQUIRED IN THESE AREAS.
737mm

DECORATIVE
NON-COMBUSTIBLE
FACING MAXIMUM
4”(102mm) THICK

30in2 (194cm2)
CHASE AIR INLET
1 1/2”(38mm)
MINIMUM HEIGHT FROM FLOOR
18”(457mm)
MAXIMUM HEIGHT FROM FLOOR
60.00” MIN
1.5m

ALTERNATE LOCATION
FOR CHASE AIR INLET CAN ALSO
BE ON OTHER SIDE OF CHASE

22 PACIFIC FP30 060514-28


Mantel Clearances
FIG. #25
NON-COMBUSTIBLE ZONE.
COMBUSTIBLE FRAMING ALLOWED DO NOT INSTALL ANY COMBUSTIBLE MATERIAL,
ABOVE THIS POINT ELECTRICAL WIRING OR GAS PLUMBING IN THIS
AREA.

MANTEL CLEARANCE
B
CHART
MANTEL CLEARANCE

16 1/2” A-CANADA 42”(1.07m)


NON-COMBUSTIBLE
CEMENT BOARD 419mm (NO GRAVITY VENT)
-NON-COMBUSTIBLE
A DECORATIVE FACING A-CANADA 34"(864mm)

(GRAVITY VENT)

A-U.S.A. 34"(864mm)

MANTEL DEPTH

B 2"(51mm) TO 12"(305mm)

PACIFIC FP30 060514-28 23


Appendix A
Troubleshooting

Problem Cause Cure


Glass is Dirty 1. Wood is wet - Use dry wood

2. Turning down air control - Do not turn down until


or damper too soon a) there is a good bed of coals
b) the wood is charred

3. Draft too low - Improper chimney height and / or diameter


- Chimney plugged or restricted, inspect and
clean
- Provide outside air for combustion

4. Door gasket leakage - Replace gasket


- Check latch

Excessive Creosote Buildup - See 1,2,3, above.

Low Heat Output 1. Wood is wet - Use dry wood


2. Fire too small - Build a larger fire
3. Draft too low - Chimney plugged or restricted, inspect and
clean

Won't Burn Overnight 1. Air control is set too high - Set control lower
2. Not enough wood - Unsplit wood is preferred for overnight burns
3. Draft too high - Excessive chimney height and/or diameter

Stove Won't Burn 1. Combustion air supply blocked - Check outside air supply for obstruction
- Check that room air cover is removed

2. Draft too low - Chimney plugged or restricted, inspect and


clean
- Chimney oversized or otherwise unsuitable,
consult Dealer

24 PACIFIC FP30 060514-28


Understanding & Operating Your Pacific Energy Stove

The Pacific Energy line of woodstoves is a culmina- OPERATING TIPS


tion of years of research and development. Designed
to be efficient, clean-burning and user-friendly, this 1. Always use dry, seasoned firewood, up to 20" long.
heater will give you years of warm service. However, Load wood endwise, a mixture of large and small
a knowledgeable operator is still the most important pieces, on top of a good ash base (1" minimum).
factor for maximum performance and part of this is
understanding the basic functions of this design. 2. Operate on a medium to high setting, for up to
1 hour from cold start. After the initial warm up pe-
Traditional wood stoves had a basic combustion riod, refuel and leave the air control on a medium
system which allowed a considerable amount of setting for 5 to 10 minutes more and then set the
heat energy to escape up the chimney as unburned air control to the desired position.
gases and particulates (smoke). Pacific Energy
has designed a system that solves the problem 3. If a slow burn is desired, set the air control to
by burning the smoke and releasing the additional low. Active secondary burning should be present
heat to the room. above the wood load. If it is not present or goes
out shortly after, proper operating temperature has
This system has two critical design features: not been reached and the stove needs additional
warm up time.
1. Above fire secondary air injection:
The hollow "air baffle" injects super-heated sec-
ondary air just above the load. With the stove at
the proper operating temperature, this will create
a secondary flame that will be evident for approxi-
mately 1/3 of the total burn time.

2. High mass and thermal insulation: 6


The high mass (weight) acts as a heat storage and
the thermal insulation keeps the combustion zone
5
hot. Active flaming takes place during the first part 3
of the burn. During this stage, heat is stored in the 4
mass of the unit and is later released slowly and
evenly. As wood chars, active flaming will dimin- 2
ish. This clean charcoal burning stage will last for
1
a considerable length of time and refuelling should
be avoided until the charcoal base has become
quite small.

1 -Boost Air 4 -Secondary Combustion Zone


2 -Main Combustion Air 5 -Radiant Heat
3 -Air Wash System 6 -Convected Heat

PACIFIC FP30 060514-28 25


Replacement Parts
ITEM DESCRIPTION PART NO.

1............ Inlet Air Shield ............................................... 7719.5


2............ Cast Ash Lip .................................... ALIP.50374753
3............ Blower ..................................................FP30.BLOW
4............ Firebrick Set ...........................................BRIC.FP30
5............ Door Gasket ........................................ FP30.DGKIT
6............ Glass Retainer Set (4 pc.) ......................FP30.7748
7............ Replacement Glass (c/w Tape) ...........FP30.GLKIT
8............ Door Casting ...........................................5035.0221
9............ Door Handle Assembly ......................... FP30.50384
10 .......... Replacement Baffle Kit ..................... SUMB.BAFKIT
10a ........ Baffle (not sold separately) ................. SUMB.BAFF
10b ........ Side Insulation ..................................... 5068.732.C
11 .......... Brick Rail Kit .................................... FP30.RAILSET
12 .......... Baffle Pin ........................................... SSER.125001
13 .......... Baffle Gasket .......................................SUMB.31396
14 .......... Flame Shield (c/w Bolt and Nut)......... SUMB.31155
15 .......... Door Catch ............................................. FP30.7763
*16 ........ Gravity Heat Duct kit ........................... FP30.GVKIT
*17 ........ Outside Air Adapter .................................FP30.7745
*18 ........ Access Cover Gasket ............................ 5068.81016
*19 ........ Gravity Heat Duct Adapter...................... FP30.9128
*20 ........ Anchor plate spacer(for use with ICC Chimney olny)
.............................................................................. FP30.7757 All parts may be ordered from your nearest Pacific Energy
*NOT SHOWN dealer. Contact Pacific Energy for the location of the dealer
nearest you.

10
14

10b

10a 15

1
13
10b
12 2
11
11
3
5

7
8
6
9

)3'5%.

26 PACIFIC FP30 060514-28


Label
DO NOT REMOVE THIS LABEL/ NE RETIREZ PAS CETTE
CERTIFIED FOR CANADA AND U.S.A.
LISTED FACTORY BUILT FIREPLACE.
CERTIFIED TO ULC S610-M87 AND
SN- 601
CONFORMS TO UL 127-2011/
Label Location FOYER PRÉFABRIQUÉ HOMOLOGUÉ / CERTIFIÉ POUR UTILISATION AU CANADA
ET AUX É.-U.TESTÉ SELON ULC S610-M87 ET UL 127-2011.
ETL#4001507
SERIES/SÉRIE: A MODEL/ MODÈLE: FP30
The rating label is located beneath the • INSTALL AND USE IN ACCORDANCE WITH THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THE
firebox on the casing floor and can be APPLIANCE. • AREAS OF THE FIREPLACE INCORPORATING WARM OR COLD AIR DUCTS SHALL BE ENCLOSED IN ACCORDANCE
WITH THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THE APPLIANCE.
viewed by removing the access cover • CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS, INSTALLATION PERMIT AND INSPECTION IN YOUR
in the bottom of the firebox. There is AREA. • DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE
• DO NOT OBSTRUCT THE OPENINGS IN FRONT OF THE FIREPLACE OR OTHERWISE RESTRICT SUPPLY AIR NECESSARY FOR
an additional clearances label on the NORMAL FIREPLACE OPERATION AS SPECIFIED IN INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THE
APPLIANCE. INADEQUATE AIR SUPPLY FOR COMBUSTION, VENTILATION AND DILUTION MAY RESULT IN DANGEROUS OPERATION
right side, of the fireplace casing. OF THIS AND OTHER APPLIANCES.
• SEE LOCAL BUILDING CODE AND MANUFACTURER'S INSTRUCTIONS FOR PRECAUTIONS REQUIRED WHEN PASSING A
CHIMNEY THROUGH A COMBUSTIBLE WALL OR CEILING. CHIMNEY SYSTEM MUST BE LISTED TO: IN CANADA - USE ONLY ICC
EXCEL CHIMNEY LISTED TO ULC-S-629, IN USA - UL-103 HT LISTED CHIMNEY
• OPTIONAL COMPONENTS: FRESH AIR KIT, GRAVITY HEAT DUCT KIT PART# FP30.GVKIT.
• OPERATE ONLY WITH FEED DOOR CLOSED. OPEN TO FEED FIRE ONLY.
• FOR SOLID WOOD FUEL ONLY. • BLOWER ELECTRICAL RATING 115V, 60HZ, 1.0AMP • REPLACE GLASS ONLY WITH 5mm
CERAMIC GLASS.
• DO NOT USE OR INSTALL COMPONENTS OR PRODUCTS NOT SPECIFIED IN PACIFIC ENERGY INSTALLATION INSTRUCTIONS.
DO NOT USE A FIREPLACE INSERT OR OTHER PRODUCTS NOT SPECIFIED FOR USE WITH THIS PRODUCT.
• THIS FIREPLACE HAS NOT BEEN TESTED WITH AN UNVENTED GAS LOG SET. TO REDUCE RISK OF FIRE OR INJURY, DO NOT
INSTALL AN UNVENTED GAS LOG SET INTO FIREPLACE.
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS/ DÉGAGEMENTS MINIMUMS AUX MATÉRIAUX
COMBUSTIBLES
A. CHASE ENCLOSURE WIDTH/ LARGEUR DE CLÔTURE DE
POURSUITE 60 in. / 1.52 m
B. BACKWALL TO CONNECTOR/ MUR ARR. AU TUYAU de RAC. 10 in./254 mm
F
C. BACKWALL TO UNIT/ MUR ARRIÈRE AU FOYER 1 in. / 25 mm
D. FRAMING OPENING/ OUVERTURE DE CADRAGE 51 in /1.3 m A
E. CORNER TO CONNECTOR/ COIN AU TUYAU de RACCOR. 39 in./991 mm J G
K
F. SIDEWALL TO CONNECTOR/ MUR LAT. au TUYAU de RAC. 28 in./711 mm U.S.A.
C
G. NON-COMBUSTIBLES ONLY ABOVE UNIT TO CEILING/ B
H
RATING LABEL NON-COMBUSTIBLES SEULEMENT AU-DESSUS FOYER À
PLAFOND
18 in. / 457 mm E
D
H. TOP OF DOOR TO MANTEL/ HAUT DE PORTE AU MANTEAU
J. CEILING TO UNIT/ DU PLAFOND AU FOYER ***
26 in. / 660 mm
D
K
K

K. FLOOR PROTECTION FROM FRONT OF UNIT/ CAN.


PROTECTEUR de PLANCHER À L’AVANT DU FOYER 18 in. / 457 mm
K. FLOOR PROTECTION TO SIDE OF UNIT/
PROTECTEUR de PLANCHER AU CÔTÉ DU FOYER 8 in./203 mm
CLEARANCES TO ALL STANDOFFS/ DÉGAGEMENTS 0 in. / 0 mm

*** IN CANADA: “H” IS 42”(1.07m) WITHOUT A GRAVITY VENT INSTALLED AND 34”(864mm) WITH A GRAVITY VENT INSTALLED.
IN THE U.S.A.: “H” IS 34”(864mm)
IN CANADA: “K” IS FROM THE SIDE FACING FLANGE/AU CANADA : «K» EST MESURÉ À PARTIR DE LA FAÇADE LATÉRALE DU
FOYER.///IN U.S.A : “K” IS FROM THE SIDE OF THE FIRING DOOR OPENING/AUX ÉTATS-UNIS : «K» EST MESURÉ À PARTIR DU
BORD DE L’OUVERTURE DE LA PORTE DE CHARGEMENT.
LE SYSTÈME DE CHEMINÉE DOIT ÊTRE HOMOLOGUÉ COMME SUIT : AU CANADA - CHEMINÉE HOMOLOGUÉE ULC-S-629, ICC
(INDUSTRIAL CHIMNEY COMPANY). AUX ÉTATS-UNIS - CHEMINÉE HOMOLOGUÉE UL-103 HT.
• INSTALLEZ ET UTILISEZ SELON LES INSTRUCTIONS D’INSTALLATION ET D’UTILISATION FOURNIES AVEC LE FOYER.
• LES PARTIES DU FOYER INCORPORANT DES CONDUITS CHAUDS OU FROIDS DOIVENT ÊTRE ENCHÂSSÉES,
CONFORMÉMENT AUX INSTRUCTIONS D’INSTALLATION ET D’UTILISATION FOURNIES AVEC LE FOYER.
• CONTACTEZ LES AGENTS LOCAUX DU CODE DU BÂTIMENT OU DU SERVICE-INCENDIE POUR LES RESTRICTIONS, PERMIS
D’INSTALLATION ET EXIGENCES D’INSPECTION DANS VOTRE RÉGION.
• NE RACCORDEZ PAS CE FOYER À UN CONDUIT DE CHEMINÉE DESSERVANT UN AUTRE APPAREIL
• NE PAS OBSTRUER PAS LES OUVERTURES DEVANT LE FOYER, NI RESTREINDRE L’ALIMENTATION D’AIR NÉCESSAIRE POUR
LE FONCTIONNEMENT NORMAL DU FOYER, TEL QUE SPÉCIFIÉ DANS LES INSTRUCTIONS D’INSTALLATION ET D’UTILISATION
FOURNIES AVEC L’APPAREIL. LA PROVISION INADEQUATE D’AIR POUR COMBUSTION, MAI DE VENTILATION ET DILUTION A POUR
RESULTAT L’OPERATION DANGEREUSE DE CECI ET AUTRES APPAREILS.
• VOIR LE CODE DU BÂTIMENT LOCAL ET LES INSTRUCTIONS DU FABRICANT, POUR LES PRÉCAUTIONS EXIGÉES LORSQU’UNE
CHEMINÉE TRAVERSE UN MUR OU PLAFOND EN MATÉRIAUX COMBUSTIBLES.
• COMPOSANTS OPTIONNELS: KIT DE PRISE D’AIR, KIT DE CONDUITS DE DISTRIBUTION DE CHALEUR (PIÈCE no FP30.GVKIT).
• UTILISEZ LES COMPOSANTS SPÉCIFIÉS DANS LES INSTRUCTIONS D’INSTALLATION DE PACIFIC ENERGY.
• UTILISEZ SEULEMENT AVEC LA PORTE DE CHARGEMENT FERMÉE. NE L’OUVREZ QUE POUR ALIMENTER LE FEU.
• POUR COMBUSTIBLE SOLIDE SEULEMENT.
• REMPLACEZ LA VITRE SEULEMENT PAR UNE VITRE EN CÉRAMIQUE.
• LA SOUFFLERIE CLASSEMENT ELECTRIQUE 115V, 60 Hz, 1.0AMP
• CETTE CHEMINEE n’A pas ETE ESSAYEE AVEC UN UNVENTED JOURNAL DE GAZ A REGLE. POUR REDUIRE LE RISQUE DE
FEU OU BLESSURE, LE PAS INSTALLE UN UNVENTED JOURNAL DE GAZ A REGLE DANS CHEMINEE.

CAUTION
HOT WHILE IN OPERATION. DO NOT TOUCH. MANUFACTURED BY/ FABRIQUÉ PAR :
PACIFIC ENERGY FIREPLACE PRODUCTS LTD.
KEEP CHILDREN, CLOTHING AND FURNITURE 2975 ALLENBY RD., DUNCAN, BC V9L 6V8

AWAY. CONTACT MAY CAUSE SKIN BURNS. SEE NAMEPLATE AND


INSTRUCTIONS./ DEVIENT TRÈS CHAUD. NE TOUCHEZ PAS. ÉLOIGNEZ LES
ENFANTS, LES VÊTEMENTS ET LES MEUBLES. UN CONTACT PEUT CAUSER
DES BRÛLURES. VOIR LA PLAQUE SIGNALÉTIQUE ET LES INSTRUCTIONS.
U.S. ENVIRONMENTAL PROTECTION AGENCY CERTIFIED DATE OF MANUFACTURE/ DATE DE FABRICATION
TO COMPLY WITH JULY, 1990, PARTICULATE EMISSION
J F M A M J J A S O N D
STANDARDS/ CERTIFIÉ CONFORME AUX NORMES
2012 2013 2014 2015 2016 2017
SUR LES ÉMISSIONS DE PARTICULES (JUILLET 1990).
MADE IN CANADA/ FABRIQUÉ AU CANADA
270612 5050.7622 FP30-1

PACIFIC FP30 060514-28 27


PACIFIC ENERGY FIREPLACE PRODUCTS LTD.
2975 Allenby Rd., Duncan, B.C. V9L 6V8
Phone: 250-748-1184
Web site: http://www.pacificenergy.net
Printed in Canada

You might also like