CMEM01060FU
CMEM01060FU
Abstract
T h e single phase flow and thermal performance of a double pipe heat
exchanger are examined by experimental methods. T h e working fluid is
water a t atmospheric pressure. Temperature measurements at the inlet and
outlet of the two streams and also at an intermediate point half way between
the inlet and outlet are made. Heat is supplied to the inner tube stream by an
immersion heater. The overall heat transfer coefficients are inferred from the
measured data. The heat transfer coefficient of the inner tube flow (circular
cross section) is calculated using the standard correlations. The heat transfer
coefficient of the outer tube flow (annular cross section) is then deduced.
1 Introduction
Double pipe heat exchangers are the simplest recuperators in which heat is
transferred from the hot fluid to the cold fluid through a separating
cylindrical wall. It consists of concentric pipes separated by mechanical
closures. Inexpensive, rugged and easily maintained, they are primarily
adapted to high-temperature, high-pressure applications d u e t o their
relatively small diameters.
Double pipe heat exchangers have a simple construction. They are fairly
cheap, but the amount of space they occupy is generally high compared with
the other types. The amount of heat transfer per section is small, that makes
the double pipe heat exchangers a suitable heat transfer device in
applications where a large heat transfer surface is not required.
Transactions on Modelling and Simulation vol 30, © 2001 WIT Press, www.witpress.com, ISSN 1743-355X
2 Experimental setup
The experiments on which this work is based, were performed for the case of
nearly uniform heat flux at the surface. This condition of uniform heat flux
is probably closer to representing the practical condition of operating double
pipe heat exchangers in concurrent flow, where the outside fluid heats the
fluid in the pipe, or vice versa. Constant heat flux should not be confused
with constant surface temperature, where the latter is closely approximated
when there is a phase change in one of the fluids, or when the fluids are in
CO-currentflow.
The experimental rig was designed and constructed in the Heat Transfer
Laboratory, Department of Mechanical Engineering. Kerman University. A
schematic diagram of the rig circuit is shown in Fig. 1 . Some geon~etrical
data about the exchanger are listed in Table 1 . The double pipe heat
exchanger is in the vertical position; it is bent 90 degrees twice.
Tank
I Pump
Fig l Schematic diagram of the rig circuit
Transactions on Modelling and Simulation vol 30, © 2001 WIT Press, www.witpress.com, ISSN 1743-355X
Calculating the film heat transfer coefficient for the tube side flow as
mentioned in step 6, requires one to know viscosity, Reynolds number,
Prandtl number, Nusselt number, and conductivity of water. These data for
operating conditions corresponding to Table 2 are listed in Table 4. The
inner tube side heat transfer coefficients based on Eq. 8 and the outer tube
side heat transfer coefficients based on Eq (A.2) are listed in Tables 5 and 6
respectively.
Where D, is the outer tube inner diameter and Du is the inner tube outer
diameter. for the case at hand D, is 6 mm. The Hausen correlation reads a s
follows:
The outer tube heat transfer coefficients evaluated according to the Hausen
correlation and using the data listed in Table 5 are included in Table 6. The
outer tube heat transfer coefficients can now be compared u i t h those
evaluated experimentally. The comparison is illustrated in Figs. 2 and 3.
Transactions on Modelling and Simulation vol 30, © 2001 WIT Press, www.witpress.com, ISSN 1743-355X
Gz= Ka s[5]
h0 h, h, an J
[W / m2."c] [W / m 2,'C] [W / ~ ? , O C ] Sellars,
experimental and
data, Eq. (A.5) Eq. 10 Eq. 1 1 Klein[6]
N~~~~~
Nu = l.2O[O.O27R ~ O Pr - (-)O P
' '$1 (13)
P,
The factor 1.20 appeared in Eqs. 12 and 13 takes care of the uniform heat
flux boundary condition at the surface of the existing heat exchanger. This is
because the Sieder-Tate correlations are for isothermal wall. Eq. 12 applies
for laminar flow (Re 2100), while Eq. 13 takes care of turbulent flow. L is
the total heat transfer length. The outer tube heat transfer coefficients are
recalculated based on Eq. 12. The results are included in Table 6 and the
comparison is shown in Figs. 2 and 3.
T h e Heat Exchanger Design H a n d b o o k , H E D H [IO], has also
recommended the Sieder-Tate correlations to be used for predicting the film
coefficients of single-phase flow in both the inner tube and the outer tube of
a double pipe heat exchanger.
h l000
.Test
500 = Eq. 11
Eq. 12
1000 1500 2000 2500
h
500
m Eq. 11
0 Eq. l 2
1000 1100 1200 1300 1400 1500 Kays
Re
Transactions on Modelling and Simulation vol 30, © 2001 WIT Press, www.witpress.com, ISSN 1743-355X
5 Conclusions
The outer tube side heat transfer coefficients deduced from experimental
data are compared with those evaluated based on standard correlations. The
comparison is illustrated schematically in Figs. 2 and 3 for counterflow and
parallel flow conditions. respectively.
In both the counterflow and parallel flow conditions, all three standard
correlations predict lower heat transfer coefficients compared with the
experimental results. The Sieder-Tate [9] correlation predicts the highest
values among the three standard correlations. they are still lower by a factor
of 1.04 to 2.64. That means, the standard correlations for laminar flow in the
outer tube side in which the Nusselt numbers are proportional to Re0j3
underestimate the heat transfer coefficients.
The outer tube side Reynolds numbers are lower by a factor of 6 to 10,
but the hydraulic diameter is lower by a factor of nearly 3. Therefore the
outer tube side heat transfer coefficients would be expected to be similar t o
the tube side heat transfer coefficients. The agreement with predictions is not
bad. The discrepancy may be because of three reasons. Firstly, there was
probably heat transfer in regions between the thermocouple wires and the
exchanger terminals, so that the actual heat transfer area was larger than
calculated. Secondly, there was probably a higher coefficient in certain
regions. such as in turnaround region, than predicted by straight pipe
equation. Thirdly. the effect of natural convection in internal flows,
especially when the forced and free convection currents are in the same
direction (aiding flow), can enhance the heat transfer coefficients by a factor
Transactions on Modelling and Simulation vol 30, © 2001 WIT Press, www.witpress.com, ISSN 1743-355X
of 1.41 compared with the case when the heat transfer mechanism is
assumed strictly on the basis of laminar forced convection [l l].
Temperatures have been rounded t o the nearest decimal. S t r e a m
temperature differences ranged from 3 to 18 degrees. Heat loads, deduced
from these temperature differences are likely to be in error by 1 t o 2 percent.
With this error in heat load, the error in the measured heat transfer
coefficients is 3-6 percent.
Hewitt et al [l21 and also H E D H [4] have recommended that the Dittus-
Boelter correlation with n=0.4 to be used for predicting the film coefficients
of both the inner tube side and the outer tube side flows for both laminar
and turbulent flows. Using the Dittus-Boelter correlation with Reo"or the
laminar flow in the outer tube side increases the heat transfer coefficients by
a factor 2 to 3. That makes us believe that Hewitt et a1 [6] and also H E D H
[4] are correct.
T h e experimental heat transfer coefficients d o n o t have a direct
relationship with the outer tube side Reynolds numbers. This behaviour is
not repeated by any of the standard correlations. This is because the
experimental heat transfer coefficients are governed by the overall heat
transfer coefficients (Eq. 5), rather than by the Reynolds number.
The purpose of this article is to recognise the mechanisms of heat transfer
that occur in double pipe heat exchangers and to report higher heat transfer
coefficients in the laminar flow regime.
References
Appendix A
The heat transfer rate in a composite cylindr~calwall is expressed in terms of
the total temperature difference and the resistance of different layers:
Q / A = (Th - T c ) /(l / h , A , +(In r, / r,)/(2nkL) + 1/ hoA,) (A.1)
The overall heat transfer coefficient is defined as the inverse of the sum of
resistances to heat flow, so that Eq.(A. I) reduces to:
Q = UA(1, - T,) (A.2)
where U can be defined in terms of either the internal or external tube areas.
In each case Eq. (A.2) applies: