Carlo - Gavazzi DPB51CM44 Datasheet PDF

This document provides information on a 3-phase monitoring relay called the DPB51. It can monitor for over and under voltage, phase sequence, and phase loss. It has adjustable voltage limits, a delay function from 0.1 to 30 seconds, and SPDT relay output. The DPB51 is a DIN rail mounted device that measures 17.5mm wide and is suitable for voltages from 208 to 480 VAC.

Uploaded by

M. Shaat
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
416 views3 pages

Carlo - Gavazzi DPB51CM44 Datasheet PDF

This document provides information on a 3-phase monitoring relay called the DPB51. It can monitor for over and under voltage, phase sequence, and phase loss. It has adjustable voltage limits, a delay function from 0.1 to 30 seconds, and SPDT relay output. The DPB51 is a DIN rail mounted device that measures 17.5mm wide and is suitable for voltages from 208 to 480 VAC.

Uploaded by

M. Shaat
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Monitoring Relays

True RMS 3-Phase, 3-Phase+N, Multi-function


Type DPB51
• TRMS 3-phase over and under voltage,
phase sequence and phase loss monitoring relay
• Detects when all 3 phases are present and have the
correct phase sequence
• Detects if all the 3-phase-phase or phase-neutral volt-
ages are within the set limits
• Upper and lower limits separately adjustable
• Measures its own power supply
• Adjustable voltage on relative scale
• Adjustable delay function (0.1 to 30 s)
• Output: 5 A SPDT relay N.E.
• For mounting on DIN-rail in accordance with
DIN/EN 50 022
• 17.5 mm DIN-rail housing
• LED indication for relay, alarm and power supply ON

Product Description Ordering Key DPB 51 C M44


3-phase or 3-phase+neutral Supply ranges from 208 to Housing
line voltage monitoring relay 480 VAC covered by one Function
for phase sequence, phase multivoltage relay. Type
loss, over and under voltage 17.5 mm wide housing suit- Item number
(separately adjustable set able both for back and front Output
points) with built-in time panel mounting. Power supply
delay function.

Type Selection
Mounting Output Supply: 208 to 480 VAC

DIN-rail SPDT DPB 51 C M44

Input Specifications Output Specifications


Input Output SPDT relay
L1, L2, L3, N Terminals L1, L2, L3, N Rated insulation voltage 250 VAC
Measures its own supply Contact ratings (AgSnO2) µ
Note: Connect the neutral only Resistive loads AC 1 5 A @ 250 VAC
if it is intrinsically at the star DC 12 5 A @ 24 VDC
centre Small inductive loads AC 15 2.5 A @ 250 VAC
Measuring ranges DC 13 2.5 A @ 24 VDC
208 to 480 ∆ VAC 177 to 550 ∆ VAC Mechanical life ≥ 30 x 106 operations
Ranges Electrical life ≥ 105 operations
Upper level +2 to +22% (at 5 A, 250 V, cos ϕ = 1)
of the nominal voltage
Lower level -22 to -2% Operating frequency ≤ 7200 operations/h
of the nominal voltage Dielectric strength
Note: The input voltage Dielectric voltage 2 kVAC (rms)
must not exceed the maximum Rated impulse withstand volt. 4 kV (1.2/50 µs)
rated voltage or drop below
the minumum rated voltage
reported above.
Hysteresis
Set points from 2 to 4% 1%
Set points from 4 to 22% 2%

Specifications are subject to change without notice (03.09.14) 1


DPB51

Supply Specifications General Specifications (cont.)


Power supply Overvoltage cat. III Indication for
Rated operational voltage (IEC 60664, IEC 60038) Power supply ON LED, green
through terminals: L1, L2, L3, N Alarm ON LED, red (flashing 2 Hz
Delta Voltage: 208 to 480 VAC ± 15% during delay time)
45 to 65 Hz Output relay ON LED, yellow
Star Voltage: 120 to 277 VAC ± 15% Environment
45 to 65 Hz Degree of protection IP 20
Rated operational power Pollution degree 3
13 VA @ 400 ∆VAC, 50 Hz Operating temperature -20 to 60°C, R.H. < 95%
Supplied by L1 and L2 Storage temperature -30 to 80°C, R.H. < 95%
Housing
Dimensions 17.5 x 90 x 67.2 mm
General Specifications Material PA66 or Noryl
Weight Approx. 100 g
Power ON delay 1 s ± 0.5 s
Screw terminals
Reaction time Tightening torque
Incorrect phase sequence or L1, L2, L3, N Min. 0.5 Nm, Max. 1.1 Nm
total phase loss < 200 ms 15, 16, 18, Z1, Z2 Min. 0.4 Nm, Max. 0.8 Nm
(input signal variation from
Product standard EN 60255-1: 2010
-20% to +20% or from
+20% to -20% of set value) Approvals UL
Alarm ON delay < 200 ms (delay < 0.1 s) CE Marking L.V. Directive 2006/95/EC
Alarm OFF delay < 200 ms (delay < 0.1 s) EMC Directive 2004/108/EC
Accuracy (15 min warm-up time) Immunity According to EN 60255-26
Temperature drift ± 1000 ppm/°C According to EN 61000-6-2
Delay ON alarm ± 10% on set value ± 50 ms Emissions According to EN 60255-26
Repeatability ± 0.5% on full-scale According to EN 61000-6-3

Mode of Operation
Connected to the 3 phases If one or more phase-phase Only 200 ms delay occurs. Example 2
(and neutral) DPB51 oper- or phase-neutral voltages The failure is indicated by the (load monitoring)
ates when all 3 phases are exceeds the upper set level red LED flashing 5 Hz during The relay releases in case of
present at the same time, the or drops below the lower set the alarm condition. interruption of one or more
phase sequence is correct level, the red LED starts phases, when one or more
and the phase-phase (or flashing 2 Hz and the output Example 1 voltages drop below the low-
phase-neutral) voltage levels relay releases after the set (mains network monitoring) er set level or exceed the
are within set limits. time period. If the phase The relay monitors over and upper set level.
sequence is wrong or one under voltage, phase loss
phase is lost, the output and correct phase sequence.
relay releases immediately.

Function/Range/Level and Time Delay Setting


Selection of monitored Centre bottom knob
voltage: (DELAY):
Connecting the terminals Setting of delay on alarm Nominal Ph-Ph voltage Nominal Ph-N voltage
Z1 and Z2: time on absolute scale (0.1 (delta connections) (star connections)
No connection: phase-phase. to 30 s). 480 VAC 277 VAC
Connected: phase-neutral. Lower knob (see on the
415 VAC 240 VAC
right):
400 VAC 230 VAC
Selection of range, level Setting of nominal delta
and time delay: voltage. 380 VAC 220 VAC
Upper knob ( ): 240 VAC 139 VAC
Setting of lower level on 220 VAC 127 VAC
relative scale. 208 VAC 120 VAC
Centre top knob ( ):
Setting of upper level on
relative scale.

2 Specifications are subject to change without notice (03.09.14)


DPB51

Operation Diagrams

Wiring Diagram
Example 1 Example 2

Dimensions
45

90

43,8 5
17,5

67,2

Specifications are subject to change without notice (03.09.14) 3