Space Input Data: Fac-V1-01 Bedroom
Space Input Data: Fac-V1-01 Bedroom
FAC-V1-01 BEDROOM
1. General Details:
Floor Area ......................................................... 36.0 m²
Avg. Ceiling Height ............................................. 3.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ......... HOTEL: Bedroom/living room
OA Requirement 1 .............................................. 2.5 L/s/person
OA Requirement 2 ............................................ 0.30 L/(s·m²)
Space Usage Defaults ....... ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ......................................................... 2.0 People
Wattage .......................................................... 13.45 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.50 Sensible ........................................................... 67.4 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 35.2 W/person
Schedule ............................................... Occupants
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 18.4 1 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 36.0 0 0
5. Infiltration:
Design Cooling ................................................. 0.33 ACH
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 9.3 m²
U-Value .......................................................... 2.400 W/(m²·K)
Uncondit. Space Max Temp .............................. 23.9 °C
Ambient at Space Max Temp ............................ 35.0 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................. 12.8 °C
FAC-V1-02 BEDROOM
1. General Details:
Floor Area ......................................................... 26.3 m²
Avg. Ceiling Height ............................................. 3.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ......... HOTEL: Bedroom/living room
OA Requirement 1 .............................................. 2.5 L/s/person
OA Requirement 2 ............................................ 0.30 L/(s·m²)
Space Usage Defaults ....... ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ......................................................... 2.0 People
Wattage .......................................................... 13.45 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.50 Sensible ........................................................... 67.4 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 35.2 W/person
Schedule ............................................... Occupants
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 17.6 1 0 0
E 17.0 1 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 26.3 0 0
5. Infiltration:
Design Cooling ................................................. 0.33 ACH
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 9.3 m²
U-Value .......................................................... 2.400 W/(m²·K)
Uncondit. Space Max Temp .............................. 23.9 °C
Ambient at Space Max Temp ............................ 35.0 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................. 12.8 °C
FAC-V1-03 M.BEDROOM
1. General Details:
Floor Area ......................................................... 50.6 m²
Avg. Ceiling Height ............................................. 3.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ......... HOTEL: Bedroom/living room
OA Requirement 1 .............................................. 2.5 L/s/person
OA Requirement 2 ............................................ 0.30 L/(s·m²)
Space Usage Defaults ....... ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ......................................................... 4.0 People
Wattage .......................................................... 13.45 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.50 Sensible ........................................................... 67.4 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 35.2 W/person
Schedule ............................................... Occupants
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 47.8 1 1 0
N 14.8 1 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 50.6 0 0
5. Infiltration:
Design Cooling ................................................. 0.33 ACH
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: Ambient at Space Min Temp ............................ 12.8 °C
Partition Type ................................... Wall Partition
Area .................................................................. 14.8 m²
U-Value .......................................................... 2.400 W/(m²·K)
Uncondit. Space Max Temp .............................. 23.9 °C
Ambient at Space Max Temp ............................ 35.0 °C
Uncondit. Space Min Temp ............................... 23.9 °C
FAC-V1-04 BEDROOM
1. General Details:
Floor Area ......................................................... 31.6 m²
Avg. Ceiling Height ............................................. 3.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ......... HOTEL: Bedroom/living room
OA Requirement 1 .............................................. 2.5 L/s/person
OA Requirement 2 ............................................ 0.30 L/(s·m²)
Space Usage Defaults ....... ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ......................................................... 2.0 People
Wattage .......................................................... 13.45 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.50 Sensible ........................................................... 67.4 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 35.2 W/person
Schedule ............................................... Occupants
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 18.0 1 0 0
E 7.1 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 39.2 0 0
5. Infiltration:
Design Cooling ................................................. 0.33 ACH
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
(No partition data).
GAC-V1-01 KITCHEN
1. General Details:
Floor Area ......................................................... 22.8 m²
Avg. Ceiling Height ............................................. 3.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage FOOD SERVICE: Cafeteria/fast food
OA Requirement 1 .............................................. 3.8 L/s/person
OA Requirement 2 ............................................ 0.90 L/(s·m²)
Space Usage Defaults ....... ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ......................................................... 4.0 People
Wattage .......................................................... 13.45 W/m² Activity Level .................................... Medium Work
Ballast Multiplier ............................................... 1.50 Sensible ........................................................... 86.5 W/person
Schedule ................................................ LIGHTING Latent ............................................................. 133.3 W/person
Schedule ............................................... Occupants
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 14.8 0 0 0
E 14.8 1 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ................................................. 0.50 ACH
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 22.8 m²
Total Floor U-Value ......................................... 3.400 W/(m²·K)
Unconditioned Space Max Temp. ..................... 23.9 °C
Ambient at Space Max Temp. ........................... 46.0 °C
Unconditioned Space Min Temp. ...................... 23.9 °C
Ambient at Space Min Temp. ............................ 12.8 °C
7. Partitions:
(No partition data).
1. General Details:
Floor Area ......................................................... 10.0 m²
Avg. Ceiling Height ............................................. 3.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ......... HOTEL: Bedroom/living room
OA Requirement 1 .............................................. 2.5 L/s/person
OA Requirement 2 ............................................ 0.30 L/(s·m²)
Space Usage Defaults ....... ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ......................................................... 2.0 People
Wattage .......................................................... 13.45 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.50 Sensible ........................................................... 67.4 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 35.2 W/person
Schedule ............................................... Occupants
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 9.3 1 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ................................................. 0.33 ACH
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ...................................... Slab Floor On Grade
Floor Area ......................................................... 10.0 m²
Total Floor U-Value ......................................... 3.400 W/(m²·K)
Exposed Perimeter ............................................. 8.0 m
Edge Insulation R-Value ................................... 1.23 (m²·K)/W
7. Partitions:
(No partition data).
GAC-V1-03 BEDROOM
1. General Details:
Floor Area ......................................................... 20.5 m²
Avg. Ceiling Height ............................................. 3.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ......... HOTEL: Bedroom/living room
OA Requirement 1 .............................................. 2.5 L/s/person
OA Requirement 2 ............................................ 0.30 L/(s·m²)
Space Usage Defaults ....... ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ......................................................... 2.0 People
Wattage .......................................................... 13.45 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.50 Sensible ........................................................... 67.4 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 35.2 W/person
Schedule ............................................... Occupants
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 14.8 1 0 0
N 14.8 1 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ................................................. 0.33 ACH
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ...................................... Slab Floor On Grade
Floor Area ......................................................... 20.5 m²
Total Floor U-Value ......................................... 3.400 W/(m²·K)
Exposed Perimeter ........................................... 16.0 m
Edge Insulation R-Value ................................... 1.23 (m²·K)/W
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 14.8 m²
U-Value .......................................................... 2.400 W/(m²·K)
Uncondit. Space Max Temp .............................. 23.9 °C
Ambient at Space Max Temp ............................ 35.0 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................. 12.8 °C
GAC-V1-04 MAJLIS
1. General Details:
Floor Area ......................................................... 31.6 m²
Avg. Ceiling Height ............................................. 3.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ......... HOTEL: Bedroom/living room
OA Requirement 1 .............................................. 2.5 L/s/person
OA Requirement 2 ............................................ 0.30 L/(s·m²)
Space Usage Defaults ....... ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ....................................................... 10.0 People
Wattage .......................................................... 13.45 W/m² Activity Level ................................ Sedentary Work
Ballast Multiplier ............................................... 1.50 Sensible ........................................................... 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ............................................... Occupants
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 18.0 1 0 0
E 7.1 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ................................................. 0.33 ACH
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ...................................... Slab Floor On Grade
Floor Area ......................................................... 31.6 m²
Total Floor U-Value ......................................... 3.400 W/(m²·K)
Exposed Perimeter ........................................... 10.0 m
Edge Insulation R-Value ................................... 1.23 (m²·K)/W
7. Partitions:
(No partition data).
GAC-V2-01 KITCHEN
1. General Details:
Floor Area ......................................................... 22.8 m²
Avg. Ceiling Height ............................................. 3.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage FOOD SERVICE: Cafeteria/fast food
OA Requirement 1 .............................................. 3.8 L/s/person
OA Requirement 2 ............................................ 0.90 L/(s·m²)
Space Usage Defaults ....... ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ......................................................... 4.0 People
Wattage .......................................................... 13.45 W/m² Activity Level .................................... Medium Work
Ballast Multiplier ............................................... 1.50 Sensible ........................................................... 86.5 W/person
Schedule ................................................ LIGHTING Latent ............................................................. 133.3 W/person
Schedule ............................................... Occupants
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 14.8 0 0 0
E 14.8 1 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ................................................. 0.50 ACH
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 22.8 m²
Total Floor U-Value ......................................... 3.400 W/(m²·K)
Unconditioned Space Max Temp. ..................... 23.9 °C
Ambient at Space Max Temp. ........................... 46.0 °C
Unconditioned Space Min Temp. ...................... 23.9 °C
Ambient at Space Min Temp. ............................ 12.8 °C
7. Partitions:
(No partition data).
GAC-V2-02 BEDROOM
1. General Details:
Floor Area ......................................................... 20.5 m²
Avg. Ceiling Height ............................................. 3.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ......... HOTEL: Bedroom/living room
OA Requirement 1 .............................................. 2.5 L/s/person
OA Requirement 2 ............................................ 0.30 L/(s·m²)
Space Usage Defaults ....... ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ......................................................... 2.0 People
Wattage .......................................................... 13.45 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.50 Sensible ........................................................... 67.4 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 35.2 W/person
Schedule ............................................... Occupants
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 14.8 1 0 0
N 14.8 1 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ................................................. 0.33 ACH
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ...................................... Slab Floor On Grade
Floor Area ......................................................... 20.5 m²
Total Floor U-Value ......................................... 3.400 W/(m²·K)
Exposed Perimeter ........................................... 16.0 m
Edge Insulation R-Value ................................... 1.23 (m²·K)/W
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 14.8 m²
U-Value .......................................................... 2.400 W/(m²·K)
Uncondit. Space Max Temp .............................. 23.9 °C
Ambient at Space Max Temp ............................ 35.0 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................. 12.8 °C
GAC-V2-03 MAJLIS
1. General Details:
Floor Area ......................................................... 39.2 m²
Avg. Ceiling Height ............................................. 3.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ......... HOTEL: Bedroom/living room
OA Requirement 1 .............................................. 2.5 L/s/person
OA Requirement 2 ............................................ 0.30 L/(s·m²)
Space Usage Defaults ....... ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ....................................................... 10.0 People
Wattage .......................................................... 13.45 W/m² Activity Level ................................ Sedentary Work
Ballast Multiplier ............................................... 1.50 Sensible ........................................................... 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ............................................... Occupants
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 18.0 1 0 0
E 7.1 0 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ................................................. 0.33 ACH
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ...................................... Slab Floor On Grade
Floor Area ......................................................... 39.2 m²
Total Floor U-Value ......................................... 3.400 W/(m²·K)
Exposed Perimeter ........................................... 10.0 m
Edge Insulation R-Value ................................... 1.23 (m²·K)/W
7. Partitions:
(No partition data).
PU-V1-01 LIVING/DINING
1. General Details:
Floor Area ......................................................... 99.3 m²
Avg. Ceiling Height ............................................. 3.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ......... HOTEL: Bedroom/living room
OA Requirement 1 .............................................. 2.5 L/s/person
OA Requirement 2 ............................................ 0.30 L/(s·m²)
Space Usage Defaults ....... ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ....................................................... 20.0 People
Wattage .......................................................... 13.45 W/m² Activity Level ................................ Sedentary Work
Ballast Multiplier ............................................... 1.50 Sensible ........................................................... 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ............................................... Occupants
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 9.6 1 0 0
S 28.3 1 0 0
E 9.0 0 0 0
W 40.0 2 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ................................................. 0.33 ACH
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ...................................... Slab Floor On Grade
Floor Area ......................................................... 99.3 m²
Total Floor U-Value ......................................... 3.400 W/(m²·K)
Exposed Perimeter ........................................... 47.0 m
Edge Insulation R-Value ................................... 1.23 (m²·K)/W
7. Partitions:
(No partition data).
1. General Details:
Floor Area ......................................................... 93.7 m²
Avg. Ceiling Height ............................................. 3.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ......... HOTEL: Bedroom/living room
OA Requirement 1 .............................................. 2.5 L/s/person
OA Requirement 2 ............................................ 0.30 L/(s·m²)
Space Usage Defaults ....... ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ....................................................... 20.0 People
Wattage .......................................................... 13.45 W/m² Activity Level ................................ Sedentary Work
Ballast Multiplier ............................................... 1.50 Sensible ........................................................... 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ............................................... Occupants
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 9.6 1 0 0
E 9.2 1 0 0
W 42.3 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 93.7 0 0
5. Infiltration:
Design Cooling ................................................. 0.33 ACH
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ...................................... Slab Floor On Grade
Floor Area ......................................................... 93.7 m²
Total Floor U-Value ......................................... 3.400 W/(m²·K)
Exposed Perimeter ........................................... 33.2 m
Edge Insulation R-Value ................................... 1.23 (m²·K)/W
7. Partitions:
(No partition data).
PU-V2-01 LIVING/DINING
1. General Details:
Floor Area ....................................................... 107.8 m²
Avg. Ceiling Height ............................................. 3.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ......... HOTEL: Bedroom/living room
OA Requirement 1 .............................................. 2.5 L/s/person
OA Requirement 2 ............................................ 0.30 L/(s·m²)
Space Usage Defaults ....... ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ....................................................... 20.0 People
Wattage .......................................................... 13.45 W/m² Activity Level ................................ Sedentary Work
Ballast Multiplier ............................................... 1.50 Sensible ........................................................... 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ............................................... Occupants
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 9.6 0 0 0
S 25.0 1 0 0
E 24.6 1 0 0
W 30.6 2 0 0
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ................................................. 0.33 ACH
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ...................................... Slab Floor On Grade
Floor Area ....................................................... 107.8 m²
Total Floor U-Value ......................................... 3.400 W/(m²·K)
Exposed Perimeter ........................................... 48.6 m
Edge Insulation R-Value ................................... 1.23 (m²·K)/W
7. Partitions:
(No partition data).
1. General Details:
Floor Area ....................................................... 119.0 m²
Avg. Ceiling Height ............................................. 3.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ......... HOTEL: Bedroom/living room
OA Requirement 1 .............................................. 2.5 L/s/person
OA Requirement 2 ............................................ 0.30 L/(s·m²)
Space Usage Defaults ....... ASHRAE Std 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ....................................................... 20.0 People
Wattage .......................................................... 13.45 W/m² Activity Level ................................ Sedentary Work
Ballast Multiplier ............................................... 1.50 Sensible ........................................................... 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ............................................... Occupants
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 42.9 1 1 0
W 22.9 1 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 119.0 0 0
5. Infiltration:
Design Cooling ................................................. 0.33 ACH
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type ...................................... Slab Floor On Grade
Floor Area ....................................................... 119.0 m²
Total Floor U-Value ......................................... 3.400 W/(m²·K)
Exposed Perimeter ........................................... 35.6 m
Edge Insulation R-Value ................................... 1.23 (m²·K)/W
7. Partitions:
(No partition data).