Fault Calculation Examples
Fault Calculation Examples
Draw the per unit zero, positive and negative networks on 100MVA, 13.8kV based in the zone of the
generator.
--------------------eqn 2
Example 2
Calculate the sub transient fault current in per unit and in kA for a bolted single line to ground short
circuit from phase a to ground at bus 2. Also calculate the per unit line to ground voltages at faulted bus
2.
Therefore
Calculate the subs transient fault current in per unit and in kA for a bolted line to line fault from phase b
to c at bus 2.
To calculate subtrasient current using this eqn
Calculate :
(c) contributions to the fault current from the motor and from the transmission line, for a bolted double
line to ground fault from phase b to c to ground at bus 2.
In this case zf =0
(a)
(b)
(c)
From Zero sequence network, the contribution to the zero-sequence fault current from the line is zero
due to transformer connection.
From possitve network, the positive terminals on the internal machine voltages can be connected, since
E”g= E”m.
Transforming to the phase domain with base current 0.41837kA for the line and 4.1837kA for the motor
Example 2
\
Bus voltages during fault
Bus 1
Bus 2
Bus 3
Bus 4
Bus 5
The bus voltage of bus 5 under faulted condition is zero because the fault impedance is zero.
QUIZ
The inductor connected to Generator 3 neutral has a reactance of 0.05 per unit using generator 3 rating
as a base. Draw the zero, positive, and negative sequence reactance diagram using a 100MVA, 765 kV
base in the zone of the line 1-2.
Determine the Thevenin equivalent of each sequence network as viewed from the fault at bus 1. Pre-
fault voltage is 1.0 per unit.
Example using Bus Impedance Matrices
Y12 =0 , Y21=0
Z10 =j0.15 -----Y10 = -j6.6667, Z12= j0.305----Y12 =-j3.2787, Z20=j0.20 ------Y20 =1/j0.20 =-j5
Line to ground voltages at bus 1 during the fault at bus 1 with k=1, n=1
The line to ground voltages at BUS 1 during the fault at bus 1
Next, the sequence components of the line to ground voltages at BUS 2 during the fault at BUS 1: k=2,
n=1