100% found this document useful (2 votes)
2K views

Manual PRO CEA6 - IN

The document describes a CEA6 controller unit that controls and monitors engine operation. It consists of a visualization module for user interaction and a measurements module that monitors signals, sensors and actuators. The measurements module measures electrical parameters, reads engine sensors, controls engine functions, and has outputs to activate contactors. It connects to the visualization module and can connect additional modules via CAN bus communication.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
2K views

Manual PRO CEA6 - IN

The document describes a CEA6 controller unit that controls and monitors engine operation. It consists of a visualization module for user interaction and a measurements module that monitors signals, sensors and actuators. The measurements module measures electrical parameters, reads engine sensors, controls engine functions, and has outputs to activate contactors. It connects to the visualization module and can connect additional modules via CAN bus communication.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 76

1. INTRODUCTION.

The CEA6 controller unit is a device able to control the operation, monitoring and protection of a
generating set. The controller unit consists of 2 different modules:

- Visualization module. The visualization module provides information about the status of the device
and, at the same time, allows the user to interact with it. With this visualization module the user is
able to control, program and configure the functions of the unit. This visualization module allows the
checking of the last ten failures registered in the control unit (Fault history).

- Measurements module. The measurements module controls and monitors the control board. It is
located in the rear part of the panel, in order to reduce the wiring and to avoid electromagnetic
disturbances. Every signal, sensor and actuator is connected to this module.(see Annex III figures)

NOTE: As an option, a programming timer module can be added to the measures module. It
can be programmed to execute automatic starting, stopping and programmed maintenance.
Likewise the programming clock module allows to extend the historical failures records
capacity.

The measurements module provides the following readings of the electric mains supply.

o Phase to neutral voltage.


o Phase to phase voltage.
o Phase amperage.
o Frequency.
o Real, apparent and reactive powers.
o Power factor and cos phî.
o Instant power (KwH) and historical power (day, month, year).

The measurements module provides the following engine features information:

o Engine alarm inputs:


ƒ Fuel reserve.
ƒ Oil pressure.
ƒ Coolant temperature.
ƒ Coolant level.
ƒ Emergency stop. (stop button).

o Analogic engine inputs


ƒ Fuel level.
ƒ Oil Pressure.
ƒ Coolant Temperature.
ƒ Configurable input (i.e. Oil temperature).
ƒ Battery charge alternator voltage.

o Configurable inputs; the measurements device has 5 inputs that can be programmed
to carry on the following functions:
ƒ Mains contactor confirmation.
ƒ Genset contactor confirmation.
ƒ Rate change notice.
ƒ Rate change.
ƒ Start disabling.
ƒ External start.
ƒ Test.
ƒ Manual override.
ƒ 3 programmable alarms.

o Engine statistics:
ƒ Number of working hours.
ƒ Number of starts.
The measurements module controls the following functions of the engine:
ƒ Pre-heating or Glow Plug.
ƒ Stop.
ƒ Start.
ƒ Coolant heater.
ƒ Fuel Transfer pump.
ƒ Alternator excitation.

The measurements module has outputs which allow monitoring of the operative conditions of the
controller:
o Engine running (on).
o Control board alarm.
o 3 programmable outputs which monitor the control board alarm conditions or the inputs
about the engine data.

The measurement module controls the outputs to relays in order to activate mains and generating set
contactors.

The connection between the measurements and visualization modules is made by the CAN bus
communication, which allows the interconnection of additional modules, allowing the expansion of the
CEA6 device.

With the bus CAN these additional modules can be added:


- Programming timer device.
- Telesignal device
- J1939 device
- Remote control device
2. VISUALIZATION MODULE FRONT VIEW
The visualization module has a backlit display and different LEDs to indicate the CEA6 device status.
Different push buttons allow the user to command and program the CEA6

1. Backlit display (4 lines of 20 digits)

2. Control board push buttons

a) Operating mode buttons.

b) Command buttons.

c) Display buttons.

d) Contactors buttons.

3. Data LEDs

a) ENGINE status LEDs

b) ALARMS LEDs

c) CONTACTORS status LEDs

d) ELECTRIC POWER status LEDs.


2.2. CONTROL BOARD PUSH BUTTONS.

2.2.a. Operating mode buttons

Automatic mode. The CEA6 device monitors the


status of the generating set and controls its working
process and the programmable inputs.

Test mode. The device starts the engine at the Led on :


same time that monitors and controls its working Automatic mode running.
process.
Led flashing: Automatic mode
blocked (automatic and manual
Block mode: The device controls the installation mode).
status, but disables every possibility of engine
starting. Led off: No active mode

Manual mode. The user controls the device.

2.2.b. Command buttons

Start engine push button (manual mode only).


It administers the start with a single press.
Led ON: Engine starting
Stop engine push button (manual mode only).
Press once, the engine stops and a cooling phase begins.
Press twice, the engine stops immediately.
Led ON: The engine is in stopping phase (with or without cooling-down)
Reset push button.
Allows the user to acknowledge and clear the alarm condition
Led flashing: There are alarms to check up.
Led on: Active alarms.
Transfer fuel pump push buttons.
In manual mode, this button activates the transfer pump if the fuel level is under the
programmed levels.
Led on: Fuel transfer pump working.

2.2.c. Display buttons

Confirmation button (V): Allows access to menu , validates and store the
entered data.

Cancellation button (X): Go back in the menu and cancels the entered data.

Up button (+): Moves along the selection displays and maintenance menus,
also increases the programmed values.

Down button (-): Moves back in the selection display and maintenance
menus, it also reduces the programmed values.
2.2.d. Contactors buttons.

Mains contactor
Switches to mains contactor (manual mode only).

Genset contactor
Switches to genset contactor (manual mode only).

2.3. DATA LEDS


2.3.a. ENGINE status LEDs.

On: Engine running detected.


Engine started
Off: Engine stopped.

On: Pre-heating function activated.


Pre-heating
Off: Pre-heating function not activated.
ENGINE

On: Engine starting activated.


Engine starting
Off: Engine starting not activated.

On: The voltage supplied by the battery


charge alternator is detected when the
engine is running.
Battery charge alternator status
Off: Engine stopped or started without
voltage signals in the battery charge
alternator.
2.3.b. ALARMS LEDS
Fuel storage

Battery levels

High temperature
ALARMS

Starting failure On: alarm caused by analog sensors.


Flashing: alarm caused by digital inputs.
Off: No alarms.
Overspeed

Low oil pressure

Aux1
(Free to programme)
Aux2
(Free to programme)

NOTE: See alarms section for more details.

2.3.c. CONTACTORS status LEDs

Mains contactor status On: contactor activated.


Flashing: alarm, confirming the contactor is
activated.
Generating set contactor status Off: Contactor deactivated.

2.3.d. ELECTRIC POWER status LEDS

Mains power status


ELECTRIC

On: Activated without errors.


POWER

Engine status Flashing: status with errors.

Off: Not activated.


Genset power status

2.4. PASSWORD.
The CEA6 device has 3 passwords levels of four digits to avoid non authorised access. Those different
access levels are:

• User access (password stored: 1111). The user access level allows the entrance in the CEA6
main menu.
• Maintenance access: (password stored: 1911). The maintenance access level allows the use
of the parameter programming option in the main menu.

The passwords in the CEA6 can be changed by the user in the main menu. The user can change the
passwords in the user access level, as well as in lower access levels.

NOTE: To enter new passwords, see annex II. Enter passwords.


3. OPERATIONAL MODES.
3.1. Manual Mode.
In the manual mode, the user operates the controller using the front panel of the visualization module.
The engine is manually started and stopped using the START and STOP buttons.

Pushing the START button activates the engine starting process (without deactivating the mains
contactor). Pushing the STOP button once stops the engine, with a cooling down cycle. Pushing the
STOP button twice stops the engine immediately, without cooling down phase.

With cooling.
Without cooling

NOTE: In manual mode, the safety devices of the controller remain activated, and if an anomaly is
detected, an alarm status is triggered.
In manual mode, the device ignores all external request previously programmed (i.e., Timer, ATS signal,
etc...).

Likewise, the activation of the mains and genset contactors is carried on by pushing RED/MAINS and
GRUPO/GEN buttons

The activation of the genset contactor is possible only if the engine is running and produces a stabilized
electric signal.

The activation of the genset contactor deactivates the mains contactor and vice versa; there is a waiting
time of one second (not programmable) between the contactors switching.

3.2. Automatic Mode.


In automatic mode, the CEA6 constantly controls the genset operation. In some situations,
that can be programmed to supply power, the controller starts the generator set activating the
genset contactor.

Programmable operational modes to start the genset:

- Maximum mains voltage alarm. (Alarms table parameter 88).


- Minimum mains voltage alarm. (Alarms table parameter 90).
- Maximum mains power supply frequency alarm. (Alarms table parameter 92).
- Minimum mains power supply frequency alarm. (Alarms table parameter 94).
- Mains sequence alarm (Alarms table parameter 96).
- Mains power failure alarm. (Alarms table parameter 98).
- Mains contactor failure alarm. (Alarms table parameter 100).
- External start (Programming table parameter 10).
- Start controlled by timer (if it is included timer programming)
- Forced start (Programming table parameter 12 and Regulations table parameter 25).

As programmable starting conditions of the genset without the activation of contactors, could be
considered:
- Rate change notice (Programming table parameter 7).
- Engine test

3.3. Test Mode.


Working in Test mode, the device commands the starting of the genset following the
procedure explained in the Engine starting excepting the mains contactor activation
process. In Test mode, the controller unit does not activate the genset contactor, as long as
the genset is not started under mains alarms or mains contactor failure alarms.

In test mode, the device does not control the functions related to the programmable inputs,
except the ones associated to the alarms.

3.4. Block Mode.


The device blocks the generating set disabling every possibility of starting under any
condition:

3.5. Interruption of modes.


When the CEA6 is in manual mode, the automatic operational mode can be blocked by pressing the
AUTO button for 5 seconds. This blocking function does not allow the change of modes and the button of
the mode running at that moment will flash. To deactivate the automatic interruption mode and allow the
change of operational modes, the button associated with the active mode has to be pressed for 5 seconds.

5” LOCK 5” UNLOCK

5”
5” LOCK 5” UNLOCK
4. WORKING MODE.
4.1. Starting the engine.
The engine works in the following way, once the controller detects an activation condition:

- Delay in the starting: Once an activation condition is detected and before going on with the
engine starting process (automatic mode), a delay in the engine starting can be programmed
(Times table parameter 3)

- Engine pre-heating phase. The control board activates the pre-heating output for a programmed
time. (Times table parameter 4)

- Engine energizing (run signal): The engine run signal is made by means of the PC (B+) output
from the measurements module. The output allows a no-excitation Stop (energise to-run) or an
excitation stop (energise to-stop) (Times table parameter 12-This output is configurable.
(Regulations table parameter 18).

- Engine starting. For a programmed period of time (Times table parameter 5), the starting
output of the measurements module is activated, waiting to detect, at least, one of the
programmed starting conditions. The possible engine starting conditions could be:

o Generator voltage. (Regulations table parameter 19). The engine would be


considered started (running) when its voltage exceeds a given value.
(Thresholds table parameter 20).

o Alternator voltage: (Regulations table parameter 20). The engine would be


considered started (running) when the battery charge alternator voltage exceeds a given
value. (Thresholds table parameter 21).

o Pick up frequency (Regulations table parameter 21). The engine would be


considered started (running) when the pick up frequency (Thresholds table parameter
22) exceeds a given value. To activate the pick up calculation through the engine ring
gear, the number of teeth of the gear must be introduced (Thresholds table parameter
24); In case the number of teeth is “0”, the frequency of the pick up will be calculated
through the generator frequency as per the equivalence-ratio 50Hz/1500 rpm or
50Hz/3000 rpm and 60 Hz/1800 rpm. (Regulations table parameter 26).

o Low oil pressure. (Regulations table parameter 22). It is not advisable to use the low
oil pressure signal as a way to detect if the engine is working, but it is useful as a
protection, in order to avoid engaging the starter while the engine is running. Exception
for this "Engine Start Detection" option is SCANIA engines and also the sensors which
have self - electrical supply.

If in the programmed time the starting of the engine is not detected, the control board waits for a
short time (Times table parameter 2) before attempting a new start. The Start failure alarm will
be raised after a specified number of attempts without detecting any starting condition (Times
table parameter 1).
In the starting cycle, the excitation of the battery charge alternator is activated through the D+
output temporarily (Times table parameter 8). Once the excitation of the alternator is finished,
the measurements module checks if the battery charge alternator is working properly. The battery
charge alternator failure alarm is raised in case of an output failure. (Alarms table parameter
10).

- Engine stabilization: Once any of the starting conditions is detected, the controller waits for a
programmed stabilization-time of the generator output, before monitoring output parameters.
- Nominal condition. Once the stabilization of the engine is reached, the next step is the checking
of the signal produced by the generator. In this way, the quality of the signal produced by the
generator set is monitored (voltage levels, frequency…).

- Genset contactor activation. If it is included in the valid signal parameters, the mains contactor
is deactivated. Depending on the Genset Contactor Confirmation programming mode (
Programming table parameter 6), the control board will wait the confirmation of the contactor
closing for a maximum time (Times table parameter 13); If after such time the confirmation of the
contactor closing is not detected, the genset contactor alarm triggers and a stop with cooling-cycle
follows. The activation of the genset contactor is disabled by a low engine temperature
(Thresholds table parameter 29).

Start operating process. Practical example.


NOTE: Before initiating the stop cycle, it is advisable that the main genset circuit breaker be switched
OFF.

OPERATING: When the START button is pressed, the starting


cycle will be initiated, and the START LED will be on. At the
same time, if the engine has glow plugs, the PR output will be
activated, and the appropriate LED will be on ( ),during
the programmed period of time (11'' by default).(1)

After this period of time, the PR outlet becomes inactive, the


LED will turn off ( ) and, soon afterwards the PC positive
contact output becomes active and 0,5" later the ARR crank
output also becomes active ( ). This output remains
activated until any of the engine started conditions is detected.
(2)

Once the engine is detected as started the LED ( ) turns


on. Then the starting cycle is finished and the START button
switches off. (3)

The LED controlling the voltage of the battery charge alternator


lights ( ) when the value of the voltage given by the
alternator is higher than the voltage threshold previously
programmed. (4)
If during the starting cycle, the engine is not detected as started,
after 5”, the ARR output becomes inactive and its related LED
switch off ( ). Afterwards and automatically the controller will
begin a new starting attempt, repeating a new cycle without any
need to push START (4 cycles by default). Having all the
attempts exhausted without any effective start, the controller will
trigger the START FAILURE alarm. (5)

To stop the starting cycle, just press the STOP button.

STAR FAILURE

NOTE: readings about the engine condition are shown on the display, and details about the start
operating process can be visualized. The sequence being as follows:
Genset: Stop
Genset : Starting
Genset : Started
Genset : Stabilized
Genset : Loading
NOTE.: The starting process in an automatic system by means of timer, ATS signal, etc... works in the
same way as a starting cycle in manual mode.

4.2. Engine stop.


The stop engine process in the automatic-mode is done according to the following process:

- Mains contactor activation. Once the generator stopping condition is detected there is a
verification time (Times table parameter 10) that checks if the quality of the mains signal is
considered as correct. Then the control board deactivates the genset contactor. Depending on
the configuration of the Mains Contactor Confirmation mode (Times table parameter 5), the
device waits fot the contactor closing confirmation during a maximum time(Times table
parameter 13); If after such time there is no confirmation of the mains contactor closing, the
mains contactor failure alarm will trigger and the engine will start again.

- Engine cooling down: Once all loads are disconnected, the engine will continue to run for
some time during the cooling time (Times table parameter 11). Under particular situations the
alarms of the controller may be programmed (Alarms table parameters 3, 6, 9...) to stop
immediately without the cooling down of the engine.

- Engine stop. After the cooling down of the engine, the PC output of the measurements module
is switched off or on, according to the programmed stop configuration (Regulations table
parameter 18). As a condition of the engine stop, it can be selected:

o Generator voltage. (Regulations table parameter 19). The engine would be


considered stopped when the generator voltage is lower than its starting threshold
(Thresholds table parameter 20).

o Alternator voltage: (Regulations table parameter 20). The engine would be


considered stopped when the battery charge alternator voltage is lower than the starting
threshold (Thresholds table parameter 21).
o Pick up frequency. (Regulations table parameter 21). The engine would be
considered stopped when the pick up frequency is lower than its starting threshold
(Thresholds table parameter 22). To activate the pick up calculation through the
engine ring gear, the number of teeth of the gear must be introduced (Thresholds table
parameter 24); In case the programmed number of teeth is “0”, the frequency of the pick
up will be calculated through the generator frequency as per the equivalence-ratio
50Hz/1500 rpm, 50Hz/3000 rpm or 60Hz/1800 rpm. (Regulations table parameter 26).

o Low Oil Pressure. (Regulations table parameter 22). The condition of Low Oil
Pressure considers the engine stopped when it detects that the sensor is closed.
Exception for this "Engine Start Detection" option is SCANIA engines and also the
sensors which have self - electrical supply.

All the programmed stopping conditions must be present for an interval of time (Alarms table parameter
71) to consider the engine as stopped. If after ten seconds it has not been detected any of the engine stop
conditions, the Stop Failure alarm will be activated.

Stop operating process. Practical example

NOTE: Before initiating the stop cycle, it is advisable that the main genset circuit breaker be switched OFF.

The genset can be stopped in several ways:


1. Manual: Press STOP button once. The genset stops with cooling down.
2. Manual: Press STOP button once again. The genset stops without cooling down.
3. Place the activation key of the board in “O” position. The genset stops without cooling down.
4. Automatic: The genset stops with cooling down cycle after the deactivation of the command
which automatically started the genset.

Sequence: Pressing the STOP button once, the stop cycle will
start with the engine cooling process. The STOP button will
light . (1)

Once the cooling time is over the PC output is activated or


deactivated, according the type of engine, to carry on with the
stopping cycle. Then the STOP button and the LED ( ) of
started engine switch off. (2)

If after a period of time an engine running condition of "started


engine" is detected, the control board will show in the display
the STOP FAILURE alarm and the LED of the STOP button STOP FAILURE

will light. (3)


The LED controlling the voltage of the battery charge alternator
( ) turns off when the value of the voltage given by the
alternator is lower than the voltage threshold previously
programmed (4).

NOTE: Readings about the engine condition are shown on the display, and details about the stop
operating process can be visualized. The sequence being as follows:
Genset : Stabilized
Genset : Cooling
Genset : Stopping
Genset : Stop

4.3. Transfer fuel pump. (BTC, BTNA)


The transfer fuel pump function process can be activated in the CEA6 device by linking its working service
to the BT relay from the measurements module. (Regulations table parameter 4). Once the transfer
pump option is activated, its operation modes are as follows (Regulations table parameter 1):

- Inhibited mode. No transfer fuel pump functions can be considered

- Manual mode: the transfer pump is operated by pressing the diesel Transference button,
provided that the fuel level is under the maximum threshold parameters (Thresholds table
parameter 19)

- Automatic mode: the transfer pump becomes operative according to the minimum activation
parameters (Thresholds table parameter 18) under which the relay BT is activated/energised
and according to the maximum deactivation parameters (Thresholds table parameter 19),
over which the relay BT is de-energised.

- Control board mode: the transfer pump operation is carried out as follows:
o When the controller is in automatic or test-mode, the transfer pump is operated
automatically.
o When the controller is manual-mode, the transfer pump operation is carried out in
manual mode.
o When the controller is in a blocked-mode, the transfer pump operation is inhibited.

For an accurate fuel level measurement (needed for the fuel pump and fuel level alarm functions) a
calibration of the tank level sender must be done, by having access to both the minimum and maximum
parameters of the level sender (Measurements table parameters 12 and 13). To adjust the minimum fuel
level of the tank it must be recorded the parameter 12 of the measurement table with the level sender in its
minimum position. To adjust the maximum fuel level of the tank, it must be recorded the parameter 13 of
the measurement table with the level sender in its maximum position.
4.4. Pre-Heating.
The engine pre-heating allows 2 activation modes:

- Assigning to the BT relay of the measurement module, the pre-heating working process (
Regulations table parameter 4).

- Assigning to any of the 4 programmable outputs of the measurement module the pre-heating
working process (Programming table parameters 1 to 4), provided the BT relay of the
measurement module is in charge of the fuel transfer pump functions. (Regulations table
parameter 4).

The following functions are executed by the engine pre-heating:


- Under an adjustable engine temperature threshold (Thresholds table parameter 29), the pre-
heating system is activated.
- Under an adjustable engine temperature threshold (Thresholds table parameter 28), the
activation of the genset contactor is disabled and the low engine temperature alarm rises
(Alarms table parameters 73 to 74).
- Over an adjustable engine temperature threshold (Thresholds table parameter 30), the pre-
heating system is deactivated.

4.5. Battery charger alternator.


E The battery charge alternator is connected to the CEA6 device by means of the digital output D+ and the
analog input DI from the measurement module.

The CEA6 can be configured to trigger an Alternator Voltage alarm (Alarms table parameter 10 to 12) if it
is detected a low voltage level provided by the battery charge alternator through the DI analog input from
the measurement module.

Two working modes of the battery charge alternator can be selected (Regulations table parameter 3)

4.6. Alternator mode.


The battery charge alternator of the CEA6, configured as alternator mode, energize the alternator, by
means of a triggering pulse of configurable duration (Times table parameter 8). This is done during the
engine starting process through the D+ output from the measurement module. When this pulse ends, the
control board test the voltage produced by the battery charge alternator.

The voltage produced by the battery charge alternator can be used as starting engine condition
(Regulations table parameter 20). For that purpose, the CEA6 expects to measure, through the DI
analog input, voltage values exceeding the alternator voltage detection threshold ( Thresholds table
parameter 21).

The CEA6 device can be configured to raise an Alternator Voltage alarm (Alarm table parameter 10 to
12) if it is detected a low voltage level provided by the battery charge alternator through the DI analog input
from the measurement module. (only if the alternator mode is configured).

4.7. Dynamo mode.


The battery charge alternator of the CEA6, configured as dynamo mode, excites the alternator with a
continuous triggering pulse by means of the D+ output from the measurement module, as long as the
engine stands in starting phase or already started.

The device, configured in dynamo mode, can not use the voltage measured through the analog input DI to
detect engine started condition.

4.8. “MAN” Inputs.


The start/stop key in “ON” position, supplies power to the CEA6 (measurements and visualization
module).
The MAN" entrance should be connected with positive of batteries (8-36V), to activate the electronic
device CEA6.
5. CEA6 inputs and outputs.
The digital inputs of the CEA6 device, with specific functions as well as the programmable ones, have
associated a stabilization time (Times table parameters 15 to 24) which requires the values of the inputs
to be stable for a period of time.
Likewise, all the inputs of the control board can be configured to be active or not active, with contact
closed to earth (Regulations table parameters 5 to 15).

The status of the inputs and outputs of the CEA6 can be visualized from the menu MAIN Æ1.
Inputs/Outputs. From this screen, the status of the digital inputs and outputs are displayed.

Input / Output index.


Input Orderly of the 13 to the 1

* I N P U T S / O U T P U T S *
3 2 1 0 9 8 7 6 5 4 3 2 1
I N : M S 3 2 1 P I X N A B R
O U T : C P R 4 B g r 3 2 + 1 M A

Output

The following characters show the detection of the active input:


IN 1. R: Fuel level (FR) (FL)
IN 2. B: Low temperature pressure
IN 3. A: High temperature
IN 4. N: Coolant level
IN 5. X: Programmable input 4. (default value, external start).
IN 6. I: Programmable input 5. (default value, start disabling).
IN 7. P: Emergency stop.
IN 8. 1: Programmable input 1.
IN 9. 2: Programmable input 2.
IN 10. 3: Programmable input 3.
IN 11. S: Stop button.
IN 12. M: Start key

The following characters show the detection of the active output:


OUT 1. A: Active alarm
OUT 2. M: Engine started
OUT 3. 1: Programmable output 1.
OUT 4. +: Battery charge alternator
OUT 5. 2: Programmable output 2.
OUT 6. 3: Programmable output 3.
OUT 7. r: Mains contactor
OUT 8. g: Generating set contactor
OUT 9. B: Fuel transfer/pre-heating
OUT 10. 4: Programmable output 4.
OUT 11. R: Pre-heating/excitation stop
OUT 12. P: De-excitation stop/excitation stop
OUT 13. C: Controller fitting.
Pressing UP/DOWN buttons, the user gain access to the analog inputs readings.

A N L O G I C S I N P U T S
F L 0 . 0 P A 0 . 0
E T 0 . 0 A A 0 . 0
D T 0 . 0 V V B 0 . 0 V

The value of the resistive analog inputs is found in Ohms and the value of the voltage analog inputs is
given in Volts. The inputs that can be seen are:
• FL/ NC: Fuel level
• OP/PA: Oil pressure
• ET/TM: Engine temperature
• AA: Analog Auxiliary
• DT/DI: Dynamo tension.
• BV/ VB: Battery voltage

5.1. Digital Inputs.

Presets inputs.
The measures module in the CEA6 has 5 digital inputs, whose working process is already pre-set.

Fixed inputs show the following situations:

High temperature (HTC).


Digital signal reporting to the controller that the thermostat of the engine has detected a failure and sets on
an alarm due to the engine high temperature ( Alarm table parameters 1 to 3).

Low oil pressure (LOP).


Digital signal reporting to the controller that the engine pressure switch has detected a failure and sets on
an alarm due to the low oil pressure ( Alarm table parameters 4 to 6).

Coolant level (CL).


Digital signal reporting to the controller that an alarm triggered due to low coolant level (Alarms table
parameters 16 to 18).

Emergency stop (EMS).


Digital signal reporting to the controller that an immediate stop without cooling must be done.

Fuel reserve (FR).


Digital signal reporting to the controller that an alarm has been generated due to a failure in the fuel
reserve. (Alarm table parameters 19 to 21).

Programmable inputs.
The measurement module of the CEA6 has 5 digital inputs whose working mode can be programmed.

The inputs of programmable functions can be configured to work in the following way:
Mains contactor confirmation (CKR).
The mains contactor confirmation configured input (Programming table parameter 5) is used to verify
the correct activation of the mains contactor.
After the activation of the mains contactor, a waiting time is produced (Times table parameter 13) to
check the activation of the contactor by means of the input programmed as mains contactor confirmation.
A mains contactor alarm triggers (Alarm table parameter 100) if, once the waiting time is over, there is no
confirmation of the mains contactor activation and the controller does not detect a mains failure alarm.
If the control board is working in automatic mode, a starting of the controller is produced with the activation
of the genset contactor in order to power the load.

Genset contactor confirmation (CKG).


The genset contactor confirmation configured input (Programming table parameter 6) is used to verify
the correct activation of the genset contactor.
After the activation of the genset contactor, a waiting time is produced (Times table parameter 13) to
check the activation of the contactor by means of the input programmed as genset contactor confirmation.
A genset contactor alarm triggers (Alarm table parameter 100), once the waiting time is over, if there is
no confirmation of the genset contactor activation.
If the control board is working in automatic mode, a stop with engine cooling is produced and also the
mains contactor is activated if this happens to be within the valid working parameters.

Rate notice signal (EJP1).


This function only works when the CEA6 functions in automatic mode.
The input configured as rate notice (Programming table parameter 7) starts the genset after activating
the relating input and once a programmed time is over.
(Times table parameter 9). The rate notification is considered finished when the EJP1 input is
deactivated and a stop with engine cooling is produced.

Rate change notice signal (EJP2).


This function only works when the CEA6 functions in automatic mode.
The input configured as rate change notice signal (Programming table parameter 8) activates the genset
contactor, provided no abnormal situation is detected in the genset.

Start disabling signal (IA).


This function only works when the CEA6 functions in automatic mode.
The input configured as start disabling signal (Programming table parameter 9) does not allow the
starting of the genset under any condition, excepting manual override starting (Programming table
parameter 12) configured as a high priority option. (Regulations table parameter 25).

External start signal (ES).


This function only works when the CEA6 functions in automatic mode
The input configured as external start (Programming table parameter 10) forces the starting of the
genset if it is working in automatic mode, provided that no of the following start disabling conditions are
present:
- The device does not control the start disabling input or it is not activated.
- The device status is not blocked by the programming timer.

Test signal (TEST).


This function only works when the CEA6 functions in automatic mode.
The input configured as test (Programming table parameter 11) allows the checking of the genset
without interfering in the mains. If any of the engine stating conditions is present, (mains power failure,
starting by programming timer…) the control board activates the genset contactor.

Manual Override (MFOR).


This function only works when the CEA6 functions are in automatic mode.
The input configured as override (Programming table parameter 12) meets the fire safety regulations
and accordingly the genset working can not be interrupted under any condition (be it alarm, external
disabling input or programmed blocking). Three manual override working modes can be configured
(Regulations table parameter 25):
- Manual override disabling. The manual override process is not managed, despite of having an
associated programmable input.
- Starting due to mains power failure. When the manual override input is activated, there is a time in
which is expected the genset to start due to any programmed condition (mains signal alarms, mains
contactor failure, external start...). In automatic mode, to stop the functions of the device, it is not
enough the mains voltage alarm disappears but must be deactivated the manual override input.
- Manual override starting. The genset starts immediately when the manual override input is activated,
without awaiting any other starting condition. To stop the device, it is necessary to change to manual
mode and stop the controller with the pushing buttons.

Programmable alarms (AL1, AL2 and AL3).


There are 3 free to be programmed alarms (Programming table parameters 13, 14 and 15) that can be
associated to any of the programmable inputs whose function is to provide additional alarms to the
controller. Its working mode is programmable. (Alarms table parameters 79 to 87).

5.2. Analog Inputs.


The CEA6 device has 5 analog inputs to measure the several engine working values. Such analog inputs
will allow to portray the engine working process and display its condition, setting on alarms if required,
being its working already pre-set. The alarms caused by the analog inputs does not stop the engine, they
are only a warning
By default, the alarms raised by analog inputs do not stop the controller (engine warnings), but can be
configured to produce the stop, with or without cooling.
The CEA6 controller carries out a continuous checking of the installed analog sensors, showing in the
visualization module display the value of the readings made.

The analog fuel level input indicates the amount of fuel left in the tank. To fit its working mode, the
maximum fuel level in the tank must be set (Measurements table parameter 13), and the same with the
minimum fuel level. (Measurements table parameter 12).

In the same way, a minimum fuel-in tank threshold (Thresholds table parameter 25) can be fixed, and it
will raise an engine warning (Alarms table parameter 55 to 57) when the fuel level is detected under
such limits.

When the BT relay from the measurement module is programmed to control the functions of the fuel
transfer pump, it will start the pump to transfer fuel to the tank if the fuel level is detected under the
minimum limits (Thresholds table parameter 18). The fuel pump is deactivated when the fuel level is
detected over the programmable threshold (Thresholds table parameter 19). Working the fuel pump in
manual mode, the threshold disables the activation of the fuel transfer pump except in case of the user
intervention.

Oil pressure input (P).


The analog fuel pressure input allows supervising the engine oil pressure value. The controller allows the
connection of VDO sensors to such analog input.
By programming a threshold, a minimum oil pressure limit can be set (Thresholds table parameter 26) in
order to raise an engine warning (Alarms table parameter 52 to 54) when the pressure is detected under
such limit.

Engine temperature input (T).


The analog engine temperature input allows to supervise the engine coolant temperature value. The
controller allows the connection of VDO type sensors to such analog input. By programming a threshold, a
maximum engine temperature limit can be set (Thresholds table parameter 27) in order to raise an
engine warning (Alarms table parameter 49 to 51) when the temperature is detected over such limit.

In the same way, if the pre-heating function is programmed (by means of the BT relay, if it is programmed
to regulate the fuel pump, or any other programmable input), the analog temperature inputs allows to
regulate the activation of the pre-heating cycle.
Analog configurable input (AnC).
The analog configurable input (AnC) allows to control an engine measurement (i.e. engine
temperature).The controller permits the connection of VDO type sensors to this analog input. The
measured value is shown in the display.

Alternator voltage input (DI).


The analog voltage input allows to supervise the value of the voltage generated by the battery charge
alternator. Such an input is used to diagnose the possible abnormal working of the alternator, if this
detects a low voltage level while the engine is on work. Under such condition an alarm signal of the battery
alternator will be triggered. (Alarms table parameter 10 to 12).

In that way, the voltage can be programmed to detect a starting condition (Regulations table parameter
20) by means of setting an alternator voltage threshold for started engine (Thresholds table parameter
21), only if it is not configured as dynamo mode (Regulations table parameter 3).

5.3. Pick–up Input. (PCK1, PCK2).


The pick up input from the measurement module controls the rotation speed of the engine in revolutions
per minute (rpm). To activate the pick up calculation through the engine ring gear, the number of teeth of
the gear must be introduced (Thresholds table parameter 24). In case the number of teeth is “0” the
controller is configured to have not available the pick up and the rotation speed will be calculated through
the genset frequency as per the equivalence-ratio 50Hz/1500 rpm or 50Hz/3000 rpm and 60 Hz/1800 rpm.
(Regulations table parameter 26).

The CEA6 device can be configured to trigger an overspeed alarm (Alarms table parameters 22 to 24)
as well as an underspeed alarm (Alarms table parameters 25 to 27) taking into account the mechanical
speed given by the pick up.

5.4. Digital outputs.


The CEA6 device has 9 outputs of specific functions (3 outputs to relay, 3 power outputs and 3 digital
inputs)
The working mode of those outputs is pre-established, though they can be configured.

Pre-heating output.
The pre-heating output (PR) of the CEA is an output connected to a high voltage short-circuitable driver
(70A) in charge of regulating the the glow plug heating procedure of the engine during the starting cycle.
The activation time of the pre-heating output is configurable (Times table parameter 4). The pre-heating
output can be also used to control the stop by excitation of engines with this kind of stop configuration
(Regulations table parameter 18).

Engine starting output.


The engine starting output (ARR) of the CEA6 is an output connected to a high voltage short-circuitable
driver (70A) which activates the starting of the engine. The activation of the engine starting remains until
any programmed starting condition is detected (Regulations table parameters 19 to 22) during a
maximum programmable time (Times table parameter 5).

Engine stop output.


The engine stop output (PC) of the CEA6 is connected to a high voltage short-circuitable driver (70A)
which controls the stopping of the engine. The engine stop input allows the configuration of its working
mode to control engines with 2 stopping modes:

ƒ De-excitation stop: The engine stop output configured as stop by de-excitation is activated
500ms after the pre-heating output is disabled and it is deactivated when the stop of the engine
is ordered.
ƒ Excitation stop. The engine stop output configured as stop by excitation is activated during a
programmable time (Times table parameter 12) when the stop of the engine is ordered.
ƒ Excitation/ de-excitation stop. The engine stop output configured as stop by excitation/de-
excitation is activated 500ms after the pre-heating output is disabled and it is deactivated when
the stop of the engine is ordered. Such output is used to enable the engine sensors. The pre-
heating output will be the responsible of the stopping phase by means of the excitation stop
cycle.

Mains contactor output.


The mains contactor output (MC) of the CEA6 controls the connection of the installation to the mains.

Genset contactor output.


The genset contactor output (GC) of the CEA6 controls the connection of the installation to the genset.

Fuel pump/pre-heating output.


The fuel pump/pre-heating (FP) of the CEA6 is an output that can be configured (Regulations table
parameter 4) to control the filling of the genset fuel tank with the fuel pump or the pre-heating process of
the engine.

Battery charge alternator excitation output (D+).


The D+ output of the CEA6 is in charge of exciting the battery charge alternator during the starting
process. This output can be configured (Regulations table parameter 3) to produce a starting pulse
(alternator mode) of a programmable time (Times table parameter 8) or to keep the alternator
continuously excited (dynamo mode).

Alarm output (AL).


The alarm output (AL) is in charge of communicating the different status of the CEA6 device. The AL
output is activated simultaneously with the flashing of the LED of the Reset button and the buzzer from the
display module of the CEA6. This input monitors the following status of the controller:

- External start of the control board. The alarm output of the device (AL) is activated for 5
seconds if it is detected a control board start ordered by a programmable input, associated to
the AE mode.

- Control board failures. The CEA6 device is activated for a maximum programmable time
(Times table parameter 14) if it is detected an active failure or a failure waiting to be
acknowledged by the user. If the user presses once the Reset button, the AL output is
deactivated. The failures that activates the AL output are suitable to the alarms which induce
the engine stop as well as the warnings which do not stop the engines, excepting the ones
raised by the quality of the mains signal:

o Mains power failure


o Maximum mains voltage
o Minimum mains voltage
o Maximum mains power supply frequency
o Minimum mains power supply frequency
o Phase sequence

Started engine output (SE).


The started engine output (SE) of the CEA6 device is activated whatever engine started condition is
detected and remains activated while the engine continues running. The started engine output (SE)
deactivates when the engine stopping cycle starts. This process includes the cooling of the engine (Times
table parameter 11) during the stopping cycle.
5.5. Programmable outputs
The CEA6 device has 3 programmable outputs whose working mode can be configured to indicate
different controller status. The possible configurations are:

Inhibited output
The programmable outputs configured as inhibited output do not obey to any action or status, they remain
constantly deactivated.

Output programmed by input status.

The programmable outputs configured as programmed by input status are activated when an associated
input is detected.

As possible inputs configurations, can be found the following:


- Fuel level input
- Coolant level input
- Programmable input 1
- Programmable input 2
- Programmable input 3
- Programmable input 4
- Programmable input 5

Programmed by alarm.
The programmable outputs configured as programmed by alarm are activated when the device detects
any activated alarm, associated to programmable outputs or that has not been yet checked by the user

As possible alarm configurations, can be found the following:


- Emergency stop
- Low oil pressure
- Battery charge alternator alarm
- High coolant temperature
- Programmable alarm 1
- Programmable alarm 2
- Programmable alarm 3

Programmed by function.

The programmable outputs configured as programmed by function are configured to allow a function
associated to an already used output. As possible functions of configurations, can be found the following:

- Heater. The output can function to activate the heater (glow plug) if the BT relay is programmed
to control the fuel pump.

Programmed by mode.

The programmable outputs configured as programmed by mode are configured to indicate the working
mode of the controller.

As possible mode configurations, can be found the following:

- Controller in blocked mode.


- Controller in manual mode.
- Controller in auto mode.
- Controller in test mode
6. CEA6 ALARMS.
The CEA6 device provides a series of alarms whose working mode can be configured to perform actions
or to be shown in the display of the visualization module.

The CEA6 distinguishes between anomalies which cause the stop of the engine (alarms) and errors which
do not stop the engine (warnings).

When an alarm or warning is detected, the controller produces an acoustic alarm, at the same time the
digital alarm output (AL) activates and the LED of RESET button flashes; this status will remain the
same as long as the failure condition continues for a programmable period of time (Times table
parameter 14).

The LED of the RESET button lights (and remains ON) when alarms or warnings are active or in need of
acknowledgement. Pressing RESET button once allows the user to visualize a record of alarms and
warnings that are active and needing to be acknowledged. The UP and DOWN buttons of the display are
used to go back and forward in the failure record.

The record of warnings that are active or in need of acknowledgement has the following format

N: To be checked N: Number of position in


the total record of errors

E: Alarm N: Number of
A: Warning errors in the record

* A L A R M * E N 1 / 3

M I N . F R E Q U E N C Y G E N S E T

In the front panel of the control board there can be found LEDs which indicate alarms detected by digital
sensors (digital inputs) or by analog sensors (analog inputs).

NOTE: The alarms which cause the engine to stop are not auto-resetting, and they must be acknowledged
and re-set by the user in order to be able to start the engine again, but only if the alarm does not remain
active.
The alarms produced by analog inputs do not stop the engine, only trigger a warning according to the
settings programmed by default. They need to be reset to erase them from the display, but only if the
warning does not remain active. The fuel level alarm is an exception, as it is automatically reset.
ALARM OPERATING PROCESS. PRACTICAL EXAMPLE.
“EN” Alarm with engine stop
“AN” Warning that needs to be reset
“A” Warning automatically reset

“EN” Alarm with engine stop

1. When an alarm is detected, the controller produces an acoustic signal, the LED of the RESET
button flashes, the display blinks and the appropriate digital alarm output (AL) is activated. In this
case the engine stops.
2. The acoustic alarm is interrupted by pressing once the RESET button. The RESET LED turns into
fixed light and the display (which stops flashing) shows the kind of alarm. i.e.: Active alarm “EN”
High coolant temperature.
3. To solve the alarm problem: In this example the temperature of the engine must be reduced when
the engine stops. Check the coolant level of the engine to detect the cause of the failure. Once
the alarm is no longer active “N” it will be possible to reset it by pressing RESET button and the
engine can be restarted.

HIGH TEMPERATURE HIGH TEMPERATURE


WATER WATER

“AN” Warning that needs to be reset.

1. When an alarm is detected, the controller produces an acoustic signal, the LED of the RESET
button flashes, the display blinks and the appropriate digital alarm output (AL) is activated.
2. The acoustic alarm is cancelled by pressing once the RESET button. Once the RESET LED turns
into fixed light and the display (which stops flashing) shows the kind of Active warning “AN”
3. To solve the warning problem: In this case, stop the engine, if we consider so, to check the cause
of the fault indicated. Once the warning is no longer active, “N” will appear in the display and it will
be possible to reset it by pressing RESET button.

WARNING WARNING
HIGH TEMPERATURE HIGH TEMPERATURE
WATER WATER
“A” Warning automatically reset

1. When an alarm is detected, the controller produces an acoustic signal, the LED of the RESET
button flashes, the display blinks and the appropriate digital alarm output (AL) is activated.
2. The acoustic alarm is interrupted by pressing the RESET button once. The RESET LED turns into
fixed light and the display (which stops flashing) shows the kind of warning. Warning “A”
3. This kind of warning is automatically reset as long as the nominal conditions of working are
restored. It is focused on the type of alarms related to fuel level (in default programming) and the
alarms related with the mains threshold.

WARNING

FUEL RESERVE
ALARMS
The alarm and the active warning list can be grouped in the following way: (according the
MANUFACTURER DEFAULT SETTINGS)

6.1. ENGINE ALARMS

Description Led in the front panel Type Action


LED Immediate engine stop
High coolant temperature Alarm
flashes with no cooling
LED Immediate engine stop
Low oil pressure Alarm
flashes with no cooling

Immediate engine stop


Emergency stop Alarm
with no cooling

Battery charge alternator failure


LED off Warning Engine does not stop
(engine running)
LED
Start failure
flashes
LED Immediate engine stop
Low coolant level Alarm
flashes with no cooling
LED
Fuel storage Warning Engine does not stop
flashes
Immediate engine stop
Overspeed LED on Alarm
with no cooling

Loss of speed Alarm Engine stop with cooling

Low battery voltage Warning No stop

High coolant temperature by sensor LED on Warning Engine does not stop

Low oil pressure by sensor LED on Warning Engine does not stop

Low fuel level by sensor LED on Warning Engine does not stop

Unexpected shutdown

Stop failure

Low engine temperature Warning Engine does not stop

Genset voltage drops Alarm Engine stop with cooling


6.2. GENSET ALARMS

Description Type Action


Overload Alarm Engine stop with cooling
Genset voltage asymmetry Alarm Engine stop with cooling
Maximum voltage of the genset Alarm Immediate engine stop with no cooling
Maximum genset frequency Alarm Immediate engine stop with no cooling
Erroneous phase sequence of the genset Alarm Engine stop with cooling
Inverse power Alarm Engine stop with cooling
Short circuit Alarm Engine stop with cooling
Minimum genset voltage Alarm Engine stop with cooling
Minimum genset frequency Alarm Engine stop with cooling

6.3 MAINS ALARMS


Description Led in the front panel Type Action
Possible failure checked.
Maximum mains voltage
The engine is started
Possible failure checked.
Minimum mains voltage The engine is started

Maximum mains power supply Possible failure checked.


frequency The engine is started
Minimum mains power supply Possible failure checked.
frequency The engine is started
Possible failure checked.
Mains phase sequence failure
The engine is started
Possible failure checked.
Mains power failure
The engine is started
Mains contactor switching failure Possible failure checked.
(CR) The engine is started

6.4. PROGRAMMABLE ALARMS AND INPUTS


There are three programmable alarms that can be associated with engine alarms and be indicated by
the LEDs Aux 1 and Aux 2 of the display

Description Type Action


Related with programmable inputs Alarm According to configuration
All inputs excepting those that the opposite is indicated, they can be configured in the following
way:
to be carried out:

- Never.
- Always.
- During the engine start.
- From the started engine condition
- From the engine nominal condition

to carry out one of the following actions:

- No actions to be performed (warning)


- Stop with engine cooling
- Immediate engine stop

High Coolant temperature.


The high coolant temperature alarm of the CEA6 is associated to the specific high coolant temperature
digital input (HTC). The status of such input must be validated during a stabilization time (Times table
parameter 17) before the high coolant temperature alarms triggers.

It can be configured as normally open or normally closed (Regulations table parameter 7).

The high coolant temperature alarm can be configured (Alarms table parameter 1) to be detected:
Always

A stabilization time can be associated to the high coolant temperature alarm (Alarms table parameter 2)
to delay the moment in which the alarm conditions are verified.

This alarm has been configured (Alarms table parameter 3) to carry out: the Immediate engine stop

Low oil pressure.


The low oil pressure alarm of the CEA6 is associated to the specific low oil pressure digital input
(LOP).The status of such input must be validated during a stabilization time (Times table parameter 16)
before the low oil pressure alarm triggers.

It can be configured as normally open or normally closed (Regulations table parameter 6).

The low oil pressure alarm is configured (Alarms table parameter 4) to be detected:
From the started engine condition

A stabilization time can be associated to the low oil pressure alarm (Alarms table parameter 5) to delay
the moment in which the alarm conditions are verified

This alarm is configured (Alarms table parameter 6) to carry out the following action:
- Immediate engine stop
Emergency stop.
The emergency stop alarm of the CEA6 is associated to the specific emergency stop digital input (EMS)

It can be configured as normally open or normally closed (Regulations table parameter11).

In the same way, the emergency stop alarm is also associated to the SETA input from the measurement
module. This input cuts the feeding to the power outputs of the measurement module (starting, pre-heating
and engine stopping) to make sure the stop of the engines configured as stop by de-excitation
(Regulations table parameter 18) without considering the electronics of the device. In engines
programmed with stop by no-excitation, such input must be connected to earth.

The emergency stop alarm always stops the engine without cooling. No delay timing can be associated to
that action, as it is immediately executed after the emergency stop input is detected (EMS).

Battery charge alternator failure.


The battery charge alternator failure alarm of the CEA6 is associated to the battery charge alternator
voltage analog input (DI). The voltage value of such input must exceed the voltage threshold of the started
engine detection (Thresholds table parameter 21); if not, the battery charge alternator failure alarm is
triggered.

The battery charge alternator alarm is configured (Alarms table parameter 10) to be detected:
- From the started engine condition

A stabilization time can be associated to the battery charge alternator low alarm (Alarms table 11). During
this time the obtained voltage values must be kept under the started engine detection threshold (through
the DI input) as a condition for the battery charge alternator failure alarm to be triggered.

This alarm is configured (Alarms table parameter 12) to carry out the following action:
- No actions to be performed (warning)

Starting failure.
The starting failure alarm of the CEA6 is triggered if all the starting attempts (Times table parameter 1),
consecutive and non effective, during the engine starting cycle are effected. Between each start attempt
there is a programmable waiting time (Times table parameter 2). Once the alarm is produced, the user
must check it before trying again with the engine starting process.

Low coolant level.


The low coolant level alarm of the CEA6 is associated to the specific low coolant level digital input (CL).
The status of this input must be validated during a stabilization time (Times parameter 18) before
triggering the low coolant level alarm

It can be configured as normally open or normally closed (Regulations table parameter 8).

The low coolant level alarm is configured (Alarms table parameter 16) to be detected:
-Always

A stabilization time (Alarms table parameter 17) can be associated to the low coolant level alarm to delay
the moment in which the alarm condition is verified.

This alarm is configured (Alarms table parameter 18) to carry out the following action:
- Immediate engine stop if the engine is not already stopped.
Fuel reserve.
The fuel reserve alarm of the CEA6 is associated to the specific fuel reserve digital input (FR) The status
of this input must be validated during a stabilization time (Times table parameter 15) before triggering
the fuel reserve alarm.

It can be configured as normally open or normally closed (Regulations table parameter 5).

The low coolant level alarm is configured (Alarms table parameter 19) to be detected:
- Always

A stabilization time (Alarms table parameter 20) can be associated to the fuel reserve alarm to delay the
moment in which the alarm condition is verified.

This alarm is configured (Alarms table parameter 21) to carry out the following action:
- No actions to be performed (warning)

Overspeed
The overspeed alarm of the CEA6 is associated to the rotation speed of the engine ring gear. This
measurement is done through the pick up input of the measurement module. The alarm functions depend
that the parameter that determines the number of teeth of the engine ring gear (Thresholds table
parameter 24) would not be zero.

The overspeed alarm is configured (Alarms table parameter 22) to be detected:


- From the engine nominal condition

A stabilization time can be associated to the overspeed alarm (Alarms table parameter 23). During this
time the rotation speed of the ring gear during this time must be over the maximum limits of the rotation
speed (Thresholds table parameter 11).

This alarm is configured (Alarms table parameter 24) to carry out the following action:
- Immediate engine stop

Underspeed
The underspeed alarm of the CEA6 is associated to the rotation speed of the engine ring gear. This
measurement is done through the pick up input of the measurement module. The alarm functions depend
that the parameter that determines the number of teeth of the engine ring gear (Thresholds table
parameter 24) would not be zero

The underspeed alarm is configured (Alarms table parameter 25) to be detected:

- From the engine nominal condition

A stabilization time can be associated to the underspeed alarm (Alarms table parameter 26). During this
time it must be kept under the programmed minimum limits (Thresholds table parameter 12).

This alarm is configured (Alarms table parameter 24) to carry out the following action:
- Stop with engine cooling

Overload.
The overload alarm of the CEA6 is associated to the effective amperage value in any of the phases. The
value must be superior to the maximum programmed overload limit (Thresholds table parameter 7) but
under the maximum limit of short-circuit (Thresholds table parameter 8).

The phases that are checked to detect the overload alarm are selected depending on the configuration of
the installation phases (Thresholds table parameter 1):
- Single-phase configuration, phase 1 is tested
- Two-phase configuration, phase 1 and 2 are tested.
- Three-phase configuration with neutral or three-phase without neutral, phase 1, 2 and 3 are
tested.

The overload alarm is configured (Alarms table parameter 28) to be detected:


- From the engine nominal condition

A stabilization time can be associated to the overload alarm (Alarms table parameter 29). During this
time the amperage values must be kept over the maximum programmed limits (Thresholds table
parameter 7).

This alarm is configured (Alarms table parameter 30) to carry out the following action:
- Stop with engine cooling

Genset voltage asymmetry.


The genset voltage asymmetry alarm of CEA6 controls that the difference found between any pair of real
voltage values among generating set voltage phases(VG12, VG23 or VG31, must be over the maximum
asymmetry programmed limits ( Thresholds table parameter 4).

The voltage asymmetry alarm is activated only when the device is configured for the measurement of
three-phase with neutral or three-phase without neutral voltage values.

The voltage asymmetry alarm is configured (Alarms table parameter 31) to be detected:
- From the engine nominal condition

A stabilization time can be associated to the voltage asymmetry alarm (Alarms table parameter 32).
During this time, the difference between any pair of voltage values of the genset phases (VG12, VG23 or
VG31) must be over the maximum asymmetry programmed limits (Thresholds table parameter 4).

This alarm is configured (Alarms table parameter 33) to carry out the following action:
- Stop with engine cooling

Maximum genset voltage.


The maximum genset voltage alarm of the CEA6 is associated to the fact that the real voltage value
obtained from any pair of phases of the genset ((VG12, VG23 or VG31) is over the maximum programmed
voltage limits (Thresholds table parameter 2).

The phases that are checked to detect the maximum genset voltage alarm are selected
depending on the configuration of the phases in the installation (Thresholds table parameter 1):
- Single-phase configuration, V1N voltage is tested
- Bi-phase configuration, V12 voltage is tested
- Three-phase configuration with neutral or three-phase without neutral, V12, V23, V13 voltages
are tested.

The maximum genset voltage alarm is configured (Alarms table parameter 34) to be
detected:
- From the engine nominal condition

A stabilization time can be associated to the maximum genset voltage alarm (Alarms table parameter 35)
During this time, the voltage values obtained between genset phases (VG12,VG23 or VG31) must be over
the maximum programmed limits. (Thresholds table parameter 2).

This alarm can be configured (Alarms table parameter 36) to carry out the following action:
- Immediate engine stop
Maximum genset frequency.
The maximum genset frequency alarm of the CEA6 is associated to the fact that the frequency generated
by the genset surpasses the maximum programmed frequency limits. (Thresholds table parameter 5).

The first-phase is used to measure the genset frequency. If no signal is detected, the measure is taken in
the second-phase. In the same way, if no signal is detected, the measure is taken in the third-phase.

The maximum genset frequency alarm is configured (Alarms table parameter 37) to
be detected:
- From the engine nominal condition

A stabilization time can be associated to the maximum genset frequency alarm (Alarms table parameter
38). During this time, the genset frequency values obtained must be kept over the maximum programmed
limits. (Thresholds table parameter 5).

This alarm is configured (Alarms table parameter 39) to carry out the following action:
- Immediate engine stop

Erroneous phase sequence of the genset.


The erroneous phase sequence of the genset alarm of the CEA6 is associated to the fact that the
maximum values of the genset signal phases are in order (phase 1, phase 2 and phase 3 in this order)

The erroneous phase sequence alarm is activated only when the device is configured to work with three-
phase with neutral or three-phase without neutral.

The erroneous phase sequence alarm is configured (Alarms table parameter 40) to be detected:
- From the engine nominal condition

A stabilization time can be associated to the erroneous phase sequence alarm (Alarms table parameter
41). During this time an erroneous order in the maximum voltage values of the genset must be detected.

This alarm is configured (Alarms table parameter 42) to carry out the following action:
- Stop with engine cooling

Inverse power.
The inverse power alarm of the CEA6 is activated when the power obtained (mains or genset) is negative,
and exceeds the resultant value after calculating the programmed factor in a hundred per cent
(Thresholds table parameter 10) of the nominal power. (Thresholds table parameter 9).

Some times, the inverse power alarms can be triggered due to an erroneous wiring of the current
transformers.

The inverse power alarm is configured (Alarms table parameter 43) to be detected:
- From the engine nominal condition

A stabilization time can be associated to the inverse power alarm (Alarms table parameter 44). During
this time the power could be out the programmed limits.

This alarm is configured (Alarms table parameter 45) to carry out the following action:
- Stop with engine cooling
Low battery voltage.
The low battery voltage alarm of the CEA6 is triggered when the voltage obtained is lower
than the programmed limits (Thresholds table parameter 17).

The low battery voltage alarm is configured (Alarms table parameter 46) to be
detected:
- Always

A stabilization time can be associated to the low battery voltage alarm (Alarms table parameter
47). During this time, the voltage value detected must be under the programmed limits.
(Thresholds table parameter 17).

This alarm is configured (Alarms table parameter 48) to carry out the
following action:
- No actions to be performed (warning)

High coolant temperature by sensor.


The high coolant temperature by sensor alarm is associated to the coolant temperature analog input (T).
The high coolant temperature by sensor alarm triggers when a temperature reading is above the
programmed limits. (Thresholds table parameter 27).

The high coolant temperature by sensor alarm is configured (Alarms table parameter 49) to be detected:
- Always

A stabilization time can be associated to the high coolant temperature by sensor alarm (Alarms table
parameter 50). During this time, the coolant temperature value detected must be over the programmed
limits. (Thresholds table parameter 27).

This alarm is configured (Alarms table parameter 51) to carry out the following action:
- No actions to be performed (warning)

Low oil pressure by sensor.


The low oil pressure by sensor alarm of the CEA6 is associated to the oil pressure analog input (T). The
low oil pressure by sensor alarm triggers when the pressure readings are under the programmed limits
(Thresholds table parameter 26).

The low oil pressure by sensor alarm is configured (Alarms table parameter 52) to be detected:
- From the started engine condition

A stabilization time can be associated to the low oil pressure by sensor alarm (Alarms table parameter
53). During this time the pressure values must be detected under the programmed limits. (Thresholds
table parameter 26).

This alarm is configured (Alarms table parameter 54) to carry out the following action:
- No actions to be performed (warning)

Low fuel level by sensor.


The low fuel level by sensor alarm of the CEA6 is associated to the fuel level analog input (NC). The low
fuel level by sensor alarm triggers when the fuel level is under the programmed limits. (Thresholds table
parameter 25).

The low fuel level by sensor alarm is configured (Alarms table parameter 55) to be detected:
- Always

A stabilization time can be associated to the low fuel level by sensor alarm (Alarms table parameter 56).
During this time the fuel level values must be detected under the programmed limits (Thresholds table
parameter 25).

This alarm is configured (Alarms table parameter 57) to carry out the following action:
- No actions to be performed (warning)
Short circuit.
The short circuit alarm of the CEA6 is associated to real amperage value when any of the phases are over
the maximum short circuit programmed limits (Thresholds table parameter 8).

The phases that are checked to detect short circuit alarm are selected depending on the configuration of
the phases in the installation (Thresholds table parameter 1):
- Single-phase configuration, phase 1 is tested
- Two-phase configuration, phase 1 and 2 are tested.
- Three-phase configuration with neutral or three-phase without neutral, phase 1, 2 and 3 are
tested.

The short circuit alarm is configured (Alarms table parameter 58) to be detected:
- From the engine nominal condition

This alarm is configured (Alarms table parameter 60) to carry out the following action:
- Stop with engine cooling

Minimum genset voltage.


The minimum genset voltage alarm of the CEA6 is associated to the fact that real voltage value obtained
from any pair of phases of the genset ((VG12, VG23 or VG31) is under the minimum programmed voltage
limits (Thresholds table parameter 3).

The phases that are checked to detect the minimum genset voltage alarm are selected depending on the
configuration of the phases in the installation (Thresholds table parameter 1):
- Single-phase configuration, V1N voltage is tested
- Bi-phase configuration, V12 voltage is tested
- Three-phase configuration with neutral or three-phase without neutral, V12, V23, V13 voltages
are tested.

The minimum genset voltage alarm is configured (Alarms table parameter 61) to be
detected:
- From the engine nominal condition

A stabilization time can be associated to the minimum genset voltage alarm (Alarms table parameter 62)
During this time, the voltage values obtained between genset phases (VG12, VG23 or VG31) must be
under the minimum programmed limits. (Thresholds table parameter 3).
.
This alarm is configured (Alarms table parameter 63) to carry out the following action:
- Stop with engine cooling

Minimum genset frequency.


The minimum genset frequency alarm of the CEA6 is associated to the fact that the frequency generated
by the genset is under the minimum programmed frequency limits. (Thresholds table parameter 6).

The first-phase is used to measure the genset frequency. If no signal is detected, the measure is taken in
the second-phase. In the same way, if no signal is detected, the measure is taken in the third-phase.

The minimum genset frequency alarm is configured (Alarms table parameter 64) to be detected:
- From the engine nominal condition

A stabilization time can be associated to the minimum genset frequency alarm (Alarms table parameter
65). During this time, the genset frequency values obtained must be kept under the minimum programmed
limits (Thresholds table parameter 6).

This alarm is configured (Alarms table parameter 66) to carry out the
following action:
- Stop with engine cooling
Unexpected shutdown.
The unexpected shutdown of the CEA6 triggers when the controller, while the engine is running, does not
detect all the engine starting conditions. (Regulations table parameters 19 to 22).

Stop failure.
The stop failure alarm of the CEA6 is raised if 15 seconds after the engine stop attempt it is not detected
any of the stopping conditions of the engine (Regulations table parameters19 to 22).

In case the stop failure alarm is disconnected (Alarms table parameter 70), the device will consider the
engine as stopped after waiting the stop conditions for a maximum time of 15 seconds.

To detect the stop of the engine, all the stopping conditions must be detected during a programmed time
(Alarms table parameter 71).

Low engine temperature.


The low engine temperature alarm of the CEA6 is associated to the analog coolant temperature input (T).
The low engine temperature alarm triggers when a temperature value is under the programmed limits.
(Thresholds table parameter 28).

The low engine temperature alarm is configured (Alarms table parameter 73) to be detected:
- Never

A stabilization time can be associated to the low engine temperature alarm (Alarms table parameter 74).
During this time, the coolant temperature values must be detected under the programmed limits
(Thresholds table parameter 28).

The low engine temperature alarm, once activated, does not allow the activation of the generating set
contactor until the engine exceeds the low temperature limits (Thresholds table parameter 28).

Genset signal failure.


The genset signal failure alarm of the CEA6 is triggered if, while the engine is running, no voltage is
detected in any of the phases.

The genset signal failure alarm is configured (Alarms table parameter 76) to be detected:

- From the engine nominal condition

A stabilization time can be associated to the genset signal failure alarm (Alarms table parameter 77).
During this time it must not be detected any signal before rising the alarm.

This alarm is configured (Alarms table parameter 78) to carry out the following action:
- Stop with engine cooling

Programmable alarm 1.
The programmable alarm 1 of the CEA6 is activated by associating one of the general digital inputs
(ENT1, ENT2, ENT3, ENT4 or ENT5) to the working mode of the programmable alarms. (Programming
table parameter 13). The status of such input must be validated during a stabilization time (Times table
parameter 19, 20, 22, 23 or 24) before triggering the programmable alarm 1 alarm.

The programmable alarm 1 is configured (Alarms table parameter 79) to be detected:


- Never

A delay time (Alarms table parameter 80) can be associated to the programmable alarm 1 in order to
restrain the moment in which the alarm conditions are checked.

This alarm is configured (Alarms table parameter 81) to carry out the following action:
- No actions to be performed (warning).
A programmable text can be associated to the programmable alarm 1 and will appear on the visualization
module display when the alarm is triggered

Programmable alarm 2.

The programmable alarm 2 of the CEA6 is activated by associating one of the general digital inputs
(ENT1, ENT2, ENT3, ENT4 or ENT5) to the working mode of the programmable alarms. (Programming
table parameter 14). The status of such input must be validated during a stabilization time (Times table
parameter 19, 20, 22, 23 or 24) before triggering the programmable alarm 2 alarm.

The programmable alarm 2 is configured (Alarms table parameter 82) to be detected:


- Never

A delay time (Alarms table parameter 83) can be associated to the programmable alarm 2 in order to
restrain the moment in which the alarm conditions are checked.

This alarm is configured (Alarms table parameter 84) to carry out the following action:
- No actions to be performed (warning)

A programmable text can be associated to the programmable alarm 2 and will appear on the visualization
module display when the alarm is triggered

Programmable alarm 3.
The programmable alarm 3 of the CEA6 is activated by associating one of the general digital inputs
(ENT1, ENT2, ENT3, ENT4 o ENT5) to the working mode of the programmable alarms. (Programming
table parameter 15). The status of such input must be validated during a stabilization time (Times table
parameter 19, 20, 22, 23 or 24) before triggering the programmable alarm 3.

The programmable alarm 3 is configured (Alarms table parameter 85) to be detected:


- Never

A delay time (Alarms table parameter 86) can be associated to the programmable alarm 3 in order to
restrain the moment in which the alarm conditions are checked.

This alarm is configured (Alarms table parameter 87) to carry out the following action:
- No actions to be performed (warning)

A programmable text can be associated to the programmable alarm 3 and will appear on the visualization
module display when the alarm is triggered

Maximum mains voltage.


The maximum mains voltage alarm of the CEA6 is associated to the fact that the real voltage value
obtained from any pair of the mains phases (VR12, VR23 or VR31) is over the maximum programmed
voltage limits ( Thresholds table parameter 13).

The phases that are checked to detect the maximum mains voltage alarm are selected
depending on the configuration of the phases in the installation (Thresholds table parameter 1)
- Single-phase configuration, V1N mains voltage is tested
- Bi-phase configuration, V12 mains voltage is tested
- Three-phase configuration with neutral or three-phase without neutral, V12, V23, V13 mains
voltages are tested.

The maximum mains voltage alarm is configured (Alarms table parameter 88):
- To be detected

A stabilization time can be associated to the maximum mains voltage alarm (Alarms table
parameter 89). During this time, the voltage values obtained between mains phases (VR12,
VR23 or VR31) must be over the maximum programmed limits (Thresholds table parameter 13).

The detection of the maximum mains alarm is considered a genset starting condition.
7. Maintenance.
7.1. Working Counters.
The CEA6 device records a number of stored values regarding the control board functions. The counters
of the device are:

- Total working hours counter. The device records the number of working hours of the genset
engine. This counter can not be reset.
- Partial working hours counter The device records the number of working hours of the genset
engine. This counter can be reset and it starts from 0.
- Succeeded starts counter. The device records the number of obtained starts. This counter can
be reset and it starts from 0.
- Failed starts counter. The device records the number of failed starts. This counter can be reset
and it starts from 0.
- Total counter of power. The device records the total amount of power produced by the genset
(MWh). This counter can not be reset.
- Partial counter of power. The device records the total amount of power produced by the genset
(MWh). This counter can be reset and it starts from 0.
- Daily counter of power (option programming timer needed). The daily counter of power registers
the quantity of power produced by the genset from the 00:00H. of the present day up to the
moment of checking. With the change of the day, the stored power values along the day are
added to the monthly energy values. The daily counter then starts from 0.
- Monthly counter of power (option programming timer needed). The monthly counter of power
registers the quantity of power produced by the genset from the fist day of the current month up
to the day before the moment of checking. With the change of month, the stored power values
are added to the annual power counter. The monthly counter then starts from 0.
- Annual counter of power (option programming timer needed). The annual counter of power
registers the quantity of power produced by the genset from 1st January up to the month before to
the moment of checking. With the change of year, the stored power values are reset and the
counter starts from 0.

The user can see the counters readings accessing from the menu Main Æ3.Counters

The partial counters can be reset to 0 by selecting with the UP/DOWN buttons and pressing RESET for 5
seconds.

7.2. Maintenance counters


The CEA6 device has 3 programmable countdown counters. An amount of time is configured and
decreases when the engine starts to run. These maintenance counters are:

- 2 engine maintenance counters: When the counter reaches 0 an engine alarm without engine
stop is triggered. The alarm disappears when the counter is recharged.
- 1 rental counter: The counter raises an alarm that can stop the engine. The alarm disappears
when the counter is recharged.

7.3. Fault history.

The CEA6 device registers the alarms and saves the status of the control board in the moment of the
detection. All the alarms are stored, excepting the alarms related with the electric mains supply:
- Minimum mains voltage failure.
- Maximum mains voltage failure.
- Maximum mains frequency failure.
- Minimum mains frequency failure.
- Mains sequence failure
- Mains power failure.

The CEA6 stores the last 10 detected failures. With the programming timer, 100 additional failures can be
added to the fault history, including the date and hour of the moment in which the failure was produced.
8. Optional expansions.
New functional options can be added to the CEA6 device with the connection of the CAN bus allowing new
expansion modules.

8.1. Visualization Display.


CEA6 and CEM6 controllers allow to add visualization modules to the device. This device shows the
current status of the control panel. When the control panel is set in automatic mode, it allows to make a
remote start of the genset.

Moreover, this visualization display allows to check the control panel status by means of "error and status
leds" and also the programming of the parameters of working.

8.2. Programming timer.


The CEA6 allows the connection of a programming timer device to the visualization module. The timer
informs the control board about the current date and hour.

The installation of a programming timer device to the CEA6 allows the weekly programming of:
- Programmed starts.
- Programmed cut-outs.
- Programmed engine tests.
- Expansion of the fault history
- Power counters (day, month, year ).

The maximum capacity of the timer is 5 daily programs. The CEA6 must be in automatic mode to carry out
the programming.

8.3. Telesignal.
The CEA6 allows the connection of a Telesignal device. This device has 12 outputs to relay (4 with
connection NO and NC, 8 with connection NO) and it can be programmed depending the status of the
control board.
The outputs of the Telesignal device can be programmed to activate depending:
- Any control board status (automatic, manual,…)
- any alarm, active or waiting to be checked.
- any activated input of the control board.
- any activated output of the control board.

Every output of the Telesignal device is activated when, at least, one of the programmed activation
conditions exist.

8.4. J1939.
The CEA6 allows the connection of a J1939 device. This device can control a number of parameters of the
engine working mode, depending on the manufacturer and the engine model (ask your distributor):
- Pressure values, temperature.
- Engine alarms.
- Engine error codes.
- Starting and stop process.
- Fine speed adjustment (synchronization).

8.5. Remote control.


The CEA6 allows the connection of a Remote control device to execute the remote connection with
modems (GPRS, UMTS, of line...)... This device enables to:
- Management of actions (start, stop, alarms...) and control by Short Message System (SMS)
- Remote management and control by a TC/IP connection.
- Remote management and control.
Annex I: Parameters table
The CEA6 device allows 3 levels of access to the configuration. To modify any parameter of the CEA6, a
validation is required, by means of a password introduction. The 3 access levels are:

1. User access. Allows the setting of the level 1 parameters.


2. Maintenance access. Allows the setting of the level 1 and 2 parameters.
3. Supervisor access Allows the setting of the level 1, 2 and 3 parameters.

TIMES
Default
Parameter Psw Description Range
Value
1 2 Number of starts 4 1..10
Time between startings
2 2 Time between one starting attempt and another. All the 5’’ 3’’..30’’
outputs are deactivated
Starting delay
3 2 0’’ 0’’..1800’’
Range of time between mains failure and engine starting
4 2 Glow plug pre-heating time 0’’ 0’’..180’’

Starting time
5 2 Maximum waiting time before detecting the starting condition. 5’’ 1’’..10’’
During this time the starting output is active.

Activation of load time


6 2 Range of time from the detection of the engine starting 3’’ 1’’..600’’
condition to the genset contactor activation.

Nominal condition time


7 2 Range of time from the detection of the engine starting 2” 2”..15”
condition to the quality validation of the generated signal.

D+ activation time
Being this time over, the voltage values of the DI input will be
8 2 checked, and the D+ output will be activated, or not, until the 3’’ 1’’..3’’
stop of the engine (according PR regulations parameter (3))

9 2 EJP1 delay 1” 1”..1800”


Mains activation delay
10 2 Time between the correct mains signal and the switching of 60’ 1”’..600’”
the contactors.
11 2 Cooling time 120’’ 2’’..1800’’
12 2 Emergency Stop activation time 10’’ 1’’..30’’
13 2 Contactor detection time 5’’ 1’’..3000
Maximum time for alarm activation
The alarm output will be activated (together with the flashing 0-Indefinido
14 2 15”
of the reset button and the buzzer on the display) when 1”..1800”
corresponds within this limited time
15 2 Filtered from FR input 1.0’’ 0.0’’..5.0’’
16 2 Filtered from LOP input 1.0’’ 0.0’’..5.0’’
17 2 Filtered from HCT input 1.0’’ 0.0’’..5.0’’
18 2 Filtered from CL input 1.0’’ 0.0’’..5.0’’
19 2 Filtered from INT4 input 1.0’’ 0.0’’..5.0’’
20 2 Filtered from INT5 input 1.0’’ 0.0’’..5.0’’
22 2 Filtered from INT1 input 1.0’’ 0.0’’..5.0’’
23 2 Filtered from INT2 input 1.0’’ 0.0’’..5.0’’
24 2 Filtered from INT3 input 1.0’’ 0.0’’..5.0’’
MEASUREMENTS
Default
Parameter Psw Description Range
Value

Conversion factor of the amperage transformers


1 2 100
Common factor to the real intensity values IR,IS,IT

12 2 Fuel level regulation EMPTY

13 2 Fuel level regulation FULL


REGULATIONS
Default
Parameter Psw Description Range
Value
0-Off
1-Manual
1 2 Transfer Fuel Pump working mode 3
2-Automatic
3-Control board
0-Locked
1-Manual
2 2 Starting mode by default 1
2-Automatic
3-Test
0-Alternator
3 2 D+ deactivation 0
1-Dynamo
0-Inhibited
BT relay output configuration
4 2 1 1-Transfer pump
Pre-heater or fuel transfer pump
2- Heater
5 2 FR input configuration 1

6 2 LOP input configuration 1

7 2 HCT input configuration 1

8 2 CL input configuration 1

9 2 INT4 input configuration 1 0-OFF


1-Normally open.
10 2 INT5 input configuration 1
2- Normally closed.
11 2 EMS input configuration 2

12 2 INT1 input configuration 1

13 2 INT2 input configuration 1

14 2 INT3 input configuration 1

15 2 EMER/CS input configuration 2


0-No programmed
1-FR
2-LOP
3-HCT
Input associated to the LED AUX1 from the 4-CL
16 2 visualization module 9 5- INT4
6- INT5
7-EMS
8-INT1
9-INT2
10-INT3
Input associated to the LED AUX2 from the
17 2 visualization module 10

Pre-heating and programmed stop inputs 0-PD/PR


18 2 configuration 0 1-PE/PR
2-PD/PE

0-Off
1-Manual
19 2 Tensión de fase como condición de arranque 1
2-Automatic
3-Control board
20 2 Alternator voltage as starting condition 1
0-Off
1-Manual
21 2 PICK-UP input as starting condition 1 2-Automatic
3-Control board

22 2 LOP input as starting condition 2

0-Not installed
23 2 Voltage transformer 0 1-Transformer
400/600
0- Output line
24 2 Amperage measurement location. 0 1-Genset control
panel
0-Not allowed
1- Starting due to
25 3 Manual override working mode 0 Mains failure
1- Starting due to
manual override.

0-50Hz/1500rpm
Rotation speed of the engine ring gear related
26 2 0 60Hz/1800rpm
with genset voltage frequency
1-50Hz/3000rpm

0-Centigrade
27 2 Temperature readings 0
1-Fahrenheit

0-Bar
28 2 Pressure readings 0
1-Psi

0-VDO
29 3 Type of analogical sensors 0 1-SCANIA EMS
2 - YANMAR

0: Manual
30 2 Type of control board selection 0 1: Automatic

NOTE: After the modification of the parameter 30, you should restarted the control board, disconnecting its
feeding, to allow the upgrade in its operation mode.
THRESHOLDS
Default
Parameter Psw Description Range
Value
0- Three-
phase without
neutral
1-Three-
Three-phase, bi-phase or single-phase without
1 2 0 phase
neutral
2-Bi-phase
3- Single
phase

2 2 Maximum Genset Voltage 440V

3 2 Minimum Genset Voltage 360V

4 2 Maximum Genset asymmetry value 80V

5 2 Maximum Genset Frequency 58Hz

6 2 Minimum Genset Frequency 45Hz

7 2 Maximum Generator Current 1000 A

8 2 Short-circuit detection 3000 A

9 2 Genset Nominal power 200 kW

10 2 Maximum Inverse Power 10% 0-20%

11 2 Maximum PICK UP speed 1740 rpm

12 2 Minimum PICK UP speed 1350 rpm

13 2 Maximum MAINS Voltage 440V

14 2 Minimum MAINS Voltage 360V

15 2 Maximum MAINS Frequency 55Hz

16 2 Minimum MAINS Frequency 45Hz

17 2 Minimum battery voltage 8V (16V) 8-23

18 2 Transfer Fuel Pump: minimum fuel level 30% 15%-40%

19 2 Transfer Fuel Pump: maximum fuel level 80% 70%-90%

20 2 Starting voltage in genset signal 40V 30-100

21 2 Starting voltage in alternator signal 8V (21v) 6-23

22 2 Starting speed (PICK UP) 1000 rpm 300-1000

24 2 Teeth of the engine ring gear 0 0-300

25 2 Fuel reserve level 10% 0..30

26 2 Low oil pressure threshold 1.2 bar 0.5-3

27 2 High coolant temperature threshold 98ºC 80-105

28 2 Low coolant temperature by sensor OFF OFF(0ºC)-40ºC

29 2 Minimum pre-heating temperature 25ºC 5 – 30ºC

30 2 Maximum pre-heating temperature


2 35ºC 10 – 40ºC
ALARMS
Default
Parameter Psw Description Range
Value
0-Not checked
1-Always checked
2-During starting
Alarm 0 management
1 1 3-From starting condition
3 High coolant temperature
(stabilized)
4- From nominal condition
(Running)
2 3 Alarm 0 delay 0’’ 0”…5”

0-Not stop the engine


3 3 Alarm 0 mode 1 1-Stop the engine
2-Stop with cooling

Alarm 1 management
4 4 0..4
3 Low oil pressure
5 3 Alarm 1 delay 15’’ 0”…30”
6 3 Alarm 1 mode 1 0..2
Alarm 3 management
10 2 3 0..4
Battery alternator charge failure
11 2 Alarm 3 filter 5’’ 0”…30”
12 2 Alarm 3 mode 0 0..2
Alarm 5 management
16 1 0..4
3 Low Coolant Level
17 3 Alarm 5 delay 5’’ 0”…30”
18 3 Alarm 5 mode 1 0..2
Alarm 6 management
19 2 1 0..4
Fuel Reserve
20 2 Alarm 6 delay 5’’ 0”…30”
21 2 Alarm 6 mode 0 0..2
Alarm 7 management
22 2 4 0..4
Overspeed
23 2 Alarm 7 filter 5’’ 0”…30”
24 2 Alarm 7 mode 1 0..2
Alarm 8 management
25 2 4 0..4
Underspeed
26 2 Alarm 8 filter 15” 0”…30”
27 2 Alarm 8 mode 2 0..2
Alarm 9 management
28 2 4 0..4
Overload
29 2 Alarm 9 filter 15 0”…30”
30 2 Alarm 9 mode 2 0..2
Alarm 10 management
31 2 3 0..4
Asymmetry
32 2 Alarm 10 filter 15 0”…30”
33 2 Alarm 10 mode 2 0..2
Alarm 11 management
34 2 3 0..4
Maximum Genset Voltage
35 2 Alarm 11 filter 5’’ 0”…30”
36 2 Alarm 11 mode 1 0..2
Alarm 12 management
37 2 4 0..4
Maximum Genset Frequency
38 2 Alarm 12 filter 1’’ 0”…30”
39 2 Alarm 12 mode 1 0..2
Alarm 13 management
40 2 4 0..4
Erroneous Phase sequence
41 2 Alarm 13 filter 5’’ 0”…30”
42 2 Alarm 13 mode 2 0..2
Alarm 14 management
43 2 4 0..4
Inverse power
44 2 Alarm 14 filter 15 0”…30”
45 2 Alarm 14 mode 2 0..2
Alarm 15 management
46 2 1 0..4
Low battery voltage
47 2 Alarm 15 filter 15 0”…30”
48 2 Alarm 15 mode 0 0..2
Alarm 16 management
49 2 High coolant temperature 1 0..4
(by sensor)
50 2 Alarm 16 filter 5’’ 0”…30”
51 2 Alarm 16 mode 0 0..2
Alarm 17 management
52 2 3 0..4
Low oil pressure (by sensor)
53 2 Alarm 17 filter 5’’ 0”…30”
54 2 Alarm 17 mode 0 0..2
Alarm 18 management
55 2 1 0..4
Low fuel level (by sensor)
56 2 Alarm 18 filter 5’’ 0”…30”
57 2 Alarm 18 mode 0 0..2
Alarm 19 management
58 2 4 0..4
Short-circuit
59 2 Alarm 19 filter __
60 2 Alarm 19 mode 2 0..2
Alarm 20 management
61 2 3 0..4
Minimum Genset Voltage
62 2 Alarm 20 filter 15’’ 0”…30”
63 2 Alarm 20 mode 2 0..2
Alarm 21 management
64 2 3 0..4
Minimum Genset Frequency
65 2 Alarm 21 filter 15’’ 0”…30”
66 2 Alarm 21 mode 2 0..2
Alarm 23 management
70 2 1 0..1
Stop Failure
71 2 Alarm 23 filter 3’’ 0”…30”
Alarm 24 management
73 2 1 0..4
Low Engine Temperature
74 2 Alarm 24 filter 15’’ 0”…30”
0-No condemn CG
75 2 Alarm 24 mode 0
1-condemn CG
Alarm 25 management
76 2 4 0..4
Genset signal failure
77 2 Alarm 25 filter 30’’ 0”…30”
78 2 Alarm 25 mode 2 0..2
Alarm 26 management
79 2 0 0..4
Programmable alarm 1

80 2 Alarm 26 delay 0’ 0”…30”

81 2 Alarm 26 mode 0 0..2


Alarm 27 management
82 2 0 0..4
Programmable Alarm 2
83 2 Alarm 27 delay 0’ 0”…30”

84 2 Alarm 27 mode 0 0..2

Alarm 28 management
85 2 0 0..4
Programmable Alarm 3
86 2 Alarm 28 delay 0’ 0”…30”

87 2 Alarm 28 mode 0 0..2


0..1
Alarm C1 management 0.Not checked
88 2 1
Maximum Mains voltage failure 1.Checked and if an error is
found, the engine is started
89 2 Alarm C1 filter 5’’ 0”…30”

Alarm C2 management
90 2 1 0..1
Minimum Mains voltage failure

91 2 Alarm C2 filter 5’’ 0”…30”


Alarm C3 management
92 2 1 0..1
Maximum Mains frequency failure
93 2 Alarm C2 filter 5’’ 0”…30”

Alarm C4 management
94 2 1 0..1
Minimum Mains frequency failure

95 2 Alarm C4 filter 5’’ 0”…30”

Alarm C5 management
96 2 1 0..1
Mains sequence failure

97 2 Alarm C5 filter 5’’ 0”…30”

Alarm C6 management
98 2 1 0..1
Mains power failure

99 2 Alarm C6 filter 5’’ 0”…30”


0.Not checked
Alarm C7 management
100 2 1 1.Checked and if an error is
MC switching failure
found, the engine is started
0. Not checked
Alarm C8 management 1. Checked and if an error is
101 2 1
GC switching failure found, the engine is stop with
cooling
PROGRAMMING
Default
Parameter Psw Description Range
Value

0-No programmed
1 2 Programmable Output Mode 1 0 1-FR input
2-LOP alarm
3- HCT alarm
4- CL input
5- INT4 input
6- INT5 input
2 2 Programmable Output Mode 2 0 7- EMS alarm
8- INT1 input
9- INT2 input
10- INT3 input
11-Coolant Heater
3 2 Programmable Output Mode 3 0 12-Bloqued Mode
13-Manual Model
14-Auto Mode
15-Test Mode
16-Alternator Alarm
17-Prg Alarm 1
4 2 Programmable Output Mode 4 0 18- Prg Alarm 2
19- Prg Alarm 3

5 2 Input associated to CKR Mode 0

6 2 Input associated to CKG Mode 0

7 2 Input associated to EJP1 Mode 0

8 2 Input associated to EJP2 Mode 0


0-No programmed
9 2 Input associated to IA Mode 6 5- INT4
6- ENT5
10 2 Input associated to AE Mode 5
8-ENT1
11 2 Input associated to TEST Mode 0 9-ENT2
10-ENT3
12 3 Input associated to MFOR Mode 0

13 2 Input associated to AL1 Mode 0

14 2 Input associated to AL2 Mode 0

15 2 Input associated to AL3 Mode 0


Annex II: CEA6 device display. Figures and readings.
Status of the device.
The CEA6 status can be read in the display and allows the user to gain access to the different figures and
readings by means of the UP/DOWN buttons.

The display of the amperage figures depends on the locational configuration of the current transformers
(Regulations table parameter 24):
• Amperage readings in output line. The amperage value is shown in the mains or generator
display, depending on which contactor (mains or genset) is ON. In the display where no
amperage reading is shown, the numeric value is replaced by a dash symbol.
• Amperage readings in genset control panel: The amperage obtained is shown on the genset
display.

Mains figures displayed.


1 .- Voltage readings between-phases and the amperage readings in each phase; and frequency.

M A I N S : 5 0 . 0 H Z
V 1 2 4 0 0 V I 1 - A
V 2 3 4 0 0 V I 2 - A
V 3 1 4 0 0 V I 3 - A

2 .- Voltage readings between the different phases, and neutral phase and the amperage per phase,
and frequency.

MA I N S : 5 0 . 0 H Z
V 1 N 2 3 0 V I 1 - A
V 2 N 2 3 0 V I 2 - A
V 3 N 2 3 0 V I 3 - A

Generator figures displayed.


3. - Voltage readings between the different phases, and neutral phase and the amperage per phase,
and frequency.

G E N E R A T O R : 5 0 . 0 H z
V 1 N 2 3 0 V I 1 0 A
V 2 N 2 3 0 V I 2 0 A
V 3 N 2 3 0 V I 3 0 A

4 .- Voltage readings between-phases and the amperage readings in each phase; and frequency.

G E N E R A T O R : 5 0 . 0 H z
V 1 2 4 0 0 V I 1 0 A
V 2 3 4 0 0 V I 2 0 A
V 3 1 4 0 0 V I 3 0 A
5 .- V., A., FL, RPM., P. readings, The voltage and amperage readings are displayed alternatively. FL fuel
level, RPM engine speed. P actual power output.

G E N E R A T O R : 5 0 . 0 H z
V 1 N 2 3 0 V I 1 0 A
F L 7 5 % R P M 1 5 0 0
P 0 k W

Engine status display.


6. - RPM., H., FL, DT, ET, BV,OP, readings.
Readings displayed: RPM engine speed, H working hours, FL fuel level, DT battery charging alternator
output voltage, ET engine temperature, BV battery voltage, OP oil pressure..

E N G I N E : 1 5 0 0 R P M 1 0 0 H
F L 7 5 %
D T 2 4 V E T 7 0 º C
B V 2 4 V O P 6 . 7 B A R

NOTE: The engine must be provided with the appropriate VDO sensors, in order to visualize the temperature and
the oil pressure.

Control board status display.


7 .- Status of the programmable alarms.

Programmable
inputs status

G E N S E T : S T O P
s I 9 A E C K G C K R 9 K -
T F J P 1 J P 2
I N H I B I T E D S T A R T

Power and energy display.


NOTE: The power display shows the stored power and the date /hour if the programming timer option is
available

8 .- Actual power values and cos. phî. per phase.

P OWE R : F P 1 . 0 0 L
3 0 k W F P 1 1 . 0 0 L
3 0 k V A F P 2 1 . 0 0 L
0 k V A R F P 3 1 . 0 0 L
9. - Total consumed power values (day, month, year).

E N E R G Y : P 3 0 k W h
D 1 0 K W h
M 1 0 0 M W h 1 7 : 5 6 : 2 3
Y 1 0 0 0 M W h 4 / 1 2 / 0 6 L

Failures record.

* A L A R M * E N 1 / 3

M I N . V O L T S G E G E N S E T

E: Alarm. N: Number of failure


A: Warning. in the record.

N: To be N: Nº of position in the
checked. total record of failures.

Control board maintenance.


Introducing password.
The main menu is, at the least, protected by one user password level (1111)
With this kind of password level, we do not have access to the Parameters option.

* * * * * * * M E N U * * * * * * *
P a s s w o r d
0 0 0 0

Main menu.
In the main menu display we can visualize:
1. Outputs / Inputs
2. Parameters (only with authorized code)
3. Counters
4. Fault History
5. Events (only with programming clock option)
6. Date/ Hour
7. Language
8. Password

* * * * * * * M E N U * * * * * * *
Æ 1 . I n p u t s / o u t p u t s
2 . P a r a m e t e r s
T 3 . C o u n t e r s
* * * * * * * M E N U * * * * * * *
Æ 4 . F a u l t H i s t o r y
S 5 . E v e n t
T 6 . D a t a / H o u r

* * * * * * * M E N U * * * * * * *
Æ 7 . L a n g u a j e
S 8 . P a s s w o r d
T

1. Inputs / Outputs.

* I N P U T S / O U T P U T S *
3 2 1 0 9 8 7 6 5 4 3 2 1
I N : M S 3 2 1 P I X N A B R
O U T : C P R 4 B g r 3 2 + 1 M A A: Active alarm
R: Fuel level M: Engine started
B: Low temperature pressure 1:Programmable output 1.
A: High temperature +: D+
N: Coolant level 2: Programmable output 2.
X: Programmable input 4. 3: Programmable output 3.
I: Programmable input 5. r: Mains contactor
P: Emergency stop. g: Generating set contactor.
1: Programmable input 1. B: Fuel transfer/Heating
2: Programmable input 1. 4: Programmable output 4.
3: Programmable input 1. R: PR/PD
S: Stop button. P: PD/PE
M: Start key. C: Controller fitting.

A N A L O G I C A L I N P U T S
F L 0 . 0 P A 0 . 0
E T 0 . 0 A A 0 . 0
D I 0 . 0 V V B 0 . 0 V

FL: Fuel level


OP: Oil pressure
ET: Engine Temperature
AA: Auxiliary analog
DI: Dinamo Voltage
BV: Battery Voltage
3. Counters.

* * * * C O U N T ER S * * * *
ÆT o t a l ho u r s 0 1 : 0 0 : 0 0
B i a s e d h o u r s 0 0 : 1 0 : 0 0
T N o r ma l s t a r t u p s 1 1 0

* * * * C O U N T E R S * * * *
Æ F a i l t o s t a r t u p s 5
S T o t a l 5 0 k W h
T A t p r e s e n t 1 0 k W h

* * * * C O U N T E R S * * * *
Æ D a y 2 0 k W h
S M o n t h 5 0 M W h
T Y e a r 1 0 0 M W h

Partial counters can be reset by pushing the RESET button for 5 seconds

4. List of failures.

* L I S T O F F A I L U R E S *
Æ1 . M A I N S M A X V O L T A G E
2 . M A I N S M I N V O L T A G E
T3 . M A I N S M A X F R E Q U E N
5. Events.
The CEA6 device needs to have the programming timer option installed if the user wants to programme
its working.

* * * * * E V E N T S * * * * *
ÆM o n d a y
T u e s d a y
T W e d n e s d a y

* * * * * E V E N T S * * * * *
Æ T h u r s d a Y
S F r i d a y
T S a t u r d a y

* * * * * E V E N T S * * * * *
ÆS u n d a y

* * * * * Mo n d a y * * * * *
ÆB L O Q 1 0 : 0 0 . . 1 1 : 0 0
F O R S 1 5 : 5 0 . . 1 7 : 0 0
T T E S T 2 0 : 0 0 . . 2 2 : 0 0

6. Data / Hour.

* * * D A T A / H O U R * * *

ÆH o u r : 1 1 : 0 0 : 5 5
D a t a : 1 0 / 1 2 / 0 6 D
7. Language selection.

* * * L A N G U A J E * * *
Æ 0 . S p a n i s h
1 . F r a n c a i s
2 . E n g l i s h

8. Password configuration.

* * * * P A S SWO R D * * * *
Æ 0 . U s e r
1 . M a i n t e n a n c e

* * * * U S U A R I O * * * *
P a s s w o r d
New password
1 1 1 1
Old password 0 0 0 0

Control board programmation.


The access of the main menu is restricted to, at least, a password of the maintenance level.

* * * * P A R A M E T E R S * * * *
Æ 1 . M e a s u r e m e n t S
2 . T i m e s
T 3 . R e g u l a t i o n s

* * * * P A R A M E T E R S * * * *
Æ 4 . T h r e s h o l d s
S 5 . A l a r m s
T 6 . P r o g r a m a t i o n I / O

* * * * P A R A M E T E R S * * * *
Æ 7 . T e x t s
S 8 . I d e n t i f i c a t o r

* * * * M E A S U R E M E N T S * * * *
Æ P 0 1 . . . . . . . . . . . 4
S P 0 2 . . . . . . . . . . . 5
T P 0 3 . . . . . . . . . . . 0
Texts.

* * * * T E X T S * * * *
Æ 1 . P R O G R A M M A B L E 1
2 . P R O G R A M M A B L E 2
T 3 . P R O G R A M M A B L E 3

* * * * T E X T S * * * *
Æ 4 . D I S P L A Y

Text personalization of the programmable alarms.


From the option of Controller texts programming, the personalization of the texts associated to the
programmable alarms is allowed.

Personalization of manufacturer’s screen.


From the option of Controller texts programming, the personalization of manufacturer’s screen is allowed.

H I MO I N S A
3 0 7 3 0 S A N J A V I E R
M U R C I A ( S p a i n )
T l f . + 3 4 9 6 8 1 9 1 1 2 8
Annex III: Dimensions, connections and mechanization.
Measures module.

Figure1: Measurement module connections.


Figure 2: Measurement module connections section 1.

Figure 3: Measurement module connections section 2.


To feed the badge it is advisable to use a cable of section 1 mm2.
Figure 4: Measurement module connections section 3.

Figure 5: Measurement module connections section 4.


Figure 6: Measurement module connections section 5.
SIGNAL DESCRIPTION TYPE CHARACTERISTICS
8±36V Battery positive Feeding Feeding device voltage from 8 to 36 V
-BAT Battery negative Feeding Negative device feeding
MAN Manual Input Digital input of starting PNP
CANL CANH line CAN bus Bus CAN communication
CANH CANH line CAN bus Bus CAN communication
FR Fuel reserve Input NPN digital input
LOP Low oil pressure Input NPN digital input
HCT High coolant temperature Input NPN digital input
CL Coolant level Input NPN digital input
ES External start Input NPN digital input
IS Inhibited starting Input NPN digital input
EMS Emergency stop Input NPN digital input
INT1 Input 1 Input NPN digital input
INT2 Input 2 Input NPN digital input
INT3 Input 3 Input NPN digital input
PCK1 Pick-up Input High speed digital input PICK-UP
PCK2 Pick-up Input High speed digital input PICK-UP
FL Fuel level Input Digital input of resistive sensor
P Pressure Input Digital input of resistive VDO sensor
T Temperature Input Digital input of resistive VDO sensor
AnC Analog auxiliary input Input Digital input of resistive VDO sensor
DI Alternator voltage Input Analog voltage input 0-40V
GND VDO sensors Input Negative to 2 terminals sensors type
D+ Alternator excitation Output PNP digital input
AL Alarm Output PNP digital input
SE Started engine Output PNP digital input
OUT1 Output 1 Output PNP digital input
OUT2 Output 2 Output PNP digital input
OUT3 Output 3 Output PNP digital input
EMER Emergency button (SETA) Output NPN digital input
CS Configurable stop Output Power PNP digital input
PH Pre-heating Output Power PNP digital input
START Starting Output Power PNP digital input
OUT4 Output 4 Output Power PNP digital input
+BAT Battery positive Feeding Digital inputs feeding voltage
FPC Fuel pump Output Fuel pump relay, C contact
FPNA Fuel pump Output Fuel pump relay, NA contact
GCC Genset contactor Output Genset contactor relay, C contact
GCNC Genset contactor Output Genset contactor relay, NC contact
GCNO Genset contactor Output Genset contactor relay, NO contact
MCC Mains contactor Output Mains contactor relay, C contact
MCNC Mains contactor Output Mains contactor relay, NC contact
MCNO Mains contactor Output Mains contactor relay, NO contact
IL3 Phase 3 amperage Input Amperage measurement analog input
IL2 Phase 2 amperage Input Amperage measurement analog input
IL1 Phase 1 amperage Input Amperage measurement analog input
ILN Shared amperage Input Amperage measurement analog input
MV3 Phase 3 mains voltage Input Voltage measurement analog input
MV2 Phase 2mains voltage Input Voltage measurement analog input
MV1 Phase 1mains voltage Input Voltage measurement analog input
MVN Neutral mains voltage Input Voltage measurement analog input
GV3 Phase 3 genset voltage Input Voltage measurement analog input
GV2 Phase 2 genset voltage Input Voltage measurement analog input
GV1 Phase 1 genset voltage Input Voltage measurement analog input
GVN Neutral genset voltage Input Voltage measurement analog input
75.8
36

188 171

117.00

202.00

Figure 7: Measurement module dimensions.


Visualization module.

FEEDING CANBUS

8-36V -BAT 8-36V -BAT MAN AUTO CANL CANH CANL CANH

BAT

CAN BUS

Figure 8: Visualization module connections 1.


To feed the badge it is advisable to use a cable of section 1 mm2.
SIGNAL DESCRIPTION TYPE CHARACTERISTICS
8÷36V Battery positive Feeding Feeding device voltage from 8 to 36 V
-BAT Battery negative Feeding Negative device feeding
MAN Manual Input Digital input PNP
AUTO Automatic Input Digital input PN
CANL CANL line bus CAB Bus CAN communication
CANH CANL line bus CAB Bus CAN communication

Figure 9: Visualization module dimensions 1.


Electric characteristics.
Symbol Parameter Conditions Min Usual Max Unit
Feeding (terminals 8÷36V, –BAT, +BAT)
8÷36V Power supply voltage of the unit 8 36 VDC
+BAT Power supply voltage of the outputs 8 36 VDC
IBAT Feeding force 8÷36V=12V 100 mA
IBAT Feeding force 8÷36V=24V 50 mA
PBAT Power consumption 1,2 W
CAN Bus (terminals CANL, CANH)
VIN CANH y CANL input voltage -27 +40 V
DRCAN Transmission speed 50 Kbps
LCAN Bus length 500 m
Nodos Number of nodes on the bus 20 nodos
Digital inputs PNP (terminals MAN)
VIN Voltage input -0,7 40 V
VIL Low level voltage input 1 V
VIH High level voltage input 5 V
IIL Low level power supply voltage VIN = 0V 0 100 uA
IIH High level power supply voltage VIN = 12V 0,8 1 mA
Digital inputs NPN (terminals FR, LOP, HTC, CL, AE, IA, PEM, ENT1, ENT2, ENT3, SETA)
VIN Low level voltage input -0,7 40 V
VIL High level voltage input 1 V
VIH Low level power supply voltage 5 V
IIL High level power supply voltage VIN = 0V 2 2,5 mA
IIH Low level voltage input VIN = 24V 0 100 uA
High speed digital inputs (terminals PCK)
VIN Input voltage 30 VAC
IIN Input power supply VIN=12VAC 2,6 3 mA
FIN Input frequency VIN=12VAC 3600 Hz
Analog inputs (terminals NC, P, T, TC, DI, GND)
VI Voltage input 5 V
RNC Fuel level resistance 0 400 Ω
RP Pressure resistance 0 200 Ω
RT Coolant temperature resistance 0 4000 Ω
RTC Oil temperature resistance 0 4000 Ω
DI Alternator voltage 0 40 V
PNP outputs (terminals D+, AL, MA, SAL1, SAL2, SAL3)
VO Output voltage +BAT V
IO Output amperage 1 A
RD+ D+ output resistance 47 Ω
Power PNP outputs (terminals PC, PR, ARR, SAL4)
VO Output voltage +BAT V
IO Output power supply T=∞ 20 A
IO Output power supply T = 1s 40 A
Relay outputs (terminals CRNA, CRNC, CRC, CGNA, CGNC, CGC, BTNA, BTC)
VO Relay contactors maximum voltage 250 VAC
IO Relay contactors power cosϕ = 0 8 A
Amperage values analog inputs (terminals NIL, IL1, IL2, IL3)
IIN Input feeding power 5 AAC
RIN Input resistance 0,05 Ω
Voltage measurements analog inputs (terminals NVR, VR1, VR2, VR3, NVG, VG1, VG2, VG3)
VIN-FF Phase to phase voltage input 600 VAC
VIN-FN Phase to neutral voltage input 350 VAC
RIN Input resistance 1 MΩ

Annex IV: CAN communications.


Introduction.
The CAN bus is a powerful and reliable industrial bus that ensures the efficient communication between
the devices in the environments full of electric disturbances. The devices provided with CAN controller can
be integrated into an industrial system of control and automation.

The most important characteristics of a control system with CAN bus communication are the following:
• It is possible to connect up to 110 devices in a single CAN network.
• Each network can reach a length of 1000 meters, easily extended (up to 2000 meters) with the use of
bridges or repeaters.
• CAN bus transmission speed 50 Kbits/s (for 1000 meters bus: 10 ms of data updating).
• Direct access to the CAN bus from a PC by means of a USB Can.
The Can bus is prepared to work in extreme conditions of noise and interferences and at the same time,
the failure checking mechanisms guarantee that the frames affected by the disturbance can be detected.
The CAN bus is designed to continue the communication even if:
• Any of the two bus wires cuts.
• Any cable is short-circuited to earth.
• Any cable is short-circuited to feeding.

Topology
The Can network uses a bus topology in which each node has an input and an output connection, The
endpoint nodes of the bus must have a 120Ω terminator: this terminator is activated by means of a switch
in each module (ON: enabled terminator, 1: disabled terminator). In each case, the impedance found
between the CANH and CANL must be, approximately, 60Ω. To do so, in each network endpoint a
resistance value must be defined to guarantee such impedance value from every connected device.

The impedance measurement must be obtained when all the equipments are not working or they have
not physical access from the network.
For more information it is recommended to consult the ISO11898 standards and the different applications
notes.

CAN bus topology.


Wiring.
The can network needs a wiring depending of the distance, the speed transmission, and the number of
nodes connected to the bus.

Wire characteristics
Bus length
Length/resistance Diameter
0,25 mm2..0,34 mm2
0 m..40 m 70 mΩ/m
AWG23,AWG22
0,34 mm2..0,6 mm2
40 m..300 m <60 mΩ/m
AWG22,AWG20
0,5 mm2..0,6 mm2
300 m..600 m <40 mΩ/m
AWG20
0,75 mm2..0,8 mm2
600 m..1 Km <26 mΩ/m
AWG18
Table 1: Wire characteristics according the distance.

Number of nodes
Bus length
32 64 100
100 m 0,25 mm2 0,25 mm2 0,25 mm2
250 m 0,34 mm2 0,50 mm2 0,50 mm2
500 m 0,75 mm2 0,75 mm2 1,00 mm2
Wire resistance <21Ω <18,5Ω <16Ω

Table 2: Wire characteristics according the number of nodes.

In order to connect the different nodes of the network a twisted pair without shielding is needed. As an
exception, the connection between the measurement and the visualization module can be done using a
wiring not twisted.
In very noisy environments affected by high electromagnetic interference (EMI), a twisted shielded wire
with the shield connected to earth can be used. Other technique to improve the immunity against the
electromagnetic interference consists in substituting the CAN terminator of the node for 2 resistances of 62
Ω and installing a decoupling capacitor between the resistances CAN and the battery negative.

Protection technique against electromagnetic interferences: Decoupling capacitor.


Wiring diagrams.
120Ω
MEASUREMENTS

H L H L O

120Ω

H L H L
O
DISPLAY

Figure 1:Device
MANUAL/AUTOMATIC

MANUAL COMMUTATION
120Ω 120Ω
MEASUREMENTS MEASUREMENTS

H L H L O H L H L O

120Ω 120Ω

H L H L H L H L
O O
DISPLAY DISPLAY

Figure 2: Device
MANUAL + COMMUTATION

120Ω 120Ω
MEASUREMENTS CCrs

H L H L O H L O

120Ω

H L H L
O
DISPLAY

Figure 3: MANUAL/AUTOMATIC DEVICE + CCrs OPTION


120Ω 120Ω
MEASUREMENTS 1 USBCan

H L H L O O
L H 9

120Ω

H L H L
O
DISPLAY

Figure 4: MANUAL/AUTOMATIC DEVICE + CCrs OPTION

MANUAL COMMUTATION
120Ω 120Ω
MEASUREMENTS MEASUREMENTS

H L H L O H L H L O

120Ω 120Ω

H L H L H L H L
O O
DISPLAY DISPLAY

120Ω
CCrs
H L
O

Figure 5: Device
MANUAL + COMMUTATION + CCRs
Annex V: Telesignal: Communication option by digital
outputs.
Introduction:
The range of CEA6, CEM6 and CEC6 controllers allow the monitoring of the devices status by means of a
number of relay outputs. The Telesignal option is connected to the range of CeA6 devices of Himoinsa
through a CAN communication cable. The configuration software of the controlboards, configured in local
mode (USB can) or remote (CCrs), allows the adjustment of its functions.
The Telesignal option is connected to the Cex6 Himoinsa controlboard with a twisted pair with or without
shielding; depending of the installation environment and it can even be of 1 Km length. The CEX6 device
allows the installation of 4 optional Telesignal equipments simultaneously.

Telesignal components:
• Feeding and communication terminal plate
• Terminal plate of digital outputs to relay
o 4 contact outputs NC/CL.
o 8 contact outputs CL
• 1 feeding led
• 12 LEDs to visualize the output status.
• Activation Microswitch, CAN terminator.
• Microswitch of 2 switches to fix the number of modules (maximum 4)

Figure 1: Telesignal module.


Telesignal programation.
The Telesignal option allows the output programation in order to monitor the status of the CEx6 device.
This programation option showed below will be available if the Telesignal option is installed. On the left of
the screen, a tree view presents all the activation conditions of each output.

Figure 2: Telesignal configuration.

The programation process of an output is the following:


1. Select the item referring the chosen output.
2. Select the file where the activation conditions we want to apply to the selected output can be
found
3. Select the desired condition.
4. Repeat the process with all the conditions needed.

By pressing the “General Alarm” button all the possible alarm conditions to activate the output are
selected.

Working mode.
The outputs of the Telesignal option can be programmed to be activated depending on:
• Any alarms of the controlboard, active or waiting to be checked.
• Any activated input of the controlboard.
• Any activated output of the controlboard.
Each output of the Telesignal device is activated if, at least, one of the programmed activation conditions is
raised.
Wiring of the Telesignal option

SIGNAL DESCRIPTIÓN TYPE CHARACTERISTICS


8÷36V Battery positive Feeding Controlboard Feeding voltage from 8 to 36V
-BAT Battery negative Feeding Controlboard negative feeding
8÷36V Battery positive Feeding Controlboard Feeding voltage from 8 to 36V
-BAT Battery negative Feeding Controlboard negative feeding

CANL CANL line CAN bus Bus CAN communication


CANH CANH line CAN bus Bus CAN communication
CANL CANL line CAN bus Bus CAN communication
CANH CANH line CAN bus Bus CAN communication
C1 Common relay output 1 Digital output Voltage free contact 8 A 250 VAC
NC1 Normally-closed contact Digital output Voltage free contact 8 A 250 VAC
relay output 1
NA1 Normally-open contact Digital output Voltage free contact 8 A 250 VAC
relay output 1
C2 Common relay output 1 Digital output Voltage free contact 8 A 250 VAC
NC2 Normally-closed contact Digital output Voltage free contact 8 A 250 VAC
relay output 2
NA2 Normally-open contact Digital output Voltage free contact 8 A 250 VAC
relay output 2
C3 Common relay output 2 Digital output Voltage free contact 8 A 250 VAC
NC3 Normally-closed contact Digital output Voltage free contact 8 A 250 VAC
relay output 3
NA3 Normally-open contact Digital output Voltage free contact 8 A 250 VAC
relay output 3
C4 Common relay output 3 Digital output Voltage free contact 8 A 250 VAC
NC4 Normally-closed contact Digital output Voltage free contact 8 A 250 VAC
relay output 4
NA4 Normally-open contact Digital output Voltage free contact 8 A 250 VAC
relay output 5
C5 Common relay output 3 Digital output Voltage free contact 8 A 250 VAC
NC5 Normally-closed contact Digital output Voltage free contact 8 A 250 VAC
relay output 4
C6 Common relay output 3 Digital output Voltage free contact 8 A 250 VAC
NC6 Normally-closed contact Digital output Voltage free contact 8 A 250 VAC
relay output 4
C7 Common relay output 3 Digital output Voltage free contact 8 A 250 VAC
NC7 Normally-closed contact Digital output Voltage free contact 8 A 250 VAC
relay output 4
C8 Common relay output 3 Digital output Voltage free contact 8 A 250 VAC
NC9 Normally-closed contact Digital output Voltage free contact 8 A 250 VAC
relay output 4
C9 Common relay output 3 Digital output Voltage free contact 8 A 250 VAC
NC9 Normally-closed contact Digital output Voltage free contact 8 A 250 VAC
relay output 4
C10 Common relay output 3 Digital output Voltage free contact 8 A 250 VAC
NC10 Normally-closed contact Digital output Voltage free contact 8 A 250 VAC
relay output 4
C11 Common relay output 3 Digital output Voltage free contact 8 A 250 VAC
NC11 Normally-closed contact Digital output Voltage free contact 8 A 250 VAC
relay output 4
C12 Common relay output 3 Digital output Voltage free contact 8 A 250 VAC
NC12 Normally-closed contact Digital output Voltage free contact 8 A 250 VAC
relay output 4
The CAN network of the controlboard has a BUS based topology. The different devices are consecutively
connected, using the CANH and CANL input and output terminals to link the modules.

The terminating resistors will be connected to the network terminal nodes, using the appropriate
microswitch.

The maximum distance between the terminal nodes of the network is 1000m

Dimensions and connections.

Figure 18: Telesignal module 1 connections.

8-36V -BAT 8-36V -BAT CANL CANH CANL CANH

BAT

CAN BUS

Figure 18 : Telesignal module 2 connections.


To feed the plates it is advisable to use 1 mm2 diameter cable

Figure 20: Telesignal module 3 connections.

SIGNAL DESCRIPTION TYPE CHARACTERISTICS


8÷36V Battery positive Feeding Controlboard feeding voltage from 8 to 36V
-BAT Battery negative Feeding Feeding controlboard negative
CANL CANL line CAN bus Bus CAN communication
CANH CANH line CAN bus Bus CAN communication
C1 Relay 1 Output Relay 1, contact C
NC1 Relay 1 Output Relay 1, contact NC
NA1 Relay 1 Output Relay 1, contact NA
C2 Relay 2 Output Relay 2, contact C
NC2 Relay 2 Output Relay 2, contact NC
NA2 Relay 2 Output Relay 2, contact NA
C3 Relay 3 Output Relay 3, contact C
NC3 Relay 3 Output Relay 3, contact NC
NA3 Relay 3 Output Relay 3, contact NA
C4 Relay 4 Output Relay 4, contact C
NC4 Relay 4 Output Relay 4, contact NC
NA4 Relay 4 Output Relay 4, contact NA
C5 Relay 5 Output Relay 5, contact C
NA5 Relay 5 Output Relay 5, contact NA
C6 Relay 6 Output Relay 6, contact C
NA6 Relay 6 Output Relay 6, contact NA
C7 Relay 7 Output Relay 7, contact C
NA7 Relay 7 Output Relay 7, contact NA
C8 Relay 8 Output Relay 8, contact C
NA8 Relay 8 Output Relay 8, contact NA
C9 Relay 9 Output Relay 9, contact C
NA9 Relay 9 Output Relay 9, contact NA
C10 Relay 10 Output Relay 10, contact C
NA10 Relay 10 Output Relay 10, contact NA
C11 Relay 11 Output Relay 11, contact C
NA11 Relay 11 Output Relay 11, contact NA
C12 Relay 12 Output Relay 12, contact C
NA12 Relay 12 Output Relay 12, contact NA
ELECTRIC CHARACTERISTICS
Symbol Parameter Conditions Minimu Usual Maximu Unit
m m

Feeding (terminals 8÷36V, –BAT)


8÷36V Power supply voltage of the unit 8 36 VDC
IBAT Feeding force 8÷36V=12V mA
IBAT Feeding force 8÷36V=24V mA
PBAT Power consumption W

CAN Bus ( CANL, CANH terminals)


VIN CANH y CANL input voltage -27 +40 V
DRCAN Transmission speed 50 Kbps
LCAN Bus length 250 m
Nodes Number of nodes on the bus 20 nodes

Relay outputs (Terminals C1, NC1, NA1, C2, NC2, NA2, C3, NC3, NA3, C4, NC4, NA4, C5, NA5, C6, NA6, C7,
NA7, C8, NA8, C9, NA9, C10, NA10, C11, NA11, C12, NA12)
VO Relay contactors maximum voltage 250 VAC
IO Relay contactors power cosϕ = 0 8 A
75

174

Figure 21: Telesignal module dimensions.

Annex VI: CCrs: Communication option via modem.


Introduction.

The range of CEA6, CEM6 and CEC6 controllers allow a remote monitoring and supervision function
thanks to the CCrs option. This option allows to establish a connection between the controlboard and the
monitorization and configuration software, by means of a modem or GPRS (NOT INCLUDED with the
CCrs option)

CCrs installation.

System requirements.
The CCrs option needs the following elements to obtain a remote connection:
• PC that fulfils the following requirements to execute the monitorization and configuration software:
o Pentium III 1.3 GHz
o Microsoft Windows XP with Microsoft .Net Framework 2.0
o 512 Mb RAM
o 50 Mb free in the hard disk
o Modem 14400 or superior (line modem or GPRS)
• Modem and serial cable to connect to the CCrs
• Optional: a null modem type cable and CCrs configuration software.

Communicating with the controlboard.


The Pc software of the controlboard automatically detects (when starting) if a local connection of
communications (USB Can option) is available or if it is detected a remote connection via modem. In case
a remote connection is found, a dialog box will appear waiting to enter the required parameters to establish
the communication.

Figure 3: Parameter box of remote communication


Communication parameters required:
• Telephone number of the controlboard.
• PIN: Pin of the SIM if required
• Password: Controlboard password, at least user level password.
• Kind of modem: Line or GPRS.
• Locate option.
The introduced parameters can be stored for the next use (except the controlboard password)

In the same way, a kind of "waiting connection" can be done, capable of allowing the connection between
the controlboards and the PC software in case any event occurs in the registration moment.

Once the dialing data are introduced, the software of the PC tries to establish the connection with the
controlboard.

Figure 4: Connection with the controlboard screen

As soon as the connection with the controboard is confirmed, the monitorization or configuration software
of the controlboard starts running.

You might also like