Manual PRO CEA6 - IN
Manual PRO CEA6 - IN
The CEA6 controller unit is a device able to control the operation, monitoring and protection of a
generating set. The controller unit consists of 2 different modules:
- Visualization module. The visualization module provides information about the status of the device
and, at the same time, allows the user to interact with it. With this visualization module the user is
able to control, program and configure the functions of the unit. This visualization module allows the
checking of the last ten failures registered in the control unit (Fault history).
- Measurements module. The measurements module controls and monitors the control board. It is
located in the rear part of the panel, in order to reduce the wiring and to avoid electromagnetic
disturbances. Every signal, sensor and actuator is connected to this module.(see Annex III figures)
NOTE: As an option, a programming timer module can be added to the measures module. It
can be programmed to execute automatic starting, stopping and programmed maintenance.
Likewise the programming clock module allows to extend the historical failures records
capacity.
The measurements module provides the following readings of the electric mains supply.
o Configurable inputs; the measurements device has 5 inputs that can be programmed
to carry on the following functions:
Mains contactor confirmation.
Genset contactor confirmation.
Rate change notice.
Rate change.
Start disabling.
External start.
Test.
Manual override.
3 programmable alarms.
o Engine statistics:
Number of working hours.
Number of starts.
The measurements module controls the following functions of the engine:
Pre-heating or Glow Plug.
Stop.
Start.
Coolant heater.
Fuel Transfer pump.
Alternator excitation.
The measurements module has outputs which allow monitoring of the operative conditions of the
controller:
o Engine running (on).
o Control board alarm.
o 3 programmable outputs which monitor the control board alarm conditions or the inputs
about the engine data.
The measurement module controls the outputs to relays in order to activate mains and generating set
contactors.
The connection between the measurements and visualization modules is made by the CAN bus
communication, which allows the interconnection of additional modules, allowing the expansion of the
CEA6 device.
b) Command buttons.
c) Display buttons.
d) Contactors buttons.
3. Data LEDs
b) ALARMS LEDs
Confirmation button (V): Allows access to menu , validates and store the
entered data.
Cancellation button (X): Go back in the menu and cancels the entered data.
Up button (+): Moves along the selection displays and maintenance menus,
also increases the programmed values.
Down button (-): Moves back in the selection display and maintenance
menus, it also reduces the programmed values.
2.2.d. Contactors buttons.
Mains contactor
Switches to mains contactor (manual mode only).
Genset contactor
Switches to genset contactor (manual mode only).
Battery levels
High temperature
ALARMS
Aux1
(Free to programme)
Aux2
(Free to programme)
2.4. PASSWORD.
The CEA6 device has 3 passwords levels of four digits to avoid non authorised access. Those different
access levels are:
• User access (password stored: 1111). The user access level allows the entrance in the CEA6
main menu.
• Maintenance access: (password stored: 1911). The maintenance access level allows the use
of the parameter programming option in the main menu.
The passwords in the CEA6 can be changed by the user in the main menu. The user can change the
passwords in the user access level, as well as in lower access levels.
Pushing the START button activates the engine starting process (without deactivating the mains
contactor). Pushing the STOP button once stops the engine, with a cooling down cycle. Pushing the
STOP button twice stops the engine immediately, without cooling down phase.
With cooling.
Without cooling
NOTE: In manual mode, the safety devices of the controller remain activated, and if an anomaly is
detected, an alarm status is triggered.
In manual mode, the device ignores all external request previously programmed (i.e., Timer, ATS signal,
etc...).
Likewise, the activation of the mains and genset contactors is carried on by pushing RED/MAINS and
GRUPO/GEN buttons
The activation of the genset contactor is possible only if the engine is running and produces a stabilized
electric signal.
The activation of the genset contactor deactivates the mains contactor and vice versa; there is a waiting
time of one second (not programmable) between the contactors switching.
As programmable starting conditions of the genset without the activation of contactors, could be
considered:
- Rate change notice (Programming table parameter 7).
- Engine test
In test mode, the device does not control the functions related to the programmable inputs,
except the ones associated to the alarms.
5” LOCK 5” UNLOCK
5”
5” LOCK 5” UNLOCK
4. WORKING MODE.
4.1. Starting the engine.
The engine works in the following way, once the controller detects an activation condition:
- Delay in the starting: Once an activation condition is detected and before going on with the
engine starting process (automatic mode), a delay in the engine starting can be programmed
(Times table parameter 3)
- Engine pre-heating phase. The control board activates the pre-heating output for a programmed
time. (Times table parameter 4)
- Engine energizing (run signal): The engine run signal is made by means of the PC (B+) output
from the measurements module. The output allows a no-excitation Stop (energise to-run) or an
excitation stop (energise to-stop) (Times table parameter 12-This output is configurable.
(Regulations table parameter 18).
- Engine starting. For a programmed period of time (Times table parameter 5), the starting
output of the measurements module is activated, waiting to detect, at least, one of the
programmed starting conditions. The possible engine starting conditions could be:
o Low oil pressure. (Regulations table parameter 22). It is not advisable to use the low
oil pressure signal as a way to detect if the engine is working, but it is useful as a
protection, in order to avoid engaging the starter while the engine is running. Exception
for this "Engine Start Detection" option is SCANIA engines and also the sensors which
have self - electrical supply.
If in the programmed time the starting of the engine is not detected, the control board waits for a
short time (Times table parameter 2) before attempting a new start. The Start failure alarm will
be raised after a specified number of attempts without detecting any starting condition (Times
table parameter 1).
In the starting cycle, the excitation of the battery charge alternator is activated through the D+
output temporarily (Times table parameter 8). Once the excitation of the alternator is finished,
the measurements module checks if the battery charge alternator is working properly. The battery
charge alternator failure alarm is raised in case of an output failure. (Alarms table parameter
10).
- Engine stabilization: Once any of the starting conditions is detected, the controller waits for a
programmed stabilization-time of the generator output, before monitoring output parameters.
- Nominal condition. Once the stabilization of the engine is reached, the next step is the checking
of the signal produced by the generator. In this way, the quality of the signal produced by the
generator set is monitored (voltage levels, frequency…).
- Genset contactor activation. If it is included in the valid signal parameters, the mains contactor
is deactivated. Depending on the Genset Contactor Confirmation programming mode (
Programming table parameter 6), the control board will wait the confirmation of the contactor
closing for a maximum time (Times table parameter 13); If after such time the confirmation of the
contactor closing is not detected, the genset contactor alarm triggers and a stop with cooling-cycle
follows. The activation of the genset contactor is disabled by a low engine temperature
(Thresholds table parameter 29).
STAR FAILURE
NOTE: readings about the engine condition are shown on the display, and details about the start
operating process can be visualized. The sequence being as follows:
Genset: Stop
Genset : Starting
Genset : Started
Genset : Stabilized
Genset : Loading
NOTE.: The starting process in an automatic system by means of timer, ATS signal, etc... works in the
same way as a starting cycle in manual mode.
- Mains contactor activation. Once the generator stopping condition is detected there is a
verification time (Times table parameter 10) that checks if the quality of the mains signal is
considered as correct. Then the control board deactivates the genset contactor. Depending on
the configuration of the Mains Contactor Confirmation mode (Times table parameter 5), the
device waits fot the contactor closing confirmation during a maximum time(Times table
parameter 13); If after such time there is no confirmation of the mains contactor closing, the
mains contactor failure alarm will trigger and the engine will start again.
- Engine cooling down: Once all loads are disconnected, the engine will continue to run for
some time during the cooling time (Times table parameter 11). Under particular situations the
alarms of the controller may be programmed (Alarms table parameters 3, 6, 9...) to stop
immediately without the cooling down of the engine.
- Engine stop. After the cooling down of the engine, the PC output of the measurements module
is switched off or on, according to the programmed stop configuration (Regulations table
parameter 18). As a condition of the engine stop, it can be selected:
o Low Oil Pressure. (Regulations table parameter 22). The condition of Low Oil
Pressure considers the engine stopped when it detects that the sensor is closed.
Exception for this "Engine Start Detection" option is SCANIA engines and also the
sensors which have self - electrical supply.
All the programmed stopping conditions must be present for an interval of time (Alarms table parameter
71) to consider the engine as stopped. If after ten seconds it has not been detected any of the engine stop
conditions, the Stop Failure alarm will be activated.
NOTE: Before initiating the stop cycle, it is advisable that the main genset circuit breaker be switched OFF.
Sequence: Pressing the STOP button once, the stop cycle will
start with the engine cooling process. The STOP button will
light . (1)
NOTE: Readings about the engine condition are shown on the display, and details about the stop
operating process can be visualized. The sequence being as follows:
Genset : Stabilized
Genset : Cooling
Genset : Stopping
Genset : Stop
- Manual mode: the transfer pump is operated by pressing the diesel Transference button,
provided that the fuel level is under the maximum threshold parameters (Thresholds table
parameter 19)
- Automatic mode: the transfer pump becomes operative according to the minimum activation
parameters (Thresholds table parameter 18) under which the relay BT is activated/energised
and according to the maximum deactivation parameters (Thresholds table parameter 19),
over which the relay BT is de-energised.
- Control board mode: the transfer pump operation is carried out as follows:
o When the controller is in automatic or test-mode, the transfer pump is operated
automatically.
o When the controller is manual-mode, the transfer pump operation is carried out in
manual mode.
o When the controller is in a blocked-mode, the transfer pump operation is inhibited.
For an accurate fuel level measurement (needed for the fuel pump and fuel level alarm functions) a
calibration of the tank level sender must be done, by having access to both the minimum and maximum
parameters of the level sender (Measurements table parameters 12 and 13). To adjust the minimum fuel
level of the tank it must be recorded the parameter 12 of the measurement table with the level sender in its
minimum position. To adjust the maximum fuel level of the tank, it must be recorded the parameter 13 of
the measurement table with the level sender in its maximum position.
4.4. Pre-Heating.
The engine pre-heating allows 2 activation modes:
- Assigning to the BT relay of the measurement module, the pre-heating working process (
Regulations table parameter 4).
- Assigning to any of the 4 programmable outputs of the measurement module the pre-heating
working process (Programming table parameters 1 to 4), provided the BT relay of the
measurement module is in charge of the fuel transfer pump functions. (Regulations table
parameter 4).
The CEA6 can be configured to trigger an Alternator Voltage alarm (Alarms table parameter 10 to 12) if it
is detected a low voltage level provided by the battery charge alternator through the DI analog input from
the measurement module.
Two working modes of the battery charge alternator can be selected (Regulations table parameter 3)
The voltage produced by the battery charge alternator can be used as starting engine condition
(Regulations table parameter 20). For that purpose, the CEA6 expects to measure, through the DI
analog input, voltage values exceeding the alternator voltage detection threshold ( Thresholds table
parameter 21).
The CEA6 device can be configured to raise an Alternator Voltage alarm (Alarm table parameter 10 to
12) if it is detected a low voltage level provided by the battery charge alternator through the DI analog input
from the measurement module. (only if the alternator mode is configured).
The device, configured in dynamo mode, can not use the voltage measured through the analog input DI to
detect engine started condition.
The status of the inputs and outputs of the CEA6 can be visualized from the menu MAIN Æ1.
Inputs/Outputs. From this screen, the status of the digital inputs and outputs are displayed.
* I N P U T S / O U T P U T S *
3 2 1 0 9 8 7 6 5 4 3 2 1
I N : M S 3 2 1 P I X N A B R
O U T : C P R 4 B g r 3 2 + 1 M A
Output
A N L O G I C S I N P U T S
F L 0 . 0 P A 0 . 0
E T 0 . 0 A A 0 . 0
D T 0 . 0 V V B 0 . 0 V
The value of the resistive analog inputs is found in Ohms and the value of the voltage analog inputs is
given in Volts. The inputs that can be seen are:
• FL/ NC: Fuel level
• OP/PA: Oil pressure
• ET/TM: Engine temperature
• AA: Analog Auxiliary
• DT/DI: Dynamo tension.
• BV/ VB: Battery voltage
Presets inputs.
The measures module in the CEA6 has 5 digital inputs, whose working process is already pre-set.
Programmable inputs.
The measurement module of the CEA6 has 5 digital inputs whose working mode can be programmed.
The inputs of programmable functions can be configured to work in the following way:
Mains contactor confirmation (CKR).
The mains contactor confirmation configured input (Programming table parameter 5) is used to verify
the correct activation of the mains contactor.
After the activation of the mains contactor, a waiting time is produced (Times table parameter 13) to
check the activation of the contactor by means of the input programmed as mains contactor confirmation.
A mains contactor alarm triggers (Alarm table parameter 100) if, once the waiting time is over, there is no
confirmation of the mains contactor activation and the controller does not detect a mains failure alarm.
If the control board is working in automatic mode, a starting of the controller is produced with the activation
of the genset contactor in order to power the load.
The analog fuel level input indicates the amount of fuel left in the tank. To fit its working mode, the
maximum fuel level in the tank must be set (Measurements table parameter 13), and the same with the
minimum fuel level. (Measurements table parameter 12).
In the same way, a minimum fuel-in tank threshold (Thresholds table parameter 25) can be fixed, and it
will raise an engine warning (Alarms table parameter 55 to 57) when the fuel level is detected under
such limits.
When the BT relay from the measurement module is programmed to control the functions of the fuel
transfer pump, it will start the pump to transfer fuel to the tank if the fuel level is detected under the
minimum limits (Thresholds table parameter 18). The fuel pump is deactivated when the fuel level is
detected over the programmable threshold (Thresholds table parameter 19). Working the fuel pump in
manual mode, the threshold disables the activation of the fuel transfer pump except in case of the user
intervention.
In the same way, if the pre-heating function is programmed (by means of the BT relay, if it is programmed
to regulate the fuel pump, or any other programmable input), the analog temperature inputs allows to
regulate the activation of the pre-heating cycle.
Analog configurable input (AnC).
The analog configurable input (AnC) allows to control an engine measurement (i.e. engine
temperature).The controller permits the connection of VDO type sensors to this analog input. The
measured value is shown in the display.
In that way, the voltage can be programmed to detect a starting condition (Regulations table parameter
20) by means of setting an alternator voltage threshold for started engine (Thresholds table parameter
21), only if it is not configured as dynamo mode (Regulations table parameter 3).
The CEA6 device can be configured to trigger an overspeed alarm (Alarms table parameters 22 to 24)
as well as an underspeed alarm (Alarms table parameters 25 to 27) taking into account the mechanical
speed given by the pick up.
Pre-heating output.
The pre-heating output (PR) of the CEA is an output connected to a high voltage short-circuitable driver
(70A) in charge of regulating the the glow plug heating procedure of the engine during the starting cycle.
The activation time of the pre-heating output is configurable (Times table parameter 4). The pre-heating
output can be also used to control the stop by excitation of engines with this kind of stop configuration
(Regulations table parameter 18).
De-excitation stop: The engine stop output configured as stop by de-excitation is activated
500ms after the pre-heating output is disabled and it is deactivated when the stop of the engine
is ordered.
Excitation stop. The engine stop output configured as stop by excitation is activated during a
programmable time (Times table parameter 12) when the stop of the engine is ordered.
Excitation/ de-excitation stop. The engine stop output configured as stop by excitation/de-
excitation is activated 500ms after the pre-heating output is disabled and it is deactivated when
the stop of the engine is ordered. Such output is used to enable the engine sensors. The pre-
heating output will be the responsible of the stopping phase by means of the excitation stop
cycle.
- External start of the control board. The alarm output of the device (AL) is activated for 5
seconds if it is detected a control board start ordered by a programmable input, associated to
the AE mode.
- Control board failures. The CEA6 device is activated for a maximum programmable time
(Times table parameter 14) if it is detected an active failure or a failure waiting to be
acknowledged by the user. If the user presses once the Reset button, the AL output is
deactivated. The failures that activates the AL output are suitable to the alarms which induce
the engine stop as well as the warnings which do not stop the engines, excepting the ones
raised by the quality of the mains signal:
Inhibited output
The programmable outputs configured as inhibited output do not obey to any action or status, they remain
constantly deactivated.
The programmable outputs configured as programmed by input status are activated when an associated
input is detected.
Programmed by alarm.
The programmable outputs configured as programmed by alarm are activated when the device detects
any activated alarm, associated to programmable outputs or that has not been yet checked by the user
Programmed by function.
The programmable outputs configured as programmed by function are configured to allow a function
associated to an already used output. As possible functions of configurations, can be found the following:
- Heater. The output can function to activate the heater (glow plug) if the BT relay is programmed
to control the fuel pump.
Programmed by mode.
The programmable outputs configured as programmed by mode are configured to indicate the working
mode of the controller.
The CEA6 distinguishes between anomalies which cause the stop of the engine (alarms) and errors which
do not stop the engine (warnings).
When an alarm or warning is detected, the controller produces an acoustic alarm, at the same time the
digital alarm output (AL) activates and the LED of RESET button flashes; this status will remain the
same as long as the failure condition continues for a programmable period of time (Times table
parameter 14).
The LED of the RESET button lights (and remains ON) when alarms or warnings are active or in need of
acknowledgement. Pressing RESET button once allows the user to visualize a record of alarms and
warnings that are active and needing to be acknowledged. The UP and DOWN buttons of the display are
used to go back and forward in the failure record.
The record of warnings that are active or in need of acknowledgement has the following format
E: Alarm N: Number of
A: Warning errors in the record
* A L A R M * E N 1 / 3
M I N . F R E Q U E N C Y G E N S E T
In the front panel of the control board there can be found LEDs which indicate alarms detected by digital
sensors (digital inputs) or by analog sensors (analog inputs).
NOTE: The alarms which cause the engine to stop are not auto-resetting, and they must be acknowledged
and re-set by the user in order to be able to start the engine again, but only if the alarm does not remain
active.
The alarms produced by analog inputs do not stop the engine, only trigger a warning according to the
settings programmed by default. They need to be reset to erase them from the display, but only if the
warning does not remain active. The fuel level alarm is an exception, as it is automatically reset.
ALARM OPERATING PROCESS. PRACTICAL EXAMPLE.
“EN” Alarm with engine stop
“AN” Warning that needs to be reset
“A” Warning automatically reset
1. When an alarm is detected, the controller produces an acoustic signal, the LED of the RESET
button flashes, the display blinks and the appropriate digital alarm output (AL) is activated. In this
case the engine stops.
2. The acoustic alarm is interrupted by pressing once the RESET button. The RESET LED turns into
fixed light and the display (which stops flashing) shows the kind of alarm. i.e.: Active alarm “EN”
High coolant temperature.
3. To solve the alarm problem: In this example the temperature of the engine must be reduced when
the engine stops. Check the coolant level of the engine to detect the cause of the failure. Once
the alarm is no longer active “N” it will be possible to reset it by pressing RESET button and the
engine can be restarted.
1. When an alarm is detected, the controller produces an acoustic signal, the LED of the RESET
button flashes, the display blinks and the appropriate digital alarm output (AL) is activated.
2. The acoustic alarm is cancelled by pressing once the RESET button. Once the RESET LED turns
into fixed light and the display (which stops flashing) shows the kind of Active warning “AN”
3. To solve the warning problem: In this case, stop the engine, if we consider so, to check the cause
of the fault indicated. Once the warning is no longer active, “N” will appear in the display and it will
be possible to reset it by pressing RESET button.
WARNING WARNING
HIGH TEMPERATURE HIGH TEMPERATURE
WATER WATER
“A” Warning automatically reset
1. When an alarm is detected, the controller produces an acoustic signal, the LED of the RESET
button flashes, the display blinks and the appropriate digital alarm output (AL) is activated.
2. The acoustic alarm is interrupted by pressing the RESET button once. The RESET LED turns into
fixed light and the display (which stops flashing) shows the kind of warning. Warning “A”
3. This kind of warning is automatically reset as long as the nominal conditions of working are
restored. It is focused on the type of alarms related to fuel level (in default programming) and the
alarms related with the mains threshold.
WARNING
FUEL RESERVE
ALARMS
The alarm and the active warning list can be grouped in the following way: (according the
MANUFACTURER DEFAULT SETTINGS)
High coolant temperature by sensor LED on Warning Engine does not stop
Low oil pressure by sensor LED on Warning Engine does not stop
Low fuel level by sensor LED on Warning Engine does not stop
Unexpected shutdown
Stop failure
- Never.
- Always.
- During the engine start.
- From the started engine condition
- From the engine nominal condition
It can be configured as normally open or normally closed (Regulations table parameter 7).
The high coolant temperature alarm can be configured (Alarms table parameter 1) to be detected:
Always
A stabilization time can be associated to the high coolant temperature alarm (Alarms table parameter 2)
to delay the moment in which the alarm conditions are verified.
This alarm has been configured (Alarms table parameter 3) to carry out: the Immediate engine stop
It can be configured as normally open or normally closed (Regulations table parameter 6).
The low oil pressure alarm is configured (Alarms table parameter 4) to be detected:
From the started engine condition
A stabilization time can be associated to the low oil pressure alarm (Alarms table parameter 5) to delay
the moment in which the alarm conditions are verified
This alarm is configured (Alarms table parameter 6) to carry out the following action:
- Immediate engine stop
Emergency stop.
The emergency stop alarm of the CEA6 is associated to the specific emergency stop digital input (EMS)
In the same way, the emergency stop alarm is also associated to the SETA input from the measurement
module. This input cuts the feeding to the power outputs of the measurement module (starting, pre-heating
and engine stopping) to make sure the stop of the engines configured as stop by de-excitation
(Regulations table parameter 18) without considering the electronics of the device. In engines
programmed with stop by no-excitation, such input must be connected to earth.
The emergency stop alarm always stops the engine without cooling. No delay timing can be associated to
that action, as it is immediately executed after the emergency stop input is detected (EMS).
The battery charge alternator alarm is configured (Alarms table parameter 10) to be detected:
- From the started engine condition
A stabilization time can be associated to the battery charge alternator low alarm (Alarms table 11). During
this time the obtained voltage values must be kept under the started engine detection threshold (through
the DI input) as a condition for the battery charge alternator failure alarm to be triggered.
This alarm is configured (Alarms table parameter 12) to carry out the following action:
- No actions to be performed (warning)
Starting failure.
The starting failure alarm of the CEA6 is triggered if all the starting attempts (Times table parameter 1),
consecutive and non effective, during the engine starting cycle are effected. Between each start attempt
there is a programmable waiting time (Times table parameter 2). Once the alarm is produced, the user
must check it before trying again with the engine starting process.
It can be configured as normally open or normally closed (Regulations table parameter 8).
The low coolant level alarm is configured (Alarms table parameter 16) to be detected:
-Always
A stabilization time (Alarms table parameter 17) can be associated to the low coolant level alarm to delay
the moment in which the alarm condition is verified.
This alarm is configured (Alarms table parameter 18) to carry out the following action:
- Immediate engine stop if the engine is not already stopped.
Fuel reserve.
The fuel reserve alarm of the CEA6 is associated to the specific fuel reserve digital input (FR) The status
of this input must be validated during a stabilization time (Times table parameter 15) before triggering
the fuel reserve alarm.
It can be configured as normally open or normally closed (Regulations table parameter 5).
The low coolant level alarm is configured (Alarms table parameter 19) to be detected:
- Always
A stabilization time (Alarms table parameter 20) can be associated to the fuel reserve alarm to delay the
moment in which the alarm condition is verified.
This alarm is configured (Alarms table parameter 21) to carry out the following action:
- No actions to be performed (warning)
Overspeed
The overspeed alarm of the CEA6 is associated to the rotation speed of the engine ring gear. This
measurement is done through the pick up input of the measurement module. The alarm functions depend
that the parameter that determines the number of teeth of the engine ring gear (Thresholds table
parameter 24) would not be zero.
A stabilization time can be associated to the overspeed alarm (Alarms table parameter 23). During this
time the rotation speed of the ring gear during this time must be over the maximum limits of the rotation
speed (Thresholds table parameter 11).
This alarm is configured (Alarms table parameter 24) to carry out the following action:
- Immediate engine stop
Underspeed
The underspeed alarm of the CEA6 is associated to the rotation speed of the engine ring gear. This
measurement is done through the pick up input of the measurement module. The alarm functions depend
that the parameter that determines the number of teeth of the engine ring gear (Thresholds table
parameter 24) would not be zero
A stabilization time can be associated to the underspeed alarm (Alarms table parameter 26). During this
time it must be kept under the programmed minimum limits (Thresholds table parameter 12).
This alarm is configured (Alarms table parameter 24) to carry out the following action:
- Stop with engine cooling
Overload.
The overload alarm of the CEA6 is associated to the effective amperage value in any of the phases. The
value must be superior to the maximum programmed overload limit (Thresholds table parameter 7) but
under the maximum limit of short-circuit (Thresholds table parameter 8).
The phases that are checked to detect the overload alarm are selected depending on the configuration of
the installation phases (Thresholds table parameter 1):
- Single-phase configuration, phase 1 is tested
- Two-phase configuration, phase 1 and 2 are tested.
- Three-phase configuration with neutral or three-phase without neutral, phase 1, 2 and 3 are
tested.
A stabilization time can be associated to the overload alarm (Alarms table parameter 29). During this
time the amperage values must be kept over the maximum programmed limits (Thresholds table
parameter 7).
This alarm is configured (Alarms table parameter 30) to carry out the following action:
- Stop with engine cooling
The voltage asymmetry alarm is activated only when the device is configured for the measurement of
three-phase with neutral or three-phase without neutral voltage values.
The voltage asymmetry alarm is configured (Alarms table parameter 31) to be detected:
- From the engine nominal condition
A stabilization time can be associated to the voltage asymmetry alarm (Alarms table parameter 32).
During this time, the difference between any pair of voltage values of the genset phases (VG12, VG23 or
VG31) must be over the maximum asymmetry programmed limits (Thresholds table parameter 4).
This alarm is configured (Alarms table parameter 33) to carry out the following action:
- Stop with engine cooling
The phases that are checked to detect the maximum genset voltage alarm are selected
depending on the configuration of the phases in the installation (Thresholds table parameter 1):
- Single-phase configuration, V1N voltage is tested
- Bi-phase configuration, V12 voltage is tested
- Three-phase configuration with neutral or three-phase without neutral, V12, V23, V13 voltages
are tested.
The maximum genset voltage alarm is configured (Alarms table parameter 34) to be
detected:
- From the engine nominal condition
A stabilization time can be associated to the maximum genset voltage alarm (Alarms table parameter 35)
During this time, the voltage values obtained between genset phases (VG12,VG23 or VG31) must be over
the maximum programmed limits. (Thresholds table parameter 2).
This alarm can be configured (Alarms table parameter 36) to carry out the following action:
- Immediate engine stop
Maximum genset frequency.
The maximum genset frequency alarm of the CEA6 is associated to the fact that the frequency generated
by the genset surpasses the maximum programmed frequency limits. (Thresholds table parameter 5).
The first-phase is used to measure the genset frequency. If no signal is detected, the measure is taken in
the second-phase. In the same way, if no signal is detected, the measure is taken in the third-phase.
The maximum genset frequency alarm is configured (Alarms table parameter 37) to
be detected:
- From the engine nominal condition
A stabilization time can be associated to the maximum genset frequency alarm (Alarms table parameter
38). During this time, the genset frequency values obtained must be kept over the maximum programmed
limits. (Thresholds table parameter 5).
This alarm is configured (Alarms table parameter 39) to carry out the following action:
- Immediate engine stop
The erroneous phase sequence alarm is activated only when the device is configured to work with three-
phase with neutral or three-phase without neutral.
The erroneous phase sequence alarm is configured (Alarms table parameter 40) to be detected:
- From the engine nominal condition
A stabilization time can be associated to the erroneous phase sequence alarm (Alarms table parameter
41). During this time an erroneous order in the maximum voltage values of the genset must be detected.
This alarm is configured (Alarms table parameter 42) to carry out the following action:
- Stop with engine cooling
Inverse power.
The inverse power alarm of the CEA6 is activated when the power obtained (mains or genset) is negative,
and exceeds the resultant value after calculating the programmed factor in a hundred per cent
(Thresholds table parameter 10) of the nominal power. (Thresholds table parameter 9).
Some times, the inverse power alarms can be triggered due to an erroneous wiring of the current
transformers.
The inverse power alarm is configured (Alarms table parameter 43) to be detected:
- From the engine nominal condition
A stabilization time can be associated to the inverse power alarm (Alarms table parameter 44). During
this time the power could be out the programmed limits.
This alarm is configured (Alarms table parameter 45) to carry out the following action:
- Stop with engine cooling
Low battery voltage.
The low battery voltage alarm of the CEA6 is triggered when the voltage obtained is lower
than the programmed limits (Thresholds table parameter 17).
The low battery voltage alarm is configured (Alarms table parameter 46) to be
detected:
- Always
A stabilization time can be associated to the low battery voltage alarm (Alarms table parameter
47). During this time, the voltage value detected must be under the programmed limits.
(Thresholds table parameter 17).
This alarm is configured (Alarms table parameter 48) to carry out the
following action:
- No actions to be performed (warning)
The high coolant temperature by sensor alarm is configured (Alarms table parameter 49) to be detected:
- Always
A stabilization time can be associated to the high coolant temperature by sensor alarm (Alarms table
parameter 50). During this time, the coolant temperature value detected must be over the programmed
limits. (Thresholds table parameter 27).
This alarm is configured (Alarms table parameter 51) to carry out the following action:
- No actions to be performed (warning)
The low oil pressure by sensor alarm is configured (Alarms table parameter 52) to be detected:
- From the started engine condition
A stabilization time can be associated to the low oil pressure by sensor alarm (Alarms table parameter
53). During this time the pressure values must be detected under the programmed limits. (Thresholds
table parameter 26).
This alarm is configured (Alarms table parameter 54) to carry out the following action:
- No actions to be performed (warning)
The low fuel level by sensor alarm is configured (Alarms table parameter 55) to be detected:
- Always
A stabilization time can be associated to the low fuel level by sensor alarm (Alarms table parameter 56).
During this time the fuel level values must be detected under the programmed limits (Thresholds table
parameter 25).
This alarm is configured (Alarms table parameter 57) to carry out the following action:
- No actions to be performed (warning)
Short circuit.
The short circuit alarm of the CEA6 is associated to real amperage value when any of the phases are over
the maximum short circuit programmed limits (Thresholds table parameter 8).
The phases that are checked to detect short circuit alarm are selected depending on the configuration of
the phases in the installation (Thresholds table parameter 1):
- Single-phase configuration, phase 1 is tested
- Two-phase configuration, phase 1 and 2 are tested.
- Three-phase configuration with neutral or three-phase without neutral, phase 1, 2 and 3 are
tested.
The short circuit alarm is configured (Alarms table parameter 58) to be detected:
- From the engine nominal condition
This alarm is configured (Alarms table parameter 60) to carry out the following action:
- Stop with engine cooling
The phases that are checked to detect the minimum genset voltage alarm are selected depending on the
configuration of the phases in the installation (Thresholds table parameter 1):
- Single-phase configuration, V1N voltage is tested
- Bi-phase configuration, V12 voltage is tested
- Three-phase configuration with neutral or three-phase without neutral, V12, V23, V13 voltages
are tested.
The minimum genset voltage alarm is configured (Alarms table parameter 61) to be
detected:
- From the engine nominal condition
A stabilization time can be associated to the minimum genset voltage alarm (Alarms table parameter 62)
During this time, the voltage values obtained between genset phases (VG12, VG23 or VG31) must be
under the minimum programmed limits. (Thresholds table parameter 3).
.
This alarm is configured (Alarms table parameter 63) to carry out the following action:
- Stop with engine cooling
The first-phase is used to measure the genset frequency. If no signal is detected, the measure is taken in
the second-phase. In the same way, if no signal is detected, the measure is taken in the third-phase.
The minimum genset frequency alarm is configured (Alarms table parameter 64) to be detected:
- From the engine nominal condition
A stabilization time can be associated to the minimum genset frequency alarm (Alarms table parameter
65). During this time, the genset frequency values obtained must be kept under the minimum programmed
limits (Thresholds table parameter 6).
This alarm is configured (Alarms table parameter 66) to carry out the
following action:
- Stop with engine cooling
Unexpected shutdown.
The unexpected shutdown of the CEA6 triggers when the controller, while the engine is running, does not
detect all the engine starting conditions. (Regulations table parameters 19 to 22).
Stop failure.
The stop failure alarm of the CEA6 is raised if 15 seconds after the engine stop attempt it is not detected
any of the stopping conditions of the engine (Regulations table parameters19 to 22).
In case the stop failure alarm is disconnected (Alarms table parameter 70), the device will consider the
engine as stopped after waiting the stop conditions for a maximum time of 15 seconds.
To detect the stop of the engine, all the stopping conditions must be detected during a programmed time
(Alarms table parameter 71).
The low engine temperature alarm is configured (Alarms table parameter 73) to be detected:
- Never
A stabilization time can be associated to the low engine temperature alarm (Alarms table parameter 74).
During this time, the coolant temperature values must be detected under the programmed limits
(Thresholds table parameter 28).
The low engine temperature alarm, once activated, does not allow the activation of the generating set
contactor until the engine exceeds the low temperature limits (Thresholds table parameter 28).
The genset signal failure alarm is configured (Alarms table parameter 76) to be detected:
A stabilization time can be associated to the genset signal failure alarm (Alarms table parameter 77).
During this time it must not be detected any signal before rising the alarm.
This alarm is configured (Alarms table parameter 78) to carry out the following action:
- Stop with engine cooling
Programmable alarm 1.
The programmable alarm 1 of the CEA6 is activated by associating one of the general digital inputs
(ENT1, ENT2, ENT3, ENT4 or ENT5) to the working mode of the programmable alarms. (Programming
table parameter 13). The status of such input must be validated during a stabilization time (Times table
parameter 19, 20, 22, 23 or 24) before triggering the programmable alarm 1 alarm.
A delay time (Alarms table parameter 80) can be associated to the programmable alarm 1 in order to
restrain the moment in which the alarm conditions are checked.
This alarm is configured (Alarms table parameter 81) to carry out the following action:
- No actions to be performed (warning).
A programmable text can be associated to the programmable alarm 1 and will appear on the visualization
module display when the alarm is triggered
Programmable alarm 2.
The programmable alarm 2 of the CEA6 is activated by associating one of the general digital inputs
(ENT1, ENT2, ENT3, ENT4 or ENT5) to the working mode of the programmable alarms. (Programming
table parameter 14). The status of such input must be validated during a stabilization time (Times table
parameter 19, 20, 22, 23 or 24) before triggering the programmable alarm 2 alarm.
A delay time (Alarms table parameter 83) can be associated to the programmable alarm 2 in order to
restrain the moment in which the alarm conditions are checked.
This alarm is configured (Alarms table parameter 84) to carry out the following action:
- No actions to be performed (warning)
A programmable text can be associated to the programmable alarm 2 and will appear on the visualization
module display when the alarm is triggered
Programmable alarm 3.
The programmable alarm 3 of the CEA6 is activated by associating one of the general digital inputs
(ENT1, ENT2, ENT3, ENT4 o ENT5) to the working mode of the programmable alarms. (Programming
table parameter 15). The status of such input must be validated during a stabilization time (Times table
parameter 19, 20, 22, 23 or 24) before triggering the programmable alarm 3.
A delay time (Alarms table parameter 86) can be associated to the programmable alarm 3 in order to
restrain the moment in which the alarm conditions are checked.
This alarm is configured (Alarms table parameter 87) to carry out the following action:
- No actions to be performed (warning)
A programmable text can be associated to the programmable alarm 3 and will appear on the visualization
module display when the alarm is triggered
The phases that are checked to detect the maximum mains voltage alarm are selected
depending on the configuration of the phases in the installation (Thresholds table parameter 1)
- Single-phase configuration, V1N mains voltage is tested
- Bi-phase configuration, V12 mains voltage is tested
- Three-phase configuration with neutral or three-phase without neutral, V12, V23, V13 mains
voltages are tested.
The maximum mains voltage alarm is configured (Alarms table parameter 88):
- To be detected
A stabilization time can be associated to the maximum mains voltage alarm (Alarms table
parameter 89). During this time, the voltage values obtained between mains phases (VR12,
VR23 or VR31) must be over the maximum programmed limits (Thresholds table parameter 13).
The detection of the maximum mains alarm is considered a genset starting condition.
7. Maintenance.
7.1. Working Counters.
The CEA6 device records a number of stored values regarding the control board functions. The counters
of the device are:
- Total working hours counter. The device records the number of working hours of the genset
engine. This counter can not be reset.
- Partial working hours counter The device records the number of working hours of the genset
engine. This counter can be reset and it starts from 0.
- Succeeded starts counter. The device records the number of obtained starts. This counter can
be reset and it starts from 0.
- Failed starts counter. The device records the number of failed starts. This counter can be reset
and it starts from 0.
- Total counter of power. The device records the total amount of power produced by the genset
(MWh). This counter can not be reset.
- Partial counter of power. The device records the total amount of power produced by the genset
(MWh). This counter can be reset and it starts from 0.
- Daily counter of power (option programming timer needed). The daily counter of power registers
the quantity of power produced by the genset from the 00:00H. of the present day up to the
moment of checking. With the change of the day, the stored power values along the day are
added to the monthly energy values. The daily counter then starts from 0.
- Monthly counter of power (option programming timer needed). The monthly counter of power
registers the quantity of power produced by the genset from the fist day of the current month up
to the day before the moment of checking. With the change of month, the stored power values
are added to the annual power counter. The monthly counter then starts from 0.
- Annual counter of power (option programming timer needed). The annual counter of power
registers the quantity of power produced by the genset from 1st January up to the month before to
the moment of checking. With the change of year, the stored power values are reset and the
counter starts from 0.
The user can see the counters readings accessing from the menu Main Æ3.Counters
The partial counters can be reset to 0 by selecting with the UP/DOWN buttons and pressing RESET for 5
seconds.
- 2 engine maintenance counters: When the counter reaches 0 an engine alarm without engine
stop is triggered. The alarm disappears when the counter is recharged.
- 1 rental counter: The counter raises an alarm that can stop the engine. The alarm disappears
when the counter is recharged.
The CEA6 device registers the alarms and saves the status of the control board in the moment of the
detection. All the alarms are stored, excepting the alarms related with the electric mains supply:
- Minimum mains voltage failure.
- Maximum mains voltage failure.
- Maximum mains frequency failure.
- Minimum mains frequency failure.
- Mains sequence failure
- Mains power failure.
The CEA6 stores the last 10 detected failures. With the programming timer, 100 additional failures can be
added to the fault history, including the date and hour of the moment in which the failure was produced.
8. Optional expansions.
New functional options can be added to the CEA6 device with the connection of the CAN bus allowing new
expansion modules.
Moreover, this visualization display allows to check the control panel status by means of "error and status
leds" and also the programming of the parameters of working.
The installation of a programming timer device to the CEA6 allows the weekly programming of:
- Programmed starts.
- Programmed cut-outs.
- Programmed engine tests.
- Expansion of the fault history
- Power counters (day, month, year ).
The maximum capacity of the timer is 5 daily programs. The CEA6 must be in automatic mode to carry out
the programming.
8.3. Telesignal.
The CEA6 allows the connection of a Telesignal device. This device has 12 outputs to relay (4 with
connection NO and NC, 8 with connection NO) and it can be programmed depending the status of the
control board.
The outputs of the Telesignal device can be programmed to activate depending:
- Any control board status (automatic, manual,…)
- any alarm, active or waiting to be checked.
- any activated input of the control board.
- any activated output of the control board.
Every output of the Telesignal device is activated when, at least, one of the programmed activation
conditions exist.
8.4. J1939.
The CEA6 allows the connection of a J1939 device. This device can control a number of parameters of the
engine working mode, depending on the manufacturer and the engine model (ask your distributor):
- Pressure values, temperature.
- Engine alarms.
- Engine error codes.
- Starting and stop process.
- Fine speed adjustment (synchronization).
TIMES
Default
Parameter Psw Description Range
Value
1 2 Number of starts 4 1..10
Time between startings
2 2 Time between one starting attempt and another. All the 5’’ 3’’..30’’
outputs are deactivated
Starting delay
3 2 0’’ 0’’..1800’’
Range of time between mains failure and engine starting
4 2 Glow plug pre-heating time 0’’ 0’’..180’’
Starting time
5 2 Maximum waiting time before detecting the starting condition. 5’’ 1’’..10’’
During this time the starting output is active.
D+ activation time
Being this time over, the voltage values of the DI input will be
8 2 checked, and the D+ output will be activated, or not, until the 3’’ 1’’..3’’
stop of the engine (according PR regulations parameter (3))
8 2 CL input configuration 1
0-Off
1-Manual
19 2 Tensión de fase como condición de arranque 1
2-Automatic
3-Control board
20 2 Alternator voltage as starting condition 1
0-Off
1-Manual
21 2 PICK-UP input as starting condition 1 2-Automatic
3-Control board
0-Not installed
23 2 Voltage transformer 0 1-Transformer
400/600
0- Output line
24 2 Amperage measurement location. 0 1-Genset control
panel
0-Not allowed
1- Starting due to
25 3 Manual override working mode 0 Mains failure
1- Starting due to
manual override.
0-50Hz/1500rpm
Rotation speed of the engine ring gear related
26 2 0 60Hz/1800rpm
with genset voltage frequency
1-50Hz/3000rpm
0-Centigrade
27 2 Temperature readings 0
1-Fahrenheit
0-Bar
28 2 Pressure readings 0
1-Psi
0-VDO
29 3 Type of analogical sensors 0 1-SCANIA EMS
2 - YANMAR
0: Manual
30 2 Type of control board selection 0 1: Automatic
NOTE: After the modification of the parameter 30, you should restarted the control board, disconnecting its
feeding, to allow the upgrade in its operation mode.
THRESHOLDS
Default
Parameter Psw Description Range
Value
0- Three-
phase without
neutral
1-Three-
Three-phase, bi-phase or single-phase without
1 2 0 phase
neutral
2-Bi-phase
3- Single
phase
Alarm 1 management
4 4 0..4
3 Low oil pressure
5 3 Alarm 1 delay 15’’ 0”…30”
6 3 Alarm 1 mode 1 0..2
Alarm 3 management
10 2 3 0..4
Battery alternator charge failure
11 2 Alarm 3 filter 5’’ 0”…30”
12 2 Alarm 3 mode 0 0..2
Alarm 5 management
16 1 0..4
3 Low Coolant Level
17 3 Alarm 5 delay 5’’ 0”…30”
18 3 Alarm 5 mode 1 0..2
Alarm 6 management
19 2 1 0..4
Fuel Reserve
20 2 Alarm 6 delay 5’’ 0”…30”
21 2 Alarm 6 mode 0 0..2
Alarm 7 management
22 2 4 0..4
Overspeed
23 2 Alarm 7 filter 5’’ 0”…30”
24 2 Alarm 7 mode 1 0..2
Alarm 8 management
25 2 4 0..4
Underspeed
26 2 Alarm 8 filter 15” 0”…30”
27 2 Alarm 8 mode 2 0..2
Alarm 9 management
28 2 4 0..4
Overload
29 2 Alarm 9 filter 15 0”…30”
30 2 Alarm 9 mode 2 0..2
Alarm 10 management
31 2 3 0..4
Asymmetry
32 2 Alarm 10 filter 15 0”…30”
33 2 Alarm 10 mode 2 0..2
Alarm 11 management
34 2 3 0..4
Maximum Genset Voltage
35 2 Alarm 11 filter 5’’ 0”…30”
36 2 Alarm 11 mode 1 0..2
Alarm 12 management
37 2 4 0..4
Maximum Genset Frequency
38 2 Alarm 12 filter 1’’ 0”…30”
39 2 Alarm 12 mode 1 0..2
Alarm 13 management
40 2 4 0..4
Erroneous Phase sequence
41 2 Alarm 13 filter 5’’ 0”…30”
42 2 Alarm 13 mode 2 0..2
Alarm 14 management
43 2 4 0..4
Inverse power
44 2 Alarm 14 filter 15 0”…30”
45 2 Alarm 14 mode 2 0..2
Alarm 15 management
46 2 1 0..4
Low battery voltage
47 2 Alarm 15 filter 15 0”…30”
48 2 Alarm 15 mode 0 0..2
Alarm 16 management
49 2 High coolant temperature 1 0..4
(by sensor)
50 2 Alarm 16 filter 5’’ 0”…30”
51 2 Alarm 16 mode 0 0..2
Alarm 17 management
52 2 3 0..4
Low oil pressure (by sensor)
53 2 Alarm 17 filter 5’’ 0”…30”
54 2 Alarm 17 mode 0 0..2
Alarm 18 management
55 2 1 0..4
Low fuel level (by sensor)
56 2 Alarm 18 filter 5’’ 0”…30”
57 2 Alarm 18 mode 0 0..2
Alarm 19 management
58 2 4 0..4
Short-circuit
59 2 Alarm 19 filter __
60 2 Alarm 19 mode 2 0..2
Alarm 20 management
61 2 3 0..4
Minimum Genset Voltage
62 2 Alarm 20 filter 15’’ 0”…30”
63 2 Alarm 20 mode 2 0..2
Alarm 21 management
64 2 3 0..4
Minimum Genset Frequency
65 2 Alarm 21 filter 15’’ 0”…30”
66 2 Alarm 21 mode 2 0..2
Alarm 23 management
70 2 1 0..1
Stop Failure
71 2 Alarm 23 filter 3’’ 0”…30”
Alarm 24 management
73 2 1 0..4
Low Engine Temperature
74 2 Alarm 24 filter 15’’ 0”…30”
0-No condemn CG
75 2 Alarm 24 mode 0
1-condemn CG
Alarm 25 management
76 2 4 0..4
Genset signal failure
77 2 Alarm 25 filter 30’’ 0”…30”
78 2 Alarm 25 mode 2 0..2
Alarm 26 management
79 2 0 0..4
Programmable alarm 1
Alarm 28 management
85 2 0 0..4
Programmable Alarm 3
86 2 Alarm 28 delay 0’ 0”…30”
Alarm C2 management
90 2 1 0..1
Minimum Mains voltage failure
Alarm C4 management
94 2 1 0..1
Minimum Mains frequency failure
Alarm C5 management
96 2 1 0..1
Mains sequence failure
Alarm C6 management
98 2 1 0..1
Mains power failure
0-No programmed
1 2 Programmable Output Mode 1 0 1-FR input
2-LOP alarm
3- HCT alarm
4- CL input
5- INT4 input
6- INT5 input
2 2 Programmable Output Mode 2 0 7- EMS alarm
8- INT1 input
9- INT2 input
10- INT3 input
11-Coolant Heater
3 2 Programmable Output Mode 3 0 12-Bloqued Mode
13-Manual Model
14-Auto Mode
15-Test Mode
16-Alternator Alarm
17-Prg Alarm 1
4 2 Programmable Output Mode 4 0 18- Prg Alarm 2
19- Prg Alarm 3
The display of the amperage figures depends on the locational configuration of the current transformers
(Regulations table parameter 24):
• Amperage readings in output line. The amperage value is shown in the mains or generator
display, depending on which contactor (mains or genset) is ON. In the display where no
amperage reading is shown, the numeric value is replaced by a dash symbol.
• Amperage readings in genset control panel: The amperage obtained is shown on the genset
display.
M A I N S : 5 0 . 0 H Z
V 1 2 4 0 0 V I 1 - A
V 2 3 4 0 0 V I 2 - A
V 3 1 4 0 0 V I 3 - A
2 .- Voltage readings between the different phases, and neutral phase and the amperage per phase,
and frequency.
MA I N S : 5 0 . 0 H Z
V 1 N 2 3 0 V I 1 - A
V 2 N 2 3 0 V I 2 - A
V 3 N 2 3 0 V I 3 - A
G E N E R A T O R : 5 0 . 0 H z
V 1 N 2 3 0 V I 1 0 A
V 2 N 2 3 0 V I 2 0 A
V 3 N 2 3 0 V I 3 0 A
4 .- Voltage readings between-phases and the amperage readings in each phase; and frequency.
G E N E R A T O R : 5 0 . 0 H z
V 1 2 4 0 0 V I 1 0 A
V 2 3 4 0 0 V I 2 0 A
V 3 1 4 0 0 V I 3 0 A
5 .- V., A., FL, RPM., P. readings, The voltage and amperage readings are displayed alternatively. FL fuel
level, RPM engine speed. P actual power output.
G E N E R A T O R : 5 0 . 0 H z
V 1 N 2 3 0 V I 1 0 A
F L 7 5 % R P M 1 5 0 0
P 0 k W
E N G I N E : 1 5 0 0 R P M 1 0 0 H
F L 7 5 %
D T 2 4 V E T 7 0 º C
B V 2 4 V O P 6 . 7 B A R
NOTE: The engine must be provided with the appropriate VDO sensors, in order to visualize the temperature and
the oil pressure.
Programmable
inputs status
G E N S E T : S T O P
s I 9 A E C K G C K R 9 K -
T F J P 1 J P 2
I N H I B I T E D S T A R T
P OWE R : F P 1 . 0 0 L
3 0 k W F P 1 1 . 0 0 L
3 0 k V A F P 2 1 . 0 0 L
0 k V A R F P 3 1 . 0 0 L
9. - Total consumed power values (day, month, year).
E N E R G Y : P 3 0 k W h
D 1 0 K W h
M 1 0 0 M W h 1 7 : 5 6 : 2 3
Y 1 0 0 0 M W h 4 / 1 2 / 0 6 L
Failures record.
* A L A R M * E N 1 / 3
M I N . V O L T S G E G E N S E T
N: To be N: Nº of position in the
checked. total record of failures.
* * * * * * * M E N U * * * * * * *
P a s s w o r d
0 0 0 0
Main menu.
In the main menu display we can visualize:
1. Outputs / Inputs
2. Parameters (only with authorized code)
3. Counters
4. Fault History
5. Events (only with programming clock option)
6. Date/ Hour
7. Language
8. Password
* * * * * * * M E N U * * * * * * *
Æ 1 . I n p u t s / o u t p u t s
2 . P a r a m e t e r s
T 3 . C o u n t e r s
* * * * * * * M E N U * * * * * * *
Æ 4 . F a u l t H i s t o r y
S 5 . E v e n t
T 6 . D a t a / H o u r
* * * * * * * M E N U * * * * * * *
Æ 7 . L a n g u a j e
S 8 . P a s s w o r d
T
1. Inputs / Outputs.
* I N P U T S / O U T P U T S *
3 2 1 0 9 8 7 6 5 4 3 2 1
I N : M S 3 2 1 P I X N A B R
O U T : C P R 4 B g r 3 2 + 1 M A A: Active alarm
R: Fuel level M: Engine started
B: Low temperature pressure 1:Programmable output 1.
A: High temperature +: D+
N: Coolant level 2: Programmable output 2.
X: Programmable input 4. 3: Programmable output 3.
I: Programmable input 5. r: Mains contactor
P: Emergency stop. g: Generating set contactor.
1: Programmable input 1. B: Fuel transfer/Heating
2: Programmable input 1. 4: Programmable output 4.
3: Programmable input 1. R: PR/PD
S: Stop button. P: PD/PE
M: Start key. C: Controller fitting.
A N A L O G I C A L I N P U T S
F L 0 . 0 P A 0 . 0
E T 0 . 0 A A 0 . 0
D I 0 . 0 V V B 0 . 0 V
* * * * C O U N T ER S * * * *
ÆT o t a l ho u r s 0 1 : 0 0 : 0 0
B i a s e d h o u r s 0 0 : 1 0 : 0 0
T N o r ma l s t a r t u p s 1 1 0
* * * * C O U N T E R S * * * *
Æ F a i l t o s t a r t u p s 5
S T o t a l 5 0 k W h
T A t p r e s e n t 1 0 k W h
* * * * C O U N T E R S * * * *
Æ D a y 2 0 k W h
S M o n t h 5 0 M W h
T Y e a r 1 0 0 M W h
Partial counters can be reset by pushing the RESET button for 5 seconds
4. List of failures.
* L I S T O F F A I L U R E S *
Æ1 . M A I N S M A X V O L T A G E
2 . M A I N S M I N V O L T A G E
T3 . M A I N S M A X F R E Q U E N
5. Events.
The CEA6 device needs to have the programming timer option installed if the user wants to programme
its working.
* * * * * E V E N T S * * * * *
ÆM o n d a y
T u e s d a y
T W e d n e s d a y
* * * * * E V E N T S * * * * *
Æ T h u r s d a Y
S F r i d a y
T S a t u r d a y
* * * * * E V E N T S * * * * *
ÆS u n d a y
* * * * * Mo n d a y * * * * *
ÆB L O Q 1 0 : 0 0 . . 1 1 : 0 0
F O R S 1 5 : 5 0 . . 1 7 : 0 0
T T E S T 2 0 : 0 0 . . 2 2 : 0 0
6. Data / Hour.
* * * D A T A / H O U R * * *
ÆH o u r : 1 1 : 0 0 : 5 5
D a t a : 1 0 / 1 2 / 0 6 D
7. Language selection.
* * * L A N G U A J E * * *
Æ 0 . S p a n i s h
1 . F r a n c a i s
2 . E n g l i s h
8. Password configuration.
* * * * P A S SWO R D * * * *
Æ 0 . U s e r
1 . M a i n t e n a n c e
* * * * U S U A R I O * * * *
P a s s w o r d
New password
1 1 1 1
Old password 0 0 0 0
* * * * P A R A M E T E R S * * * *
Æ 1 . M e a s u r e m e n t S
2 . T i m e s
T 3 . R e g u l a t i o n s
* * * * P A R A M E T E R S * * * *
Æ 4 . T h r e s h o l d s
S 5 . A l a r m s
T 6 . P r o g r a m a t i o n I / O
* * * * P A R A M E T E R S * * * *
Æ 7 . T e x t s
S 8 . I d e n t i f i c a t o r
* * * * M E A S U R E M E N T S * * * *
Æ P 0 1 . . . . . . . . . . . 4
S P 0 2 . . . . . . . . . . . 5
T P 0 3 . . . . . . . . . . . 0
Texts.
* * * * T E X T S * * * *
Æ 1 . P R O G R A M M A B L E 1
2 . P R O G R A M M A B L E 2
T 3 . P R O G R A M M A B L E 3
* * * * T E X T S * * * *
Æ 4 . D I S P L A Y
H I MO I N S A
3 0 7 3 0 S A N J A V I E R
M U R C I A ( S p a i n )
T l f . + 3 4 9 6 8 1 9 1 1 2 8
Annex III: Dimensions, connections and mechanization.
Measures module.
188 171
117.00
202.00
FEEDING CANBUS
8-36V -BAT 8-36V -BAT MAN AUTO CANL CANH CANL CANH
BAT
CAN BUS
The most important characteristics of a control system with CAN bus communication are the following:
• It is possible to connect up to 110 devices in a single CAN network.
• Each network can reach a length of 1000 meters, easily extended (up to 2000 meters) with the use of
bridges or repeaters.
• CAN bus transmission speed 50 Kbits/s (for 1000 meters bus: 10 ms of data updating).
• Direct access to the CAN bus from a PC by means of a USB Can.
The Can bus is prepared to work in extreme conditions of noise and interferences and at the same time,
the failure checking mechanisms guarantee that the frames affected by the disturbance can be detected.
The CAN bus is designed to continue the communication even if:
• Any of the two bus wires cuts.
• Any cable is short-circuited to earth.
• Any cable is short-circuited to feeding.
Topology
The Can network uses a bus topology in which each node has an input and an output connection, The
endpoint nodes of the bus must have a 120Ω terminator: this terminator is activated by means of a switch
in each module (ON: enabled terminator, 1: disabled terminator). In each case, the impedance found
between the CANH and CANL must be, approximately, 60Ω. To do so, in each network endpoint a
resistance value must be defined to guarantee such impedance value from every connected device.
The impedance measurement must be obtained when all the equipments are not working or they have
not physical access from the network.
For more information it is recommended to consult the ISO11898 standards and the different applications
notes.
Wire characteristics
Bus length
Length/resistance Diameter
0,25 mm2..0,34 mm2
0 m..40 m 70 mΩ/m
AWG23,AWG22
0,34 mm2..0,6 mm2
40 m..300 m <60 mΩ/m
AWG22,AWG20
0,5 mm2..0,6 mm2
300 m..600 m <40 mΩ/m
AWG20
0,75 mm2..0,8 mm2
600 m..1 Km <26 mΩ/m
AWG18
Table 1: Wire characteristics according the distance.
Number of nodes
Bus length
32 64 100
100 m 0,25 mm2 0,25 mm2 0,25 mm2
250 m 0,34 mm2 0,50 mm2 0,50 mm2
500 m 0,75 mm2 0,75 mm2 1,00 mm2
Wire resistance <21Ω <18,5Ω <16Ω
In order to connect the different nodes of the network a twisted pair without shielding is needed. As an
exception, the connection between the measurement and the visualization module can be done using a
wiring not twisted.
In very noisy environments affected by high electromagnetic interference (EMI), a twisted shielded wire
with the shield connected to earth can be used. Other technique to improve the immunity against the
electromagnetic interference consists in substituting the CAN terminator of the node for 2 resistances of 62
Ω and installing a decoupling capacitor between the resistances CAN and the battery negative.
H L H L O
120Ω
H L H L
O
DISPLAY
Figure 1:Device
MANUAL/AUTOMATIC
MANUAL COMMUTATION
120Ω 120Ω
MEASUREMENTS MEASUREMENTS
H L H L O H L H L O
120Ω 120Ω
H L H L H L H L
O O
DISPLAY DISPLAY
Figure 2: Device
MANUAL + COMMUTATION
120Ω 120Ω
MEASUREMENTS CCrs
H L H L O H L O
120Ω
H L H L
O
DISPLAY
H L H L O O
L H 9
120Ω
H L H L
O
DISPLAY
MANUAL COMMUTATION
120Ω 120Ω
MEASUREMENTS MEASUREMENTS
H L H L O H L H L O
120Ω 120Ω
H L H L H L H L
O O
DISPLAY DISPLAY
120Ω
CCrs
H L
O
Figure 5: Device
MANUAL + COMMUTATION + CCRs
Annex V: Telesignal: Communication option by digital
outputs.
Introduction:
The range of CEA6, CEM6 and CEC6 controllers allow the monitoring of the devices status by means of a
number of relay outputs. The Telesignal option is connected to the range of CeA6 devices of Himoinsa
through a CAN communication cable. The configuration software of the controlboards, configured in local
mode (USB can) or remote (CCrs), allows the adjustment of its functions.
The Telesignal option is connected to the Cex6 Himoinsa controlboard with a twisted pair with or without
shielding; depending of the installation environment and it can even be of 1 Km length. The CEX6 device
allows the installation of 4 optional Telesignal equipments simultaneously.
Telesignal components:
• Feeding and communication terminal plate
• Terminal plate of digital outputs to relay
o 4 contact outputs NC/CL.
o 8 contact outputs CL
• 1 feeding led
• 12 LEDs to visualize the output status.
• Activation Microswitch, CAN terminator.
• Microswitch of 2 switches to fix the number of modules (maximum 4)
By pressing the “General Alarm” button all the possible alarm conditions to activate the output are
selected.
Working mode.
The outputs of the Telesignal option can be programmed to be activated depending on:
• Any alarms of the controlboard, active or waiting to be checked.
• Any activated input of the controlboard.
• Any activated output of the controlboard.
Each output of the Telesignal device is activated if, at least, one of the programmed activation conditions is
raised.
Wiring of the Telesignal option
The terminating resistors will be connected to the network terminal nodes, using the appropriate
microswitch.
The maximum distance between the terminal nodes of the network is 1000m
BAT
CAN BUS
Relay outputs (Terminals C1, NC1, NA1, C2, NC2, NA2, C3, NC3, NA3, C4, NC4, NA4, C5, NA5, C6, NA6, C7,
NA7, C8, NA8, C9, NA9, C10, NA10, C11, NA11, C12, NA12)
VO Relay contactors maximum voltage 250 VAC
IO Relay contactors power cosϕ = 0 8 A
75
174
The range of CEA6, CEM6 and CEC6 controllers allow a remote monitoring and supervision function
thanks to the CCrs option. This option allows to establish a connection between the controlboard and the
monitorization and configuration software, by means of a modem or GPRS (NOT INCLUDED with the
CCrs option)
CCrs installation.
System requirements.
The CCrs option needs the following elements to obtain a remote connection:
• PC that fulfils the following requirements to execute the monitorization and configuration software:
o Pentium III 1.3 GHz
o Microsoft Windows XP with Microsoft .Net Framework 2.0
o 512 Mb RAM
o 50 Mb free in the hard disk
o Modem 14400 or superior (line modem or GPRS)
• Modem and serial cable to connect to the CCrs
• Optional: a null modem type cable and CCrs configuration software.
In the same way, a kind of "waiting connection" can be done, capable of allowing the connection between
the controlboards and the PC software in case any event occurs in the registration moment.
Once the dialing data are introduced, the software of the PC tries to establish the connection with the
controlboard.
As soon as the connection with the controboard is confirmed, the monitorization or configuration software
of the controlboard starts running.