Configuration Documents For MFM Integration v2
Configuration Documents For MFM Integration v2
b. 243:Master_MODBUS Settings-
Step-I - Add User In Serial ports, qty. as per requirement.
Step-II - In Serial port we have a TAB for Task Level Protocol Setting, here
please refer to the parameter attached-
Step-III - Now Setting for Protocol at Module Level, please refer to the
parameter attached -
Step-IV - Now Select Total No. of SPI,DPI,COUNTER,DO from Data Num
Column and Put in USER MODULE
Step-V – Now Assign Name for DI,AI,ENERGY, DO according to I/O List-
typedef struct
//AI 1 INT16
//AI 2 UINT16
//CI 1 INT32
//CI 2 UINT32
//CI 3 Float32
// Year 2 bytes
// Month 2bytes
// Day 2bytes
// Hours 2 bytes
// Minutes 2 bytes
// Seconds 2 bytes
// Milliseconds 2 bytes
WORD rsv[8];
}PACKED PTFuncInfo;
Above is Data Structure of Modbus setting, we may refer to all above points to
finalize the Modbus setting at module level.
II. Type of MFMs
a. AE- 900
1) Regarding the port and address setting, refer to manual, clause 3.2. SET 2 -
Configuration Mode.
2) Regarding mapping setting, refer to MFM mapping sheet and parameter
format.
[00000055-43308]Txd: 02 03 00 00 00 16 C4 37
[00000057-43687]Rxd: 02 03 2C
B4 97 48 5A
24 69 48 5A
53 25 48 5B
5F 00 47 FB
49 55 47 FD
20 C5 42 A0
0A 3D 42 93
24 B2 [OK]
[00000059-44697]Txd: 02 03 00 1D 00 02 54 3E
[00000061-44997]Rxd: 02 03 04
C5 81 [OK]
[00000063-46008]Txd: 02 03 00 2B 00 0A B5 F6
[00000065-46339]Rxd: 02 03 14
18 80 4B 0F
CC 00 4B 17
3D E0 4B 07
59 5B [OK]
b. SATEC PM130
1) Regarding the port and address setting, refer to related manual.
2) Regarding mapping setting, refer to MFM mapping sheet and parameter
format.
3) Configuration of AI value
The following is frame of SATEC MFM communication
[00000005-03323]Txd: 0C 03 01 00 00 18 45 21
[00000006-03642]Rxd: 0C 03 30
11 48--Ur/Ury 4424
11 A0
11 8C
05 0E--Ir 1294
05 1A
05 01
13 E7--KW_L1 5095
13 EA
13 E7
13 8C--KVAR_L1 5004
13 89
13 8A
13 E7--KVA_L1 5095
13 EA
13 E7
27 0A--PF_L1 9904
27 0F
27 0F
27 0F--PF 9999
14 A9--KW 5289
13 90--KVAR 5008
14 A9--KVA 5289
00 1F--In 31
09 D3--F 2515
96 61—CRC check [OK]
6. Above values all are required to convert to real value. In our maintenance
software, we may set a, b, c in logic database. The formula is: send value=raw
value*a/b+c, we may fill in the correct setting in database.
c. Secure ELITE 440-000
1) Regarding the port and address setting, refer to related manual.
2) Regarding mapping setting, refer to MFM mapping sheet and parameter
format.
d. Other MFMs