2014-04-092-H01-0003 - c1 - Set Point and Alarm List R1
This document contains the settings for an automatic generator controller, including settings for various protection functions, alarms, and shutdowns. It lists 27 generator protection functions with their set points and timers. It also lists 14 bus protection functions. In addition, it includes settings for 8 digital inputs, 12 analog inputs, and rotor earth fault protection settings.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
77 views4 pages
2014-04-092-H01-0003 - c1 - Set Point and Alarm List R1
This document contains the settings for an automatic generator controller, including settings for various protection functions, alarms, and shutdowns. It lists 27 generator protection functions with their set points and timers. It also lists 14 bus protection functions. In addition, it includes settings for 8 digital inputs, 12 analog inputs, and rotor earth fault protection settings.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4
Function Description Set Point Timer Warning Block CB TRIP Shutdown
Gen -P> Reverse Power 1 -5% 7 sec X
Gen -P> Reverse Power 2 -10% 0.1 sec X I> Overcurrent 1 100% 30 sec X I> Overcurrent 2 105% 10 sec X I> Overcurrent 3 115% 5 sec X I> Overcurrent 4 120% 1 sec X I>> Fast Overcurrent 1 150% 0.5 sec X I>> Fast Overcurrent 2 200% 0.3 sec X Gen U> Gen Overvoltage 1 105% 30 sec X Gen U>> Gen Overvoltage 2 110% 5 sec X X Automatic Genset controller settings
Gen U< Gen Undervoltage 1 95% 30 sec X
Gen U<< Gen Undervoltage 2 90% 5 sec X X Gen U<< Gen Undervoltage 3 85% 3 sec X X Gen F> Gen Over Frequency 1 107% 30 sec X Gen F>> Gen Over Frequency 2 110% 5 sec X X Gen F>> Gen Over Frequency 3 115% 3 sec X X Gen F< Gen Under Frequency 1 95% 30 sec X Gen F<< Gen Under Frequency 3 85% 3 sec X X BUS U> BUS Overvoltage 1 105% 30 sec X BUS U>> BUS Overvoltage 2 110% 5 sec X BUS U>> BUS Overvoltage 3 115% 3 sec X BUS U< BUS Undervoltage 1 95% 30 sec X BUS U<< BUS Undervoltage 2 90% 5 sec X BUS U<< BUS Undervoltage 3 85% 3 sec X BUS U<< BUS Undervoltage 4 80% 1 sec X BUS F> BUS Over Frequency 1 107% 30 sec X BUS F>> BUS Over Frequency 2 110% 5 sec X BUS F>> BUS Over Frequency 3 115% 3 sec X BUS F< BUS Under Frequency 1 95% 30 sec X BUS F<< BUS under Frequency 2 90% 5 sec X BUS F<< BUS under Frequency 3 85% 3 sec X BUS F<< BUS under Frequency 4 80% 1 sec X Gen P> OVELOAD 1 105% 30 sec X Gen P>> OVELOAD 2 110% 10 sec X Gen P>> OVELOAD 3 115% 5 sec X Gen P>> OVELOAD 4 120% 3 sec X Gen P>> OVELOAD 5 125% 1 sec X Gen Unbalance U 10% 10 sec X Gen Unbalance I 30% 10 sec X Gen -Q> VAR IMPORT 35% 0.5 sec X Gen Q> VAR EXPORT 75% 10 sec X G neg. seq. I 20% 0.5 sec X G neg. seq. U 5% 0.5 sec X G Zero seq. U 5% 3 sec X Zero seq. I 20% 0.5 sec X BUS Unbalance U 6% 10 sec X GB Sync Failue N/A 60 sec X DI #46 DC Alternator charging Fail - - X X Automatic Genset controller settings
DI #47 High Water Temperature - - X X
DI #48 Low Oil Pressure - - X X DI #49 Low Water Level - - X X DI #50 Fire Alarm from fire panel - - X X DI #51 G60 & GPM-F protection fault - - X X DI #52 Diode Failure protection - - X X DI #53 PT Fuse Fail. X X E Stop Emergency Stop - - X X AI #102.1 High Water Tempertature 100 5 sec X AI #102.2 High Water Tempertature 102 5 sec X X AI #105.1 Low Oil Pressure Warning 1.4 20 sec X AI #105.2 Low Oil Pressure Shutdown 1 20 sec X X Overspeed 1 110% - X Overspeed 2 115% - X X Hz/V Failure N/A 30 sec X X Start Failure - - X Stop Failure - 40 sec X X U<aux. 1 Low Battery 18 V 5 sec X U>aux. 1 High Battery 30 V 1 sec X AI #90.1 L1 Winding Temp. 100 °C 1 sec X AI #90.2 L1 Winding Temp. 110 °C 1 sec X X AI #92.1 L2 Winding Temp. 100 °C 1 sec X AI #92.2 L2 Winding Temp. 110 °C 1 sec X X AI #94.1 L3 Winding Temp. 100 °C 1 sec X AI #94.2 L3 Winding Temp. 110 °C 1 sec X X AI #96.1 Bearing Temp. 80 °C 1 sec X AI #96.2 Bearing Temp. 85 °C 1 sec X X Source Polarizing Polarizing Volt Op Current POS SEQ Offset Forward ECA Forward Limit Forward Reverse Limit Reverse Neutral Directional Over Restraint Angle Pickup Angle Pickup Current NEUTR (SRC 1) Voltage Calculated V0 Calculated 3I0 0.063 0.00 ohms 75 ° Lag 90 deg 0.050 pu 90 deg 0.050 pu Field Ground Field Ground Field Ground Field Ground Field Ground Field Ground Field Ground Field Ground Field Ground Function Injection Inj Connection Stg1 Pickup Stg1 Delay Stg2 Pickup Stg2 Delay UC Pickup UC Delay 1st and 2nd Rotor earth Frequency Type fault Relay Enabled 1.00 Hz Single Point 20 kohms 10.0 s 5 kohms 3.0 s 1.00 mA 20.00 s g G60 & GPM-F Relay Setting
Xfmr Vol Xfmr Vol Rev Reach
Direction Shape Reach RCA Rev Reach Comp Limit Connection Connection RCA Back up Impedance Forward Mho None None 2.00 ohms 85 deg 2.00 ohms 85 deg 90 deg relay DIR Comp Quad Right Quad Right Quad Left Quad Left DIR RCA Supervision Volt Level Delay Limit Blinder Blinder RCA Blinder Blinder RCA 85 deg 90 deg 10.00 ohms 85 deg 10.00 ohms 85 deg 0.200 pu 0.000 pu 0.000 s Line End Neutral End p Pickup p 1 Slope Break 1 p 2 Slope Break 2 Generator Differential Source Source LINE (SRC 2) NEUTR (SRC 1) 0.300 pu 30% 1.20 pu 60% 9.00 pu Source Input Pickup Curve TD Multiplier Reset Ground Time Over Current NEUTR (SRC 1) Phasor 0.320 pu Definite Time 0.8 Instantaneous Source VHZ Voltage Pickup Curves TD Multiplier T Reset Overfluxing protection Mode G
of Generator LINE (SRC 2) Phase to 1 10 pu
1.10 Definite Time 3 10s 1.0 Ground Source Input Pickup Curve TD Multiplier Reset Neutral Time Over Current NEUTR (SRC 1) Phasor 0.320 pu Definite Time 0.8 Instantaneous Source Pickup Delay Reset Delay Neutral Instantaneous Over Current NEUTR (SRC 1) 0.40 pu 0.00 s 0.00 s