2014-04-092-H01-0003 - c1 - Set Point and Alarm List R1

This document contains the settings for an automatic generator controller, including settings for various protection functions, alarms, and shutdowns. It lists 27 generator protection functions with their set points and timers. It also lists 14 bus protection functions. In addition, it includes settings for 8 digital inputs, 12 analog inputs, and rotor earth fault protection settings.

Uploaded by

Midha Neer
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
77 views4 pages

2014-04-092-H01-0003 - c1 - Set Point and Alarm List R1

This document contains the settings for an automatic generator controller, including settings for various protection functions, alarms, and shutdowns. It lists 27 generator protection functions with their set points and timers. It also lists 14 bus protection functions. In addition, it includes settings for 8 digital inputs, 12 analog inputs, and rotor earth fault protection settings.

Uploaded by

Midha Neer
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Function Description Set Point Timer Warning Block CB TRIP Shutdown

Gen -P> Reverse Power 1 -5% 7 sec X


Gen -P> Reverse Power 2 -10% 0.1 sec X
I> Overcurrent 1 100% 30 sec X
I> Overcurrent 2 105% 10 sec X
I> Overcurrent 3 115% 5 sec X
I> Overcurrent 4 120% 1 sec X
I>> Fast Overcurrent 1 150% 0.5 sec X
I>> Fast Overcurrent 2 200% 0.3 sec X
Gen U> Gen Overvoltage 1 105% 30 sec X
Gen U>> Gen Overvoltage 2 110% 5 sec X X
Automatic Genset controller settings

Gen U< Gen Undervoltage 1 95% 30 sec X


Gen U<< Gen Undervoltage 2 90% 5 sec X X
Gen U<< Gen Undervoltage 3 85% 3 sec X X
Gen F> Gen Over Frequency 1 107% 30 sec X
Gen F>> Gen Over Frequency 2 110% 5 sec X X
Gen F>> Gen Over Frequency 3 115% 3 sec X X
Gen F< Gen Under Frequency 1 95% 30 sec X
Gen F<< Gen Under Frequency 3 85% 3 sec X X
BUS U> BUS Overvoltage 1 105% 30 sec X
BUS U>> BUS Overvoltage 2 110% 5 sec X
BUS U>> BUS Overvoltage 3 115% 3 sec X
BUS U< BUS Undervoltage 1 95% 30 sec X
BUS U<< BUS Undervoltage 2 90% 5 sec X
BUS U<< BUS Undervoltage 3 85% 3 sec X
BUS U<< BUS Undervoltage 4 80% 1 sec X
BUS F> BUS Over Frequency 1 107% 30 sec X
BUS F>> BUS Over Frequency 2 110% 5 sec X
BUS F>> BUS Over Frequency 3 115% 3 sec X
BUS F< BUS Under Frequency 1 95% 30 sec X
BUS F<< BUS under Frequency 2 90% 5 sec X
BUS F<< BUS under Frequency 3 85% 3 sec X
BUS F<< BUS under Frequency 4 80% 1 sec X
Gen P> OVELOAD 1 105% 30 sec X
Gen P>> OVELOAD 2 110% 10 sec X
Gen P>> OVELOAD 3 115% 5 sec X
Gen P>> OVELOAD 4 120% 3 sec X
Gen P>> OVELOAD 5 125% 1 sec X
Gen Unbalance U 10% 10 sec X
Gen Unbalance I 30% 10 sec X
Gen -Q> VAR IMPORT 35% 0.5 sec X
Gen Q> VAR EXPORT 75% 10 sec X
G neg. seq. I 20% 0.5 sec X
G neg. seq. U 5% 0.5 sec X
G Zero seq. U 5% 3 sec X
Zero seq. I 20% 0.5 sec X
BUS Unbalance U 6% 10 sec X
GB Sync Failue N/A 60 sec X
DI #46 DC Alternator charging Fail - - X X
Automatic Genset controller settings

DI #47 High Water Temperature - - X X


DI #48 Low Oil Pressure - - X X
DI #49 Low Water Level - - X X
DI #50 Fire Alarm from fire panel - - X X
DI #51 G60 & GPM-F protection fault - - X X
DI #52 Diode Failure protection - - X X
DI #53 PT Fuse Fail. X X
E Stop Emergency Stop - - X X
AI #102.1 High Water Tempertature 100 5 sec X
AI #102.2 High Water Tempertature 102 5 sec X X
AI #105.1 Low Oil Pressure Warning 1.4 20 sec X
AI #105.2 Low Oil Pressure Shutdown 1 20 sec X X
Overspeed 1 110% - X
Overspeed 2 115% - X X
Hz/V Failure N/A 30 sec X X
Start Failure - - X
Stop Failure - 40 sec X X
U<aux. 1 Low Battery 18 V 5 sec X
U>aux. 1 High Battery 30 V 1 sec X
AI #90.1 L1 Winding Temp. 100 °C 1 sec X
AI #90.2 L1 Winding Temp. 110 °C 1 sec X X
AI #92.1 L2 Winding Temp. 100 °C 1 sec X
AI #92.2 L2 Winding Temp. 110 °C 1 sec X X
AI #94.1 L3 Winding Temp. 100 °C 1 sec X
AI #94.2 L3 Winding Temp. 110 °C 1 sec X X
AI #96.1 Bearing Temp. 80 °C 1 sec X
AI #96.2 Bearing Temp. 85 °C 1 sec X X
Source Polarizing Polarizing Volt Op Current POS SEQ Offset Forward ECA Forward Limit Forward Reverse Limit Reverse
Neutral Directional Over Restraint Angle Pickup Angle Pickup
Current NEUTR (SRC 1) Voltage Calculated V0 Calculated 3I0 0.063 0.00 ohms 75 ° Lag 90 deg 0.050 pu 90 deg 0.050 pu
Field Ground Field Ground Field Ground Field Ground Field Ground Field Ground Field Ground Field Ground Field Ground
Function Injection Inj Connection Stg1 Pickup Stg1 Delay Stg2 Pickup Stg2 Delay UC Pickup UC Delay
1st and 2nd Rotor earth Frequency Type
fault Relay
Enabled 1.00 Hz Single Point 20 kohms 10.0 s 5 kohms 3.0 s 1.00 mA 20.00 s
g
G60 & GPM-F Relay Setting

Xfmr Vol Xfmr Vol Rev Reach


Direction Shape Reach RCA Rev Reach Comp Limit
Connection Connection RCA
Back up Impedance Forward Mho None None 2.00 ohms 85 deg 2.00 ohms 85 deg 90 deg
relay DIR Comp Quad Right Quad Right Quad Left Quad Left
DIR RCA Supervision Volt Level Delay
Limit Blinder Blinder RCA Blinder Blinder RCA
85 deg 90 deg 10.00 ohms 85 deg 10.00 ohms 85 deg 0.200 pu 0.000 pu 0.000 s
Line End Neutral End p
Pickup p 1
Slope Break 1 p 2
Slope Break 2
Generator Differential Source Source
LINE (SRC 2) NEUTR (SRC 1) 0.300 pu 30% 1.20 pu 60% 9.00 pu
Source Input Pickup Curve TD Multiplier Reset
Ground Time Over
Current NEUTR (SRC 1) Phasor 0.320 pu Definite Time 0.8 Instantaneous
Source VHZ Voltage Pickup Curves TD Multiplier T Reset
Overfluxing protection Mode
G

of Generator LINE (SRC 2) Phase to 1 10 pu


1.10 Definite Time 3 10s
1.0
Ground
Source Input Pickup Curve TD Multiplier Reset
Neutral Time Over
Current NEUTR (SRC 1) Phasor 0.320 pu Definite Time 0.8 Instantaneous
Source Pickup Delay Reset Delay
Neutral Instantaneous
Over Current NEUTR (SRC 1) 0.40 pu 0.00 s 0.00 s