8 DC In/6 Out Micro PLC Specs

This document provides specifications for the C0-01DD1-D 8 DC Input/6 Sinking DC Output Micro PLC, including details on its built-in input and output specifications. The input module has 8 inputs that operate between 21.6-26.4VDC and consume between 4-5mA. The output module has 6 sinking outputs that can operate between 5-27VDC and supply up to 0.1A per point. Response times for inputs and outputs are typically in the microseconds to milliseconds range.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
86 views1 page

8 DC In/6 Out Micro PLC Specs

This document provides specifications for the C0-01DD1-D 8 DC Input/6 Sinking DC Output Micro PLC, including details on its built-in input and output specifications. The input module has 8 inputs that operate between 21.6-26.4VDC and consume between 4-5mA. The output module has 6 sinking outputs that can operate between 5-27VDC and supply up to 0.1A per point. Response times for inputs and outputs are typically in the microseconds to milliseconds range.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

For the latest prices, please check AutomationDirect.com.

Standard PLC
Built-in I/O Specifications - Inputs
C0-01DD1-D Inputs per Module 8 (Sink/Source)

8 DC Input/6 Sinking DC Output Micro PLC Operating Voltage Range 24VDC


Input Voltage Range 21.6–26.4 VDC
X1-2: Typ 5mA @ 24VDC
Wiring Diagram Input Current X3-8: Typ 4mA @ 24VDC
X1-2: 6.0 mA @ 26.4 VDC
C0-01DD1-D 24VDC Maximum Input Current X3-8: 5.0 mA @ 26.4 VDC
X1-2: 4.7 k @ 24VDC
Input Impedance X3-8: 6.8 k @ 24VDC

+
X1-2: > 19VDC
ON Voltage Level

+
X3-8: > 19VDC
PWR
X1-2: < 4VDC
RUN OFF Voltage Level X3-8: < 7VDC
ERR
X1-2: 4.5 mA

+
Minimum ON Current X3-8: 3.5 mA
+
PORT1
X1-2: 0.1 mA
TX1 Maximum OFF Current X3-8: 0.5 mA
RX1
X1-2: Typ 5µs Max 20µs
OFF to ON Response X3-8: Typ 2ms Max 10ms
TX2 L
X1-2: Typ 5µs Max 20µs
RX2 L ON to OFF Response X3-8: Typ 3ms Max 10ms
PORT2
+

L 5 - 27VDC
L Status Indicators Logic Side (8 points, green LED)
RS-485
PORT3 Commons 2 (4 points/common) Isolated
TX3
L
+

L
Built-in I/O Specifications - Outputs
+

RX3
5 - 27VDC 24VDC

Outputs per Module 6 (Sink)


Operating Voltage Range 5–27 VDC
Output Voltage Range 4–30 VDC
NOTE: When using Standard PLCs, you must use CLICK 0.1 A/point; C3: 0.4 A/common, C4: 0.2
Maximum Output Current A/common
programming software version V1.20 or later.
Minimum Output Current 0.2 mA
Equivalent Input Circuit Maximum Leakage Current 0.1 mA @ 30.0 VDC
Internal Module Circuitry On Voltage Drop 0.5 VDC @ 0.1 A
Maximum Inrush Current 150mA for 10ms
INPUT Optical Isolator
Y1: typ 5µs; max 20µs
+
X1-X4
Typical OFF to ON Response Y2-6: < 0.5 ms
+
Y1: typ 5µs; max 20µs
24 VDC ON to OFF Response Y2-6: < 0.5 ms
C1 COM
Status Indicators Logic Side (6 points, red LED)
To X2-X4
commons Commons 2 (4 points/com & 2 points/com)
INPUT
X5-X8
Optical Isolator
External DC Power 20–28 VDC Maximum @ 60mA
+ Typical Required (All Points On)
+
24 VDC
General Specifications
C2 COM

To X6-X8
Current Consumption at 24VDC 140mA
commons
Terminal Block Replacement Part No. C0-16TB
Equivalent Output Circuit Weight 5.0 oz (140g)
Internal Module Circuitry
ZIPLink Pre-Wired PLC
24 VDC C0-01DD1-D Temperature Derating Chart
+ +V
Optical Isolator Connection Cables and Modules
OUTPUT
+
L
Y1 8
High response
Inputs
5 - 27 VDC
* circuit
6
Outputs ZL-RTB20 20-pin
Points

4 feed-through

Optical Isolator 2
* connector module
OUTPUT
+ Y2-Y4
L
5 - 27 VDC * 0

C3 COM 0 10 20 30 40 50 55 °C
32 50 68 85 104 122 131 °F
Surrounding Temperature (°C/°F)
Optical Isolator * Use every other input/output.
OUTPUT
+ Y5-Y6
L
5 - 27 VDC
* 20-pin connector cable
C4 COM
ZL-C0-CBL20 (0.5 m length)
Note: C3 & C4 are not internally connected.
ZL-C0-CBL20-1 (1.0 m length)
ZL-C0-CBL20-2 (2.0 m length)
* Zener Diode Power Dissipation: 200 mW

www.automationdirect.com/click-plc CLICK PLCs tCLP-45