EATON-POWERWARE 9390 KVA RECONFIGURATION INSTRUCTIONS
This procedure will step you through the power reconfiguration process for the Powerware 9390 products.
KVA Upgrade part numbers are:
PW9390 KVA Part Number
80/40 to 50KVA 103004754-001
80/40 to 60KVA 103004754-002
80/40 to 80KVA 103004754-003
80/50 to 60KVA 103004754-004
80/50 to 80KVA 103004754-005
80/60 to 80KVA 103004754-006
120/100 to 120KVA 103004754-007
160/100 to 120KVA 103004754-008
160/100 to 160KVA 103004754-009
160/120 to 160KVA 103004754-010
1. Connect a computer running the XCP Service Software Tool V03.00.00 or newer to the unit’s service
serial port.
EATON-Powerware
DESCRIPTION: POWERWARE 9390 KVA RECONFIGURATION INSTRUCTIONS
CREATED BY: DATE CREATED: CATEGORY: REVISION: RN/CN/SPRN NO: APPROVED BY: DATE APPROVED:
Don Temple 09/19/05 Procedure A00 ECN: INDI-0581 Don Temple 10/03/05
CHECKED BY: DATE CHECKED: CODE IDENT: DRAWING NO: CUSTOM NO: SHEET: 1
Don Temple 09/19/05 164700574 of 5
THESE DRAWINGS AND SPECIFICATIONS ARE THE PROPERTY OF POWERWARE CORPORATION AND SHALL NOT BE REPRODUCED
OR COPIED OR USED AS THE BASIS FOR MANUFACTURE OR SALE OF APPARATUS WITHOUT PERMISSION.
2. Click the EEPROM tab and select “Change KVA Rating”.
3. In the box provided, enter the desired KVA “Rating” (Powerware 9390 CTO drawing 110577083).
4. The KVA Reprogramming window will appear requiring the authorization number for the desired KVA
upgrade. Enter the authorization number provided and click on OK.
EATON-Powerware
DESCRIPTION: POWERWARE 9390 KVA RECONFIGURATION INSTRUCTIONS
CREATED BY: DATE CREATED: CATEGORY: REVISION: RN/CN/SPRN NO: APPROVED BY: DATE APPROVED:
Don Temple 09/19/05 Procedure A00 ECN: INDI-0581 Don Temple 10/03/05
CHECKED BY: DATE CHECKED: CODE IDENT: DRAWING NO: CUSTOM NO: SHEET: 2
Don Temple 09/19/05 164700574 of 5
THESE DRAWINGS AND SPECIFICATIONS ARE THE PROPERTY OF POWERWARE CORPORATION AND SHALL NOT BE REPRODUCED
OR COPIED OR USED AS THE BASIS FOR MANUFACTURE OR SALE OF APPARATUS WITHOUT PERMISSION.
5. The KVA security program in the UPS will validate the authorization number and automatically update
the KVA and associated settings along with new the CTO number. Once programming is completed you
will receive a pop up stating KVA Reprogramming Complete. If the authorization number is found to be
invalid, a pop up will appear stating an ERROR Reprogramming UPS. A confirmation is provided either
way so that the user knows if the operation was successful or not.
6. To verify the unit has been successfully upgraded go to EEPROM 230 and verify the current setting for
the KVA. Note that the setting in the EEP address will be 10 times the desired KVA. (For example: 800
= 80KVA).
EATON-Powerware
DESCRIPTION: POWERWARE 9390 KVA RECONFIGURATION INSTRUCTIONS
CREATED BY: DATE CREATED: CATEGORY: REVISION: RN/CN/SPRN NO: APPROVED BY: DATE APPROVED:
Don Temple 09/19/05 Procedure A00 ECN: INDI-0581 Don Temple 10/03/05
CHECKED BY: DATE CHECKED: CODE IDENT: DRAWING NO: CUSTOM NO: SHEET: 3
Don Temple 09/19/05 164700574 of 5
THESE DRAWINGS AND SPECIFICATIONS ARE THE PROPERTY OF POWERWARE CORPORATION AND SHALL NOT BE REPRODUCED
OR COPIED OR USED AS THE BASIS FOR MANUFACTURE OR SALE OF APPARATUS WITHOUT PERMISSION.
7. After verifying the upgrade was successful cut the UL mark out of the new label. (see example below)
Place the new label over the old one on the unit. Ensure the original UL mark shows through the cut out.
If you do not cut out the UL mark, on the new CTO label, it will result in an agency violation. The unit will
no longer be UL certified and could result in fines.
EATON-Powerware
DESCRIPTION: POWERWARE 9390 KVA RECONFIGURATION INSTRUCTIONS
CREATED BY: DATE CREATED: CATEGORY: REVISION: RN/CN/SPRN NO: APPROVED BY: DATE APPROVED:
Don Temple 09/19/05 Procedure A00 ECN: INDI-0581 Don Temple 10/03/05
CHECKED BY: DATE CHECKED: CODE IDENT: DRAWING NO: CUSTOM NO: SHEET: 4
Don Temple 09/19/05 164700574 of 5
THESE DRAWINGS AND SPECIFICATIONS ARE THE PROPERTY OF POWERWARE CORPORATION AND SHALL NOT BE REPRODUCED
OR COPIED OR USED AS THE BASIS FOR MANUFACTURE OR SALE OF APPARATUS WITHOUT PERMISSION.
Powerware 9390 KVA Upgrade Authorization Form
This document is to verify that system wiring for the UPS meets the new KVA rating requirements and
complies with both national and local electrical codes.
From: ___________________ To: _______________________________
KVA Reconfiguration Being Made (Old & New)
Input: ___________________ Output: ____________________________
Voltage Rating of UPS (Input & Output)
Input: ___________________ Output: ____________________________
AWG size of Customer Supplied Wiring (Input & Output)
Input: ___________________ Output: ____________________________
Rating of Customer Supplied Over-Current Protection (Input & Output)
_________________________________________________________
Serial Number of UPS
_________________________________________________________
Printed Name of Customer Date
_________________________________________________________
Authorized Customer Signature Title
_________________________________________________________
Company Name and Address
This document is to be returned to and maintained by EATON-Powerware. (164700574)