0% found this document useful (0 votes)
1K views118 pages

VS Mini J7 Series Instruction Manual: Compact General-Purpose Inverter (Voltage Vector Control)

Uploaded by

Shan Ahmad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views118 pages

VS Mini J7 Series Instruction Manual: Compact General-Purpose Inverter (Voltage Vector Control)

Uploaded by

Shan Ahmad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 118

VS mini J7 Series

Instruction Manual
COMPACT GENERAL-PURPOSE INVERTER
(VOLTAGE VECTOR CONTROL)
PREFACE
YASKAWA’s VS mini J7 is a compact and simple
inverter that is as easy to use as a contactor. This
instruction manual describes installation, maintenance,
inspection, troubleshooting, and specifications of the
VS mini J7. Read this instruction manual thoroughly
before operation.

YASKAWA ELECTRIC CORPORATION

General Precautions
• Some drawings in this manual are shown with the protective covers and shields
removed, in order to illustrate detail with more clarity. Make sure all covers and
shields are replaced before operating this product.
• This manual may be modified when necessary to reflect improvements to the
product, or changes in specifications.
Such modifications are denoted by a revised manual No.
• To order a copy of this manual, contact your YASKAWA representative.
• YASKAWA is not responsible for any modification of the product made by the
user. Any modifications will void the warranty.

2
CONTENTS
NOTES FOR SAFE OPERATION. . . . . . . . . . . . . . . . . . . . . 5
1. RECEIVING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
• Checking the Name Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2. IDENTIFYING THE PARTS . . . . . . . . . . . . . . . . . . . . . . 13
3. SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
• Standard Specifications (200V Class) . . . . . . . . . . . . . . . . . . 15
• Standard Specifications (400V Class) . . . . . . . . . . . . . . . . . . 18
• Standard Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
• Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
• Parameters List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4. MOUNTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
• Choosing a Location to Mount the Inverter . . . . . . . . . . . . . . 35
• Mounting Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
• Mounting/Removing Components . . . . . . . . . . . . . . . . . . . . . 37
5. WIRING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
• Wiring Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
• Wire and Terminal Screw Sizes . . . . . . . . . . . . . . . . . . . . . . 39
• Wiring the Main Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
• Recommended Peripheral Devices . . . . . . . . . . . . . . . . . . . . 43
• Wiring the Control Circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
• Wiring Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
6. OPERATING THE INVERTER . . . . . . . . . . . . . . . . . . . . 47
• Test Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
• Operating the Digital Operator. . . . . . . . . . . . . . . . . . . . . . . . 49
• LED Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
• Simple Data Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

3
7. PROGRAMMING FEATURES . . . . . . . . . . . . . . . . . . . . 57
• Parameter Set-up and Initialization . . . . . . . . . . . . . . . . . . . . 57
• Setting V/f pattern . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
• Switching LOCAL/REMOTE Modes . . . . . . . . . . . . . . . . . . . 61
• Selecting Run/Stop Commands. . . . . . . . . . . . . . . . . . . . . . . 62
• Selecting Frequency Reference . . . . . . . . . . . . . . . . . . . . . . 63
• Setting Operation Condition . . . . . . . . . . . . . . . . . . . . . . . . . 65
• Selecting Stopping Method . . . . . . . . . . . . . . . . . . . . . . . . . . 82
• Building Interface Circuits with External Devices. . . . . . . . . . 84
• Setting Frequency by Current Reference Input . . . . . . . . . . . 89
• Decreasing Motor Speed Fluctuation . . . . . . . . . . . . . . . . . . 93
• Motor Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
• Selecting Cooling Fan Operation. . . . . . . . . . . . . . . . . . . . . . 96
• Using MEMOBUS (MODBUS) Communications
(when option card is installed). . . . . . . . . . . . . . . . . . . . . . . 96
8. MAINTENANCE AND INSPECTION . . . . . . . . . . . . . . . 99
• Periodical Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
• Part Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
9. FAULT DIAGNOSIS AND CORRECTIVE ACTIONS. . 103
APPENDIX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
• CE Conformance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111

4
NOTES FOR SAFE OPERATION
Read this instruction manual thoroughly before installation, operation, maintenance or
inspection of the VS mini. In this manual, NOTES FOR SAFE OPERATION are
classified as “WARNING” or “CAUTION”.

WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death
or serious injury to personnel.

CAUTION
Indicates a potentially hazardous situation which, may result in minor or moderate
injury to personnel, and possible damage to equipment if not avoided. It may also be
used to alert against unsafe practices.
Items described in CAUTION may also result in a vital accident in some situations. In
either case, follow these important notes.
These are steps to be taken to ensure proper operation.

RECEIVING
CAUTION
(Ref. page)
• Do not install or operate any inverter which is damaged or
has missing parts.
Failure to observe this caution may result in personal injury or
equipment damage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

5
MOUNTING
CAUTION
(Ref. page)
• Lift the inverter by the cooling fin. When moving the unit, never
lift by the plastic case or the terminal covers.
Failure to observe this caution may cause the unit to be dropped resulting in
damage to the unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
• Mount the inverter on nonflammable material (i.e., metal).
Failure to observe this caution can result in a fire. . . . . . . . . . . . . . . . . . . . . . . 13
• When mounting open chassis in an enclosure, install a fan
or other cooling device to keep the intake air temperature
below 122°F (50°C).
Overheating may cause a fire or damage to the unit. . . . . . . . . . . . . . . . . . . . . 35
• The VS mini J7 generates heat. For effective cooling, mount it
vertically.
Refer to the figure in “Mounting Dimensions” on page 16.

WIRING
WARNING
(Ref. page)
• Start wiring only after verifying that the power supply
is turned OFF for at least one minute, and all LED’s and
change LED’s are extinguished.
Failure to observe this warning can result in electric shock
or fire. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
• Wiring should be performed only by qualified personnel.
Failure to observe this warning can result in electric shock
or fire. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
• When wiring the emergency stop circuit, check the wiring
thoroughly before operation.
Failure to observe this warning can result in personal injury. . . . . . . . . . . . . . 39

6
WARNING
(Ref. page)
• For 400V class, make sure to ground the supply neutral.
• Make sure to ground the ground terminal according to the
local ground code.
Failure to observe this warning can result in electric shock
or fire. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

CAUTION
(Ref. page)
• Verify that the inverter rated voltage coincides with the
AC power supply voltage.
Failure to observe this caution can result in personal injury
or fire.
• Do not perform a withstand voltage test of the inverter.
It may cause semi-conductor elements to be damaged.
• Make sure to tighten terminal screws of the main circuit
and the control circuit.
Failure to observe this caution can result in a malfunction,
damage or a fire. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
• Never connect the AC main circuit power supply to output
terminals U, V and W.
The inverter will be damaged and void the warranty. . . . . . . . . . . . . . . . . . . . 42
• Do not connect or disconnect wires or connectors while
power is applied to the circuit.
Failure to observe this caution can result in personal injury.
• Do not change signal/control wiring during operation.
The machine or the inverter may be damaged.

7
OPERATION
WARNING
(Ref. page)
• Only turn ON the input power supply after replacing the
digital operator or optional blank cover.
Do not remove the digital operator or the covers while
current is flowing.
Failure to observe this warning can result in electric shock.
• Never operate the digital operator or dip switches when
your hand is wet.
Failure to observe this warning can result in electric shock.
• Never touch the terminals while current is flowing, even
when the inverter is stopped.
Failure to observe this warning can result in electric shock.
• When the fault retry function is selected, stand clear of
the inverter or the load. It may restart unexpectedly
after being stopped.
(Construct machine system, so as to assure safety for personnel,
even if the inverter should restart.) Failure to observe this
warning can result in personal injury.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
• When continuous operation after power recovery is selected,
stand clear of the inverter or the load. It may restart
unexpectedly after being stopped.
(Construct machine system, so as to assure safety for personnel,
even if the inverter should restart.) Failure to observe this
warning can result in personal injury.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
• Since the digital operator stop button can be disabled by a
parameter setting, install a separate external emergency stop switch.
Failure to observe this warning can result in personal injury.
• If an alarm is reset with the operation signal ON, the inverter
restarts automatically. Only reset the alarm after verifying that
the operation signal is OFF.
Failure to observe this warning can result in personal injury. . . . . . . . . . . . . . 46

8
CAUTION
(Ref. page)
• Never touch the heatsink or braking resistor, the
temperature is very high.
Failure to observe this caution can result in harmful burns
to the body.
• Since it is easy to change operation speed from low to
high speed, verify the safe working range of the motor
and machine before operation.
Failure to observe this caution can result in personal injury
and machine damage.
• Install a holding brake separately if necessary.
Failure to observe this caution can result in personal injury.
• Do not change signals during operation.
The machine or the inverter may be damaged.
• All the parameters of the inverter have been preset at
the factory. Do not change the settings unnecessarily.
The inverter may be damaged. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

MAINTENANCE AND INSPECTION

WARNING
(Ref. page)
• Never touch high-voltage terminals in the inverter.
Failure to observe this warning can result in an electrical shock. . . . . . . . . . . 99
• Disconnect all power before performing maintenance or
inspection. Then wait at least one minute after the power
supply is disconnected and all LEDs and CHARGE LED
are extinguished.
The capacitors discharge slowly, and may be dangerous. . . . . . . . . . . . . . . . . 99

9
WARNING
(Ref. page)
• Do not perform a voltage withstand test on any part of
the VS mini J7.
This electronic equipment uses semiconductors and it is vulnerable
to high voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
• Only authorized personnel should perform
maintenance, inspections or parts replacement.
[Remove all metal objects (watches, bracelets, etc.) before operation.]
(Use tools which are insulated against electrical shock.)
Failure to observe this warning can result in an electrical shock. . . . . . . . . . . 99

CAUTION
(Ref. page)
• The control PC board employs CMOS ICs.
Do not touch the CMOS elements.
They are easily damaged by static electricity.
• Do not connect or disconnect wires, digital operator,
connectors, or cooling fan while power is applied to the circuit.
Failure to observe this caution can result in personal injury. . . . . . . . . . . . . . . 99

Others

WARNING
(Ref. page)
• Never modify the product.
Failure to observe this warning can result in an electrical shock or
personal injury and will void the warranty.

10
WARNING LABEL
A warning label is displayed on the front cover of the inverter, as shown below. Follow
these instructions when handling the inverter.

PLASTIC ENCLOSURE

NAME-
PLATE

STATUS
INDICATOR
LAMP
WARNING
LABEL

Warning Label

• Read manual before installing.


• Wait 1 minute for capacitor. discharge after
disconnecting power supply.
• To conform to CE requirements make sure to
ground the supply neutral for 400V class.

11
1. RECEIVING
After unpacking the VS mini J7, check the following:
• Verify that the part numbers match your purchase order or packing slip.
• Check the unit for physical damage that may have occurred during shipping.
If any part of VS mini J7 is missing or damaged, call for service immediately.

• Checking the Nameplate


U.S. and Canadian Safety Standards for Types of 3-phase, 200VAC,
0.13HP (0.1kW)

Example of 3-phase, 220VAC, 0.13 (0.1kW)

12
2. IDENTIFYING THE PARTS

13
Notes

14
3. Specifications
• Standard Specifications (200V Class)
Voltage Class 200V single- / 3-phase
Model 3-phase
20P1 20P2 20P4 20P7 21P5 22P2 23P7
CIMR-J7AU!!!! Single-phase
B0P1 B0P2 B0P4 B0P7 B1P5 - -
0.13 0.25 0.5 1 2 3 5
Max. Applicable Motor Output HP (kW)†
(0.1) (0.2) (0.4) (0.75) (1.5) (2.2) (3.7)
Inverter Capacity (kVA) 0.3 0.6 1.1 1.9 3.0 4.2 6.7
Characteristics

Rated Output Current (A) 0.8 1.6 3 5 8 11 17.5


Output

3-phase models, 200 to 230V (proportional to input voltage)


Max. Output Voltage (V)
Single-phase models, 200 to 240V (proportional to input
(3-phase output only)
voltage)
Max. Output Frequency (Hz) 400 Hz (Programmable)
Rated Input Voltage and 3-phase, 200 to 230V, 50/60Hz
Supply
Power

Frequency Single-phase, 200 to 240V, 50/60Hz


Allowable Voltage Fluctuation -15 to +10%
Allowable Frequency Fluctuation ±5%
Control Method Sine wave PWM (V/f control)
Frequency Control Range 0.1 to 400Hz
Frequency Accuracy Digital reference: ±0.01% (-10 to +50°C)
(Temperature Change) Analog reference: ±0.5% (25±10°C)
Digital reference: 0.1Hz (less than 100Hz) / 1Hz (100Hz or
Frequency Setting Resolution more)
Control Characteristics

Analog reference: 1 / 1000 of max. output frequency


Output Frequency Resolution 0.01Hz
Overload Capacity 150% rated output current for one minute
0 to 10VDC (20kΩ), 4 to 20mA (250Ω), 0 to 20mA (250Ω)
Frequency Reference Signal
Frequency setting volume (Selectable)
0.1 to 999sec.
Accel/Decel Time
(accel/decel time are independently programmed)
Short-term average deceleration torque‡
0.13HP, 0.25HP (0.1, 0.25kW): 150%
0.5HP, 1HP (0.55, 1.1kW): 100%
Braking Torque
2HP (1.5kW): 50%
3HP (2.2kW) or more: 20%
Continuous regenerative torque: Approx. 20%
V/f Characteristics Possible to program any V/f pattern
† Based on a standard 4-pole motor for max. applicable motor output.
‡ Shows deceleration torque for uncoupled motor decelerating from 60Hz with the shortest possible
deceleration time.

15
Voltage Class 200V single- / 3-phase
Model 3-phase 20P1 20P2 20P4 20P7 21P5 22P2 23P7
CIMR-J7AU!!!! Single-phase B0P1 B0P2 B0P4 B0P7 B1P5 - -
Motor Overload Protection Electronic thermal overload relay
Motor coasts to a stop at approx. 200% of inverter rated
Instantaneous Overcurrent
current
Motor coasts to a stop after 1 minute at 150% of inverter rated
Overload
output current
Protective Functions

Overvoltage Motor coasts to a stop if DC bus voltage exceed 410V


Stops when DC bus voltage is approx. 200V or less (approx.
Undervoltage
160V or less for single-phase series)
Following items are selectable: Not provided (stops if power
Momentary Power Loss loss is 15ms or longer), continuous operation if power loss is
approx. 0.5s or shorter, continuous operation
Cooling Fin Overheat Protected by electronic circuit
Individual levels during accel/running, enable/disable provided
Stall Prevention Level
during deceleration
Cooling Fan Fault Protected by electronic circuit (fan stalling detection)
Ground Fault Protected by electronic circuit (rated output current level)
RUN lamp stays ON or digital operator LED stays ON.
Power Charge Indication (Charge LED is provided for 400V)
ON until the DC bus voltage becomes 50V or less.
Four of the following input signals are selectable: Reverse run
Input Signals

(3-wire sequence), fault reset, external fault (NO/NC contact


input), multi-step speed operation, Jog command, accel/decel
Multi-function Input time select, external baseblock (NO/NC contact input), speed
search command, accel/decel hold command, LOCAL/
REMOTE selection, communication/control circuit terminal
Other Functions

selection, emergency stop fault emergency stop alarm


Following output signals are selectable (1 NO/NC contact
output):
Output Signals

Fault, running, zero speed, at frequency, frequency detection


(output frequency ≤ or ≥ set value), during over torque
Multi-function Output
detection, minor error, during baseblock, operation mode,
inverter run ready, during fault retry, during UV, during speed
search, during speed search, data output through
communication
Full-range automatic torque boost, slip compensation, DC
injection braking current/time at start/stop frequency reference
Standard Functions
bias/gain, [MEMOBUS communications (RS-485/422, max.
19.2K bps).]

16
Voltage Class 200V single- / 3-phase
Model 3-phase 20P1 20P2 20P4 20P7 21P5 22P2 23P7
CIMR-J7AU!!!! Single-phase B0P1 B0P2 B0P4 B0P7 B1P5 - -
Status Indicator LED RUN and ALARM provided as standard LED’s

Display
Other Functions
Digital Operator Available to monitor frequency reference, output frequency,
(JVOP-140) output current. 3 character, 7 segment LED Display.
Main circuit: screw terminals
Terminals
Control circuit: plug-in screw terminal
Wiring Distance between
328ft (100m) or less‡
Inverter and Motor
Enclosure Open chassis
Cooling fan is provided for 200V, 0.75kW (3-phase), 400V,
Cooling Method
1.5kW (single-phase), others are self-cooling
Open chassis: -10 to +50°C (14 to 122°F)
Ambient Temperature
(not frozen)
Environmental

Humidity 95% RH or less (non-condensing)


Conditions

Storage Temperature† -4 to 140°F (-20 to +60°C)


Location Indoor (free from corrosive gases or dust)
Elevation 3280ft (1000m) or less

Vibration Up to 9.8m / S2 (1G) at less than 20Hz, up to 2m / S 2 (0.2G) at


less than 20 to 50Hz
†Temperature during shipping (for short period)
‡ If the wiring distance between inverter and motor is long, reduce the inverter carrier frequency.
For details, refer to “Reducing motor noise or leakage current (n46)”on page 79.

17
• Standard Specifications (400V Class)
Voltage Class 400V 3-phase
Model
3-phase 40P2 40P4 40P7 41P5 42P2 43P7
CIMR-J7A!!!!
0.25 0.5 1 2 3 5
Max. Applicable Motor Output HP (kW)*
(0.2) (0.4) (0.75) (1.5) (2.2) (3.7)
Characteristics

Inverter Capacity (kVA) 0.9 1.4 2.6 3.7 4.2 6.5


Rated Output Current (A) 1.2 1.8 3.4 4.8 5.5 8.6
Output

Max. Output Voltage (V) 3-phase, 380 to 460V (proportional to input voltage)
Max. Output
400 Hz (Programmable)
Frequency (Hz)
Rated Input Voltage
3-phase, 380 to 460V, 50/60Hz
and Frequency
Supply
Power

Allowable Voltage
-15 to +10%
Fluctuation
Allowable Frequency
±5%
Fluctuation
Control Method Sine wave PWM (V/f control)
Frequency Control Range 0.1 to 400Hz
Digital reference: ±0.01%, 14 to 122°F (-10 to
Frequency Accuracy
+50°C)
(Temperature Change)
Analog reference: ±0.5%, 59 to 95°F (25 ±10°C)
Digital reference: 0.1Hz (less than 100Hz) / 1Hz
Frequency Setting Resolution (100Hz or more)
Control Characteristics

Analog reference: 1 / 1000 of max. output frequency


Output Frequency
0.01Hz
Resolution
Overload Capacity 150% rated output current for one minute
Frequency Reference 0 to 10VDC (20kΩ), 4 to 20mA (250Ω), 0 to 20mA
Signal (250Ω) Frequency setting volume (Selectable)
0.1 to 999 sec. (accel/decel time are independently
Accel/Decel Time
programmed)
Short-term average deceleration torque†
0.2kW: 150%
0.75kW: 100%
Braking Torque
2HP (1.5kW): 50%
3HP (2.2kW) or more: 20%
Continuous regenerative torque: Approx. 20%
V/f Characteristics Possible to program any V / f pattern
* Based on a standard 4-pole motor for max. applicable motor output.
† Shows deceleration torque for uncoupled motor decelerating from 60Hz with the shortest
possible deceleration time.

18
Voltage Class 400V 3-phase
Model
3-phase 40P2 40P4 40P7 41P5 42P2 43P7
CIMR-J7A!!!!
Motor Overload Protection Electronic thermal overload relay
Motor coasts to a stop at approx. 200% of inverter
Instantaneous Over Current
rated current
Motor coasts to a stop after 1 minute at 150% of
Overload
inverter rated output current
Motor coasts to a stop if DC bus voltage exceed
Protective Functions

Over Voltage
820V
Under Voltage Stops when DC bus voltage is approx. 400V or less
Following items are selectable: Not provided (stops if
power loss is 15ms or longer), continuous operation
Momentary Power Loss
if power loss is approx. 0.5s or shorter, continuous
operation
Cooling Fin Overheat Protected by electronic circuit
Individual levels during accel/running, enable/disable
Stall Prevention Level
provided during deceleration.
Cooling Fan Fault Protected by electronic circuit (fan stalling detection)
Protected by electronic circuit (rated output current
Ground Fault
level)
Charge LED is provided
Power Charge Indication
On until the DC bus voltage becomes 50V or less.
Four of the following input signals are selectable:
Reverse run (3-wire sequence), fault reset, external
Input Signals

fault (NO/NC contact input), multi-step speed


operation, Jog command, accel/decel time select,
Multi-function Input external baseblock (NO/NC contact input), speed
search command, accel/decel hold command,
LOCAL/REMOTE selection, communication/control
circuit terminal selection, emergency stop fault,
Other Functions

emergency stop alarm


Following output signals are selectable (1 NO/NC
contact output,):
Output Signals

Fault, running, zero speed, at frequency, frequency


detection (output frequency ≤ or ≥ set value), during
Multi-function Output over torque detection, during under voltage
detection, minor error, during baseblock, operation
mode, inverter run ready, during fault retry, during
UV, during speed search, data output through
communication
Full-range automatic torque boost, slip
compensation, DC injection braking current/time at
Standard Functions start/stop frequency reference bias/gain, frequency
reference with built-in volume, [MEMOBUS
communications (RS-485/422, max. 19.2K).]

19
Voltage Class 400V 3-phase
Model
3-phase 40P2 40P4 40P7 41P5 42P2 43P7
CIMR-J7A!!!!
Status Indicator LED RUN and ALARM provided as standard LEDs
Display
Available to monitor frequency reference, output
Other Functions

Digital Operator
frequency, output current. 3 character, 7 segment
LED display.
Main circuit: screw terminals
Terminals
Control circuit: plug-in screw terminal
Wiring Distance between
328ft (100m) or less†
Inverter and Motor
Enclosure Open chassis or enclosed wall-mounted
Cooling fan is provided for 200V, 0.75kW (3-/single
Cooling Method phase), 200V, 0.75kW (1.5HP), others are self-
cooling
Open chassis: -10 to +50°C (14 to 122°F)
Ambient Temperature
(not frozen)
Environmental

Humidity 95% RH or less (non-condensing)


Conditions

Storage Temperature* -20 to 60°F (-4 to +140°C)


Location Indoor (free from corrosive gases or dust)
Elevation 3280ft (1000m) or less

Vibration Up to 9.8m / S 2 (1G) at less than 20Hz, up to 2m / S 2


(0.2G) at less than 20 to 50Hz

* Temperature during shipping (for short period)


† If the wiring distance between inverter and motor is long, reduce the inverter carrier
frequency.
For details, refer to “Reducing motor noise or leakage current (n46)” on page 79.

20
• Standard Wiring

21
Terminal Description
Type Terminal Name Function (Signal Level)
Use main circuit power input (for single-phase inverter,
R/L1,
R/L1, S/L2).
S/L2, AC power supply input
Even thought T/L3 is available, do not use the terminal
T/L3
for other purposes such as relay terminal.
U/T1,
Main Circuit

V/T2, Inverter output Inverter output


W/T3
When connecting optional DC reactor, remove the main
+2, +1 DC reactor connection
circuit short-circuit bar between +2 and +1.
+1, (–) DC power supply input DC power supply input (+1: positive, –: negative) *
Grounding 200V: grounding to 100Ω or less
Grounding
400V: grounding to 10Ω or less
S1 Forward run input Closed: FWD run
S2 Multi-function input selection 2 Factory setting closed: REV run
Photo-
S3 Multi-function input selection 3 Factory setting: Fault reset
Sequence

coupler
Factory setting: External fault (N.O. insulation
S4 Multi-function input selection 4
contact)
24VDC,
Input

Factory setting: Multi-step speed 8mA.


S5 Multi-function input selection 5
reference 1
Control Circuit

SC Multi-function input selection common Control signal common


Multi-function Frequency

FS Power for frequency setting +12V (permissible current 20mA max.)


contact output reference

FR Master speed frequency reference 0 to +10DC (20kΩ) or 4 to 20mA (250Ω) or 20mA (250Ω) (1/1000 resolution)
FC Frequency reference common 0V
MA NO contact output
Contact capability
MB NC contact output Form C contact
250VAC 1A or less,
Factory setting: running
Output

MC Contact output common 30VDC 1A or less


Factory setting: 0 to+10VDC, 2mA or
AM Analog monitor output
Output frequency 0 to +10VDC less,
AC Analog monitor common 0V 8-bit resolution
* DC power supply input terminal is not available on CE/UL standards.

22
• Dimensions

23
Dimensions in inches (mm)/mass in lb (kg)
Voltage Capacity
W H D W1 H1 H2 d Mass Fig.
class HP (kW)
0.13 (0.1) 2.68 (68) 5.04 (128) 2.76 (70) 2.20 (56) 4.65 (118) 0.20 (5) M4 1.32 (0.6) 1
0.25 (0.2) 2.68 (68) 5.04 (128) 2.76 (70) 2.20 (56) 4.65 (118) 0.20 (5) M4 1.32 (0.6) 1
0.5 (0.4) 2.68 (68) 5.04 (128) 4.02(102) 2.20 (56) 4.65 (118) 0.20 (5) M4 1.98 (0.9) 1
200V
1 (0.75) 2.68 (68) 5.04 (128) 4.80(122) 2.20 (56) 4.65 (118) 0.20 (5) M4 2.43 (1.1) 1
3-phase
2 (1.5) 4.25 (108) 5.04 (128) 5.08 (129) 3.78 (96) 4.65 (118) 0.20 (5) M4 3.09 (1.4) 2
3 (2.2) 4.25 (108) 5.04 (128) 6.06 (154) 3.78 (96) 4.65 (118) 0.20 (5) M4 3.31 (1.5) 2
5 (3.7) 5.51 (140) 5.04 (128) 6.34 (161) 5.04(128) 4.65 (118) 0.20 (5) M4 4.63 (2.1) 2
0.13 (0.1) 2.68 (68) 5.04 (128) 2.76 (70) 2.20 (56) 4.65 (118) 0.20 (5) M4 1.32 (0.6) 1
200V 0.25 (0.2) 2.68 (68) 5.04 (128) 2.76 (70) 2.20 (56) 4.65 (118) 0.20 (5) M4 1.54 (0.7) 1
single- 0.5 (0.4) 2.68 (68) 5.04 (128) 4.41 (112) 2.20 (56) 4.65 (118) 0.20 (5) M4 2.20 (1.0) 1
phase 1 (0.75) 4.25 (108) 5.04 (128) 5.08 (129) 3.78 (96) 4.65 (118) 0.20 (5) M4 3.31 (1.5) 2
2 (1.5) 4.25 (108) 5.04 (128) 6.06 (154) 3.78 (96) 4.65 (118) 0.20 (5) M4 3.31 (1.5) 2
0.25 (0.2) 4.25 (108) 5.04 (128) 3.19 (81) 3.78 (96) 4.65 (118) 0.20 (5) M4 2.20 (1.0) 2
0.5 (0.4) 4.25 (108) 5.04 (128) 3.90 (99) 3.78 (96) 4.65 (118) 0.20 (5) M4 2.43 (1.1) 2
400V
1 (0.75) 4.25 (108) 5.04 (128) 5.08 (129) 3.78 (96) 4.65 (118) 0.20 (5) M4 3.31 (1.5) 2
3-phase
2 (1.5) 4.25 (108) 5.04 (128) 6.06 (154) 3.78 (96) 4.65 (118) 0.20 (5) M4 3.31 (1.5) 2
3 (2.2) 4.25 (108) 5.04 (128) 6.06 (154) 3.78 (96) 4.65 (118) 0.20 (5) M4 3.31 (1.5) 2
5 (3.7) 5.51 (140) 5.04 (128) 6.34 (161) 5.04(128) 4.65 (118) 0.20 (5) M4 4.63 (2.1) 2

24
• Parameters List
First Functions (Parameters n001 to n049)

Register
No. for Initial *User Ref.
No. Name Description
Trans- Setting Setting Page
mission
0: Parameter n001 set / read and
parameter n02 ~ n79 can be read.
(FREF of the operator can be set.)
1: Functions (parameters n01 ~ n79)
can be set / read.
6: Clear fault history
Parameter write-in 8: 2 wire initialize
01 0101H 1 57
prohibit / initialize (Japanese Specification)
9: 3 wire initialize
(Japanese Specification)
10: 2 wire initialize
(American Specification)
11: 3 wire initialize
(American Specification)
0: Operator
Operation reference
02 0102H 1: Control circuit terminal 1 62
selection
2: Communication
0: Volume
1: Frequency reference 1 (n21)
2: Control circuit terminal
(voltage 0 ~ 10V)
3: Control circuit terminal
Frequency reference
03 0103H (current 4 - 20 mA) 2 63
selection
4: Control circuit terminal
(current 0 - 20 mA)
5: Not used (setting error)
6: Communication
(register number 0002H)
Stopping method 0: Decel to stop
04 0104H 0 82
selection 1: Coast to stop
0: Reverse run enabled
05 0105H REV run prohibit 0 65
1: Reverser run disabled
0: Stop key enabled
Operation stop key
06 0106H 1: Stop key is enabled only when run 0 81
selection
command is selected to the operator.
Frequency reference
0: Volume
07 0107H selection 0 (Note4) 63
1: Frequency reference selection (n21)
in local mode
0: Frequency reference setting by the
operator is enabled with the ENTER
Setting method selection key input
08 0108H 0 63
for frequency reference 1: Frequency reference setting by the
operator is not required the ENTER
key input.

25
Register
No. for Initial *User Ref.
No. Name Description
Trans- Setting Setting Page
mission
Setting unit: 0.1Hz (less than 100Hz) /
Maximum output 1Hz (100Hz or greater)
09 0109H 60.0Hz 58
frequency Setting range: 50.0 ~ 400Hz

Setting unit: 1V
10 010AH Maximum voltage Setting range: 1 ~ 255V 230V (Note 1) 58

Setting unit: 0.1Hz (less than 100Hz) /


Maximum voltage output
11 010BH 1Hz (100Hz or greater) 60.0Hz 58
frequency
Setting range: 0.2 ~ 400Hz
Setting unit: 0.1Hz (less than 100Hz) /
12 010CH Mid. output frequency 1Hz (100Hz or greater) 1.5Hz 58
Setting range: 0.1 ~ 399Hz
Setting unit: 1V
13 010DH Mid. output frequency 12V (Note1) 58
Setting range: 1 - 255V
Minimum output Setting unit: 0.1Hz
14 010EH 1.5Hz 58
frequency Setting range: 0.1 ~ 10.0Hz
Mid. output frequency Setting unit: 1V
15 010FH 12V (Note1) 58
voltage Setting range: 1 ~ 50V
Setting unit: 0.1s (less than 100s) / 1s
16 0110H Acceleration time 1 (100s or greater) 10.0s 69
Setting range: 0.0 ~ 999s
Setting unit: 0.1s (less than 100s) / 1s
17 0111H Deceleration time 1 (100s or greater) 10.0s 69
Setting range: 0.0 ~ 999s
Setting unit: 0.1s (less than 100s) / 1s
18 0112H Acceleration time 2 (100s or greater) 10.0s 69
Setting range: 0.0 ~ 999s
Setting unit: 0.1s (less than 100s) / 1s
19 0113H Deceleration time 2 (100s or greater) 10.0s 69
Setting range: 0.0 ~ 999s
0: No S-curves
S-curve accel / decel 1: 0.2s
20 0114H 0 72
selection 2: 0.5s
3: 1.0s
Frequency reference 1 Setting unit: 0.1Hz (less than 100Hz) /
21 0115H (Master speed frequency 1Hz (100Hz or greater) 0.0Hz 65
reference) Setting range: 0.0 ~ 400Hz
Setting unit: 0.1Hz (less than 100Hz) /
22 0116H Frequency reference 2 1Hz (100Hz or greater) 0.0Hz 65
Setting range: 0.0 ~ 400Hz
Setting unit: 0.1Hz (less than 100Hz) /
23 0117H Frequency reference 3 1Hz (100Hz or greater) 0.0Hz 65
Setting range: 0.0 ~ 400Hz

26
Register
No. for Initial *User Ref.
No. Name Description
Trans- Setting Setting Page
mission
Setting unit: 0.1Hz (less than 100Hz) /
24 0118H Frequency reference 4 1Hz (100Hz or greater) 0.0Hz 65
Setting range: 0.0 ~ 400Hz
Setting unit: 0.1Hz (less than 100Hz) /
25 0119H Frequency reference 5 1Hz (100Hz or greater) 0.0Hz 65
Setting range: 0.0 ~ 400Hz
Setting unit: 0.1Hz (less than 100Hz) /
26 011AH Frequency reference 6 1Hz (100Hz or greater) 0.0Hz 65
Setting range: 0.0 ~ 400Hz
Setting unit: 0.1Hz (less than 100Hz) /
27 011BH Frequency reference 7 1Hz (100Hz or greater) 0.0Hz 65
Setting range: 0.0 ~ 400Hz
Setting unit: 0.1Hz (less than 100Hz) /
28 011CH Frequency reference 8 1Hz (100Hz or greater) 0.0Hz 65
Setting range: 0.0 ~ 400Hz
Setting unit: 0.1Hz (less than 100Hz) /
29 011DH Jog frequency reference 1Hz (100Hz or greater) 6.00Hz 66
Setting range: 0.0 ~ 400Hz
Frequency reference Setting unit: 1%
30 011EH 100% 69
upper limit Setting range: 0 ~ 110%
Frequency reference Setting unit: 1%
31 011FH 0% 69
lower limit Setting range: 0 ~ 110%
Setting unit: 0.1A
Setting range: 0 ~ 120% of inverter
32 0120H Motor rated current rated output current (Note 2) 94
Note: if set to 0%, then electronic ther-
mal motor overload is disabled.
0: Standard motor application
Electronic thermal motor 1: Specialized motor application
33 0121H 0 94
protection 2: No electronic motor overload protec-
tion

27
Register
No. for Initial *User Ref.
No. Name Description
Trans- Setting Setting Page
mission
Parameter selection at
Setting unit: 1min
34 0122H electronic thermal motor 8 min 94
Setting range: 1 ~ 60min
protection
Cooling fan operation 0: Controls the cooling fan OFF / ON
35 0123H 0 96
selection 1: Operates when power is ON.
1: Not used
2: Reverse run reference (2 wire
sequence)
3: External fault (N. O. contact input)
4: External fault (N. C. contact input)
5: Fault reset
6: Multi speed reference 1
8: Multi speed reference 2
7: Multi speed reference 3
9: Not used
10: Jog reference
11: Accel / decel time switching refer-
ence
12: External baseblock reference
(N. O. contact input)
13: External baseblock reference
Multi-function input (N. C. contact input)
36 0124H 2 82
selection 2 14: Speed search command from Max.
output frequency
15: Speed search command set fre-
quency
16: Accel / decel hold
17: Local / remote switching
18: Communication / control circuit ter-
minal switching
19: Emergency stop fault
(N. O. contact input)
20: Emergency stop alarm
(N. O. contact input)
21: Emergency stop fault
(N. C. contact input)
22: Emergency stop alarm
(N. C. contact input)
23~ 33: Unused
0: Forward / reverse command
Multi-function input
37 0125H (3 wire sequence) 5 84
selection 3
Others are the same as parameter 36
Multi-function input
38 0126H Same as parameter 36 3 84
selection 4
Same as parameter 36
Multi-function input 34: Up/down reference
39 0127H 6 84
selection 5 35: Self-test
(Note: valid power ON / OFF)

28
Register
No. for Initial *User Ref.
No. Name Description
Trans- Setting Setting Page
mission
0: Fault
1: During run
2: Frequency agree
3: During zero speed
4: Frequency detection
(detection level or greater)
5: Frequency detection
(detection level or less)
6: During over torque detection
(N. O. contact output)
7: During over torque detection
Multi-function output
40 0128H (N. C. contact output) 1 87
selection
8: Not used
9: Not used
10: Minor fault (during warning display)
11: During baseblock
12: Run mode
13: Inverter ready
14: During fault retry
15: During UV
16: During reverse run
17: During speed search
18: Data output through communication
Analog frequency Setting unit: 1%
41 0129H 100% 67
reference gain Setting range: 0 - 255%
Analog frequency Setting unit: 1%
42 012AH 0% 67
reference bias Setting range: –99 ~ 99%
Setting unit: 0.01s
Analog frequency
Setting range: 0.00 ~ 2.00s
43 012BH reference filter time 0.10s -
(Note)
parameter
When 0.00s is set, there is no filter

29
Register
No. for Initial User Ref.
No. Name
Trans- Setting Setting Page
mission
0: Output frequency
44 012CH Monitor item selection 0 78
1: Output current
Setting unit: 0.01
45 012DH Monitor gain 1.00 78
Setting range: 0.01 ~ 2.00
Set value: 1 ~ 4 carrier frequency = set
value ¥ 2.5kHz
46 012EH Carrier frequency 4(Note 3) 79
Set value: Synchronous type of 7 ~ 9
lower limit 1kHz and upper limit 2.5 kHz
0: Operation does not continue.
1: Operation continues within momen-
Operation selection after
47 012FH tary power ride through time 0 70
momentary power loss
2: Operation always continues. (No
UV1 fault detection)
Setting unit: time
48 0130H Fault reset 0 time 75
Setting range: 0 ~ 10 times
Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
49 0131H Jump frequency 1 Setting range: 0.00 ~ 400Hz 0.0Hz 75
(Note) If 0.0Hz is set, jump frequency 1
is enabled.
Setting unit: 0.1Hz (less than 100Hz) /
1Hz (100Hz or greater)
50 0132H Jump frequency 2 Setting range: 0.00 ~ 400Hz 0.0Hz 75
(Note) If 0.0Hz is set, jump frequency 2
is disabled.
Setting unit: 0.1Hz
Setting range: 0.0 ~ 25.5Hz
51 0133H Jump frequency width 0.0Hz 75
(Note) If 0.0Hz is set, jump frequencies
1 ~ 2 are disabled.
Setting unit: 1%
DC injection braking Setting range: 0 ~ 100%
52 0134H 50% 76
current (note) If 0% is set, it becomes base-
block status.
Setting unit: 0.1s
DC injection braking time Setting range: 0.0 ~ 25.5s
53 0135H 0.0s 83
at stop (Note) If 0.0s is set, this function will no
operate.
Setting unit: 0.1s
DC injection braking time Setting range: 0.0 ~ 25.5s
54 0136H 0.0s 76
at start (Note) If 0.0s is set, this function will not
operate.
0: Stall prevention function is enabled
Stall prevention (current during deceleration.
55 0137H 0 92
limit) during decel 1: Stall prevention function is disabled
during deceleration.
Setting unit: 1%
Setting range: 30 ~ 200%
Stall prevention (current (Note): If set at 200%, this function will
56 0138H 170% 91
limit) during accel not operate.
(Note): For rated output range, the
operator level is automatically reduced.

30
Register
No. for Initial User Ref.
No. Name
Trans- Setting Setting Page
mission
Setting unit: 1%
Stall prevention (current Setting range: 30 ~ 200%
57 0139H 160% 92
limit) during running (Note): If set at 200%, this function will
not operate.
Setting unit: 0.1Hz (less than 100Hz) /
Frequency detection
58 013AH 1Hz (100Hz or greater) 0.0Hz 74
level
Setting range: 0.00 ~ 400Hz
0: Overtorque detection disabled.
1: Detects only at speed agree, opera-
tion continues after detection.
2: Detects only at speed agree, output
59 013BH Overtorque detection is shut down after detection. 0 73
3: Detects during run, operation contin-
ued after detection.
4: Detects during run, output is shut
down after detection.
Overtorque detection Setting unit: 1%
60 013CH 160% 73
level Setting range: 30 ~ 200%
Overtorque detection Setting unit: 0.1s
61 013DH 0.1s 73
time Setting range: 0.1 ~ 10.0s
Memory selection of hold 0: Hold output frequency is not stored.
62 013EH 0 86
output frequency 1: Hold output frequency is stored.
Torque compensation Setting unit: 0.1
63 013FH 1.0 60
gain Setting range: 0.0 ~ 2.5
Setting unit: 0.1Hz
64 0140H Motor rated slip (Note 2) -
Setting range: 0.0 ~ 20.0Hz
Setting unit: 1%
65 0141H Motor no-load current (Note 2) -
Setting range: 0 ~ 99%
Setting unit: 0.1
66 0142H Slip compensation gain 1.0 93
Setting range: 0.0 ~ 2.5
Slip compensation Setting unit: 0.1s
67 0143H 2.0s 93
primary delay time Setting range: 0.0 ~ 25.5s
0: Timeover detection enabled. (Coast
to stop)
1: Timeover detection enabled.
(Deceleration stop by deceleration
time 1)
Timeover detection
68 0144H 2: Timeover detection enabled. 0 -
selection
(Deceleration stop by deceleration
time 2)
3: Timeover detection enabled.
(Operation continues, alarm displays)
4: Timeover detection disabled.
Setting unit selection of 0: 0.1Hz / 1
communications 1: 0.01Hz / 1
69 0145H 0 -
frequency reference/ 2: 100% / 30000
frequency monitor 3: 0.1% / 1

31
Register
No. for Initial User Ref.
No. Name
Trans- Setting Setting Page
mission
Setting unit: 1
70 0146H Slave address 0 -
Setting range: 0 ~ 32
0: 2400 bps
1: 4800 bps
71 0147H Baud rate selection 2 -
2: 9600 bps
3: 19200 bps
0: Even parity
72 0148H Parity selection 1: Odd parity 0 -
2: No parity
Setting unit: 1 = 1ms
73 0149H Send waiting time 10ms -
Setting range: 10 ~ 65 ms
0: RTS control enabled.
74 014AH RTS control 0 -
1: RTS control disabled.
75 –
0: Execution completed / execution
command receive condition
1: READ execute
76 2: COPY execute
3: VRFY execute
4: kVA display
5: Software No. display
0: READ prohibited.
77
1: READ allowed.
The 1 newest event is displayed
78 014EH Fault history - 54
(Note) Setting is disabled.
Lower 3 digits of software numbers are
79 014FH Software No. displayed. - -
(Note): Setting is disabled.

1. Upper limit of setting range and initial setting are doubled at 400 class.
2. Changes depending on inverter capacity. Refer to the next page.
3. Initial setting of the model with digital operator (without volume) is 1.
Setting can be set to 0 by parameter initialization.

32
• KVA Dependant Parameter Default Settings
200V class 3-phase
No. Name Unit Factory setting
– Inverter capacity kW 0.1kW 0.2kW 0.4kW 0.75kW 1.5kW 2.2kW – 3.7kW
n32 Motor rated current A 0.6 1.1 1.9 3.3 6.2 8.5 – 14.1
n64 Motor rated slip Hz 2.5 2.6 2.9 2.5 2.6 2.9 – 3.3
Motor no-load
n65 % 72 73 62 55 45 35 – 32
current

200V class single-phase


No. Name Unit Factory setting
– Inverter capacity kW 0.1kW 0.2kW 0.4kW 0.75kW 1.5kW 2.2kW – 3.7kW
n32 Motor rated current A 0.6 1.1 1.9 3.3 6.2 8.5 – 14.1
n64 Motor rated slip Hz 2.5 2.6 2.9 2.5 2.6 2.9 – 3.3
Motor no-load
n65 % 72 73 62 55 45 35 – 32
current

400V class 3-phase


No. Name Unit Factory setting
– Inverter capacity kW – 0.2kW 0.4kW 0.75kW 1.5kW 2.2kW – 3.7kW
n32 Motor rated current A – 0.6 1.0 1.6 3.1 4.2 7.0 7.0
n64 Motor rated slip Hz – 2.5 2.7 2.6 2.5 3.0 3.2 3.2
Motor no-load
n65 % – 73 63 52 45 35 33 33
current

33
Notes

34
4. MOUNTING
• Choosing a Location to Mount the Inverter
Be sure the inverter is protected from the following conditions:
• Extreme cold and heat. Use only within the ambient temperature range (for open
chassis type): 14 to 122°F (-10 to +50°C)

• Rain, moisture.

• Oil sprays, splashes.

• Salt spray.

• Direct sunlight. (Avoid using outdoors).

• Corrosive gases (e.g. sulfurized gas) or liquids.

• Dust or metallic particles in the air.

• Physical shock, vibration.

• Magnetic noise. (Example: welding machines, power devices, etc.)

• High humidity.

• Radioactive substances.

• Combustibles: thinner, solvents, etc.

35
• Mounting Dimensions
Clearances as shown below are required when mounting the VS mini.

36
• Mounting/Removing Components
Removing and Mounting Digital Operator and Covers
• Removing front cover
Use a screwdriver to loosen the screw on
the front cover surface to direction 1 to
remove it. Then press the right and left
sides to direction 2 and lift the front cover
to direction 3.
• Mounting front cover
Insert the tab of the upper part of the front
cover into the groove of the inverter. Press
the lower part of front cover onto the
plastic case until the cover snaps shut.
Tighten the screws.

• Removing option cover


After removing front cover, remove the
option cover to direction 2 with section A
as a supporting point.
• Mounting option cover
Mount the terminal cover in the reverse
order of the above removal procedure.
• Removing upper/bottom covers
After removing front cover, lift the top and
bottom covers to direction 1.
• Mounting upper/bottom covers
Mount the front cover in the reverse order
of the above removal procedure.

37
Notes

38
5. WIRING
• Wiring Instructions
(1) Always connect the power supply via a molded-case circuit breaker (MCCB) to the
power input terminals R/L1, S/L2, and T/L3 (R/L1, S/L2 for single-phase). Never
connect the power supply to U/T1, V/T2, W/T3,-,+1 or +2.
The single-phase (200V class) inverter can be connected to a 200V 3-phase input.
However, when a single-phase supply is used, never use the terminal T/L3 for other
purposes.
Inverter Power Supply Connection Terminals
200V 3-phase Input Power Supply 200V Single Input Power Supply 400V 3-phase Input Power Supply
Specification Product Specification Product. Specification Product.
CIMR-J7!!2!!! CIMR-J7!!B!!! CIMR-J7!!4!!!
Connect to R/L1, S/L2, T/L3 Connect to R/L1, S/L2 Connect to R/L1, S/L2, T/L3

(2) Connect the motor wiring to terminals U, V, and W on the main circuit output side
(bottom of the inverter).
(3) If the wiring distance between inverter and motor is long, reduce the inverter
carrier frequency. For details, refer to “Reducing motor noise or leakage current
(n46)” on page 79.
(4) Control wiring must be less than 164ft(50m) in length and separate from the power
wiring. Use twisted-pair shielded wire when inputting the frequency signal
externally.
(5) Tighten the screws on the main circuit and control circuit terminals.
(6) Do not connect or disconnect wiring, or perform signal checks while the power
supply is turned ON.

• Wire and Terminal Screw Sizes


1. Control Circuit
Wire
Tightening Recommend
Model Terminal Symbol Screw Torque Applicable size
size
lb • in (N • m) Type
mm2 AWG mm2 AWG
4.44 to 5.33 twisted wire 0.5 to 1.25 20 to 16
Common MA, MB, MC M3 0.75 18 Shielded
(0.5 to 0.6) single 0.5 to 1.25 20 to 16
to wire or
S1 to 1.94 to 2.21 twisted wire 0.5 to 0.75 20 to 18
all models S5,SC,FS,FR,FC,AM,AC
M2 (0.22 to 0.25) single 0.5 to 1.25 20 to 16
0.75 18 equivalent

39
2. Main Circuit
200V Class 3-phase Input Series
Tightening Wire
Torque Applicable Recommended
Model Terminal Symbol Screw size size
lb • in Type
(N • m) mm2 AWG mm2 AWG
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3 7.1 to 8.88 18 to
CIMR-J7*U20P1 M3.5 0.75 to 2 2 14
(0.8 to 1.0) 14
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3 7.1 to 8.88 18 to
CIMR-J7*U20P2 M3.5 0.75 to 2 2 14
(0.8 to 1.0) 14
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3 7.1 to 8.88 18 to
CIMR-J7*U20P4 M3.5 0.75 to 2 2 14
(0.8 to 1.0) 14 600V vinyl-
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3 7.1 to 8.88 18 to sheathed
CIMR-J7*U20P7 M3.5 0.75 to 2 2 14
(0.8 to 1.0) 14 wire or
R/L1,S/L2,-,+1,+2,U/T1,V/T2,W/T3 7.1 to 8.88 14 to equivalent
CIMR-J7*U21P5 M3.5 2 to 5.5 2 14
(0.8 to 1.0) 10
R/L1,S/L2,-,+1,+2,U/T1,V/T2,W/T3 7.1 to 8.88 14 to
CIMR-J7*U22P2 M3.5 2 to 5.5 3.5 14
(0.8 to 1.0) 10
R/L1,S/L2,-,+1,+2,U/T1,V/T2,W/T3 10.7 to 13.3 14 to
CIMR-J7*U23P7 M4 2 to 5.5 5.5 10
(1.2 to 1.5) 10

Note: The wire size indicated is for copper wires at 160°F (75°C)
200V Class Single-phase Input Series
Tightening Wire
Torque Applicable Recommended
Model Terminal Symbol Screw size size
lb • in Type
(N • m) mm2 AWG mm2 AWG
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3 7.1 to 8.88 18 to
CIMR-J7*UB0P1 M3.5 0.75 to 2 2 14
(0.8 to 1.0) 14
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3 7.1 to 8.88 18 to
CIMR-J7*UB0P2 M3.5 0.75 to 2 2 14
(0.8 to 1.0) 14 600V vinyl-
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3 7.1 to 8.88 18 to sheathed
CIMR-J7*UB0P4 M3.5 0.75 to 2 2 14
(0.8 to 1.0) 14 wire or
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3 7.1 to 8.88 14 3.5 12 equivalent
CIMR-J7*UB0P7 M4 2 to 5.5
(0.8 to 1.0) to10 2 14
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3 7.1 to 8.88 14 to 5.5 10
CIMR-J7*UB1P5 M4 2 to 5.5
(0.8 to 1.0) 10 2 14
Note: The wire size indicated is for copper wires at 160°F (75°C)
Note: Three-phase input is also acceptable for single-phase input series.

40
400V Class 3-phase Input Series
Tightening Wire
Torque Applicable Recommended
Model Terminal Symbol Screw size size
lb • in Type
(N • m) mm2 AWG mm2 AWG
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3 7.1 to 8.88 14 to
CIMR-J7*U40P2 M3.5 2 to 5.5 2 14
(0.8 to 1.0) 10
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3 7.1 to 8.88 14 to
CIMR-J7*U40P4 M3.5 2 to 5.5 2 14
(0.8 to 1.0) 10
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3 7.1 to 8.88 14 to
CIMR-J7*U40P7 M3.5 2 to 5.5 2 14 600V vinyl-
(0.8 to 1.0) 10
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3
sheathed
7.1 to 8.88 14 to
CIMR-J7*U41P5 M3.5 2 to 5.5 2 14 wire or
(0.8 to 1.0) 10
equivalent
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3 10.65 to 13.31 14 to
CIMR-J7*U42P2 M4 2 to 5.5 2 14
(1.2 to 1.5) 10
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3 10.65 to 13.31 14 to 2 14
CIMR-J7*U43P0 M4 2 to 5.5
(1.2 to 1.5) 10 3.5 12
R/L1,S/L2,T/L3,-,+1,+2,U/T1,V/T2,W/T3 10.65 to 13.31 14 to 2 14
CIMR-J7*U43P7 M4 2 to 5.5
(1.2 to 1.5) 10 3.5 12

Note: The wire size indicated is for copper wires at 160°F (75°C)

41
• Wiring the Main Circuit

(Example of 3-phase,
200V class, 1.5kW
inverters)

• Main Circuit Input Power Supply


Connect the power supply wiring to input When several VS mini J7 units are used
terminals L1 (R), L2(S) and L3(T) [L1(R), side by side, ground each unit as shown in
L2(S) for single-phase inverters]. Never examples. Do not loop the ground wires.
connect them to U/T1, V/T2, W/T3, -, +1,
or +2. Otherwise the inverter may be
damaged. Single-phase voltage may be
connected to inverter but do not use
terminal T/L3 for any other purposes.
On Single-phase models, terminal
T/L3 is connected internally within
the inverter. Never use the terminal • Wiring the Main Circuit Terminals
for other purposes. Pass the cables through wiring hole and
connect. Be sure to mount the cover in its
• Grounding (Use ground terminal .) original position.
Make sure to ground the ground terminal
according to the local grounding code.
Never ground the VS mini J7 to welding
machines, motors, or other electrical
equipment.

Connect with a Phillips (plus)


screwdriver.

42
• Recommended Peripheral Devices
It is recommended that the following periheral devices be mounted between the AC
main circuit power supply and VS mini J7 input terminals R/L1, S/L2, and T/L3.
• MCCB (Molded-case circuit breaker):
A circuit breaker should be connected for wiring protection.
• Magnetic contactor:
Mount a surge suppressor on the coil (refer to the table shown below).
To assure optimum inverter life when using a magnetic contactor to start and stop
the inverter, do not exceed one stop per hour.
Recommended MCCB and magnetic contactor
• 200V 3-Phase
VS mini J7 model J7 * * J7 * * J7 * * J7 * * J7 * * J7 * * J7 * *
20P1 20P2 20P4 20P7 21P5 22P2 23P7
Capacity (kVA) 0.3 0.6 1.1 1.9 3.0 4.2 6.7
Rated Output Current (A) 0.8 1.6 3 5 8 11 17.5
MCCB type NF30
5A 5A 5A 10A 20A 20A 30A
(MITSUBISHI)
Magnetic contactor type HI
HI-7E HI-7E HI-7E HI-7E HI-10-2E HI-10-2E HI-20E
(YASKAWA CONTROL)

• 200V single-Phase
J7 * * J7 * * J7 * * J7 * * J7 * *
VS mini J7 model
B0P1 B0P2 B0P4 B0P7 B1P5
Capacity (kVA) 0.3 0.6 1.1 1.9 3.0
Rated Output Current (A) 0.8 1.6 3 5 8
MCCB type NF30, NF50
5A 5A 10A 20A 20A
(MITSUBISHI)
Magnetic contactor type HI
HI-7E HI-7E HI-7E HI-10-2E HI-15E
(YASKAWA CONTROL)

• 400V 3-Phase
J7 * * J7 * * J7** J7 * * J7 * * J7 * *
VS mini J7 model
40P1 40P2 40P4 41P5 42P2 43P7
Capacity (kVA) 0.9 1.4 2.6 3.7 4.2 7.0
Rated Output Current (A) 1.2 1.8 3.4 4.8 5.5 9.2
MCCB type NF30, NF50
5A 5A 5A 10A 10A 20A
(MITSUBISHI)
Magnetic contactor type HI
HI-7E HI-7E HI-7E HI-10-2E HI-10-2E HI-10-2E
(YASKAWA CONTROL)

43
Surge suppressors
Surge Suppressors Model
Specifications Code No.
Coils and relays DCR2-
250VAC
Large size magnetic contactors 50A22E C002417
0.5µF 200Ω
200V
to Control relays
230V MY-2, -3 (OMRON) 250VAC
10A25C C002482
HH-22, -23 (FUJI) 0.1µF 100Ω
MM-2. -4 (OMRON)

• Ground fault interrupter:


Select a ground fault interrupter not affected by high frequencies. To prevent
malfunctions, the leakage current sensitivity should be 200mA or more and the
operating time 0.1 sec. or more.
Example: " NV series by Mitsubishi Electric Co., Ltd. (manufactured in 1988 and
after).
" EGSG series by Fuji Electric Co., Ltd.(manufactured in 1984 and after).

• AC and DC reactor:
Install an AC reactor to connect to a power supply transformer of large capacity
(600kVA or more) or to improve power factor on the power supply side.
• Noise filter:
Use a noise filter exclusively for inverter if radio noise generated from the inverter
causes other control devices to malfunction.

NOTE: (1) Never connect a general LC/RC noise filter to the inverter output circuit.
(2) Do not connect a phase advancing capacitor to the I/O sides and/or a surge
suppressor to the output side.
(3) When a magnetic contactor is installed between the inverter and the motor,
do not turn it ON/Off during operation.
For the details of the peripheral devices, refer to the catalog.

44
• Wiring the Control Circuit
Only basic insulation is provided for the control circuit terminals.
Additional insulation may be necessary in the end product.
• Control Circuit terminals
Pass the cable through wiring hole and connect. Be sure to mount all the covers in the
original position.

* SW7 can be changed according to sequence input


signal (S1 to S5) polarity.
0V common: NPN side (factory setting)
24 common: PNP side
Refer to pages 89 for SW8

Wiring the control circuit terminals

Screwdriver blade width

Insert the wire into the lower part of the terminal block and connect it tightly with a
screwdriver.

Wire sheath strip length must be 0.22 in. (5.5mm).

45
Open the front cover and verify that the strip length is 0.22 in. (5.5mm)

• Wiring Inspection
After completing wiring, check the following:
• Wiring is properly connected.
• Wire clippings or screws are not left inside the unit.
• Screws are securely tightened.
• Bare wires in the terminal do not come in contact with other terminals.
If the FWD (REV) run command is given during the operation reference selec-
tion (n02=1) from the control circuit terminal, the motor will start automatically
after the main circuit input power supply is turned ON.

46
6. OPERATING THE INVERTER
• Test Run
The inverter operates by setting the frequency (speed).
There are three types of operation modes for the VS mini J7:
1. Run command from the digital operator (local potentiometer/digital setting).
2. Run command from the control circuit terminal.
3. Run command from communications (MEMOBUS).
(Communication option card is required)
Prior to shipping, the drive is set up to receive run command and frequency reference
from the control circuit terminal. Following are instructions for running the VS mini J7
using the digital operator (with volume). For instructions on operation, refer to page
47.
Operation reference or frequency reference parameters can be selected separately as
shown below.
Name Parameter
n02 = 0 --- Enables operator RUN, STOP/RESET
Operation Reference
= 1 --- Enables control circuit terminal run/stop
Selection
= 2 --- Enables communications (MEMOBUS)
n03 = 0 --- Enables operator volume
= 1 --- Enables frequency reference 1 (parameter 24)
Frequency Reference = 2 --- Enables voltage reference (0 to 10V) of control circuit terminal
Selection = 3 --- Enables current reference (4 to 20mA) of control circuit terminal
= 4 --- Enables current reference (0 to 20mA) of control circuit terminal
= 6 --- Enables communications (MEMOBUS)

47
Operator 12-LED Status
Operation Steps
Display Display Indicator LED
1. Turn the local pot (volume control) fully counter clockwise 0.00 RUN
after turning the power ON.

ALARM

2. Press DSPL 5 times to illuminate Lo/RE Lo Lo/RE RUN


Select Lo (local mode) using or key

ALARM

3. F/R blinks. For RUN


Select FWD/REV run using keys or
Never select REV when reverse run REV
is prohibited. ALARM

4. Press DSPL to illuminate FREF. Then press RUN. 0.00 RUN

ALARM

5. Operate the motor by turning the volume clockwise. 0.00 to 60.00 RUN
(Frequency reference corresponding to the volume position Minimum
is displayed.) output
If the volume is switched rapidly, the motor also frequency is ALARM
accelerates or decelerates rapidly corresponding to 1.5Hz
the volume movement. Pay attention to load status
and adjust the volume to the desired speed.

Status indicator lamp : ON : Blinking : OFF

Operation Check Points


• Motor rotates smoothly.
• Motor rotates in the correct direction.
• Motor does not have abnormal vibration or noise.
• Acceleration or deceleration is smooth.
• Current is appropriate for the load (No overload).
• Status indicator LED’s and digital operator display are correct.

48
• Operating the Digital Operator
All functions of the VS mini J7 are set by the digital operator. Below are descriptions
of the display and keypad sections.
Digital Operator

49
Description of Status Indicator LED’s
There are two LED’s on the middle right section of the face of the VS mini. The
inverter status is indicated by various combinations of the LED’s (ON, BLINKING
and OFF). RUN indicator and status indicator of the RUN button have the same
functions.

For details on how the status indicator LED’s function at inverter faults, refer to
Section 8 “FAULT DIAGNOSIS AND CORRECTIVE ACTIONS” on page 103. If a
fault occurs, the ALARM LED lights.
STOP
The fault can be reset by turning ON the fault reset signal (or pressing RESET key
on the digital operator) when the operation signal is removed or by turning OFF
the power supply. If the operation signal is ON, the fault cannot be reset by the
fault reset signal.

50
• LED Description
By pressing on the digital operator, each of the function LED’s can be
selected.
The following flowchart describes each function LED.

51 and 52

51
Parameter

Parameter No. (Refer to page 57)

Return to

Multi-Function monitor
• Selecting monitor
Press key. When is ON, data can be displayed by
selecting monitor No.
[Example] Monitoring Output Voltage Reference

52
• Monitoring
Following items can be monitored by U-parameters
Parameter
Name Description
No.
Frequency reference Frequency reference can be monitored.
U-01 Hz
(FREF) (Same as FREF)
Output frequency Output frequency can be monitored.
U-02 Hz
(FOUT) (Same as FOUT)
Output current Output current can be monitored.
U-03 AMP
(IOUT) (Same as IOUT)
U-04 Output voltage V Output voltage can be monitored.
U-05 DC voltage V Main circuit DC bus voltage can be monitored.
Input terminal status of control circuit terminals can be
U-06 Input terminal status —
monitored.
Output terminal status of control circuit terminals can
U-07 Output terminal status —
be monitored.
U-09 Fault history — Last four fault history is displayed.
U-10 Software No. — Software No. can be checked.
Contents of MEMOBUS communications data
U-15 Data reception error — reception error can be checked. (contents of
transmission register No. 003DH are the same)

53
Fault history display method
Fault description is displayed when U09 is selected.
(Example)
!!!: Fault description (“---” is displayed if there is no fault.)
(Refer to page 103 for details.)

• Clearing fault history


Set parameter n001 to 6 to clear fault history. Set data returns to its initial value
after completion of 6 setting.
Note: Parameter initialize (n01 = 10, 11) also clears the fault history.

Setting and referring parameters


The following figure shows how to select and change parameters.

54
• Simple Data Setting
Volume setting (Refer to 5, OPERATING THE INVERTER) and digital setting are
both available for simple accel/decel operation of the VS mini.
Frequency reference by analog voltage is set with initial setting (n03 = 2).
Following is an example in which the function LEDs are used to set frequency
reference, acceleration time, deceleration time, and motor direction.

55
Notes

56
7. PROGRAMMING FEATURES
Factory settings of the parameters are shown as in the tables.

• Parameter Set-up and Initialization


Parameter selection/initialization (n01)
The following table describes the data which can be set or read when n01 is set.
Unused parameters among n01 to n79 are not displayed.
n001 Setting Parameter that can be set Parameter that can be viewed
0 n01 n01 to n79
1 n01 to n79* n01 to n79
6 Fault history cleared
7 Not used
10 Initialize (2-wire sequence)
11 Initialize (3-wire sequence)=
* Excluding setting disabled parameters.
= Refer to page 85.

“ ” appears on the LED display for one second and the set data returns to
its initial values in the following cases:
(1) The set values of input terminal function selection 2 to 5 (n36 to n39) are the same.
(2) The following conditions are not satisfied in the V/f pattern setting:
Max. output frequency (n09) > Max. voltage output frequency (n11)
> Mid. output frequency (n12)
> Min. output frequency (n14)
For details, refer to “Adjusting torque according to application” (V/f pattern set-
ting) on page 56.
(3) If the following conditions are not satisfied in the Jump frequency setting:
Jump frequency 2 (n50) < Jump frequency 1 (n49)

(4) If Frequency reference lower limit (n31) > Frequency reference upper limit (n30)
(5) If motor rated current (n32) > 150% of inverter rated current

57
• Selecting V/f pattern
Adjusting torque according to application
Adjust motor torque by using “V/f pattern” and “full-range automatic torque boost”.
• V/f pattern setting
Set V/f pattern by parameters n09 to n15 as described below. Set each pattern when
using a special motor (high-speed motor, etc.) or when requiring special torque
adjustment of machine.
Be sure to satisfy the following conditions for
the setting of n09 to n15.
n14 < n12 < n11 < n09
If n14 = n12, the set value of n13 is disabled.

Parameters
Name Unit Setting range Initial Setting
No.
n09 Max. output frequency 0.1Hz 50.0 to 400Hz 60.0Hz
1 to 255V 230V
n10 Max. voltage 1V
(0.1 to 510V) (460V)
Max. voltage output frequency
n11 0.1Hz 0.2 to 400Hz 60.0Hz
(base frequency)
n12 Mid. output frequency 0.1Hz 0.1 to 399Hz 1.5Hz
0.1 to 255V 12V
n13 Mid. output frequency voltage 1V
(0.1 to 510V) (24V)
n14 Min. output frequency 0.1Hz 0.1 to 10.0Hz 1.5Hz
1 to 50V 12V
n15 Min. output frequency voltage 1V
(0.1 to 100V) (24V)

58
• Typical setting of V/f pattern
Set the V/f pattern according to the application as described below. For 400V class,
the voltage values (n10, n13, and n15) should be doubled. When running at a
frequency exceeding 50Hz/60Hz, change the maximum output frequency (n09).
Note: Be sure to set the maximum output frequency according to the motor
characteristics.

Increasing voltage of V/f pattern increases motor torque, but excessive increase may
cause motor over excitation, motor overheat, or vibration.

59
When operating with frequency larger than 60Hz/50Hz, change only maximum output
frequency (n09).

• Full-range automatic torque boost


Motor torque requirement changes according to load conditions. Full range
automatic torque boost adjusts voltage of V/f pattern according to the requirement.
The VS mini J7 automatically adjusts the voltage during constant-speed operation
as well as during acceleration.
The required torque is calculated by the inverter. This ensures tripless operation and
energy-saving effects.

Output voltage ∝ Torque compensation gain (n63) × Required torque

Operation

Normally, no adjustment is necessary for torque compensation gain (n63 factory


setting: 1.0). When wiring distance between the inverter and motor is long or when
motor generates vibration, change the automatic torque compensation gain. In these
cases, it may also be beneficial to adjust the V/f pattern (n09 to n15).

60
• Switching LOCAL/REMOTE Modes
The following functions can be selected by switching the LOCAL or REMOTE
mode. To select RUN/STOP commands or frequency reference, change the mode
in advance depending on the following applications.

• LOCAL Mode:
Enables the digital operator for RUN/STOP commands and
FWD/REV run commands. Frequency reference can be set by
volume or .
• REMOTE Mode:
Run by the n02 setting (operation reference selection).
Frequency reference can be set by n03 (frequency reference selection) setting.

• How to select LOCAL/REMOTE modes

(When 17 is not set to (When 17 is set to any


any parameters n36 to parameters n36 to n39)
n39)

61
• Selecting Run/Stop Commands
Refer to page 63 to select either the LOCAL mode or REMOTE mode.
Operation method (RUN / STOP commands, FWD / REV run commands) can be
selected by the following method.
• LOCAL Mode
When Lo (local mode) is displayed on the digital operator (when is
illuminated), or when the LOCAL / REMOTE changeover function is set as a
multi-function input and the input terminal is turned ON, run operation is enabled
by the or of the digital operator. FWD/REV is selected by
illuminating and using or key to select FWD or REV.
• REMOTE mode
• Select remote mode
The following two methods are used to select remote mode:
1. Select rE (remote mode) for selection.
2. When the local / remote switching function is selected as multi-function
input selection, turn OFF the input terminal to select remote mode.
• Select operation method by setting the parameter n02.
n02=0: Enables the digital operator (same with local mode)
=1: Enables the multi-function input terminal (see fig. below)
=2: Enables communications (refer to page 96)

• Example for using the multi-function input terminal as operation reference


(two-wire sequence) follows. For 3-wire sequencing, refer to page 85.

• Operating (RUN /STOP commands) by communications


(When option card is installed)
Setting parameter n02 to 2 in REMOTE mode can give RUN / STOP commands by
communication (MEMOBUS). For details, refer to page 96.

62
• Selecting Frequency Reference
Frequency reference can be selected by the following methods.
• Setting by operator
Select REMOTE or LOCAL mode in advance. For the method of selecting the
mode, refer to page 62.
LOCAL mode
Parameter n07 determines where the frequency reference is input from when in the
local mode.
n07 =0: Enables the setting by volume on digital operator (initial setting)
Factory setting of the model with operator
(without volume) is n07=1.
=1: Enables the digital setting by digital operator, setting value is stored
in parameter n21 (frequency reference 1).
• Digital setting by digital operator
Input frequency while FREF is illuminated (press ENTER after setting the desired
frequency value).
Frequency reference setting is immediately effective when n08 = 1 The ENTER
key does not have to be pressed to enter the reference.
n08 =0: Enables frequency reference acceptance by ENTER key.
=1: Disable frequency reference setting by ENTER key. It is not necessary
to press the ENTER key to accept the reference.

REMOTE mode
Parameter n03 determines where the frequency reference is accepted from when in
the REMOTE mode.
n03 =0: Enables frequency reference setting by volume on digital operator.
=1: Frequency reference 1 (parameter n21) is effective
=2: Voltage reference terminal “FR” is effective (0 to 10V)
(See the figure below)
=3: Current reference terminal “FR” is effective(4 to 20mA)
(Refer to page 90)*
=4: Current reference terminal “FR” is effective (0 to 20mA)
(Refer to page 90)*
=6: Communication (Refer to page 97)

63
*NOTE: SWB must be set to the “I” position when using terminal “FR” as a
current reference input.
Example of frequency reference by voltage signal

n03: 2 (factory setting)

SW8 is set to “V” position when


using terminal “FR” as a voltage
reference (default setting)

64
• Setting Operation Conditions
Reverse run prohibit (n06)
The “Reverse run disabled” setting will not accept a reverse run command from the
control circuit terminal or digital operator. This setting is used for applications where a
reverse run command is undesirable.
Setting Description
0 Reverse run enabled
1 Reverse run disabled

Multi-step speed selection


Up to 8 preset references can be selected by using Multi-Function inputs.
Example: 8-step speed reference
n02=1 (operation mode selection) n36=2 (Multi-function contact input terminal S2)
n03=1 (Frequency reference selection) n37=6 (Multi-function contact input terminal S3)
n21=25.0Hz (Frequency reference 1) n38=7 (Multi-function contact input terminal S4)
n22=30.0Hz (Frequency reference 2) n39=8 (Multi-function contact input terminal S5)
n23=35.0Hz (Frequency reference 3)
n24=40.0Hz (Frequency reference 4)
n25=45.0Hz (Frequency reference 5)
n26=50.0Hz (Frequency reference 6)
n27=55.0Hz (Frequency reference 7)
n28=60.0Hz (Frequency reference 8)
When all multi-function reference
inputs are OFF, frequency reference
selected by parameter n03
(frequency reference selection)
becomes effective.

65
Operating at Jog frequency reference
By inputting a jog command and then a forward or (reverse) run command, operation is
enabled at the jog frequency set in n29. When multi-step speed references 1, 2, 3 or 4
are input simultaneously with the jog command, the jog command has priority.
Name parameter No. Setting
Jog frequency reference n29 Factory setting: 6.00Hz
Jog command n36 to n39 Set to “10” for any parameter.

66
• Adjusting speed setting signal
The relationship between the analog input signal and internal (terminal “FR”)
frequency reference can be set by parameters n41 and n42.

FREQUENCY REFERENCE

(a) Frequency reference gain (n41)


The analog input voltage level for the maximum output frequency (n09) can be set
in units of 1%. (maximum output frequency n09=100%)
∗ Factory setting : 100%

(b) Frequency reference bias (n42)


The frequency reference provided when the analog input is 0V (4mA or 0mA) can
be set in units of 1%. (Maximum output frequency n09=100%)
∗ Factory setting : 0%

Example settings:
• To operate the inverter with frequency reference of 0% to 100% at 0 to 5V input

Gain n41 = 200%


Bias n42 = 0%

67
• To operate the inverter with frequency reference of 50% to 100% at 0 to
10V input

Gain n41 = 100%


Bias n42 = 50%

68
Adjusting frequency upper and lower limits
Frequency reference upper (n30) and lower
(n31) limits determines the range over which the
inverter will operate.
• Frequency reference upper limit (n30)
Sets the upper limit of the frequency
reference in units of 1%.
(n09: Maximum output frequency = 100%)
Factory setting: 100%
• Frequency reference lower limit (n31)
Sets the lower limit of the frequency
reference in units of 1%.
(n09: Maximum output frequency = 100%)
When operating at frequency reference 0,
operation is continued at the frequency
reference lower limit.
However, when frequency reference lower
limit is set to less than the minimum output
frequency (n14), operation is not performed.
Factory setting: 0%
Using two accel/decel times

* When “deceleration to a stop” is selected (n04 = 0)


Two acceleration times and two deceleration times can be selected via a multi-function
input. Programming any of terminals S2 through S5 (parameter n36 to n39) to “11”
“Accel/Decel time select”, provides the ability to switch between the 2 acceleration
times (n16 and n18) and deceleration (n17 and n19) through a contact closure applied
to the appropriate terminal (See timing diagram above).
69
At OFF: n16 (accel time 1) are used.
n17 (decel time 1)
At ON: n18 (accel time 2) are used.
n19 (decel time 2)
• Accel time
Set the time needed for output frequency to reach 100% from 0%.
• Decel time
Set the time needed for output frequency to reach 0% from 100%.
(Maximum output frequency n09 = 100%)

Automatic restart after momentary power


loss (n47)
The inverter has the ability to ride thru momentary power outages provided the control
logic power supplies are maintained.
When momentary power loss occurs, operation restarts automatically.
Setting. Description
0 Continuous operation after momentary power loss not provided.
Continuous operation after power recovery within momentary
1*
power loss ride thru time is provided.
Continuous operation after power recovery (Fault output not
2*†
provided)
* Maintain the run command to continue operation after recovery from a momentary power loss.
† When 2 is selected, operation restarts if power supply voltage reaches its normal level while control
power supply is held. No fault signal is output.

70
Soft-start characteristics (n020)
To prevent shock at machine start/stop, accel/decel can be performed in a S-curve
pattern.
Setting S-curve characteristic time
0 S-curve characteristic not provided
1 0.2 second
2 0.5 second
3 1.0 second
Note: The S-curve characteristics time from accel/decel rate 0 to a regular accel/decel rate
determined by the set accel/decel time.

71
The following time chart shows FWD/REV run switching at deceleration to a stop.

Overtorque detection
If an excessive load is applied to the machine, output current increase can be detected
to output alarm signals to multi-function output terminals MA and MB.
To output an overtorque detection signal, set output terminal function selection n40 to
“overtorque detection” [Setting:6 (NO contact) or 7 (NC contact)].

∗ Overtorque detection release width (hysterisis) is set at approx. 5% of inverter rated current.

72
• Overtorque detection function selection (n59)
Setting Description
0 Overtorque detection not provided
Detected during speed agree, (alarm).
1
Operation continues after detection.
Detected during speed agree (fault). Operation stops during
2
detection.
Detected during running,
3
operation continues after detection. (alarm).
Detected during running,
4
operation stops during detection. (fault).
(1) To detect overtorque at accel/decel, set to 3 or 4.
(2) To continue the operation after overtorque detection, set to 1 or 3.
During detection, the operator displays “ ” alarm (blinking).
(3) To halt inverter by a fault at overtorque detection, set to 2 or 4. At detection, the
operator displays “ ” fault (ON).
• Overtorque detection level (n60)
Sets the overtorque detection current level in units of 1%. (Inverter rated current =
100%)
Factory setting: 160%
• Overtorque detection time (n61)
If the time when the motor current exceeds the overtorque detection level (n61),
the overtorque detection function operates.
Factory setting: 0.1sec.

73
Frequency detection (n58)
Effective when the multi-function output terminal MA-MB-MC (parameter n40) is set
to “frequency detection” (setting: 4 or 5). “Frequency detection” turns ON when output
frequency is higher or lower than the frequency detection level (n58).
• Frequency detection 1 (Output frequency > Frequency detection level n58)
(Set n40 to “4”.)

• Frequency detection2 (Output frequency < Frequency detection level n58)


(Set n40 to “5”.)

74
Jump frequencies (n49 to n51)
This function allows the prohibit or “jumping” of critical frequencies so that the motor
can operate without resonance caused by machine characteristics. This function is also
used for dead band control. Setting the value to 0.00Hz disables this function.
Set prohibited frequency 1, 2 or as follows:

n49 > n50


If this condition is not satisfied the
inverter displays for one second
and restores the data to original
settings.

Continuous operation is prohibited within the jump frequency range.


However, during accel/decel the output frequency ramps through the jump frequency
range (without jumping).

Continuing operation by automatic


fault reset (n48)
Sets the inverter to restart and reset fault detection after a fault occurs.
The number of self-diagnosis and retry attempts can be set with n48 (0 thru 10 restarts).
The inverter will automatically restart after the following faults occur:
• OC (overcurrent)
• GF (ground fault)
• OV (over voltage)
The number of retry attempts are cleared to 0 during the following cases:
(1) If no other fault occurs within 10 minutes after retry
(2) When the fault reset signal is ON after the fault is detected
(3) Input power is turned OFF

75
Starting into a rotating motor - Tripless Operation
To start into a coasting motor without trip, use the speed search command or DC
injection braking at start.
• Speed search command
Speed matches into a coasting motor upon starting without stopping the motor.
This function enables smooth switching between motor commercial power supply
operation and inverter operation.
Set input terminal function selection (n36 to n39) to “14” (search command from
maximum output frequency) or “15” (search command from set frequency).
Build a sequence so that FWD (REV) run command is input at the same time as the
search command or after the search command. If the run command is input before
the search command, the search command becomes disabled.
• Time chart at search command input

• DC injection braking at start (n52, n54)


When starting into a coasting motor, use DC injection to gradually brake the motor
before beginning the acceleration ramp. Set the DC injection braking time at start
in n54 in units of 0.1 second. Set DC injection braking current in n52 in units of 1%
(inverter rated current = 100%). When the setting of n54 is “0”, DC injection
braking is not performed and acceleration starts from the minimum output
frequency.
When n52 is set to 0, acceleration starts from the minimum output frequency after
base blocking for n54 setting time.

76
Accel/Decel Hold
To hold acceleration or deceleration, use a multi-function input that is set to a value of
“16: Accel/Decel Hold. The output frequency is kept constant when the accel/decel
hold command is input during acceleration or deceleration.
When the run command is removed during an accel/decel hold condition, accel/decel
hold is internally released and operation ramps to stop.
Set multi-function input terminal selection (n36 to n39) to 16 (accel/decel hold
command).

Note: When the FWD (REV) run command is input along with the accel/decel hold com-
mand, the motor does not operate. However, when frequency reference lower limit
(n31) is set greater than or equal to minimum output frequency (n14), the motor
operates at frequency reference lower limit (n31).

77
Using a frequency meter or ammeter (n44)
Determines whether output frequency or output current is indicated on the analog
output terminals, AM-AC, for monitoring.
Setting Description
0 Output frequency
1 Output current
Initial setting-analog voltage of approx. 10V is output when output frequency (output
current) is 100%.

Calibrating frequency meter or ammeter (n045)


Used to adjust analog output gain.

Scales the analog output voltage signal level at 100% of output frequency (output
current).
Example: Frequency meter displays 0 to 60Hz with 0 to 3V.
10V x n45 setting (0.30V) = 3V (3V is output at 100% output frequency)

78
Reducing motor noise leakage current (n46)
Set inverter output transistor switching frequency (carrier frequency).
Audible Noise RFI Noise and
Setting Carrier Frequency (kHz)
from Motor Current Leakage
7 12 fout (Hz)
Higher Smaller
8 24 fout (Hz)
9 36 fout (Hz)
1 2.5 (kHz)
2 5.0 (kHz)
3 7.5 (kHz)
Not Larger
audible
4 10.0 (kHz)
Setting values 7, 8, or 9 provides a synchronous carrier frequency that changes with
output frequency as follows.

79
Carrier Frequency Varies According to Inverter Capacity (kVA).
Initial Setting Maximum
Reduced
Capacity Continuous
Voltage Class Carrier Current (A)
hp(kW) Setting Output Current
Frequency *1
(A)
0.13 (0.1) 4 10kHz 0.8
0.25 (0.2) 4 10kHz 1.6

200V 0.5 (0.4) 4 10kHz 3.0
Single-phase 1 (0.75) 4 10kHz 5.0
3-phase 2 (1.5) 3 7.5kHz 8.0 7.0
3 (2.2) 3 7.5kHz 11.0 10.0
5 (3.7) 3 7.5kHz 17.5 16.5
0.25 (0.2) 3 7.5kHz 1.2 1.0
0.5 (0.4) 3 7.5kHz 1.8 1.6
1 (0.75) 3 7.5kHz 3.4 3.0
400V
2 (1.5) 3 7.5kHz 4.8 4.0
3-phase
3 (2.2) 3 7.5kHz 5.5 4.8
4 (3.0) 3 7.5kHz 7.2 6.3
5 (3.7) 3 7.5kHz 9.2 7.6

(1) Reduce continuous output current by changing carrier frequency to a


setting of 4 (10 kHz) for 200V class inverters (size > 1.5kW) and all 400V
class inverters. Refer to the table above for the reduced current.
[Operation Condition]
• Input power supply voltage: 3-phase 200 to 230V (200V class)
Single-phase 200 to 240V (200V class)
3-phase 380 to 460V (400V class)
• Ambient temperature: 14 to 122 oF (-10 to +50oC)

(2) If the wiring distance is long (approx. 50 meters), reduce the inverter car-
rier frequency as described below.
Wiring Distance between
Up to 50m Up to 100m More than 100m
Inverter and Motor
10kHz or less 5kHz or less
Carrier frequency 2.5kHz or less
(n46=1, 2, 3, 4, (n46=1, 2,
(n46 setting) (n46=1, 7, 8, 9)
7, 8, 9) 7, 8, 9)

(3) Carrier frequency can be automatically reduced to 2.5 kHz when (n75) is set
to 1 and the following conditions are satisfied.
Output frequency < 5Hz
Output frequency > 100%
Factory Setting (n75) is 0 (disabled)

80
Operator stop key selection (n06)
Selects whether the “STOP” key on the digital operator is effective when operating the
inverter by an external source (input terminals or serial communications).
Setting Description
STOP key effective when running either from multi-function input terminals or communications.
When STOP key is pressed, the inverter stops according to the setting of parameter n04. At this
0 time, the digital operator displays “ ” alarm (blinking). This stop command is held in the
inverter until both forward and reverse run commands are open, or until run command from
communications becomes zero.
STOP key is ineffective when running either from multi-function input terminals or
1
communications.

81
• Selecting Stopping Method
Selecting stopping method (n04)
Selects the stopping method when the run command is removed.
Setting Description
0 Deceleration to stop
1 Coast to stop

• Deceleration to stop (n04 =0)

* When frequency reference is changed during running.

Upon removal of the FWD (REV) run command, the motor decelerates at the decel rate
determined by the time set to decel time 1 (n17) and DC injection braking is applied
immediately before stop. DC injection braking is also applied when the motor
decelerates by setting the frequency reference lower than minimum output frequency
while the(n14) with FWD (REV) run command remains ON.
If the decel time is short or the load inertia is large, an over voltage (OV) fault may
occur during deceleration. In this case, increase the decel time.

82
• Coast to stop (n04=1)

* When frequency reference is changed during running.

Upon removal of the FWD (REV) run command, the motor starts coasting.

Applying DC injection braking


• DC injection braking current (n52)
Sets DC injection braking current level in units of 1%. (Inverter rated
current=100%)
• DC injection braking time at stop (n53)
Sets the DC injection braking time at stopping in units of 0.1 second. When the
setting of n53 is 0, DC injection braking is not performed but inverter output is shut
OFF at the timing of DC injection braking start.

When coast to a stop is selected as the stopping method selection (n04), DC injection
braking at stop does not operate.

83
• Building Interface Circuits with External Devices
Using input signals
Multi-function input terminal S2 to S5 functions can be changed when necessary by
setting parameters n36 thru n39 respectively. Parameters n36 thru n39 cannot be set to
the same value.
Setting Name Description Ref.
FWD/REV run command
0 (3 wire sequence selection) Setting enabled only for n37 85
Reverse run
2 (2 wire sequence selection) 65
3 External fault (NO contact input) Inverter stops by external fault signal input –
4 External fault (NC contact input) Digital operator display is EF!*. –
Resets the fault. Fault reset not
5 Fault Reset effective with the run signal ON. 75
6 Multi-step speed reference 1 65
7 Multi-step speed reference 2 65
8 Multi-step speed reference 3 65
10 JOG command 66
11 Accel/Decel time select 69
External baseblock Motor coast to a stop by this
12 (NO contact input) signal input. –
Digital operator display is
External baseblock
13 (NC contact input) –

Search command from


14 maximum frequency Speed search 76
15 Search command from reference signal 76
set frequency
16 Accel/decel hold command 77
17 LOCAL/REMOTE selection 61
Communication/control circuit
18 terminal selection 87
Emergency stop fault Inverter stops by emergency stop signal input
19 (NO contact input) –
according to stopping method selection (n04).
Emergency stop alarm When frequency coasting to a stop (n04 is set
20 (NO contact input) –
to 1) method is selected, inverter coasts to a
Emergency stop fault stop according to decel time setting 2 (n19).
21 –
Srp
(NC contact input)
Emergency stop alarm Digital operator display is
22 (NC contact input) (lit at fault, blinking at alarm).

Setting enabled only for
34 UP/DOWN command n39 (terminal S5) 86
Setting enabled only for
35 Self-test n39 (terminal S5) _
* Numbers 2 to 5 is displayed in !corresponding to the terminal numbers S2 to S5 respectively.

Fault Reset
Fault reset is not effective No. Terminal Initial Setting
with the run signal ON. n36 S2 2
n37 S3 5
n38 S4 3
n39 S5 6

84
Terminal function at 3-wire sequence selection
When 0 is set at the terminal S3 (n37), terminal S1 becomes run command, terminal S2
becomes stop command, and terminal S3 becomes FWD/REV run command.

• LOCAL/REMOTE select (setting: 17)


Select operation reference either by the digital operator or by the settings of
operation method selection (n02) and frequency reference selection (n03). LOCAL/
REMOTE select is available only during stop.
Open: Run according to the setting of run command selection (n02) or frequency
reference selection (n03)
Closed: Run by frequency reference and run command from the digital operator.
Example:Set n02 = 1, n03 = 2, n07 = 0.
Open: Run by frequency reference from multi-function input terminal FR and
run command from multi-function input terminals S1 to S7.
Closed: Run by volume frequency reference and run command from the digital
operator.
• UP/DOWN command (setting: 34)
With the FWD (REV) run command entered, accel/decel is initiated by inputting
the UP or DOWN commands to multi-function input terminals S4 and S5. Closing
the S4 input will cause the output frequency to increase. Closing the S5 input will
cause the output frequency to decrease (as indicated in the following table. When
UP/DOWN commands are specified by n39, any function set to n38 becomes
disabled; terminal S4 becomes an input terminal for the UP command and terminal
S5 for the DOWN command.
Multi-function Input Terminal
Closed Open Open Closed
S4 (UP command)
Multi-function Input Terminal
Open Closed Open Closed
S5 (DOWN command)
Operation Status Accel Decel Hold Hold

85
Time Chart at UP/DOWN Command Input

Notes:
(1) When UP/DOWN command is selected, the upper limit speed is set regardless of frequency
reference.
Upper limit speed = Maximum output frequency (n09)
x Frequency reference upper limit (n030)/100
(2) Lower limit value is either minimum output frequency (n14) or Maximum output frequency
(n09) x frequency reference lower limit (n31)/100% (whichever is greater).
(3) When the FWD (REV) run command is input, operation starts at the lower limit speed without an
UP/DOWN command.
(4) If the jog command is input while running by the UP/DOWN command, the jog command has
priority.
(5) Multi-step speed reference 1 to 3 is not effective when UP/DOWN command is selected. Multi-
step speed reference is effective during running in hold status.
(6) When “1” is set for HOLD output frequency memory selection (n62), output frequency can be
recorded during HOLD.
Setting Description
0 Output frequency is not recorded during HOLD.
When HOLD status is continued for 5 seconds or longer, the output frequency
1
during HOLD is recorded and the inverter restarts at the recorded frequency.

86
• Communication/multi-function input terminal selection input (setting: 18)
(This function is effective when option card is installed)
Operation can be changed from communication command, or from multi-function
input terminal or digital operator command.
Run command and frequency reference from communication options are effective
when multi-function input terminal for this setting is “closed.”
Run command and frequency reference in LOCAL/REMOTE mode are effective
when “Open.”
Using output signals (n40)
Multi-function output terminal MA and MB functions can be changed when necessary
by setting parameter n40.
• Terminal MA and MB functions: Set to n40
Setting Name Description Ref page
0 Fault Closed when inverter fault occurs. –
Closed when either FWD/REV command is input or
1 Inverter Run –
voltage is output from the inverter.
Closed when setting frequency agrees with inverter
2 Agreed frequency 88
output frequency.
Closed when inverter output frequency is less than
3 Zero speed –
minimum output frequency.
4 Frequency detection Output frequency ≥ frequency detection level (n58) 74
5 Frequency detection Output frequency ≤ frequency detection level (n58) 74
Overtorque detection
6 — 73
(NO contact output)
Overtorque detection
7 — 73
(NC contact output)
10 Minor Fault Closed when the alarm is indicated. –
11 Base blocked Closed when the inverter output is shut off. –
Closed when “LOCAL” is selected by LOCAL/REMOTE
12 Operation mode –
selection.
Closed when inverter fault is not detected, and
13 Inverter ready –
operation is ready.
14 Fault restart Closed during fault retry –
15 In UV Closed when undervoltage is detected. –
16 In reverse run Closed during reverse run. –
17 In speed search Closed when inverter conducts speed search. –
Operates multi-function output terminal independently
Data output from
18 from inverter operation (by MEMOBUS –
communication
communication).

87
Initial setting of multi-function output terminal
No. Terminals Initial Setting
n40 MA, MB 1 (Inverter Run)

+ 2HZ

OUTPUT FREQUENCY

88
• Setting Frequency by Current Reference Input
When setting frequency by inputting
current reference (4-20mA or 0-20mA)
from the control circuit terminal FR,
switch the DIP switch SW8 on the control
circuit board to “I” side.
SW8 is accessed by removing the
terminal cover.

SW8

Never input voltage reference to control circuit terminal FR


when DIP switch SW8 is switched to “I” side. Damage to the
inverter may result.

89
Current reference selection
After changing DIP switch (SW8) to the “I” side, PRESS PRGM on the digital
operator, then set the following parameters.
4-20mA…n03 = 3
0-20mA…n03 = 4
Press the digital operator keys to run or stop
the inverter. Switch run and stop direction by
setting F/R LED.
Set frequency by the analog current signal
[0-100% (max frequency)/4-20mA or 0-
20mA] connected to the control circuit
terminal.

Set run/stop and FWD/REV run with


switching device connected to the control
circuit terminal.
Multi-function input terminal S2 is set to
Reverse run/stop (n36 = 2).
Set frequency by the analog current signal
[0-100% (max. frequency)/4-20mA or 0-
20mA] connected to the control circuit
terminal.

Frequency reference gain (n41)/bias (n42) can be set even when current reference input
is selected. For details, refer to “Adjusting speed setting signal” on page 69.

90
• Preventing Motor from Stalling (Current Limit)
This function automatically limits the output current in response to load changes by
adjusting the output frequency to prevent motor stalling.
• Stall prevention (current limit) level during acceleration (n56)
Sets the stall prevention (current limit) level during acceleration in units of 1%
(Inverter rated current = 100%).
Factory setting: 170%
A setting of 200% disables the stall prevention (current limit) during acceleration.
During acceleration, if the output current exceeds the value set for n56, acceleration
stops and frequency is maintained. When the output current goes down to the value set
for n56, acceleration continues.

* Stops the acceleration to prevent the motor


from stalling.
† Release width (hysteresis) of stall prevention
during accel is approx. 5% of inverter rated
current.

*
In the constant horsepower area [output frequency > max. voltage output frequency
(n11)], following equation automatically decreases the stall prevention (current limit)
level during acceleration.

*Note: The lower limit of the stall prevention level is 40% of the level set in n56.

91
• Stall prevention (current limit) level during running (n57)
Sets the stall prevention (current limit) level during running in units of 1% (Inverter
current = 100%).
Factory setting: 160%
A setting of 200% disables the stall prevention (current limit) during running.
If the output current during speed agree exceeds the value set for n57 for longer than
100msec, deceleration starts.
As long as the output current exceeds the value set for n57 deceleration continues.
When the output current goes below the value set for n57, acceleration begins to the set
frequency.
The accel/decel rates during stall prevention are determined by the accel time (n16 or
n18) and decel time (n17 or n19) that is selected at the time of the stall prevention
condition.

* Decreases frequency to prevent the motor


from stalling.
† At acceleration start, output hysteresis is
approx. 5% of inverter rated current.

• Stall prevention (current limit) function during deceleration (n55)


To prevent overvoltage during deceleration, the inverter automatically lengthen the
deceleration time according to the value of main circuit DC voltage.

Stall prevention (current limit) during


Setting
deceleration
0 Provided
1 Not Provided

92
• Decreasing Motor Speed Fluctuation
Slip compensation
As the load becomes larger, rotor speed is reduced as motor slip increases. The slip
compensating function regulates the motor shaft speed as the load increases by
increasing the output frequency.
When inverter output current is equal to the motor rated current (n32), the
compensation frequency is added to the output frequency.

Compensation frequency = Motor rated slip (n64)

Output current – Motor no-load current n65


× --------------------------------------------------------------------------------------------------------------------------------------------
Electronic thermal – Motor no-load current (n65)
reference current (n32)
× Slip compensation gain (n66)

Parameters
Parameters Initial
Name Unit Setting Range
No. Setting

n032 Motor rated current 0.1A 0 to 120% of inverter rated current *

n64 Motor rated slip 0.1Hz 0.0 to 20Hz *

n65 Motor no-load current 1% 0 to 99% (100% = Motor rated current n32) *

n66 Slip compensation gain 0.1 0.0 to 2.5 0.0

Slip compensation primary 0.0 to 25.5s


n67 0.1s 2.0s
delay time When 0.0s is set, delay time becomes 2.0s
* Differs depending on inverter capacity.
Notes:1. Slip compensation is not performed in the following condition:
Output frequency < minimum output frequency (n14).
2. Slip compensation is not performed during regeneration.
3. Slip compensation is not performed when motor rated current (n32) is set to 0.0A.

93
• Motor Protection
Motor overload detection
Built-in electronic thermal overload protection is provided to protect against motor
overheating.
• Motor rated current (electronic thermal reference current, n32)
Set to the rated current value shown on the motor nameplate.

• Motor overload protection selection (n33, n34).

n33 Setting Electronic Thermal Characteristics


0 Applied to general-purpose motor (limited speed range)
1 Applied to inverter duty motor (wide speed range)
2 Electronic thermal overload protection not provided

Parameters
Name Unit Setting Range Initial Setting
No.
Protection parameter
n34 1min 1 to 60min 8min
selection
The electronic thermal overload function calculates motor temperature, based on
inverter output current and time, to protect the motor from overheating. When the
electronic thermal overload relay is enabled and excessive current is flowing to the
motor, an “ ” error occurs, shutting OFF the inverter output and preventing
excessive overheating in the motor. When operating with one inverter connected to one
motor, an external thermal relay is not needed. When operating several motors with
one inverter, install a thermal relay on each motor and disable the electronic overload
protection (n33=2).

94
• General-purpose motor and inverter motor
Induction motors are classified as general-purpose motors (limited speed range) or
inverter motors (wide speed range), based on their cooling capabilities. Therefore,
the motor overload function operates differently between these two motor types.

Example of 200V class motor


Electronic Thermal
Cooling Effect Torque Characteristics
overload
Effective when operated error (motor
at 50/60Hz from
overload protection)
commercial power
occurs when
supply
continuously operated at
50/60Hz or less at 100%
load.
General-purpose Motor

Base Frequency 60Hz


(V/f for 60Hz, 220V Input Voltage)

For low-speed operation, torque must be


limited in order to stop motor temperature
rise.
Effective even when Electronic thermal
operated at low speed overload protection not
(approx. 6Hz) activated even when
continuously operated at
50/60Hz or less at 100%
load.
Inverter Duty Motor

Base Frequency 60Hz


(V/f for 60Hz, 220V Input Voltage)

Use an inverter duty motor for continuous


operation at low speed.

95
• Selecting Cooling Fan Operation
In order to increase fan life, the cooling fan can be set to operate when inverter is
running or when power is supplied.
n35 = 0 (factory setting) : Operates only when inverter is running.
(Continues operation for 1 minute after
inverter is stopped.)
=1 : Operates while power is ON.

• Using MEMOBUS (MODBUS) Communications


Serial transmission is available with VS mini J7 using programmable controller
(MEMOCON series) and MEMOBUS. In order to perform serial communications, RS-
485/422 interface card (optional) must be installed.
• MEMOBUS (MODBUS) communications
MEMOBUS system is composed of a single master (PLC) and slaves (1 to 31
VS-mini units).
Transmission between master and slave (serial communication) is controlled
according to the master program with the master initiating communication and the
slave responding.
The master sends a signal to one slave at a time. Each slave has a pre-registered
address No., and the master specifies the number and conducts signal
communication. The slave receives the transmission to carry out designated
functions and reply to the master.

VS mini J7 VS mini J7 VS mini J7

96
• Communications specifications
Interface RS-422, RS485
Synchronization Asynchronous (Start-stop synchronization)
Communication Baud rate: Selected from 2400/4800/9600/19200 bps
parameters Data length: 8 bits fixed
Parity: Selected from even/odd/none
Stop bits: 1 bit fixed
Communication
MEMOBUS (MODBUS) (RTU mode only)
protocol
Max. number of
inverters that
31 units (When using RS-485)
can be
connected

97
Notes

98
8. Maintenance and Inspection
• Periodical Inspection
Periodically inspect the inverter as described in the following table to prevent accidents
and to ensure high performance with high-reliability.
Location to Check Check For Solution
Terminal, unit mounting Connection hardware is properly
Properly seat and tighten hardware.
screws, etc. seated and securely tightened.
Blow with dry compressed air:
Cooling fins Built up dust, dirt, and debris 39.2 X 104 to 58.8 X 104 Pa, 57 to 85 psi (4
to 6kg / cm2) pressure.
Blow with dry compressed air:
39.2 X 104 to 58.8 X 104 Pa, 57 to 85 psi (4
Accumulation of conductive
Printed circuit board to 6kg / cm2) pressure.
material or oil mist
If dust or oil cannot be removed, replace the
inverter unit.
Power elements and
Abnormal odor or discoloration Replace the inverter unit.
smoothing capacitor
Abnormal noise or vibration.
Cooling fan Cumulative operation time Replace the cooling fan.
exceeding 20,000 hours.

• Part Replacement
Inverter’s maintenance periods are noted below. Keep them as reference.

Part Replacement Guidelines


Part Standard Replacement Period Replacement Method
Cooling fan 2 to 3 years Replace with new part.
Replace with new part.
Smoothing capacitor 5 years
(Determine need by inspection).
Breaker relays — Determine need by inspection.
Fuses 10 years Replace with new part.
Electrolytic capacitors on Replace with new board. (Determine need
5 years
PCBs by inspection).
Note: Usage conditions are as follows:
• Ambient temperature: Yearly average of 30°C.
• Load factor: 80% max.
• Operating rate: 12 hours max. per day.

99
Replacement of cooling fan
• Inverter having W-dimension (width) 2.68 inches (68mm)

1. Removal
(1) Press the right and left tabs of the fan
cover inward (direction 1), and then pull
them outward (direction 2) to remove the
fan assembly from the inverter unit.
(2) Carefully pull the wiring in (direction 3)
from the fan cover rear face, and remove
the protective tube and connector.
(3) Open the left and right sides of the fan
cover to remove the cooling fan from the
cover.

2. Mounting
(1) Mount the cooling fan to the fan cover.
The arrow indicating the air flow direction
of the cooling fan must be pointing away
from the cover.
(2) Connect the connector and mount the pro-
tective tube firmly. Mount the connector
joint section on the fan cover rear face.
(3) Mount the fan cover on the inverter. Be
sure to snap-in the right and left tabs of
the fan cover on the cooling fin.

AIR FLOW DIRECTION

100
• Inverter having W-dimension (width) 108mm (4.25 inches)
1. Removal
(1) Remove the front cover and terminal
cover, and then remove the cooling fan
connector (CN10).
(2) Press the right and left tabs of the fan
cover inward (direction 1), and pull the
fan cover downward (direction 2) to
remove it from the inverter unit. Pull out
the wiring from the cable lead-in hole at
the bottom of the plastic case.
(3) Open the right and left sides of the fan
cover to remove the cover from the cool-
ing fan.

2. Mounting
(1) Mount the cooling fan to the fan cover.
The arrow mark indicating the air flow
direction must point away from the cover.
(2) Mount the fan cover on the inverter. Be
sure to snap-in the right and left tabs of
the fan cover on the cooling fin. Lead in
the wiring from the cable lead-in hole at
the bottom of the plastic case to the inside
of the inverter.
(3) Connect the wiring to the cooling fan con-
nector (CN10) and mount the front cover
and the terminal cover.

101
NOTES

102
9. Fault Diagnosis and Corrective Actions
This section describes the alarm and fault displays, explanations for fault conditions
and corrective actions to be taken if the VS mini J7 malfunctions.

< Corrective Actions for models without digital operator >


1. Input fault reset or cycle the power supply OFF and ON.
2. When a fault cannot be corrected:
Turn the power supply OFF and check the wiring and control logic.

103
< Corrective Actions of Models with Digital Operator >

: ON : Blinking : OFF

Alarm Display and Contents


Alarm Display
Inverter Causes and
Digital RUN ALARM Explanation
Status Corrective Actions
Operator (Green) (Red)
UV (Main circuit low voltage) Check the following:
Main circuit DC voltage drops • Power supply
below the low-voltage voltage
detection level while the • Main circuit power
inverter output is OFF. supply wiring is
200V: Main circuit DC voltage connected.
become lowered below • Terminal screws are
approx. 200V (160V for securely tightened.
Blinking single phase)
400V:Main circuit DC voltage
become lowered below
approx. 400V.

OV (Main circuit over voltage) Check the power


Main circuit DC voltage supply voltage.
exceeds the over voltage
Warning
detection level while the
inverter output is OFF.
Fault contacts
Blinking Detection level: approx. 410V
do not change
or more (approx. 820V for
state.
400V class).
OH (Cooling fin overheat) Check the intake air
Intake air temperature rises temperature.
while the inverter output is
OFF.
Blinking

CAL (MEMOBUS Check communication


communications waiting) devices and
Correct data has not been transmission signals.
received from the PLC when
the parameters n02
(operation command
Blinking selection) is 2 or n03
(frequency reference
selection) is 6, and power is
turned ON.

104
Alarm Display
Inverter Causes and
Digital RUN ALARM Explanation
Status Corrective Actions
Operator (Green) (Red)
OP! (parameters setting Check the setting
error when the parameters values.
setting is performed through
the MEMOBUS
communications)
OP1: Two or more values are
set for multi-function
input selection.
(parameters n36 to
n39)
OP2: Relationship among
V / f parameters is not
correct.
(parameters n09, n11,
n12, n14)
OP3: Setting value of motor
rated current exceeds
Blinking 120% of inverter rated
current. (parameter
n32)
Warning OP4: Upper/lower limit of
frequency reference is
Fault contacts reversed. (parameters
do not change n30, n31)
state. OP5: Setting values of jump
frequencies 1 and 2 are
not appropriate.
(parameters n49 to
n50)
OP9: Carrier frequency
setting is incorrect.
(parameter n46)
OL 3 (Over torque detection) Reduce the load and
Motor current exceeded the expand the accel/decel
preset value in parameter time.
n98.
Blinking

SER (Sequence error) Check the external


Inverter receives LOCAL/ circuit (sequence).
REMOTE select command or
communication/control circuit
terminal changing signals
Blinking from the multi-function
terminal while the inverter is
outputting.

105
Alarm Display
Inverter Causes and
Digital RUN ALARM Explanation
Status Corrective Actions
Operator (Green) (Red)
BB (External base block) Check the external
Baseblock command at multi- circuit (sequence).
function terminal is active.
The inverter output is shut
OFF (motor coasting).
Blinking Temporary condition is
cleared when input command
is removed.
EF (Simultaneous FWD/REV Check the external
run commands) circuit (sequence).
When FWD and REV run
commands are
simultaneously input for over
Blinking
500ms, the inverter stops
according to parameter n04.
STP (Operator function stop) Open FWD/REV
STOP/RESET is pressed command of control
Warning during running by the control circuit terminals.
circuit terminals FWD/REV
or Fault contacts command, or by the run
do not change command from
state. communications. The inverter
stops according to parameter
Blinking n04. Check the external
STP (Emergency stop) circuit (sequence).
Inverter receives emergency
stop alarm signal. Inverter
stops according to parameter
n04.
FAN (Cooling fan fault) Check the following:
Cooling fan is locked. • Cooling fan
• Cooling fan wiring is
not connected.
Blinking

CE (MEMOBUS Check the


communications fault) communication devices
or communication
signals.
Blinking

106
Alarm Display
Inverter Causes and
Digital RUN ALARM Explanation
Status Corrective Actions
Operator (Green) (Red)
OC (Over current) • Short circuit or
Inverter output current grounding at inverter
momentarily exceeds approx. output side.
200% of rated current. • Excessive load GD2
(Control power supply fault) • Extremely rapid
Voltage fault of control power accel/decel time
supply is detected. (parameters n19 to
n22)
• Special motor used
Starting motor during
coasting
• Motor of a capacity
greater than the
inverter rating has
been started.
• Magnetic contactor
open/closed at the
inverter output side.
GF (Ground fault) Ground • Check the motor
fault current at the inverter insulation.
output exceeded inverter • Check that the
rated current. connection between
inverter and motor is
not damaged.

Protective OV (Main circuit over voltage) • Insufficient decel


Operation Main circuit DC voltage time (parameters
exceeds the overfatigue n20 and n22)
Output is shut detection level because of • Lowering of
OFF and motor excessive regenerative overhauling load
coasts to a energy from the motor. (elevator, etc.)
stop. Detection level: ⇓
200V: Stops at main circuit • Increase decel time.
DC voltage below
approx. 410V
400V: Stops at main circuit
DC voltage approx.
820V or more
UV1 (Main circuit low voltage) • Reduction of input
Main circuit DC voltage drops power supply voltage
below the low voltage • Open phase of input
detection level while the supply
inverter output is ON. • Occurrence of
200V: Stops at main circuit momentary power
DC voltage below loss
approx. 200V (160V for ⇓
single phase) Check the following:
400V: Stops at main circuit • Power supply
DC voltage approx. voltage
400V or more • Main circuit power
supply wiring is
connected.
• Terminal screws are
securely tightened.

107
Alarm Display
Inverter Causes and
Digital RUN ALARM Explanation
Status Corrective Actions
Operator (Green) (Red)

OH (Cooling fin overheat) • Excessive load


Temperature rise because of • Improper V/f pattern
inverter overload operation or setting
intake air temperature rise. • Insufficient axel time
if the fault occurs
during acceleration.
• Intake air
temperature
exceeding 122°F
(50°C)
• Calling fan stops

Check the following:
• Load size
• V/f pattern setting
(parameters n11 to
n17)
Protective • Intake air
Operation temperature
OL1 (Motor overload) • Check the load size
Output is shut
Motor overload protection or V/f pattern setting
OFF and motor
operates by built-in electronic (parameters n09 to
coasts to a
thermal overload relay. n15)
stop.
• Set the motor rated
current shown on the
nameplate by
parameter n36.
OL2 (Inverter overload) • Check the load size
Inverter overload protection or V/f pattern setting
operates by built-in electronic (parameters n09 to
thermal overload relay. n15)
• Check the inverter
capacity.
OL3 (Over torque detection) Check the driven
Inverter output current machine and correct
exceeded the preset value in the cause of the fault,
parameter n60. or increase the value of
When over torque is detected, parameter n60 up to
inverter performs operation the highest value
according to the preset setting allowed for the
of parameter n59. machine.

108
Alarm Display
Inverter Causes and
Digital RUN ALARM Explanation
Status Corrective Actions
Operator (Green) (Red)
EF! Check the external
(External fault) circuit (sequence).
Inverter receives an external
fault input from control circuit
terminal.
EF0: External fault reference
through MEMOBUS
communications
EF2: External fault input
command from control
circuit terminal S2
EF3: External fault input
command from control
circuit terminal S3
EF4: External fault input
command from control
circuit terminal S4
EF5: External fault input
command from control
circuit terminal S5

Protective
Operation

Output is shut
OFF and motor
coasts to a
stop.

CPF-00 Cycle power.


Initial memory fault is If the fault remains,
detected. replace the digital
operator or inverter.

CPF-01 Cycle power. If the fault


ROM error is detected. remains, replace the
digital operator or
inverter.

CPF-04 • Record all parameter


EEPROM fault of inverter data and initialize the
control circuit is detected. parameters. (Refer
to page 25 for
parameter
initialization)
• Cycle power.
If the fault remains,
replace the inverter.

109
Alarm Display
Inverter Causes and
Digital RUN ALARM Explanation
Status Corrective Actions
Operator (Green) (Red)
CPF-05 Cycle power.
AD converter fault is detected If the fault remains,
replace the inverter.

CPF-06 Remove power to the


• Option card connecting inverter.
Protective fault Check the connection
Operation • A non-corresponding option of the digital operator.
card is connected. Verify inverter software
Output is shut number (n179).
OFF and motor CPF-07 Cycle power. If the fault
coasts to a Operator control circuit remains, replace the
stop. (EEPROM or AD converter) digital operator or
fault inverter.
CE (MEMOBUS Check the
communications fault) communication devices
Normal reception of or communication
communication data is not signals.
possible.
STP (Emergency stop) Check the external
The inverter stops according circuit (sequence).
to parameter n04 after
or receiving the emergency stop
fault signal.

Stops
according to • Insufficient power supply Check the following:
parameter. voltage • Power supply
• Control power supply fault voltage.
• Hardware fault • Main circuit power
— supply wiring is
(OFF) connected.
• Terminal screws are
securely tightened.
• Control sequence.
Replace the inverter.
For display/clear of fault history, refer to page 29.

110
Appendix - CE Conformance
CE Conformance - Low Voltage Directive (LVD) Compliance

• These circuits are hazardous and are separated from accessibility by protective
separation.
‚ These circuits are not separated from hazardous circuits by protective
separation, but only with basic insulation. These circuits cannot be accessed and
must not be interconnected with any circuits which are accessible, unless they
are isolated from accessible circuits by supplemental insulation. These circuits
can be connected only to the following circuits:
30VDC or less (overvoltage category 2)
250 VAC or less (overvoltage category 2)
ƒ These circuits are not separated from hazardous circuits by protective
separation, but only with basic insulation. These circuits cannot be accessed and
must not be interconnected with any circuits which are accessible, unless they
are isolated from accessible circuits by supplemental insulation.
111
CE Conformance - Electro-Magnetic Compatibility (EMC)
Compliance
In order to conform to EMC standards, exclusive-use methods are required for line
filter application, cable shielding and inverter installation. An outline of the methods
follows.
The line filter and the inverter must be mounted on the same metal plate. The filter
should be mounted as close to the inverter as practical. Keep cable as short as possible.
The metal plate should be securely grounded. The ground of the line filter and inverter
must be bonded to the metal plate with as much area as possible.
For line power input cable, screened cable is recommended at least within the panel.
The screen of the cable should be connected to a solid ground. For the motor cable,
screened cable (max. 20m) must be used and the screen of the motor cable is connected
to ground at both ends by a short connection, using as large an area as practical.
For a more detailed explanation, please refer to Making YASKAWA Inverter Products
Conform with EMC Directive (G-TI#99012-V7).
The following table and figures show the line filter list for EMC standards and the
installation/wiring of inverter and line filter.

Line Filter List for EMC Conformance

Recommended Line Filters for VS mini J7 made by Rasmi Electronics Ltd


(200V single phase)

Current Weight Dimension


VS mini J7 Model
(A) (kg) W×D×H
CIMR-J7AUB0P1
CIMR-J7AUB0P2 RS 1010-J7 10 0.6 71 x 45 x 169
CIMR-J7AUB0P4
CIMR-J7AUB0P7 RS 1020-J7 20 1.0 111 x 50 x 169
CIMR-J7AUB1P5
CIMR-J7AUB2P2 RS 1030-J7 30 1.1 144 x 50 x 174
CIMR-J7AUB3P7 RS 1040-J7 40 1.2 174 x 50 x 174

Rated Voltage: AC 250V single phase


Ambient Temperature: 40°C (max.)

112
Recommended Line Filters for VS mini J7 made by Rasmi Electronic Ltd
(200 V three phase)

Current Weight Dimension


VS mini J7 Model
(A) (kg) W×D×H
CIMR-J7AU20P1
CIMR-J7AU20P2 RS 2010-J7 10 0.8 82 x 50 x 194
CIMR-J7AU20P4
CIMR-J7AU20P7
CIMR-J7AU21P5 RS 2020-J7 16 1.0 111 x 50 x 169
CIMR-J7AU22P2
CIMR-J7AU23P7 RS 2030-J7 26 1.1 144 x 50 x 174

Rated Voltage: AC 250V three phase


Ambient Temperature: 40°C (max.)

Recommended Line Filters for VS mini J7 made by Rasmi Electronic Ltd


(400 V three phase)

Current Weight Dimension


VS Mini J7 Model
(A) (kg) W×D×H
CIMR-J7AU40P2 RS 3005-J7 5 1.0 111 x 45 x 169
CIMR-J7AU40P4
CIMR-J7AU40P7
CIMR-J7AU41P5 RS 3010-J7 10 1.0 111 x 45 x 169
CIMR-J7AU42P2
CIMR-J7AU43P7 RS 3020-J7 20 1.1 144 x 50 x 174

Rated Voltage: AC 480V three phase


Ambient Temperature: 40°C (max.)

113
Installation of Line Filter and Inverter VS mini J7 (CIMR-J7 ¨¨20P1 to 23 P7)

L1 L2 L3 P E

Shield
Cable

Control Panel

Rasmi
RFI
Filter

L1 L2 L3
E

R S T

VS mini Ground
J7 Bonds
(remove
any
paint)

U V W

Shield
Cable
Ground Bonds
(remove any paint)

Max.20m
Motor Cable

1M
3-Ph

114
Installation of Line Filter and Inverter VS mini J7 (CIMR-J7 ¨¨B0P1 to B1P5)

L N P E
Shield
Cable

Control Panel
Metal
Rasmi Mounting
RFI Plate
Filter

L N
E

R S

Ground
VS mini Bonds
J7 (remove
any
paint)

U V W

Shield
Cable
Ground Bonds
(remove any paint)

Max.20m
Motor Cable

1M
3-Ph

115
Safety Warnings and Operating Information for Inverters
Introduction
Depending on their protection rating configuration, parts of inverters can have live, uninsulated and
hot surfaces during operation. If housing components, the control unit or terminal covers are
removed, incorrect installation and operation can lead to serious injuries and damage to other
installations. It is thus absolutely essential to observe all the warnings and instructions in the
operating manual. Installation, setup and maintenance should only be performed by properly
qualified staff. IEC 364 / Cenelec HD 384 or DIN VDE 0100 and IEC 664 or DIN VDE. The
applicable national safety and accident prevention regulations must also be observed.) For the
purpose of observance of the safety requirement qualified staff are defined as individuals who are
familiar with the installation, setup and operation of the converters and who have the proper
qualifications for this work.

Proper use for intended purpose


Inverters are designed for installation in electrical systems or machines. A converter installed in a
machine may only be activated if the machine conforms to the provisions of EU directive 89/392/
EEC (machine directives). EN 60204 must also be observed. The converter may also only be operated
if the requirements of the EMC directive (89/336/EEC) are also satisfied. This frequency converter
conforms to the requirements of the low voltage directive, 73/23/EEC. The harmonized standards of
the prEN 50178/DIN VDE 0160 series have been applied, in combination with EN 660439-1 / VDE
06600 Part 500 and EN 60146 / VDE 0558. The specifications on the ratings plate and the
specifications and connection requirements described in the documentation must be observed at all
times.

Transportation and storage


All instructions for transport, storage and proper handling must be observed. Climatic and
environmental conditions must conform to the requirements of prEN 50178.

Installation
The converters must be installed and cooled in compliance with the regulations outlines and referred
to in the documentation. The cooling air flow direction is an important requirement that must be
observed. This means that the unit may only be installed and operated in the specified orientation (e.g.
upright). All distances specified must also be observed. The converters must be protected against
excessive stresses. No components may be bent and no distances required for proper insulation may
be changed. To prevent the risk of static electricity damage never touch electronic components or
contacts.

Electrical connections
All national safety regulations (e.g. VBG 4) must be observed when working on live equipment. The
electrical installation of the units must conform to the applicable regulations. For further information
please refer to the documentation. In particular, please take care to observe all installation instructions
regarding proper EMC immunity, e.g. for shielding, earthing, location of filters and cable routing.
This also applies for equipment with CE approvals. Compliance with the EMC legislation limits is the
responsibility of the machine or system manufacturer.

RCCBs
For information on the use of RCCBs with inverters please contact your supplier or Yaskawa
representative.

Operation
In some systems it may be necessary to install additional monitoring and protective facilities to
comply with the applicable safety and accident prevention regulations. The only changes permitted
are to the operator software of the inverters. Please note that the capacitors can remain charged for up
to around 5 minutes after the frequency converter has been disconnected from the power supply. You
should thus always wait for a short period before opening the unit and touching the electrical
connections.

116
EU Manufacturer’s Declaration
Products
Static inverter, series VS mini J7
Scope
YASKAWA inverters are components (BDM*, defined by IEC 22g/21CDV) designed exclusively
for installation in machines or systems (end products) by qualified re-users (e.g. mechanical
engineering manufacturers).

Responsibility
As a component manufacturer we are responsible for the provision of installation instructions. These
can be found in the installation guidelines publication G-TI#99012-V7 (a Yaskawa publication free
upon request).
Our products have been tested by authorized bodies pursuant to the requirements of the standard
listed below. The products conform to these standards listed below. The products conform to these
standards listed below. The products conform to these standards, subject to due and proper
observation of the installation instructions provided in section 10 of this manual:

Immunity - EMC resistance pursuant to EN50082-2 (1995)

ENV50204 (1995)
EN61000-4-2 (1996)
EN61000-4-4 (1995)
EN61000-4-6 (1996)
EN61000-4-8 (1994)

Emission - EMC interference emissions pursuant to EN500081-2 (1993)

EN55011 (1991) Class B Group 1


Up to 10m motor cable

Class A Group 1
Up to 20m motor cable

YASKAWA Electric Europe GmbH


Am Kronberger Hang 2
65824 Schwalbach am Taunus
Germany

Always observe all the safety instructions provided in this product documentation!

*AdÜ: Abkürzung bitte kontrollieren.

117
YASKAWA ELECTRIC AMERICA, INC.
Chicago-Corporate Headquarters2121 Norman Drive South, Waukegan, IL 60085, U.S.A.
Phone: (847) 887-7000 Fax: (847) 887-7310 Internet: http://www.yaskawa.com
MOTOMAN INC.
805 Liberty Lane, West Carrollton, OH 45449, U.S.A.
Phone: (937) 847-6200 Fax: (937) 847-6277
YASKAWA ELECTRIC CORPORATION
New Pier Takeshiba South Tower, 1-16-1, Kaigan, Minatoku, Tokyo, 105-0022, Japan
Phone: 81-3-5402-4511 Fax: 81-3-5402-4580 Internet: http://www.yaskawa.co.jp
YASKAWA ELETRICO DO BRASIL COMERCIO LTDA.
Avenida Fagundes Filho, 620 Bairro Saude Sao Paolo-SP, Brasil CEP: 04304-000
Phone: 55-11-5071-2552 Fax: 55-11-5581-8795 E-mail: [email protected]
YASKAWA ELECTRIC EUROPE GmbH
Am Kronberger Hang 2, 65824 Schwalbach, Germany
Phone: 49-6196-569-300 Fax: 49-6196-888-301 Internet: http://www.yaskawa.de
MOTOMAN ROBOTICS AB
Box 504 S38525, Torsas, Sweden
Phone: 46-486-48800 Fax: 46-486-41410
MOTOMAN ROBOTEC GmbH
Kammerfeldstraβe 1, 85391 Allershausen, Germany
Phone: 49-8166-900 Fax: 49-8166-9039
YASKAWA ELECTRIC UK LTD.
1 Hunt Hill Orchardton Woods Cumbernauld, G68 9LF, Scotland, United Kingdom
Phone: 44-12-3673-5000 Fax: 44-12-3645-8182
YASKAWA ELECTRIC KOREA CORPORATION
Paik Nam Bldg. 901 188-3, 1-Ga Euljiro, Joong-Gu, Seoul, Korea
Phone: 82-2-776-7844 Fax: 82-2-753-2639
YASKAWA ELECTRIC (SINGAPORE) PTE. LTD.
Head Office:151 Lorong Chuan, #04-01, New Tech Park Singapore 556741, SINGAPORE
Phone: 65-282-3003 Fax: 65-289-3003
TAIPEI OFFICE (AND YATEC ENGINEERING CORPORATION)
10F 146 Sung Chiang Road, Taipei, Taiwan
Phone: 886-2-2563-0010 Fax: 886-2-2567-4677
YASKAWA JASON (HK) COMPANY LIMITED
Rm. 2909-10, Hong Kong Plaza, 186-191 Connaught Road West, Hong Kong
Phone: 852-2803-2385 Fax: 852-2547-5773
BEIJING OFFICE
Room No. 301 Office Building of Beijing International Club,
21 Jianguomanwai Avenue, Beijing 100020, China
Phone: 86-10-6532-1850 Fax: 86-10-6532-1851
SHANGHAI OFFICE
27 Hui He Road Shanghai 200437 China
Phone: 86-21-6553-6600 Fax: 86-21-6531-4242
SHANGHAI YASKAWA-TONJI M & E CO., LTD.
27 Hui He Road Shanghai 200437 China
Phone: 86-21-6533-2828 Fax: 86-21-6553-6677
BEIJING YASKAWA BEIKE AUTOMATION ENGINEERING CO., LTD.
30 Xue Yuan Road, Haidian, Beijing 100083 China
Phone: 86-10-6232-9943 Fax: 86-10-6234-5002
SHOUGANG MOTOMAN ROBOT CO., LTD.
7, Yongchang-North Street, Beijing Economic & Technological Development Area,
Beijing 100076 China
Phone: 86-10-6788-0551 Fax: 86-10-6788-2878

Yaskawa Electric America, Inc., November 1999 YEA-TOA-S606-12 Printed In U.S.A.

You might also like