Modulo 11: MAESTRIA EN OPERACIONES PETROLERAS

Mecanismos Finales de Actuación

Ejercicio 245 Nombres y Apellidos: Humberto Ivan Gonzales Tapia

YPFB TRANSPORTE S. A. Pressure Relief Valve Calculation Report


Santa Cruz de la Sierra, Doble Vía a La Guardia km 7-1/12 9-dic-2020

Bolivia
+59133566000
[email protected]
Quote Number: No Prpd. Chk. Appr. Date Revision
Client: My Company
Location: End-User Ref. No.:
Project: My Project Project Ref. No.:
1 VALVE ID 11 CALCULATION NOTES
2 Tag No. PSV438 12
3 Valve Model No. 1.5F2JOS-E15D Qty. 1 13
4 SIZING DATA 14
5 Design Code ASME Section VIII Sizing Std. API 520 15
6 Fluid State at Inlet Gas / Vapor 16
7 CALCULATION SUMMARY
8 Required 964,000 SCFM 18 Required 0,318 in²
Flow Area
9 Rated 1050,730 SCFM 19 Selected 0,347 in²
10 Reaction Force, Open Discharge 21,04 daN 20 Noise Level (db), Open Discharge 104,5 at 100 ft
Variable Type Variable Name Symbol Input Value Equation Value
Fluid Properties Molecular Weight M 28,970 28,970
Ratio of Specific Heats k 1,400 1,400
Compressibility Z 1,000 1,000
Process Cond. Required Volumetric Flow Vreq 964,000 SCFM 964,000 SCFM
Set Pressure Pset 160 psig 160 psig
Over Pressure Pover 16,0 psig 16,0 psig
Inlet Line Loss Ploss 0 psig 0 psig
Back Pressure Pback 0 psig 0 psig
Atmospheric Pressure Patm 14,696 psia 14,696 psia
Relieving Temperature T 60 °F 519,670 °R
Distance from Valve (noise) r 100 ft 100 ft
Rupture Disc CCF Kc 1,0 1,0
Valve Data Discharge Coefficient (actual) Kd 0,962 0,962
Discharge Coefficient (derated) K 0,866 0,866
Orifice Area A 0,347 in² 0,347 in²
Back Press. Correction Factor Kb 1,0 1,0
Outlet Diameter Do 2,07 in 2,07 in
Calculate Inlet Relieving Pressure, Outlet Pressure, Absolute Pressure Ratio
P1 = Pset + Pover - Ploss + Patm P1 190.696 psia
P2 = Pback + Patm P2 14.696 psia
PR = P2 / P1 PR 0.077

Calculate Gas Constant C 356.1


C = 520 * {k * [2 / (k + 1)]^[(k + 1) / (k - 1)] }^0.5

Calculate Volumetric Critical Flow V 1050,730 SCFM 1050.973053866 SCFM


V = 6.32 * A * C * K * P1 * Kb * Kc / (M * T * Z)^0.5

Calculate Required Orifice Area Areq 0,318 in² 0.3183 in²


Areq = A * Vreq / V

Printed On: 9-dic-2020 PRV²SIZE Software Version pr7_20200224.1 Page : 1


Emerson Automation Solutions and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license
agreement.  Not for resale. All rights reserved.  All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright © 2020 Emerson Electric Co.
YPFB TRANSPORTE S. A. Pressure Relief Valve Calculation Report
Santa Cruz de la Sierra, Doble Vía a La Guardia km 7-1/12 9-dic-2020

Bolivia
+59133566000
[email protected]
Quote Number: No Prpd. Chk. Appr. Date Revision
Client: My Company
Location: End-User Ref. No.:
Project: My Project Project Ref. No.:
1 VALVE ID 11 CALCULATION NOTES
2 Tag No. PSV438 12
3 Valve Model No. 1.5F2JOS-E15D Qty. 1 13
4 SIZING DATA 14
5 Design Code ASME Section VIII Sizing Std. API 520 15
6 Fluid State at Inlet Gas / Vapor 16
7 CALCULATION SUMMARY
8 Required 964,000 SCFM 18 Required 0,318 in²
Flow Area
9 Rated 1050,730 SCFM 19 Selected 0,347 in²
10 Reaction Force, Open Discharge 21,04 daN 20 Noise Level (db), Open Discharge 104,5 at 100 ft
Calculate Mass Critical Flow (for Noise Calc) W 5351.55727892281 lb/hr
W = A * C * Kd * P1 * Kb * Kc * [M / (T * Z)]^0.5

Calculate Noise Level at 100-ft (30-m) L100 104.475972408063 db


L100 = [6.5 * log( 1/PR ) + 51.28] + [10 * log(0.29354 * W * k * T / M)]

Calculate Noise Level at Distance, r Lp 104.475972408063 db


Lp = L100 - 20 * log(r / 100)

Calculate Reaction Force for Open Discharge Fr 21,04 daN 47.30 lbf
Fr = (A * C * Kd * P1 * Kc / 366) * {k / [(k + 1) * Z]}^0.5

Printed On: 9-dic-2020 PRV²SIZE Software Version pr7_20200224.1 Page : 2