Data Communication

of S7-1200 Stations
with TeleControl
Server Basic V3.1
Siemens
CP 1242-7 V2 / CP 1243-1 / TCSB V3.1 Industry
Online
https://support.industry.siemens.com/cs/ww/en/view/39863979 Support
Legal information

Legal information
Use of application examples
Application examples illustrate the solution of automation tasks through an interaction of several
components in the form of text, graphics and/or software modules. The application examples are
a free service by Siemens AG and/or a subsidiary of Siemens AG (“Siemens”). They are non-
binding and make no claim to completeness or functionality regarding configuration and
equipment. The application examples merely offer help with typical tasks; they do not constitute
customer-specific solutions. You yourself are responsible for the proper and safe operation of the
products in accordance with applicable regulations and must also check the function of the
respective application example and customize it for your system.
Siemens grants you the non-exclusive, non-sublicensable and non-transferable right to have the
application examples used by technically trained personnel. Any change to the application
examples is your responsibility. Sharing the application examples with third parties or copying the
application examples or excerpts thereof is permitted only in combination with your own products.
The application examples are not required to undergo the customary tests and quality inspections
of a chargeable product; they may have functional and performance defects as well as errors. It is
your responsibility to use them in such a manner that any malfunctions that may occur do not
result in property damage or injury to persons.

Disclaimer of liability
Siemens shall not assume any liability, for any legal reason whatsoever, including, without
limitation, liability for the usability, availability, completeness and freedom from defects of the
application examples as well as for related information, configuration and performance data and
any damage caused thereby. This shall not apply in cases of mandatory liability, for example
under the German Product Liability Act, or in cases of intent, gross negligence, or culpable loss of
life, bodily injury or damage to health, non-compliance with a guarantee, fraudulent
non-disclosure of a defect, or culpable breach of material contractual obligations. Claims for
damages arising from a breach of material contractual obligations shall however be limited to the
© Siemens AG 2018 All rights reserved

foreseeable damage typical of the type of agreement, unless liability arises from intent or gross
negligence or is based on loss of life, bodily injury or damage to health. The foregoing provisions
do not imply any change in the burden of proof to your detriment. You shall indemnify Siemens
against existing or future claims of third parties in this connection except where Siemens is
mandatorily liable.
By using the application examples you acknowledge that Siemens cannot be held liable for any
damage beyond the liability provisions described.

Other information
Siemens reserves the right to make changes to the application examples at any time without
notice. In case of discrepancies between the suggestions in the application examples and other
Siemens publications such as catalogs, the content of the other documentation shall have
precedence.
The Siemens terms of use (https://support.industry.siemens.com) shall also apply.

Security information
Siemens provides products and solutions with industrial security functions that support the secure
operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary
to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept.
Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems, machines
and networks. Such systems, machines and components should only be connected to an
enterprise network or the internet if and to the extent such a connection is necessary and only
when appropriate security measures (e.g. firewalls and/or network segmentation) are in place.
For additional information on industrial security measures that may be implemented, please visit
https://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them more secure.
Siemens strongly recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are no longer
supported, and failure to apply the latest updates may increase customer’s exposure to cyber
threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed
at: http://www.siemens.com/industrialsecurity.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 2
Table of Contents

Table of Contents
Legal information ......................................................................................................... 2
1 Task ..................................................................................................................... 5
2 Solution............................................................................................................... 6
2.1 Overview............................................................................................... 6
2.2 Description of the core functionality ..................................................... 8
2.3 Overview and description of the user interface .................................... 9
2.4 Hardware and software components ................................................. 11
2.4.1 Validity ................................................................................................ 11
2.4.2 Components used .............................................................................. 11
3 Mode of Operation ........................................................................................... 13
3.1 Complete overview of the configuration ............................................. 13
3.2 Functionality of Station 1 / Station 2 ................................................... 18
3.2.1 Program details about the "SimProgCP12xx" FB .............................. 18
3.2.2 Call of the "SimProgCP12xx" FB in OB1 ........................................... 20
3.2.3 Program details about the "DataThresSim" FB .................................. 21
3.2.4 Call of the "DataThresSim" FB in OB1 ............................................... 23
3.2.5 Program details about the "InflowFilllevelSim" FB ............................. 24
3.2.6 Call of the "InflowFilllevelSim" FB in OB1 .......................................... 25
3.3 Partner status ..................................................................................... 26
3.4 CP diagnostics ................................................................................... 26
© Siemens AG 2018 All rights reserved

4 Configuration and Project Engineering ......................................................... 27


4.1 IP addresses in the application example............................................ 27
4.2 Configuring Station 1 .......................................................................... 28
4.3 Configuring the data points for Station 1 / Station 2 .......................... 32
4.4 Configuring Station 2 .......................................................................... 36
4.5 Configuring TeleControl Server Basic (TCSB) ................................... 38
4.6 Configuring UaExpert ......................................................................... 41
5 Installation and Startup ................................................................................... 45
5.1 Installing the hardware ....................................................................... 45
5.1.1 Station 1 hardware configuration ....................................................... 45
5.1.2 Station 2 hardware configuration ....................................................... 46
5.1.3 Master station hardware configuration ............................................... 47
5.2 Installing the software ......................................................................... 47
5.3 Installing the application software ...................................................... 48
5.4 Startup ................................................................................................ 48
5.4.1 Assigning the IP address of the master station .................................. 48
5.4.2 Configuring the DSL router................................................................. 49
5.4.3 Inserting the "39863979_S7-1200_with_TCSB.bak" database
backup copy into TCSB V3.1.0.1 ....................................................... 50
5.4.4 Configuring the IP address and the ports of TeleControl Server
Basic V3.1 .......................................................................................... 54
5.4.5 Opening the "39863979_S7-1200_with_TCSB.uap" UaExpert
configuration file ................................................................................. 56
5.4.6 Loading Station 1 / Station 2 .............................................................. 59
6 Operation of the Application .......................................................................... 61
6.1 Overview............................................................................................. 61
6.2 Starting / stopping the simulation ....................................................... 63
6.3 Station 1 / Station 2 sends data to the master station on a
"threshold-triggered" basis ................................................................. 65
6.4 Station 1 / Station 2 cyclically sends data to the master station ........ 66

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 3
Table of Contents

6.5 Station 1 / Station 2 sends data to the master station on an


"event-triggered" basis ....................................................................... 67
6.6 Monitoring value changes in UaExpert .............................................. 68
7 Appendix .......................................................................................................... 70
7.1 Service and Support ........................................................................... 70
8 Links & Literature ............................................................................................ 71
9 History............................................................................................................... 71
© Siemens AG 2018 All rights reserved

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 4
1 Task

1 Task
Introduction
The infrastructure of a sewage treatment plant contains two SIMATIC S7-1200
substations. One station is to communicate with a master station via the cellular
network and the other station is to communicate via Ethernet.
The TeleControl Server Basic V3.1 software is installed in the master station. Its
OPC interface allows you to connect any OPC client, for example WinCC.

Overview of the automation task


The figure below provides an overview of the automation task.
Figure 1-1
Master station

TCSB
WinCC Adv

Ethernet
© Siemens AG 2018 All rights reserved

Internet

Fill level Fill level


Outflow Outflow
Inflow Inflow

Station 1 Station 2

Requirements
This application example is intended to meet the following requirements:
• Both remote stations send some process tags to the master station on a
"threshold-triggered" basis.
• Both remote stations cyclically send important process tags to the master
station.
• Both remote stations send some process tags to the master station on an
"event-triggered" basis.
• The master station monitors the status of the connected remote stations.
The simulated process in the remote stations is to be operated and controlled with
the aid of visualization software.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 5
2 Solution

2 Solution
2.1 Overview
Diagrammatic representation
The diagrammatic representation below shows the most important components of
the solution:
Figure 2-1

Master station

TCSB
© Siemens AG 2018 All rights reserved

SCALANCE
M816

Internet

Cellular network

Station 1 Station 2
S7-1200 with S7-1200 with
CP 1242-7 V2 CP 1243-1

Industrial Ethernet
Tunnel connection

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 6
2 Solution

Configuration
TeleControl Server Basic V3.1 (TCSB) in the master station allows a direct
connection to the S7-1200 stations.
Communication takes place via the following paths and communication modules:
• S7-1200 with CP 1242-7 V2: communication via the cellular network and the
Internet.
• S7-1200 with CP 1243-1: communication via Ethernet. By using single-mode
optical fiber technology, here, too, systems can span several kilometers.
Any OPC client visualizes the data via the integrated OPC UA server of
TCSB V3.1. In this example, we demonstrate the functions using UaExpert and the
WinCC Advanced SCADA system.

Advantages
The solution presented here offers the following advantages:
• TeleControl Server Basic V3.1 enables economic data communication
between remote stations and a master station.
• The core application areas are industrial applications where the objective is to
transmit data in a cost-effective way on a wireless basis, for example in water
treatment plants, for water purification or in pumping stations.
• TCSB's OPC UA interfaces provide the data of the connected stations to one
or more connected OPC UA clients.
© Siemens AG 2018 All rights reserved

• GPRS and Internet: Always-on functionality.


• To increase reliability, the CPs can, in the event of a connection failure, buffer
the data of events of different classes and transfer the aggregated data to the
TeleControl server.
• If there is a brief interruption on the connection between the OPC UA client and
the TCSB OPC UA server, the data remains available in the data buffer. Once
the connection has been re-established, all values that have not been
transferred will be sent to the OPC UA client.

Scope
This application does not include a description of
• SIMATIC NET TeleControl Server Basic. See document \4\.
• SIMATIC HMI configuration
• the LAD/FBD/STL/SCL programming languages.
Basic knowledge of these topics is required.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 7
2 Solution

2.2 Description of the core functionality


Functions implemented
The following core functions are implemented in the application example:

Threshold-triggered
Data is not transmitted until the current data has changed by a threshold compared
to the last sent data.

Time-triggered
The data is transmitted from the CP to TCSB in a specified time frame.

Event-triggered
The data is transmitted when a configured trigger signal is triggered. The edge
change (0 → 1) of a trigger tag set by the user program is evaluated as a signal.
Once the data has been successfully transferred, the trigger tag will be reset.

Transfer after call by master station


The data is transmitted at the initiative of the master station.
© Siemens AG 2018 All rights reserved

Status monitoring
The master station monitors the status of the connected remote stations.

Note For a more detailed description of these functions, please refer to Chapter 3 and
the following chapters.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 8
2 Solution

2.3 Overview and description of the user interface


The application example is visualized with WinCC Advanced using two configured
screens: "TCSB Communication" and "S7-1200 Application".

"TCSB Communication"
The "TCSB Communication" screen shows the status of the connection to the two
substations. It additionally shows the process data sent from the stations.
Figure 2-2

1 3

2 4
© Siemens AG 2018 All rights reserved

5 6

Table 2-1
No. Item Description
1. Communication Status: Information about the communication status of
• Connectionstate Station 1
• SignalQuality
• PLCConnected
• PLCCpuState TCSB itself determines the values.

2. Buffer Maximum inflow, outflow and fill level of Station 1 that


are saved in the master station.
Overflow alarm:
– green: no overflow
– red: overflow
3. Communication Status: Information about the communication status of
• Connectionstate Station 2
• PLCConnected
• PLCCpuState TCSB itself determines the values.

4. Buffer Maximum inflow, outflow and fill level of Station 2 that


are saved in the master station.
5. Change screen Click the buttons to display the appropriate screens.
6. Stop Runtime Clicking this button stops Runtime.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 9
2 Solution

"S7-1200 Application"
The "S7-1200 Application" screen visualizes the processes of stations 1 and 2.
Figure 2-3

1 2

3 4

5 6
© Siemens AG 2018 All rights reserved

Table 2-2
No. Item Description
1. Filling level and Inflow Current fill level and inflow of Station 1.
2. Filling level and Inflow Current fill level and inflow of Station 2.
3. Parameters for the threshold • Outflow: current outflow
trigger process of Station 1. • On: starts the data simulation
• Off: stops the data simulation
4. Parameters for the threshold • Outflow: current outflow
trigger process of Station 2. • On: starts the data simulation
• Off: stops the data simulation
5. Change screen Click the buttons to display the appropriate
screens.
6. Stop Runtime Clicking this button stops WinCC Runtime.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 10
2 Solution

2.4 Hardware and software components


2.4.1 Validity

This application is valid for


• CP 1242-7 V2 (FW V3.1)
• CP 1243-1 (FW V3.1)
• STEP 7 V15.1
• S7-1200 CPU V4.1 or higher
• TCSB V3.1.0.1

Note For the STEP 7 V13 SP1 project, refer to the archive on the download page of
the entry (see \2\).
To configure the SIMATIC CP 1243-1 module with STEP 7 V13 SP1, you need
HSP 0170. (See \3\)

2.4.2 Components used

The application was created with the following components:


© Siemens AG 2018 All rights reserved

Station 1 hardware components


Table 2-3
Component No. Article number Note
S7-1200 PM1207 1 6EP1332-1SH71 Power supply
SIMATIC S7-1200 1 6ES7217-1AG40-0XB0 Any S7-1200 CPU V4.1 or
CPU 1217C higher can be used.
DC/DC/DC
CP 1242-7 V2 1 6GK7242-7KX31-0XE0 Firmware V3.1
COMMUNICATIONS
PROCESSOR
ANT794-4MR 1 6NH9860-1AA00 GSM quad-band and
ANTENNA UMTS and LTE (Europe)
SIMATIC Memory 1 6ES7954-8LF01-0AA0 Memory card for the
Card S7-1200 CPU

Station 2 hardware components


Table 2-4
Component No. Article number Note
S7-1200 PM1207 1 6EP1332-1SH71 Power supply
SIMATIC S7-1200 1 6ES7217-1AG40-0XB0 Any S7-1200 CPU V4.1 or
CPU 1217C higher can be used.
DC/DC/DC
CP 1243-1 1 6GK7243-1BX30-0XE0
COMMUNICATIONS
PROCESSOR
SIMATIC Memory 1 6ES7954-8LF01-0AA0 Memory card for the
Card S7-1200 CPU

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 11
2 Solution

Accessories
Table 2-5
Component No. Article number Note
SIM card 1 Available from your mobile service Enabled for data
provider communication
DSL router & 1 Specialist retailers SCALANCE M816
modem
Static IP address for 1 Can be requested from your
DSL Internet service provider
or
DynDNS

Software components
Table 2-6
Component No. Article number Note
SIMATIC STEP 7 V15.1 1 6ES7822-1AA05-0YA5 Trial download:
The software is subject to
export restrictions. The
download is only available
for registered users. (See
\5\)
TCSB 8 V3.1.0.1 1 6NH9910-0AA31-0AA0 Number of connectable
© Siemens AG 2018 All rights reserved

software stations: 8.
(see \9\) The product is available in
other configurations and
license options, see
document \5\.
SIMATIC WinCC 1 6AV2102-0AA05-0AA7 Trial download:
Advanced V15.1 The software is subject to
export restrictions. The
download is only available
for registered users. (See
\5\)
UaExpert v1.4.4 1 Free download from Requires registration with
Unified Automation the vendor (see \8\)

Sample files and projects


The following list contains all files and projects that are used in this example.
Table 2-7
Component Note
39863979_S7_1200_WinCC_Adv_PROJ_V20.zip This zip file contains:
• the STEP 7 / WinCC
Advanced V15.1 project
• TCSB project
• UaExpert project
39863979_S7_1200_WinCC_Adv_DOC_V20_en.pdf This document.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 12
3 Mode of Operation

3 Mode of Operation
Key points of this application example:
• Configuration of an S7-1200 station with the CP 1242-7 V2 for data
communication with the master station via the cellular network and the Internet.
• Configuration of an S7-1200 station with the CP 1243-1 for data
communication with the master station via Ethernet.
• Configuration of TeleControl Server Basic in the master station.
• Data exchange between the stations and the master station.

3.1 Complete overview of the configuration


With the CP, it is not necessary to program program blocks in order to transfer data
to the master station. The data areas in the memory of the S7-1200 CPU intended
for communication with the master station are configured in the CP on a data point-
related basis. In this configuration, each data point is linked to a PLC tag in the
CPU.
In this example, the current fill level, outflow value and inflow of the station are read
and transferred to the master station via the CP. The following transfer methods
are set in the data configuration in STEP 7:

Threshold-triggered
© Siemens AG 2018 All rights reserved

The current outflow is transmitted to the master station if it has changed by a


threshold compared to the last sent outflow.
The threshold calculation does not evaluate the absolute value of the current
outflow value's deviation from the last saved outflow value, but the value of the
integrated deviation.
Deviations of the current outflow value are totalized in each calculation cycle
(500 ms). The trigger is not set and the current outflow is not transmitted until the
totalized value reaches the configured threshold trigger value (here: 2).
Figure 3-1
Threshold= 2
Integr:value= -0.9

Integr:value= -0.7
Integr:value= -1.1
Integr:value= 2.3
Integr:value= 1.8
Integr:value= 0.9

Integr:value= -2

Integr:value= 0
Integr:value= 0

Integr:value= 0
Integr:value= 0

22 0.9 0.9
0.5 0 0
21.5
0
21 -0.2 -0.2

-1.1 0
20.2
20 -1.3

Time
500ms 1s 1.5s 2s 2.5s 3s 3.5s 4s 4.5s 5s 5.5s

Transmitted value
Currently acquired value

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019Intergr.value=2. 13
1 0,8
0,5 0,5
0 0,3
3 Mode of Operation

Time-triggered
The current fill level is cyclically (here: 30s) transmitted to the master station.

Event-triggered
The inflow alarm bit (overflow) is transmitted to the master station if the trigger
signal is triggered. The trigger signal is set by the user program if the current inflow
is greater than the limit value. This transfer of the alarm bit resets the trigger signal.
The following figure shows the configuration of the S7-1200 stations for data
communication with the master station.
Figure 3-2

Master station
WinCC

HMI tag OPC tag TCSB


3
4
2
© Siemens AG 2018 All rights reserved

Station x

S7-1200 CPU CP 12xx-x


Data DB Data point
PLC tag

Table 3-1
No. Station 1 Station 2
1. In the CP, the "Data.fillLevel" PLC tag is used to configure the "FillLevel" data point.
2. The data point is sent to the master station when the transmission criteria are met.
3. It is then passed on to the WinCC OPC client as an OPC tag.
4. The OPC tag is used to configure the HMI tag.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 14
3 Mode of Operation

Station 1 / Station 2 program overview


The structure for the simulation program is identical for both stations. The figure
below shows the most important elements.
Figure 3-3

SimProg
Main
CPx

DataThres Data
Data points
Sim

InflowFill
levelSim
Station 1: CP 1242-7 V2
User block Data blocks Station 2: CP 1243-1
© Siemens AG 2018 All rights reserved

Table 3-2
Element Symbolic name Description
OB1 Main Cyclic OB: call of the user program
FB1 SimProgCPx The "SimProgCPx" FB contains the
simulation for the event-triggered
process (Table 3-1, step 4).
FB2 DataThresSim The "DataThresSim" FB simulates the
"outflow" for the threshold-triggered
process.
FB3 InflowFilllevelSim The "InflowFilllevelSim" FB simulates the
"inflow" and "filllevel" parameters.
DB1 Data Global data block for saving the data:
• Send data
• Status tags
• Tags for the data simulation
Data points Configured data points for data exchange between a station and the
master station.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 15
3 Mode of Operation

Global data block: "Data" (DB1)


The "Data" DB contains:
• The PLC tags required for the data configuration of the CP12xx-x,
• the PCL tags used for the data simulation for the threshold-triggered process,
• the status tags.
The structure of the global data block is identical for both stations.
Figure 3-4
© Siemens AG 2018 All rights reserved

Table 3-3
Name Data type Description
fillLevel Real Current fill level of Station 1 or
Station 2.
inflow Real Current inflow of Station 1 / Station 2.
inflowUp Real Limit value of the inflow of Station 1 / Station 2.
Start value: 25.0
overflow Bool Indicates the status of the current inflow.
True:
current inflow has exceeded limit value.
False:
current inflow less than limit value.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 16
3 Mode of Operation

Name Data type Description


start Bool True:
data simulation active.
False:
data simulation stopped.
startMirror Bool Mirrors the "start" tag.
maxAmplitude Real Maximum value for the implemented function in
the simulation program, "DataThresSim"
(triangle function)
Start value: 22.0
minAmplitude Real Minimum value for the implemented function in
the simulation program, "DataThresSim"
(triangle function)
Start value: 20.0
period Time Duration of the implemented function (start
value: 16 s)
outflow Real Current value of the outflow of Station 1 /
Station 2.
Start value: 21.0
done Bool The data was successfully transferred to the
CP.
partnerStatus Word Status of connection to TCSB (see
Chapter 3-3).
© Siemens AG 2018 All rights reserved

networkStatus UInt Status of connection to data service in cellular


network (see Chapter 3-4).

Only relevant for CP1242-7 V2


triggerDiag Bool Diagnostics trigger tag.
Set when the sample plant is started for the first
time to enable the CP 1242-7 V2's advanced
diagnostics (networkStatus).

Only relevant for CP1242-7 V2.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 17
3 Mode of Operation

3.2 Functionality of Station 1 / Station 2


3.2.1 Program details about the "SimProgCP12xx" FB

The "SimProgCPxx" function block sets the trigger signal for sending an alarm bit
("overflow") to the master station if the current inflow of Station 1 or Station 2 is
greater than the limit value (inflowUp).
The trigger signal is automatically reset when the data is transmitted to the CP.
Figure 3-5

Start

Inflow
Limit value
Inflow<> no
InflowOld

yes

no
Inflow >
© Siemens AG 2018 All rights reserved

Limit value

yes

500ms
delay

yes

Set
trigger signal

End

If the inflow of Station 1 or Station 2 is greater than the limit value (inflow >
inflowUp), a timer is started in the user program. When the time (500ms) has
elapsed, the "statTriggerOverflow" trigger signal is set in the user program and the
inflow status (Overflow) is sent to the master station.

Note It is recommended to set the trigger signal for the event-triggered process with a
delay of approx. 500ms to ensure that the value change of the PLC tag is reliably
applied to the appropriate data point.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 18
3 Mode of Operation

Note Each trigger signal should be linked to a static tag in the instance data block in
the CPU.
If the trigger signal is interconnected with a global tag, it is possible that the
trigger signal may not be automatically reset. This is due to runtime differences
between the CPU cycle and the CP cycle.

The following figure and table show the call interface of the user block, FB
"SimProgCP12xx" (FB1). It is identical for both stations.
Figure 3-6

Table 3-4
Name Data type Description
inflow Real Current inflow of Station 1 or
Station 2.
© Siemens AG 2018 All rights reserved

Input

inflowUp Real Limit value of the inflow of Station 1 /


Station 2.
Entered manually by the user.
Start value: 25 %.
overflow Bool Indicates the status of the current inflow.
True:
InOut

current inflow has exceeded limit value.


False:
current inflow less than limit value.
done Bool True:
the data was successfully transferred to the
Out

CP. (only for one cycle)

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 19
3 Mode of Operation

3.2.2 Call of the "SimProgCP12xx" FB in OB1

The "SimProgCP12xx" FB (FB1) is called cyclically in OB1. The input and output
parameters are stored in the global data block, "Data".
Figure 3-7
© Siemens AG 2018 All rights reserved

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 20
3 Mode of Operation

3.2.3 Program details about the "DataThresSim" FB

Using a cyclic triangle function, the "DataThresSim" function block simulates the
"outflow" of the process.
Figure 3-8

Max. amplitude
Min. amplitude Start
Duration
Outflow

t>0& no
t <=
duration/2

yes

(2*dA*t) / dur.+
min. amplitude

t > dur./2 no
© Siemens AG 2018 All rights reserved

&
t <= dur.

Outflow (-2*dA*t) / dur. +


min. amplitude +
2*dt

t>
duration

min. amplitude

dA= max. amplitude- min. amplitude

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 21
3 Mode of Operation

The following figure and table show the call interface of the user block, FB
"DataThresSim" (FB2). It is identical for both stations.
Figure 3-9

Table 3-5
Name Data type Description
start Bool True:
The data simulation for the threshold-triggered
process is active.
False:
The data simulation for the threshold-triggered
© Siemens AG 2018 All rights reserved

process was stopped.


maxAmplitude Real Maximum value for the implemented function in
Input

the simulation program, "DataThresSim"


(triangle function)
Start value: 22.0
minAmplitude Real Minimum value for the implemented function in
the simulation program, "DataThresSim"
(triangle function)
Start value: 20.0
period Time Duration of the implemented function (start
value: 16 s)
outflow Real Current value of the outflow of Station 1 /
Station 2.
InOut

Start value: 21.0

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 22
3 Mode of Operation

3.2.4 Call of the "DataThresSim" FB in OB1

The "DataThresSim" FB (FB2) is called cyclically in OB1. The input and output
parameters are stored in the global data block, "Data".
Figure 3-10
© Siemens AG 2018 All rights reserved

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 23
3 Mode of Operation

3.2.5 Program details about the "InflowFilllevelSim" FB

The "InflowFilllevelSim" function block simulates the values for the "Inflow" and
"Filllevel" tags. The "LGF_Sawtooth" function block from the "LGF_Library" was
used to generate a sawtooth signal.
In addition to this, the "Start" tag sent from the master station is relocated to the
"StartMirror" tag and then sent back to the master station. As an acknowledgment
mechanism, this procedure ensures that the values sent from the master station
have been written in the CPU.
Figure 3-11

Start

Start no
set

yes

Set
© Siemens AG 2018 All rights reserved

StartMirror

Sawtooth
simulation for
inflow

Sawtooth
simulation for
fill level

no
Start
reset

yes

Reset
StartMirror

End

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 24
3 Mode of Operation

The following figure and table show the call interface of the user block, FB
"DataThresSim" (FB2). It is identical for both stations.
Figure 3-12

Table 3-6
Name Data type Description
start Bool True:
The data simulation for the inflow and fill level is
Input

active.
False:
The data simulation for the inflow and fill level
was stopped.
inflow Real Current value of the inflow of Station 1 /
startMirror

Station 2.
Output

filllevel Real Current value of the fill level of Station 1 /


Station 2.
© Siemens AG 2018 All rights reserved

startMirror Bit Mirrors the "start" tag.

3.2.6 Call of the "InflowFilllevelSim" FB in OB1

The "InflowFilllevelSim" FB (FB3) is called cyclically in OB1. The input and output
parameters are stored in the global data block, "Data".
Figure 3-13

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 25
3 Mode of Operation

3.3 Partner status


Using the "Report partner status" function in the CP configuration, the CP signals
the status of the connection to TCSB to the CPU. This information is written to the
"partnerStatus" PLC tag in the "Data" DB.
The following figure shows the bit assignment of the "partnerStatus" tag (Word).
Figure 3-14

Byte1 Byte 0

Not assigned

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Not assigned 0: Partner not reachable


1: Partner reachable

0: All paths to partner OK


© Siemens AG 2018 All rights reserved

1: Paths to partner not OK

0: Send buffer OK
1: Send buffer overflow imminent
(above 80% of fill level )
3: Send buffer overflow imminent
(above 100% of fill level)

Bits 2 and 3 will be reset to 0 as


soon as the value is below 50% of
the fill level.

3.4 CP diagnostics
Advanced "CP diagnostics" in the CP 1242-7 configuration (see \5\) allow you to
read the status of the connection to the data service in the cellular network from the
CP.
This information is written to the "networkStatus" PLC tag (UInt) in the "Data" DB.
Table 3-7
networkStatus Meaning
0 Cellular network status: not connected
1 Wrong PIN number
2 SIM card missing or defective
3 Waiting for PIN to be entered
4 Cellular network status: connected

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 26
4 Configuration and Project Engineering

4 Configuration and Project Engineering

Note In the project, the configuration and project engineering have already been fully
implemented. This chapter is for information only.

The configuration is performed in the following configuration tools (first STEP 7,


then TeleControl Server Basic):
• STEP 7 V15.1:
– Configuring Station 1 (S7-1200 CPU with CP 1242-7 GPRS V2)
– Configuring Station 2 (S7-1200 CPU with CP 1243-1)
– Configuring the data points for both stations
• TeleControl Server Basic V3.1:
– Creating and configuring the project
– Creating and configuring connections
– Configuring general parameters
• UaExpert
– Establishing the connection to the server
– Configuring OPC items
© Siemens AG 2018 All rights reserved

– Creating the History Trend View

4.1 IP addresses in the application example


This application example uses the IP addresses shown in the following table.
Table 4-1
Station Module IP address
Internal External
Master station PG/PC 172.16.62.100/16
Engineering station PG/PC 192.168.0.100/24 (for loading the stations)
DSL router SCALANCE M816 172.16.0.1/16 Static IP address
from provider or
DynDNS
Station 1 CP 1242-7 V2 Dynamic IP address
CPU 192.168.0.1/24
Station 2 CP 1243-1 172.16.62.1/16
CPU 192.168.0.2/24

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 27
4 Configuration and Project Engineering

4.2 Configuring Station 1


The following table shows you how to configure an S7-1200 station with the
CP 1242-7 GPRS V2 for data communication with the master station via the
cellular network and the Internet.
Table 4-2
No. Action
1. Create a STEP 7 V15.1 project.
2. In the security settings, create a user with "administrator rights".
© Siemens AG 2018 All rights reserved

3. Add the S7-1200 CPU (V4.1 or higher) for SIMATIC Station 1.


4. Insert the CP 1242-7 GPRS V2 into the station.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 28
4 Configuration and Project Engineering

No. Action
5. Enable telecontrol communication and S7 communication:
"Properties > General > Communication types".

6. Make the required mobile wireless communications settings:


"Properties > Mobile wireless communications settings":
• Enable PIN
• Enable data services
• Make the APN settings / depend on the provider.
© Siemens AG 2018 All rights reserved

7. Enable the security functions.


"Properties > Security > Security properties".

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 29
4 Configuration and Project Engineering

No. Action
8. Configure the CP parameters required to configure the TeleControl server:
"Properties > Partner stations > Connection to partner"
• Partner IP address (static IP address / depends on the provider)
• Partner port

„WAN-IP-ADDRESS“

"Properties > Security > CP identification"


• "Project number"
• "Station number"
© Siemens AG 2018 All rights reserved

• "Telecontrol password" (here: "CP1242-7")

The parameters assigned here must be identical to the parameters in TCSB.


9. Check "Report partner status":
"Properties > Partner stations > Advanced settings"

Link a PLC tag you have created in the user program.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 30
4 Configuration and Project Engineering

No. Action
10. Check "Enable advanced CP diagnostics":
"Properties > Communication with the CPU > CP diagnostics".
© Siemens AG 2018 All rights reserved

Link the "diagnostics trigger tag" and the PLC tags you want to read from the CP
1242-7 GPRS V2.
11. Configure the desired data points (see Chapter 4.2).

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 31
4 Configuration and Project Engineering

4.3 Configuring the data points for Station 1 / Station 2


With the CP 1242-7 GPRS V2 or CP 1243-1, it is not necessary to program
program blocks in order to transfer user data between station and master station.
The data areas in the memory of the CPU intended for communication with the
master station are configured in the CP 1242-7 GPRS V2 or CP 1243-1 on a data
point-related basis. In this configuration, each data point is linked to a PLC tag in
the CPU (see Figure 3-2).

Threshold trigger
The value of the data point is transmitted when it reaches a certain threshold.
The threshold calculation does not evaluate the absolute value of the process
value's deviation from the last saved value, but the value of the integrated deviation
(see Figure 3-1).
Table 4-3
No. Action
1. Open the data point configuration
editor.
© Siemens AG 2018 All rights reserved

2. Insert the "outflow" data point as an analog input and link it to the "Data.outflow" PLC
tag.

3. Set the transfer method for this data point (here: Current value triggered).

4. Set the data point index.

Note:
The index of a data point of the Input type must be unique across all data point types
(digital inputs, analog inputs, etc.).

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 32
4 Configuration and Project Engineering

No. Action
5. As the communication partner, select "Telecontrol server".

6. Configure the "threshold trigger":


"Properties > General > Trigger > Threshold value trigger"

Time trigger
The data point value is transmitted cyclically (30 s).
Table 4-4
No. Action
© Siemens AG 2018 All rights reserved

1. In the data point configuration editor, insert the "fillLevel" data point as an analog
input and link it to the "Data.fillLevel" PLC tag.

2. Set the transfer method for this data point (here: Current value triggered).

3. Set the data point index.

Note:
The index of a data point of the Input type must be unique across all data point
types
(digital inputs, analog inputs, etc.).
4. As the communication partner, select "Telecontrol server".

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 33
4 Configuration and Project Engineering

No. Action
5. Configure the "time trigger":
"Properties > General > Trigger > Time trigger"

Event trigger
The data point value is transmitted when a configured trigger signal is triggered.
Table 4-5
No. Action
1. In the data point configuration editor, insert the "overflow" data point as an analog
input and link it to the "Data.overflow" PLC tag.
© Siemens AG 2018 All rights reserved

2. Set the transfer method for this data point (here: Current value triggered).

3. Set the data point index.

Note:
The index of a data point of the Input type must be unique across all data point
types
(digital inputs, analog inputs, etc.).
4. As the communication partner, select "Telecontrol Server".

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 34
4 Configuration and Project Engineering

No. Action
5. Configure the "event trigger":
"Properties > General > Trigger > Event trigger"

In the user program, create a trigger tag and link it to the "event trigger".

Note It is recommended to set the trigger tag with a delay of approx. 500 ms to ensure
that the value change of the inflow is reliably applied to the appropriate data
point.
© Siemens AG 2018 All rights reserved

Note The trigger signal should be linked to a static tag in the instance data block in the
CPU.
If the trigger signal is interconnected with a global tag, it is possible that the
trigger signal may not be automatically reset. This is due to runtime differences
between the CPU cycle and the CP cycle.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 35
4 Configuration and Project Engineering

4.4 Configuring Station 2


The following table shows you how to configure an S7-1200 station with the
CP 1243-1 for data communication with the master station via Ethernet.
Table 4-6
No. Action
1. Add a second S7-1200 CPU (V4.0 or higher) for SIMATIC Station 2.
2. Insert the CP 1243-1 (V3.1) into the station.

3. Enable telecontrol communication and S7 communication:


"CP 1243-1 Properties > General > Communication types"
© Siemens AG 2018 All rights reserved

4. Create an Ethernet network and connect the CP to the Ethernet network.


"CP 1243-1 Properties > Ethernet interface"

5. Enable the security functions.


"CP 1243-1 Properties > Security > Security properties"

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 36
4 Configuration and Project Engineering

No. Action
6. Configure the CP parameters required to configure the TeleControl server:
"CP 1243-1 Properties > Partner stations > Connection to partner"
• Partner IP address
• Partner port

"CP 1243-1 Properties > Security > CP identification"


• "Project number"
• "Station number"
• "Telecontrol password" (here: "CP1243-1")
© Siemens AG 2018 All rights reserved

The parameters assigned here must be identical to the parameters in TCSB.


7. Check Report partner status:
"CP 1243-1 Properties > Partner stations > Advanced settings"

Link a PLC tag you have created in the user program.


8. Configure the desired data points (see Chapter 4.2).
The configuration is identical to that of Station 1.
9. Download the project data to the station.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 37
4 Configuration and Project Engineering

4.5 Configuring TeleControl Server Basic (TCSB)


Table 4-7
No. Action
1. Start the configuration and monitoring user interface of TCSB (CMT):

"Windows Start menu > All Programs > Siemens Automation > SIMATIC > TCS
Basic > Config and Monitoring Tool"
2. After starting the program, the CMT Logon window opens.

Enter a configured user name or keep the default user name.


• Enter the associated password.
© Siemens AG 2018 All rights reserved

• Enter the IP address or the TeleControl server name resolvable by DNS.


– Computer name
or
– IP address (default IP address: 127.0.0.1)

Default logon data:

User name: administrator


Password: 0000
3. Create a new project:
• In the navigation pane, select the "Projects" item.
• In the command bar, click the "Add" button.
The new project appears in the navigation pane and in the object pane.
4. Configure the new project:
In the navigation pane or object pane, select the project and click the "Settings"
tab.
5. Enter the following project
parameters: "Project name", "Project
number", "Server password".
Click "Create".

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 38
4 Configuration and Project Engineering

No. Action
6. "Save & activate" the configuration to
activate the configuration data for
connection establishment.

7. Create a new connection for Station 1:


• In the navigation pane, select a project for which you want to create a new
connection.
• In the command bar, select the required connection type from the
"Connection type" drop-down list.
• In the object pane, select the "Add" button from the command bar. Select the
desired CP.
• Enter the "station name".
• Enter the "station number".
• Enter the "telecontrol password".

Note:
The parameters assigned here must be identical to the parameters in the
STEP 7 project.

• Click OK.
© Siemens AG 2018 All rights reserved

The new connection appears in the object pane.


8. Save the changes and activate the
project.

9. Repeat steps 7 and 8 for Station 2.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 39
4 Configuration and Project Engineering

No. Action
10. Configure the IP address and the ports of the TeleControl server:

"TCSB system > "TCM" tab > General > Address TCM 1".

11. Save the changes and activate the


project.
© Siemens AG 2018 All rights reserved

Note Once the stations have established a connection to TeleControl Server Basic,
the configured data points are known to the server. Only then can you assign the
"Archive" and "Data buffer" attributes to the data points.
Both attributes are necessary for this application.

Note If you create a new TCSB project for this application example, modify the
relevant HMI tags in the visualization software accordingly.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 40
4 Configuration and Project Engineering

4.6 Configuring UaExpert


TCSB's OPC server enables OPC clients (UaExpert) to access process tags of the
connected stations and status information of the individual connections. TCSB's
OPC server is displayed with the name "OPC.SimaticNET.TCSB". Monitoring the
OPC items requires an existing connection to TCSB.
Table 4-8
No. Action
1. Open UaExpert:

"Windows Start menu > All Programs > Unified Automation > UaExpert"
2. Insert the OPC server:
© Siemens AG 2018 All rights reserved

3. Enter the following URL:


"opc.tcp://172.16.62.100:4852"

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 41
4 Configuration and Project Engineering

No. Action
4. Select the OPC.SimaticNET.TCSB server and choose the desired authentication
method (here: no authentication). Check "Connect Automatically":
© Siemens AG 2018 All rights reserved

5. Open the DP directory of the first station:

"OPC.SimaticNET.TCSB > CP12xx-x with TCSB > Process Stations >


Station 1.101 > Objects > DP".

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 42
4 Configuration and Project Engineering

No. Action
6. Use drag and drop to move any data points to the "Data Access View" area.
© Siemens AG 2018 All rights reserved

7. Create a "History Trend View":

Select the "History Trend View" and click "Add" to confirm:

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 43
4 Configuration and Project Engineering

No. Action
8. Check the data points' attributes in the CMT.
Only data points with the "Archive" attribute can be monitored using the
"History Trend View".

9. Use drag and drop to move any data points with the "Archive" attribute to the
"Configuration" area:
© Siemens AG 2018 All rights reserved

10. Repeat steps 5, 6 and 9 for Station 2.

Note If you create a new project for this application example, modify the relevant HMI
tags in the visualization software accordingly.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 44
5 Installation and Startup

5 Installation and Startup


5.1 Installing the hardware
For the necessary hardware components, please refer to Chapter 2.4.

Note Always follow the installation guidelines for all components.

NOTICE Before you switch on the power supply, complete and check the
installation!

5.1.1 Station 1 hardware configuration

The following figure shows the hardware configuration of Station 1: S7-1200 CPU
with the CP 1242-7 GPRS V2.
Figure 5-1
© Siemens AG 2018 All rights reserved

24 V

CP 1242-7 CPU 1217C


GPRS V2

Table 5-1
No. Action
1. Insert your SIM card into the CP 1242-7 GPRS V2.
2. Insert the SIMATIC Memory Card into the CPU.
3. Connect the CPU to the CP 1242-7 GPRS V2 via the backplane bus.
4. Attach the two modules to a suitable rack.
5. Connect the antenna to the CP 1242-7 GPRS V2.
6. Connect the CPU and the CP 1242-7 GPRS V2 to a 24 V DC power source.
7. Connect the DC power source to the power grid
(220 / 230 V AC).

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 45
5 Installation and Startup

5.1.2 Station 2 hardware configuration

The following figure shows the hardware configuration of Station 2: S7-1200 CPU
with the CP 1243-1.
Figure 5-2

Master station

CP 1243-1 CPU 1217C

24 V

172.16.62.1 172.16.62.100
Industrial Ethernet

Table 5-2
No. Action
© Siemens AG 2018 All rights reserved

1. Insert the SIMATIC Memory Card into the CPU.


2. Connect the CPU to the CP 1243-1 via the backplane bus.
3. Attach the two modules to a suitable rack.
4. Connect all relevant components to a 24 V DC power source.
5. Connect the DC power source to the power grid
(220 / 230 V AC).
6. Connect the master station to the Ethernet interface of the CP 1243-1.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 46
5 Installation and Startup

5.1.3 Master station hardware configuration

The following figure shows the hardware configuration of the master station.
Figure 5-3

Master station DSL router

TCSB V3.1
WinCC Adv. Static IP address
Internet
(DSL)

172.16.62.100 172.16.0.1

Industrial Ethernet

Table 5-3
No. Action
1. Connect your PC on which TeleControl Server Basic is installed to the router
© Siemens AG 2018 All rights reserved

via Ethernet.
2. If the DSL modem is not integrated in the router, connect the router to the
DSL modem.

5.2 Installing the software


Engineering PC/PG
Table 5-4
No. Action Comment
1. Install STEP 7 V15.1.
2. Install WinCC Advanced V15.1. Follow the instructions of the installation
program.

PC/PG as the master station


Table 5-5
No. Action Comment
1. Install TeleControl Server Basic
V3.1.0.1 Follow the instructions of the installation
2. Install WinCC Advanced V15.1 program.
Runtime.
3. Install UaExpert. optional

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 47
5 Installation and Startup

5.3 Installing the application software


Unzip the "39863979_S7_1200_WinCC_Adv_PROJ_V20.zip" file. This folder
contains:
• The archived STEP 7 project,
"39863979_S7-1200_WinCC_Adv_CODE_V20.ap15_1":
– "S7-1200_CP1242-7" Station 1 project
– "S7-1200_CP1243-1" Station 2 project
– "Data communication TCSB" WinCC project
• "39863979_S7-1200_with_TCSB.bak" TCSB configuration file
• "39863979_S7-1200_with_TCSB.uap" UaExpert configuration file.

5.4 Startup
5.4.1 Assigning the IP address of the master station

The following table shows the network properties you must set for the master
station.
Table 5-6
© Siemens AG 2018 All rights reserved

No. Action
1. Open the Internet Protocol (TCP/IP) Properties:

"Start > Control Panel > Network and Internet > Network Connections > Local
Connections"
2. In the open window, select Internet Protocol (TCP/IPv4) and open Properties.
3. Enter the IP address for your master
station.
In the "Default gateway" and
"Preferred DNS server" fields, enter
the DSL router's internal IP address.

Select "OK" to close the window.

4. If your PG has a WLAN interface, disable it.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 48
5 Installation and Startup

5.4.2 Configuring the DSL router

For the configuration, no specific router will be discussed as the screen forms will
differ from router to router.

Table 5-7
No. Action
1. Open the router's configuration user This can be additional software,
interface. "Telnet" or a Web page.
2. Enter the access data for your Internet Login, password, etc. you received
account. from your provider.
3. Enter your DNS server. The address is provided with your
access data.
4. Assign a LAN IP address to the router. In this example:
172.16.0.1.
5. Forward the partner port. TCP port 55097 to port 55097 of
172.16.62.100.

Note To configure the router, you have to assign an IP address to your PG/PC that is
in the router's internal network.
© Siemens AG 2018 All rights reserved

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 49
5 Installation and Startup

5.4.3 Inserting the "39863979_S7-1200_with_TCSB.bak"


database backup copy into TCSB V3.1.0.1

Table 5-8
No. Action
1. Stop the existing database by selecting
"Windows Task Manager" > "Services" tab > "Services" button > "TCS Basic
Database Service" (right-click) > "Stop".
© Siemens AG 2018 All rights reserved

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 50
5 Installation and Startup

No. Action
2. Start SQL Server Management Studio as an administrator:
"Start > All programs > Microsoft SQL Server 2008 R2 > SQL Server
Management Studio (right-click) > Run as administrator"
© Siemens AG 2018 All rights reserved

The "Connect to Server" dialog opens with the following settings:


• Server type: Database Engine
• Server name: <PC name>\TCSB
• Authentication: Windows Authentication
3. Verify the server name; it must be as follows:
"<PC name>\TCSB".
Then click "Connect".

SQL Server Management Studio opens with the database's


object navigation.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 51
5 Installation and Startup

No. Action
4. Select the "Databases" item.

5. Select the context menu (right-click) "Restore Database...".


© Siemens AG 2018 All rights reserved

The "Restore Database…" dialog opens.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 52
5 Installation and Startup

No. Action
6. • In the "Destination for restore" field, select the "TCSB" database ("To
database").
• In the "Source for restore" field, select the "From device" option and use
the "..." button to open the "Specify Backup" dialog.
• Select the "39863979_S7-1200_with_TCSB.bak" backup copy by first
opening the file browser using the "Add" button.
© Siemens AG 2018 All rights reserved

7. In the "Restore Database - TCSB" dialog, select the selected “backup set” in
the "Restore" column and click "OK".
8. Click "OK" to close Management Studio.
9. Restart the computer.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 53
5 Installation and Startup

5.4.4 Configuring the IP address and the ports of TeleControl Server Basic
V3.1

Table 5-9
No. Action
1. Start the configuration and monitoring user interface of TCSB (CMT):

"Windows Start menu > All Programs > Siemens Automation > SIMATIC > TCS
Basic > Config and Monitoring Tool".
2. After starting the program, the CMT Logon window opens.

• User name: administrator


• Password: administrator
• Enter the IP address or the TeleControl server name resolvable by DNS.
© Siemens AG 2018 All rights reserved

– Computer name
or
– IP address (default IP address: 127.0.0.1)
3. Configure the Telecontrol server's IP address by selecting:
"TCSB system > Edit > Address TCM 1".
Set "IPT listener-port" to 55097.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 54
5 Installation and Startup

No. Action
4. Configure the settings for the integrated OPC server.
© Siemens AG 2018 All rights reserved

5. Save the changes and activate the project.

6. Restart the computer.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 55
5 Installation and Startup

5.4.5 Opening the "39863979_S7-1200_with_TCSB.uap"


UaExpert configuration file

To monitor the process data at the master station, you must open the
"39863979_S7-1200_with_TCSB.uap" UaExpert configuration file included in the
project.
Table 5-10
No. Action
1. Open UaExpert:

"Windows Start menu > All Programs > Unified Automation > UaExpert"
2. Open the "39863979_S7-1200_with_TCSB.uap" file:
"File > Open …".
3. Open the OPC server settings:
© Siemens AG 2018 All rights reserved

4. Enter the following endpoint URL:


"opc.tcp://172.16.62.100:4852"
Alternatively, you can enter the PC name instead of the IP address.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 56
5 Installation and Startup

No. Action
5. Connect UaExpert to the OPC UA server:

6. In the next dialog, select "Trust Server Certificate" to confirm the certificate
and then click "Continue":
© Siemens AG 2018 All rights reserved

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 57
5 Installation and Startup

No. Action
7. Open the "OPC.SimaticNET.TCSB" server. If the connection to the server was
successful, you will see the OPC items.
© Siemens AG 2018 All rights reserved

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 58
5 Installation and Startup

5.4.6 Loading Station 1 / Station 2

Requirements
• Connect your PG to the CPU.
• The CPU must be in a mode that allows downloading.
• Before downloading the user program, a general reset of the CPU should be
performed to ensure that no "old" blocks are on the CPU.

Table 5-11
No. Action
1. Connect the engineering PG to the PROFINET interface of the S7 CPU.
2. Unzip the "39863979_S7-1200_WinCC_Adv_PROJ_V20.zip" project.
3. Open the following STEP 7 project:
"39863979_S7-1200_WinCC_Adv_CODE_V20.ap15_1"
4. Log on:
© Siemens AG 2018 All rights reserved

User name: administrator


Password: administrator
5. Customize the mobile wireless
communications settings of the
CP 1242-7 GPRS V2:
"Properties > Mobile wireless
communications settings":
• Activate and enter the PIN
• Change the APN settings

Note:
This step is only required for the CP
1242-7 GPRS V2.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 59
5 Installation and Startup

No. Action
6. Change the partner IP address (static IP address of your DSL router) required for
the connection to the TeleControl server in the master station:

"Properties > Partner stations > Connection to partner"

„WAN-IP-ADDRESS“

Note:
This step is only required for the CP 1242-7 GPRS V2.
7. Compile and save the project.
8. Select the "S7-1200_CP1242-7" or "S7-1200_CP1243-1" station.
© Siemens AG 2018 All rights reserved

9. Download the project to Station 1 or Station 2.

10. Configure the hardware as described in Chapter 5.1.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 60
6 Operation of the Application

6 Operation of the Application


6.1 Overview
HMI menu
The application is visualized with WinCC Advanced using two configured screen forms:
"TCSB Communication" and "S7-1200 Application".

Figure 6-1
Start screen
© Siemens AG 2018 All rights reserved

TCSB Communication S7-1200 Application

"Start screen" main menu


The "Start screen" main menu allows you to open the application example and
toggle between "TCSB Communication" and "S7-1200 Application".

"TCSB Communication" screen


The "TCSB Communication" screen shows the status of the connection to the
remote stations. It additionally provides information about data traffic. You can
toggle between "Start screen" and "S7-1200 Application".

"S7-1200 Application" screen


The "S7-1200 Application" screen visualizes the processes of stations 1 and 2. You
can toggle between "Start screen" and "TCSB Communication".

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 61
6 Operation of the Application

Watch table of Station 1 / Station 2


The "WT_SetResetParameter" watch table also allows you to monitor or modify the
tags of the "Data" DB directly in the CPU.
For a description of the tags, please refer to Table 3-3.

Figure 6-2

Note For Station 1 (CP 1242-7 GPRS), the TeleService function must be activated in
order to monitor or modify the table's tags as the master station and the CP are
not in the same IP network. (See \7\)
© Siemens AG 2018 All rights reserved

The TeleService function is not necessary for Station 2 as the master station and
the CP are in the same IP network.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 62
6 Operation of the Application

6.2 Starting / stopping the simulation


To start or stop the simulation, proceed as follows:
Table 6-1
No. Action
1. Click the "Start Simulation" icon to start the WinCC Advanced simulation.
© Siemens AG 2018 All rights reserved

2. Go to the "TCSB Communication" screen.

Verify that both nodes have established a connection ("Connection = 1"). If this is not
the case, check the hardware configuration and the configuration of both stations.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 63
6 Operation of the Application

3. Go to the "S7-1200 Application" screen.

4. Use the "On" button to start the data simulation for the respective station.
The master station therefore sends a 'start data simulation' command to the station.
The station reports that the data simulation has started. In the HMI system, the "On"
button is displayed in green.
5. To stop the data simulation, click the "Off" button.
6. To stop WinCC Runtime, click "Stop Runtime".
© Siemens AG 2018 All rights reserved

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 64
6 Operation of the Application

6.3 Station 1 / Station 2 sends data to the master station


on a "threshold-triggered" basis
Station 1 or Station 2 sends its outflow value to TeleControl Server Basic in the
master station on a threshold-triggered basis.
Table 6-2
No. Action
1. When the threshold value "2" is reached
(see Figure 3-1), the outflow value is sent
to the master station.

In the "S7-1200 Application" screen, the


"Outflow" field displays the value the
master station has received.
© Siemens AG 2018 All rights reserved

2. Go to the "TCSB Communication" screen.


The outflow value received by the master station can also be monitored in this
screen; it is displayed in the "Outflow" field.

Alternatively, you can monitor the data using UaExpert.

Note:
"Threshold trigger"=2 was configured in the data point configuration (see
Chapter 4-2).
3. Repeat the step for Station 2.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 65
6 Operation of the Application

6.4 Station 1 / Station 2 cyclically sends data to the master


station
Station 1 or Station 2 sends its fill level value to TeleControl Server Basic in the
master station at a defined interval. The following table provides instructions for this
job.
Table 6-3
No. Action
1. Open the "S7 1200 Application" screen
and monitor the current fill level value.
The fill level value is updated after 30
seconds.
© Siemens AG 2018 All rights reserved

2. Go to the "TCSB Communication" screen. In this screen, you can also monitor the
fill level value.

Alternatively, you can monitor the data using UaExpert.

3. Repeat the step for Station 2.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 66
6 Operation of the Application

6.5 Station 1 / Station 2 sends data to the master station


on an "event-triggered" basis
If the inflow of Station 1 or Station 2 exceeds a maximum value, the inflow value is
sent to the master station. The following table provides instructions for this job.
Table 6-4
No. Action
1. Open the "TCSB Communication" screen.
2. The "InflowUp" field displays the
maximum inflow value.
In the application example, the value in
the program is set to 25%.
© Siemens AG 2018 All rights reserved

3. Open the "S7-1200 Application" screen.


The "inflow" field displays the current
inflow value.
If this value exceeds the maximum
inflow value (InflowUp) (e.g., 25%), an
overflow alarm is sent to the master
station.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 67
6 Operation of the Application

No. Action
4. The overflow alarm is displayed in the "TCSB Communication" screen.

Alternatively, you can monitor the data using UaExpert.

5. Repeat the step for Station 2.


© Siemens AG 2018 All rights reserved

6.6 Monitoring value changes in UaExpert


The "History Trend View" allows you to monitor value changes of data points.
UaExpert graphically represents the trend.
Table 6-5
No. Action
1. Check the data points' attributes in the CMT.
Only data points with the "Archive" attribute can be monitored using the
"History Trend View".

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 68
6 Operation of the Application

No. Action
2. Open the "History Trend View" in UaExpert.

3. Use drag and drop to move the desired data points to the "Configuration" area.
© Siemens AG 2018 All rights reserved

4. Select "Cyclic Update" and click "Start".

5. Go to WinCC and start the value simulation as described in Chapter 6.2. Now you
can monitor the data points' trend.
Alternatively, you can use the "Trend view" WinCC control. To this end, an optional
screen is configured in the HMI.

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 69
7 Appendix

7 Appendix
7.1 Service and Support
Industry Online Support
Do you have any questions or need assistance?
Siemens Industry Online Support offers round the clock access to our entire
service and support know-how and portfolio.
Industry Online Support is the central address for information about our products,
solutions and services.
Product information, manuals, downloads, FAQs, application examples and videos
– all information is accessible with just a few mouse clicks at:
https://support.industry.siemens.com/

Technical Support
The Technical Support of Siemens Industry provides you with fast and competent
support regarding all technical queries with numerous tailor-made offers
– ranging from basic support to individual support contracts.
You send queries to Technical Support via Web form:
https://www.siemens.en/industry/supportrequest
© Siemens AG 2018 All rights reserved

SITRAIN – Training for Industry


With our globally available training courses for our products and services, we help
you achieve these goals – with practical experience, innovative learning methods,
and a concept that’s tailored to the customer's specific needs.
For more information on our offered trainings and courses, as well as their
locations and dates, refer to:
https://www.siemens.en/sitrain

Service offer
Our range of services includes the following:
• Plant data services
• Spare parts services
• Repair services
• On-site and maintenance services
• Retrofitting and modernization services
• Service programs and contracts
You can find detailed information on our range of services in the service catalog:
https://support.industry.siemens.com/cs/sc

Industry Online Support app


You will receive optimum support wherever you are with the "Siemens Industry
Online Support" app. The app is available for Apple iOS, Android and Windows
Phone:
https://support.industry.siemens.com/cs/ww/en/sc/2067

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 70
8 Links & Literature

8 Links & Literature


Table 8-1
Topic
\1\ Siemens Industry Online Support
http://support.industry.siemens.com
\2\ Download page of the entry
https://support.industry.siemens.com/cs/ww/en/view/39863979
\3\ Support packages for the hardware catalog in the TIA Portal (HSP)
https://support.industry.siemens.com/cs/ww/en/view/72341852
\4\ SIMATIC NET Industrial Remote Communication - TeleControl TeleControl Server
Basic - Version V3.1
https://support.industry.siemens.com/cs/ww/en/view/109755138
\5\ SIMATIC STEP 7 V15.1 and WinCC V15.1 TRIAL Download
https://support.industry.siemens.com/cs/ww/en/view/109752566
\6\ How do you read out advanced diagnostics data from the CP 1242-7 GPRS V2?
https://support.industry.siemens.com/cs/ww/en/view/109480967
\7\ TeleService of an S7-1200 station via mobile network (Set 33)
https://support.industry.siemens.com/cs/ww/en/view/56720905
\8\ UaExpert download page
https://www.unified-automation.com/downloads/opc-ua-clients.html
\9\ Sales and delivery release TeleControl Server Basic V3.1 + Update 1 (V3.1.0.1)
© Siemens AG 2018 All rights reserved

https://support.industry.siemens.com/cs/ww/en/view/109757071

9 History
Table 9-1
Version Date Modifications
V1.0 05/2016 First version
V1.1 02/2018 • Upgraded to STEP 7 V14.
• New block and data point link for the simulation and
transfer of fill level and inflow.
V1.2 06/2018 • Upgraded to STEP 7 V15.
• New TCSB functions added.
• OPC Scout replaced by UaExpert.
V2.0 09/2019 Upgraded to STEP 7 V15.1

S7-1200 with TCSB


Entry ID: 39863979, V2.0, 09/2019 71