Osmena Plant Surge Tank Deiign

This document details the design of a surge tank for the Osmena Mini Hydro Power Plant located in Gov. Generoso, Davao Oriental, Philippines. Calculations are shown to determine key specifications of the surge tank, including a total height of 12.68 meters and minimum cross-sectional area of 7.07 square meters. Based on a pressure of 124.36 megapascals, the required wall thickness is calculated as 8.00 millimeters. The surge tank specifications are then listed, including a height of 12.68 meters, diameter of 2.50 meters, and wall thickness of 8.00 millimeters.

Uploaded by

UHPB Team
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
72 views2 pages

Osmena Plant Surge Tank Deiign

This document details the design of a surge tank for the Osmena Mini Hydro Power Plant located in Gov. Generoso, Davao Oriental, Philippines. Calculations are shown to determine key specifications of the surge tank, including a total height of 12.68 meters and minimum cross-sectional area of 7.07 square meters. Based on a pressure of 124.36 megapascals, the required wall thickness is calculated as 8.00 millimeters. The surge tank specifications are then listed, including a height of 12.68 meters, diameter of 2.50 meters, and wall thickness of 8.00 millimeters.

Uploaded by

UHPB Team
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

PROJECT: OSMENA

 MINI  HYDRO  POWER  PLANT


LOCATION: GOV.  GENEROSO,  DAVAO  ORIENTAL
DESIGN  OF  SURGE  TANK  
GIVEN:
Length  of  Conveyance  Line  (L) = 3,120.00 m
Gravitational  Force  (g) = 9.81 m/sec2
Head  Loss  Due  to  Bends  (hb) = ? m  (as  computed  from  headrace)
Head  Loss  Due  to  Friction  (hf) = ? m  (as  computed  from  headrace)
Gross  Head  of  Power  Plant  (H) = 61.00 m
Net  Head  of  Power  Plant  (Hn) = ? m
Velocity  at  Head  Race  (V 1  ) = 1.86 m/sec
Velocity  at  Head  Race  (V 2 ) = 2.64 m/sec
Pressure  Head  (Z) = ? m
Upsurge  (h up ) = ? m
Downsurge  (h down) = ? m
Elevation  @  Intake = 154.00 masl
Elevation  @  Surge  Tank = 143.14 masl
Diameter  of  Conveyance  Line = 1.2 m
Coefficient  of  Friction = 0.012
Upsurge  if  Friction  losses  are  ignored  (Z) = ?
Minimum  Area  of  Surge  Tank  (F) = 1.75 FROM  THOMA  FORMULA
h f  =  fL  V2 /D2g 11.29 eq.  1
h up  =  Z  –  (2/3)  H L eq.  2
h down  =  Z  +  (1/6)  H L eq.  3
2
F  =  (0.75LfV )/(gHn H f ) eq.  4
2
H n  =  H  –  Hf  –  V /2g eq.  5
1/2
Z  =  2π(Lf/gF) eq.  6
H L  =  hf  +  hb eq.  7
Using  eq.  1
h f   5.48 m use 5.48 meters
hb 0.55 m Headloss  (Headrace)
Vh 0.18 m
Using  eq.  5
Hn 54.80 m
Using  eq.  4
F 0.07 m (min)
D 1.75 m 3.00 meters
2
F 7.07 m Area  of  Surge  Tank
Using  eq.  6
Z 4.62 m
Using  eq.  7
HL 6.20 m
Using  eq.  2
h up 0.94 m
Using  eq.  3
h down 5.53 m
Height  of  Surge  Tank  (Ht)
Ht 12.68 m  Total  Height  of  Surge  Tank
Thickness  of  Shell  wall  (Assuming  1  meter  width)
Pressure  (P) 124.36 Mpa
Thickness  of  Wall  (T) 8.00 mm

SURGE  TANK  SPECIFICATIONS

HEIGHT  OF  SURGE  TANK =                           12.68


  m
DIAMETER =                                2.50
ASTM  A36  Grade  B =        413,700.00 kPa
THICKNESS  OF  PIPE  (COMPUTED) =                                5.22 mm
STANDARD  MINIMUM  THICKNESS =                                8.00 mm
USE  (ACTUAL  THICKNESS) =                                8.00 mm(nominal  thichness)

LAYER MS  PLATE  THICKNESS


1  to  5 8 mm
REST 6.35 mm