Data sheet 3RT2026-1BB40

power contactor, AC-3 25 A, 11 kW / 400 V 1 NO + 1 NC, 24 V DC 3-pole,


Size S0 screw terminal

product brand name SIRIUS


product designation Power contactor
product type designation 3RT2
General technical data
size of contactor S0
product extension
● function module for communication No
● auxiliary switch Yes
power loss [W] for rated value of the current at AC in hot 4.8 W
operating state
● per pole 1.6 W
power loss [W] for rated value of the current without 5.9 W
load current share typical
surge voltage resistance
● of main circuit rated value 6 kV
● of auxiliary circuit rated value 6 kV
maximum permissible voltage for safe isolation between 400 V
coil and main contacts acc. to EN 60947-1
shock resistance at rectangular impulse
● at DC 10g / 5 ms, 7,5g / 10 ms
shock resistance with sine pulse
● at DC 15g / 5 ms, 10g / 10 ms
mechanical service life (switching cycles)
● of contactor typical 10 000 000
● of the contactor with added electronically optimized 5 000 000
auxiliary switch block typical
● of the contactor with added auxiliary switch block 10 000 000
typical
reference code acc. to IEC 81346-2 Q
Ambient conditions
installation altitude at height above sea level maximum 2 000 m
● ambient temperature during operation -25 ... +60 °C
● ambient temperature during storage -55 ... +80 °C
Main circuit
number of poles for main current circuit 3
number of NO contacts for main contacts 3
● operating voltage at AC-3 rated value maximum 690 V
operational current

3RT20261BB40 Subject to change without notice


12.17.2020
Page 1/2 © Copyright Siemens
● at AC-1 at 400 V at ambient temperature 40 °C 40 A
rated value
● at AC-1
— up to 690 V at ambient temperature 40 °C 40 A
rated value
— up to 690 V at ambient temperature 60 °C 35 A
rated value
● at AC-3
— at 400 V rated value 25 A
— at 500 V rated value 18 A
— at 690 V rated value 13 A
● at AC-4 at 400 V rated value 15.5 A
● at AC-5a up to 690 V rated value 35.2 A
● at AC-5b up to 400 V rated value 20.7 A
● at AC-6a
— up to 230 V for current peak value n=20 rated 20.2 A
value
— up to 400 V for current peak value n=20 rated 20.2 A
value
— up to 500 V for current peak value n=20 rated 20.2 A
value
— up to 690 V for current peak value n=20 rated 12.9 A
value
● at AC-6a
— up to 230 V for current peak value n=30 rated 13.5 A
value
— up to 400 V for current peak value n=30 rated 13.5 A
value
— up to 500 V for current peak value n=30 rated 13.5 A
value
— up to 690 V for current peak value n=30 rated 13 A
value
minimum cross-section in main circuit at maximum AC-1 10 mm²
rated value
operational current for approx. 200000 operating
cycles at AC-4
● at 400 V rated value 9A
● at 690 V rated value 9A
operational current
● at 1 current path at DC-1
— at 24 V rated value 35 A
— at 110 V rated value 4.5 A
— at 220 V rated value 1A
— at 440 V rated value 0.4 A
— at 600 V rated value 0.25 A
● with 2 current paths in series at DC-1
— at 24 V rated value 35 A
— at 110 V rated value 35 A
— at 220 V rated value 5A
— at 440 V rated value 1A
— at 600 V rated value 0.8 A
● with 3 current paths in series at DC-1
— at 24 V rated value 35 A
— at 110 V rated value 35 A
— at 220 V rated value 35 A
— at 440 V rated value 2.9 A
— at 600 V rated value 1.4 A
operational current
● at 1 current path at DC-3 at DC-5
— at 24 V rated value 20 A
— at 110 V rated value 2.5 A

3RT20261BB40 Subject to change without notice


12.17.2020
Page 2/3 © Copyright Siemens
— at 220 V rated value 1A
— at 440 V rated value 0.09 A
— at 600 V rated value 0.06 A
● with 2 current paths in series at DC-3 at DC-5
— at 24 V rated value 35 A
— at 110 V rated value 15 A
— at 220 V rated value 3A
— at 440 V rated value 0.27 A
— at 600 V rated value 0.16 A
● with 3 current paths in series at DC-3 at DC-5
— at 24 V rated value 35 A
— at 110 V rated value 35 A
— at 220 V rated value 10 A
— at 440 V rated value 0.6 A
— at 600 V rated value 0.6 A
operating power
● at AC-3
— at 230 V rated value 5.5 kW
— at 400 V rated value 11 kW
— at 500 V rated value 11 kW
— at 690 V rated value 11 kW
operating power for approx. 200000 operating cycles
at AC-4
● at 400 V rated value 4.4 kW
● at 690 V rated value 7.7 kW
operating apparent power at AC-6a
● up to 230 V for current peak value n=20 rated value 8 kV·A
● up to 400 V for current peak value n=20 rated value 13.9 kV·A
● up to 500 V for current peak value n=20 rated value 17.4 kV·A
● up to 690 V for current peak value n=20 rated value 15.4 kV·A
operating apparent power at AC-6a
● up to 230 V for current peak value n=30 rated value 5.3 kV·A
● up to 400 V for current peak value n=30 rated value 9.3 kV·A
● up to 500 V for current peak value n=30 rated value 11.6 kV·A
● up to 690 V for current peak value n=30 rated value 15.5 kV·A
short-time withstand current in cold operating state
up to 40 °C
● limited to 1 s switching at zero current maximum 375 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 5 s switching at zero current maximum 299 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 10 s switching at zero current maximum 200 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 30 s switching at zero current maximum 128 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 60 s switching at zero current maximum 106 A; Use minimum cross-section acc. to AC-1 rated value
no-load switching frequency
● at AC 5 000 1/h
● at DC 1 500 1/h
operating frequency
● at AC-1 maximum 1 000 1/h
● at AC-2 maximum 750 1/h
● at AC-3 maximum 750 1/h
● at AC-4 maximum 250 1/h
Control circuit/ Control
type of voltage of the control supply voltage DC
control supply voltage at DC
● rated value 24 V
operating range factor control supply voltage rated
value of magnet coil at DC
● initial value 0.8
● full-scale value 1.1
closing power of magnet coil at DC 5.9 W

3RT20261BB40 Subject to change without notice


12.17.2020
Page 3/4 © Copyright Siemens
holding power of magnet coil at DC 5.9 W
closing delay
● at DC 50 ... 170 ms
opening delay
● at DC 15 ... 17.5 ms
arcing time 10 ... 10 ms
control version of the switch operating mechanism Standard A1 - A2
Auxiliary circuit
number of NC contacts for auxiliary contacts 1
instantaneous contact
number of NO contacts for auxiliary contacts 1
instantaneous contact
operational current at AC-12 maximum 10 A
operational current at AC-15
● at 230 V rated value 10 A
● at 400 V rated value 3A
● at 500 V rated value 2A
● at 690 V rated value 1A
operational current at DC-12
● at 24 V rated value 10 A
● at 48 V rated value 6A
● at 60 V rated value 6A
● at 110 V rated value 3A
● at 125 V rated value 2A
● at 220 V rated value 1A
● at 600 V rated value 0.15 A
operational current at DC-13
● at 24 V rated value 10 A
● at 48 V rated value 2A
● at 60 V rated value 2A
● at 110 V rated value 1A
● at 125 V rated value 0.3 A
● at 220 V rated value 0.3 A
● at 600 V rated value 0.3 A
contact reliability of auxiliary contacts 1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value 21 A
● at 600 V rated value 22 A
yielded mechanical performance [hp]
● for single-phase AC motor
— at 110/120 V rated value 2 hp
— at 230 V rated value 3 hp
● for 3-phase AC motor
— at 200/208 V rated value 5 hp
— at 220/230 V rated value 7.5 hp
— at 460/480 V rated value 15 hp
— at 575/600 V rated value 20 hp
contact rating of auxiliary contacts according to UL A600 / P600
Short-circuit protection
design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required gG: 100 A (690 V, 100 kA), aM: 50 A (690 V, 100 kA), BS88: 100 A (415
V, 80 kA)
— with type of assignment 2 required gG: 35A (690V, 100kA), aM: 20A (690V, 100kA), BS88: 35A (415V,
80kA)
● for short-circuit protection of the auxiliary switch gG: 10 A (500 V, 1 kA)
required
Installation/ mounting/ dimensions

3RT20261BB40 Subject to change without notice


12.17.2020
Page 4/5 © Copyright Siemens
mounting position +/-180° rotation possible on vertical mounting surface; can be tilted
forward and backward by +/- 22.5° on vertical mounting surface
fastening method screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
● side-by-side mounting Yes
height 85 mm
width 45 mm
depth 107 mm
required spacing
● with side-by-side mounting
— forwards 10 mm
— upwards 10 mm
— downwards 10 mm
— at the side 0 mm
● for grounded parts
— forwards 10 mm
— upwards 10 mm
— at the side 6 mm
— downwards 10 mm
● for live parts
— forwards 10 mm
— upwards 10 mm
— downwards 10 mm
— at the side 6 mm
Connections/ Terminals
type of electrical connection
● for main current circuit screw-type terminals
● for auxiliary and control circuit screw-type terminals
● at contactor for auxiliary contacts Screw-type terminals
● of magnet coil Screw-type terminals
type of connectable conductor cross-sections
● for main contacts
— solid 2x (1 ... 2.5 mm²), 2x (2.5 ... 10 mm²)
— solid or stranded 2x (1 ... 2,5 mm²), 2x (2,5 ... 10 mm²)
— finely stranded with core end processing 2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), 1x 10 mm²
● at AWG cables for main contacts 2x (16 ... 12), 2x (14 ... 8)
connectable conductor cross-section for main
contacts
● solid 1 ... 10 mm²
● stranded 1 ... 10 mm²
● finely stranded with core end processing 1 ... 10 mm²
connectable conductor cross-section for auxiliary
contacts
● solid or stranded 0.5 ... 2.5 mm²
● finely stranded with core end processing 0.5 ... 2.5 mm²
type of connectable conductor cross-sections
● for auxiliary contacts
— solid or stranded 2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²)
— finely stranded with core end processing 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG cables for auxiliary contacts 2x (20 ... 16), 2x (18 ... 14)
● AWG number as coded connectable conductor 16 ... 8
cross section for main contacts
● AWG number as coded connectable conductor 20 ... 14
cross section for auxiliary contacts
Safety related data
B10 value with high demand rate acc. to SN 31920 1 000 000
proportion of dangerous failures
● with low demand rate acc. to SN 31920 40 %
● with high demand rate acc. to SN 31920 73 %

3RT20261BB40 Subject to change without notice


12.17.2020
Page 5/6 © Copyright Siemens
failure rate [FIT] with low demand rate acc. to SN 31920 100 FIT
product function
● mirror contact acc. to IEC 60947-4-1 Yes
T1 value for proof test interval or service life acc. to 20 y
IEC 61508
protection class IP on the front acc. to IEC 60529 IP20
touch protection on the front acc. to IEC 60529 finger-safe, for vertical contact from the front
suitability for use safety-related switching OFF Yes
Certificates/ approvals
General Product Approval EMC

KC

Declaration of Conformity Test Certificates Marine / Shipping

Miscellaneous Type Test Special Test Miscellaneous


Certificates/Test Certificate
Report

Marine / Shipping other

Confirmation

other

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RT2026-1BB40
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RT2026-1BB40
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RT2026-1BB40
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RT2026-1BB40&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RT2026-1BB40/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RT2026-1BB40&objecttype=14&gridview=view1

3RT20261BB40 Subject to change without notice


12.17.2020
Page 6/7 © Copyright Siemens
3RT20261BB40 Subject to change without notice
12.17.2020
Page 7/8 © Copyright Siemens
3RT20261BB40 Subject to change without notice
12.17.2020
Page 8/9 © Copyright Siemens
last modified: 12/15/2020

3RT20261BB40 Subject to change without notice


12.17.2020
Page 9/9 © Copyright Siemens